Toshiba RAS-13UKV-E2, RAS-13UAV-E2 User Manual

SERVICE MANUAL
AIR CONDITIONER
RAS-13UKV-E2 / RAS-13UAV-E2
FILE NO. SVM-03008
SPLIT WALL TYPE
Jun., 2003
CONTENTS
1-1 Specifications 1-2 Operation Characteristic Curve 1-2 Capacity Variation Ratio According to Temperature
2. REFRIGERANT R410A
2-1 Safety During Installation/Servicing 2-2 Refrigerant Piping Installation 2-3 Tools 2-4. Recharging of Refrigerant 2-5. Brazing of Pipes
3. CONSTRUCTION VIEWS
3-1 Indoor Unit 3-2 Outdoor Unit
4. WIRING DIAGRAM
4-1 Indoor Unit 4-2 Outdoor Unit
FILE NO. SVM-03008
5. SPECIFICATION OF ELECTRICAL PARTS
5-1 Indoor Unit 5-2 Outdoor Unit
6. REFRIGERANT CYCLE DIAGRAM
6-1 Refrigerant Cycle Diagram 6-2 Operation Data
7. CONTROL BLOCK DIAGRAM
7-1 Indoor Unit 7-2 Outdoor Unit (Inverter Assembly)
8. OPERATION DESCRIPTION
8-1 Outlined of Air Conditioner Control 8-2 Description of Operation Circuit 8-3 Temporary Operation 8-4 Auto Restart Function 8-5 Filter Check Lamp 8-6 Remote Control and its Functions 8-7 Hi POWER Mode ([Hi POWER] button on the remote control is pushed.)
9. INSTALLATION PROCEDURE
9-1 Safety Cautions 9-2 INDOOR UNIT 9-3 OUTDOOR UNIT
– 1 –
10. HOW T O DIAGNOSE THE TROUBLE
10-1 First Confirmation 10-2 Primary Judgment 10-3 Judgment by Flashing LED of Indoor Unit 10-4 Self-Diagnosis by Remote Control (Check Code) 10-5 Judgment of Trouble by Every Symptom 10-6 Check Code 1C (Miswiring in indoor/outdoor units) and 1E 10-7 How to Diagnose Trouble in Outdoor Unit 10-8 How to Check Simply the Main Parts 10-9 How to Simply Judge Whether Outdoor Fan Motor is Good or Bad
11. HOW TO REPLACE THE MAIN PARTS
11-1 Indoor Unit 11-2 Microcomputer 11-3 Outdoor Unit
12. EXPLODED VIEWS AND PARTS LIST
12-1 Indoor Unit (E-Parts Assy) 12-2 Indoor Unit 12-3 Outdoor Unit 12-4 Outdoor Unit (E-Parts Assy)
FILE NO. SVM-03008
– 2 –
1-1. Specifications
FILE NO. SVM-03008
1. SPECIFICATIONS
Unit model Indoor RAS-13UKV-E2
Current limited — Cooling capacity (kW) 3.5 Cooling capacity range (kW) 0.9 – 4.0 Heating capacity (kW) 4.2 Heating capacity range (kW) 0.9 – 6.0 Power supply 220 – 240V –1Ph –50/60Hz Electric Indoor Operation mode Cooling Heating characteristics Running current (A) 0.15 0.15
COP (Cooling / Heating) 3.33/3.72 Operation noise Indoor High (Cooling / Heating) (dB•A) 39/39
Indoor unit Unit model RAS-13UKV-E2
Outdoor unit Unit model RAS-13UAV-E2
Piping connection Type Flare connection
Refrigerant Name of refrigerant R410A
Wiring connection Power supply 3 Wires: includes earth (Outdoor)
Usable temperature range Indoor (Cooling / Heating) (°C) 21 – 32 / 0 – 28
Accessory Indoor unit Installation plate 1
Outdoor RAS-13UAV-E2
Power consumption (W) 30 30 Power factor (%) 87 87
Outdoor Operation mode Cooling Heating
Running current (A) 4.65 5.01 Power consumption (W) 1020 1100 Power factor (%) 95 95 Starting current (A) 5.31
Medium (Cooling / Heating) (dB•A) 33/34 Low (Cooling / Heating) (dB•A) 26/28
Outdoor (Cooling / Heating) (dB•A) 48/50
Dimension Height (mm) 275
Width (mm) 790
Depth (mm) 208 Net weight (kg) 10 Fan motor output (W) 30 Air flow rate (Cooling / Heating) (m3/h) 530/620
Dimension Height (mm) 550
Width (mm) 780
Depth (mm) 720 Net weight (kg) 40 Compressor Motor output (W) 750
Type Twin rotary type with DC-inverter variable speed control
Model DA91A1F-45F Fan motor output (W) 43 Air flow rate (Cooling / Heating) (m3/h) 2410/2410
Indoor unit Liquid side ∅6.35
Gas side ∅9.52 Outdoor unit Liquid side ∅6.35
Gas side ∅9.52 Maximum length (Per unit) (m) 15 Maximum chargeless length (m) 15 Maximum height difference (m) 10
Weight (kg) 0.9
Interconnection 4 Wires: includes earth
Outdoor (Cooling / Heating) (°C) 10 – 43 / –10 – 24
Wireless remote control 1
Remote controller holder 1
Flat head wood screw 2 (∅3.1 x 16L)
Purifying filter 1
Zeolite filter 1
Batteries 2
Mounting screw 6 (∅4 x 25L)
Installation manual 1
Owner’s manual 1 Outdoor unit Drain nipple 1
The specification may be subject to change without nitice for purpose of improvement. – 3 –
1-2.Operation Characteristic Curve
<Cooling> <Heating>
FILE NO. SVM-03008
7
6
5
4
3
Current (A)
2
Conditions Indoor : DB 27°C/WB 19°C Outdoor : DB 35°C
1
Air flow : High Pipe length : 5m 230V
0
0 20 40 60 80 100
Compressor speed (rps)
7
6
5
4
3
Current (A)
2
Conditions Indoor : DB 20°C Outdoor : DB 7°C/WB 6°C
1
Air flow : High Pipe length : 5m 230V
0
0 20 40 60 80 100
Compressor speed (rps)
1-3.Capacity Variation Ratio According to Temperature
<Cooling> <Heating>
105 100
95 90 85 80 75 70
Capacity ratio (%)
65 60 55 50
32 34
Current Limited Start
Conditions Indoor : DB27°C/WB19°C Indoor air flow : High Pipe length 5m
36 38 40 4233 35 37 39 41 43
Outdoor temp. (°C)
120 110 100
90 80 70 60 50
Capacity ratio (%)
40 30 20 10
0
−10−9−8−7−6−5−4−3−2−1012345678910
Conditions
Indoor : DB 20°C Indoor air flow : High Pipe length : 5m
Outdoor temp. (°C)
Capacity ratio : 100% = 3.5 kW
*
– 4 –
2. REFRIGERANT R410A
FILE NO. SVM-03008
This air conditioner adopts the new refrigerant HFC (R410A) which does not damage the ozone layer.
The working pressure of the new refrigerant R410A is
1.6 times higher than conventional refrigerant (R22).
The refrigerating oil is also changed in accordance with change of refrigerant, so be careful that water, dust, and existing refrigerant or refrigerating oil are not entered in the refrigerant cycle of the air conditioner using the new refrigerant during installation work or servicing time.
The next section describes the precautions for air conditioner using the new refrigerant. Conforming to contents of the next section together with the general cautions included in this manual, perform the correct and safe work.
2-1.Safety During Installation/Servicing
As R410A’s pressure is about 1.6 times higher than that of R22, improper installation/servicing may cause a serious trouble. By using tools and materials exclu­sive for R410A, it is necessary to carry out installation/ servicing safely while taking the following precautions into consideration.
(1) Never use refrigerant other than R410A in an air
conditioner which is designed to operate with R410A. If other refrigerant than R410A is mixed, pressure in the refrigeration cycle becomes abnormally high, and it may cause personal injury, etc. by a rupture.
(2) Confirm the used refrigerant name, and use tools
and materials exclusive for the refrigerant R410A. The refrigerant name R410A is indicated on the visible place of the outdoor unit of the air condi­tioner using R410A as refrigerant. To prevent mischarging, the diameter of the service port differs from that of R22
(3) If a refrigeration gas leakage occurs during instal-
lation/servicing, be sure to ventilate fully. If the refrigerant gas comes into contact with fire, a poisonous gas may occur.
(4) When installing or removing an air conditioner,
do not allow air or moisture to remain in the refrigeration cycle. Otherwise, pressure in the refrigeration cycle may become abnormally high so that a rupture of personal injury may be caused.
(5) After completion of installation work, check to
make sure that there is no refrigeration gas leakage. If the refrigerant gas leaks into the room, coming into contact with fire in the fan-driven heater, space heater, etc., a poisonous gas may occur.
(6) When an air conditioning system charged with a
large volume of refrigerant is installed in a small room, it is necessary to exercise care so that, even when refrigerant leaks, its concentration does not exceed the marginal level. If the refrigerant gas leakage occurs and its concentration exceeds the marginal level, an oxygen starvation accident may result.
(7) Be sure to carry out installation or removal
according to the installation manual. Improper installation may cause refrigeration trouble, water leakage, electric shock, fire, etc.
(8) Unauthorized modifications to the air conditioner
may be dangerous. If a breakdown occurs please call a qualified air conditioner technician or electrician. Improper repair’s may result in water leakage, electric shock and fire, etc.
2-2.Refrigerant Piping Installation
2-2-1. Piping materials and joints used
For the refrigerant piping installation, copper pipes and joints are mainly used. Copper pipes and joints suit­able for the refrigerant must be chosen and installed. Furthermore, it is necessary to use clean copper pipes and joints whose interior surfaces are less affected by contaminants.
(1) Copper Pipes
It is necessary to use seamless copper pipes which are made of either copper or copper alloy and it is desirable that the amount of residual oil is less than 40 mg/10 m. Do not use copper pipes having a collapsed, deformed or discolored portion (especially on the interior surface). Otherwise, the expansion valve or capillary tube may become blocked with contaminants. As an air conditioner using R410A incurs pressure higher than when using R22, it is necessary to choose adequate materials. Thicknesses of copper pipes used with R410A are as shown in Table 2-2-1. Never use copper pipes thinner than 0.8 mm even when it is available on the market.
– 5 –
FILE NO. SVM-03008
Table 2-2-1 Thicknesses of annealed copper pipes
Thickness (mm)
Nominal diameter Outer diameter (mm) R410A R22
1/4 6.35 0.80 0.80 3/8 9.52 0.80 0.80 1/2 12.70 0.80 0.80 5/8 15.88 1.00 1.00
(2) Joints
For copper pipes, flare joints or socket joints are used. Prior to use, be sure to remove all contaminants.
a) Flare Joints
Flare joints used to connect the copper pipes cannot be used for pipings whose outer diameter exceeds 20 mm. In such a case, socket joints can be used. Sizes of flare pipe ends, flare joint ends and flare nuts are as shown in Tables 2-2-3 to 2-2-6 below.
Table 2-2-2 Minimum thicknesses of socket joints
Nominal diameter
Reference outer diameter of Minimum joint thickness
1/4 6.35 0.50 3/8 9.52 0.60 1/2 12.70 0.70 5/8 15.88 0.80
b) Socket Joints
Socket joints are such that they are brazed for connections, and used mainly for thick pipings whose diameter is larger than 20 mm. Thicknesses of socket joints are as shown in Table 2-2-2.
copper pipe jointed (mm) (mm)
2-2-2. Processing of piping materials
When performing the refrigerant piping installation, care should be taken to ensure that water or dust does not enter the pipe interior, that no other oil other than lubricating oils used in the installed air conditioner is used, and that refrigerant does not leak. When using lubricating oils in the piping processing, use such lubricating oils whose water content has been removed. When stored, be sure to seal the container with an airtight cap or any other cover.
(1) Flare Processing Procedures and Precautions
a) Cutting the Pipe
By means of a pipe cutter, slowly cut the pipe so that it is not deformed.
b) Removing Burrs and Chips
If the flared section has chips or burrs, refrigerant leakage may occur. Carefully remove all burrs and clean the cut surface before installation.
c) Insertion of Flare Nut
– 6 –
d) Flare Processing
Make certain that a clamp bar and copper pipe have been cleaned. By means of the clamp bar, perform the flare processing correctly. Use either a flare tool for R410A or conventional flare tool. Flare processing dimensions differ according to the type of flare tool. When using a conventional flare tool, be sure to secure “dimension A” b y using a gauge for size adjustment.
D
A
Fig. 2-2-1 Flare processing dimensions
FILE NO. SVM-03008
Table 2-2-3 Dimensions related to flare processing for R410A
Nominal
diameter
1/4 6.35 0.8 0 to 0.5 1.0 to 1.5 1.5 to 2.0 3/8 9.52 0.8 0 to 0.5 1.0 to 1.5 1.5 to 2.0 1/2 12.70 0.8 0 to 0.5 1.0 to 1.5 2.0 to 2.5 5/8 15.88 1.0 0 to 0.5 1.0 to 1.5 2.0 to 2.5
Nominal
diameter
1/4 6.35 0.8 0 to 0.5 0.5 to 1.0 1.0 to 1.5 3/8 9.52 0.8 0 to 0.5 0.5 to 1.0 1.0 to 1.5 1/2 12.70 0.8 0 to 0.5 0.5 to 1.0 1.0 to 2.0
Outer
diameter
(mm)
Table 2-2-4 Dimensions related to flare processing for R22
Outer
diameter
(mm)
Thickness
(mm)
Thickness
(mm)
Flare tool for R410A
clutch type
Flare tool for R410A
clutch type
A (mm)
Conventional flare tool
Clutch type Wing nut type
A (mm)
Conventional flare tool
Clutch type Wing nut type
5/8 15.88 1.0 0 to 0.5 0.5 to 1.0 1.0 to 2.0
Table 2-2-5 Flare and flare nut dimensions for R410A
Nominal
diameter
1/4 6.35 0.8 9.1 9.2 6.5 13 17 3/8 9.52 0.8 13.2 13.5 9.7 20 22 1/2 12.70 0.8 16.6 16.0 12.9 23 26 5/8 15.88 1.0 19.7 19.0 16.0 25 29
Nominal
diameter
1/4 6.35 0.8 9.0 9.2 6.5 13 17
Outer
diameter
(mm)
Outer
diameter
(mm)
Thickness
(mm)
Table 2-2-6 Flare and flare nut dimensions for R22
Thickness
(mm)
ABCD
ABCD
Dimension (mm)
Dimension (mm)
Flare nut
width
(mm)
Flare nut
width
(mm)
3/8 9.52 0.8 13.0 13.5 9.7 20 22 1/2 12.70 0.8 16.2 16.0 12.9 20 24 5/8 15.88 1.0 19.7 19.0 16.0 23 27 3/4 19.05 1.0 23.3 24.0 19.2 34 36
– 7 –
FILE NO. SVM-03008
Fig. 2-2-2 Relations between flare nut and flare seal surface
(2) Flare Connecting Procedures and Precautions
a) Make sure that the flare and union portions do
not have any scar or dust, etc.
b) Correctly align the processed flare surface with
the union axis.
c) Tighten the flare with designated torque by
means of a torque wrench. The tightening torque for R410A is the same as that for conventional R22. Incidentally, when the torque is weak, the gas leakage may occur.
Table 2-2-7 Tightening torque of flare for R410A [Reference values]
Nominal Outer diameter Tightening torque
diameter (mm) N·m (kgf·cm)
1/4 6.35 14 to 18 (140 to 180) 16 (160), 18 (180) 3/8 9.52 33 to 42 (330 to 420) 42 (420) 1/2 12.70 50 to 62 (500 to 620) 55 (550) 5/8 15.88 63 to 77 (630 to 770) 65 (650)
When it is strong, the flare nut may crack and may be made non-removable. When choosing the tightening torque, comply with values designated by manuf acturers. Table 2-2-7 shows reference values.
Note:
When applying oil to the flare surface, be sure to use oil designated by the manufacturer. If any other oil is used, the lubricating oils may deteriorate and cause the compressor to burn out.
Tightening torque of torque
wrenches available on the market
N·m (kgf·m)
8
FILE NO. SVM-03008
2-3. T ools
2-3-1. Required tools
The service port diameter of packed valve of the outdoor unit in the air conditioner using R410A is changed to prevent mixing of other refrigerant. To reinforce the pressure-resisting strength, flare processing dimensions and opposite side dimension of flare nut (For 12.70 copper pipe) of the refrigerant piping are lengthened.
The used refrigerating oil is changed, and mixing of oil may cause a trouble such as generation of sludge, clogging of capillary, etc. Accordingly, the tools to be used are classified into the following three types.
(1) Tools exclusive for R410A (Those which cannot be used for conventional refrigerant (R22)) (2) Tools exclusive for R410A, but can be also used for conventional refrigerant (R22) (3) Tools commonly used for R410A and for conventional refrigerant (R22) The table below shows the tools exclusive for R410A and their interchangeability.
Tools exclusive for R410A (The following tools for R410A are required.)
Tools whose specifications are changed for R410A and their interchangeability
R410A air conditioner Conventional air
installation conditioner installation
No. Used tool Usage Existence of Whether Whether new equipment
new equipment conventional can be used with for R410A equipment can conventional refrigerant
be used
1 Flare tool Pipe flaring Yes *(Note 1) 2 Copper pipe gauge Flaring by
for adjusting projection conventional flare Yes *(Note 1) *(Note 1) margin tool
3 Torque wrench Connection of
(For 12.70) flare nut
4 Gauge manifold 5 Charge hose
6 Vacuum pump adapter Vacuum evacuating Yes
Electronic balance for
7
refrigerant charging
8 Refrigerant cylinder Refrigerant charge Yes 9 Leakage detector Gas leakage check Yes ! Charging cylinder Refrigerant charge (Note 2)
Evacuating, refrigerant charge, Yes run check, etc.
Refrigerant charge Yes
Yes
(Note 1) When flaring is carried out for R410A using the conventional flare tools, adjustment of projection
margin is necessary. For this adjustment, a copper pipe gauge, etc. are necessary.
(Note 2) Charging cylinder for R410A is being currently developed.
General tools (Conventional tools can be used.)
In addition to the above exclusive tools, the following equipments which serve also for R22 are necessary as the general tools. (1) Vacuum pump (4) Reamer (9) Hole core drill (∅65)
Use vacuum pump by (5) Pipe bender (10) Hexagon wrench
attaching vacuum pump adapter. (6) Level vial (Opposite side 5 mm) (2) Torque wrench (For 6.35) (7) Screwdriver (+, –) (11) Tape measure (3) Pipe cutter (8) Spanner of Monkey wrench (12) Metal saw
Also prepare the following equipments for other installation method and run check. (1) Clamp meter (3) Insulation resistance tester (2) Thermometer (4) Electroscope
– 9 –
FILE NO. SVM-03008
2-4. Recharging of Refrigerant
When it is necessary to recharge refrigerant, charge the specified amount of new refrigerant according to the following steps.
Recover the refrigerant, and check no refrigerant remains in the equipment.
When the compound gauges pointer has indi­cated -0.1 Mpa (-76 cmHg), place the handle Low
Connect the charge hose to packed valve service port at the outdoor units gas side.
in the fully closed position, and turn off the vacuum pump’s power switch.
Connect the charge hose to the vacuum pump adapter.
Open fully both packed valves at liquid and gas sides.
Keep the status as it is for 1 to 2 minutes, and ensure that the compound gauges pointer does not return.
Set the refrigerant cylinder to the electronic balance, connect the connecting hose to the cylinder and the connecting port of the electronic balance, and charge liquid refrigerant.
Place the handle of the gauge manifold Low in
(For refrigerant charging, see the figure below.)
the fully opened position, and turn on the vacuum pumps power switch. Then, evacuating the refrigerant in the cycle.
1 Never charge refrigerant exceeding the specified amount. 2 If the specified amount of refrigerant cannot be charged, charge refrigerant bit by bit in COOL mode. 3 Do not carry out additional charging.
When additional charging is carried out if refrigerant leaks, the refrigerant composition changes in the refrigeration cycle, that is characteristics of the air conditioner changes, refrigerant exceeding the specified amount is charged, and working pressure in the refrigeration cycle becomes abnormally high pressure, and may cause a rupture or personal injury.
(INDOOR unit)
Refrigerant cylinder
(With siphon pipe)
Check valve
Open/Close valve
for charging
Electronic balance for refrigerant charging
Fig. 2-4-1 Configuration of refrigerant charging
(Liquid side)
(Gas side)
– 10 –
(OUTDOOR unit)
Opened
Closed
Service port
FILE NO. SVM-03008
1 Be sure to make setting so that liquid can be charged. 2 When using a cylinder equipped with a siphon, liquid can be charged without turning it upside down.
It is necessary for charging refrigerant under condition of liquid because R410A is mixed type of refrigerant. Accordingly, when charging refrigerant from the refrigerant cylinder to the equipment, charge it turning the cylinder upside down if cylinder is not equipped with siphon.
[Cylinder with siphon] [Cylinder without siphon]
Gauge manifold
OUTDOOR unit
Refrigerant
cylinder
Electronic
balance
R410A refrigerant is HFC mixed refrigerant. Therefore, if it is charged with gas, the composition of the charged refrigerant changes and the characteristics of the equipment varies.
Gauge manifold
OUTDOOR unit
Refrigerant
cylinder
Electronic
balance
Siphon
Fig. 2-4-2
2-5. Brazing of Pipes
2-5-1. Materials for brazing (1) Silver brazing filler
Silver brazing filler is an alloy mainly composed of silver and copper. It is used to join iron, copper or copper alloy, and is relatively expensive though it excels in solderability.
(2) Phosphor bronze brazing filler
Phosphor bronze brazing filler is generally used to join copper or copper alloy.
(3) Low temperature brazing filler
Low temperature brazing filler is generally called solder, and is an alloy of tin and lead. Since it is weak in adhesive strength, do not use it for refrigerant pipes.
1 Phosphor bronze brazing filler tends to react
with sulfur and produce a fragile compound water solution, which may cause a gas leakage . Therefore, use any other type of brazing filler at a hot spring resort, etc., and coat the surface with a paint.
2 When performing brazing again at time of
servicing, use the same type of brazing filler.
2-5-2. Flux (1) Reason why flux is necessary
By removing the oxide film and any foreign matter on the metal surface, it assists the flow of brazing filler.
In the brazing process, it prevents the metal surface from being oxidized.
By reducing the brazing filler’s surface tension, the brazing filler adheres better to the treated metal.
– 11 –
FILE NO. SVM-03008
(2) Characteristics required for flux
Activated temperature of flux coincides with the brazing temperature.
Due to a wide effective temperature range, flux is hard to carbonize.
It is easy to remove slag after brazing.
The corrosive action to the treated metal and
brazing filler is minimum.
It excels in coating performance and is harmless to the human body.
As the flux works in a complicated manner as described above, it is necessary to select an adequate type of flux according to the type and shape of treated metal, type of brazing filler and brazing method, etc.
(3) Types of flux
Noncorrosive flux
Generally, it is a compound of borax and boric acid. It is effective in case where the brazing temperature is higher than 800°C.
Activated flux
Most of fluxes generally used for silver brazing are this type. It features an increased oxide film removing capability due to the addition of compounds such as potassium fluoride, potassium chloride and sodium fluoride to the borax-boric acid compound.
2-5-3. Brazing
As brazing work requires sophisticated techniques, experiences based upon a theoretical knowledge, it must be performed by a person qualified. In order to prevent the oxide film from occurring in the pipe interior during brazing, it is effective to proceed with brazing while letting dry Nitrogen gas (N2) flow.
Never use gas other than Nitrogen gas.
(1) Brazing method to prevent oxidation
1 Attach a reducing valve and a flow-meter to the
Nitrogen gas cylinder.
2 Use a copper pipe to direct the piping material,
and attach a flow-meter to the cylinder.
3 Apply a seal into the clearance between the
piping material and inserted copper pipe for Nitrogen in order to prevent backflow of the Nitrogen gas.
4 When the Nitrogen gas is flowing, be sure to
keep the piping end open.
5 Adjust the flow rate of Nitrogen gas so that it is
lower than 0.05 m3/Hr or 0.02 Mpa (0.2 kgf/ cm2) by means of the reducing valve.
6 After performing the steps above, keep the
Nitrogen gas flowing until the pipe cools down to a certain extent (temperature at which pipes are touchable with hands).
7 Remove the flux completely after brazing.
(4) Piping materials for brazing and used brazing
filler/flux
Piping Used brazing Used
material filler flux
Copper - Copper Phosphor copper Do not use
Copper - Iron Silver Paste flux
Iron - Iron Silver Vapor flux
1 Do not enter flux into the refrigeration cycle. 2 When chlorine contained in the flux remains
within the pipe, the lubricating oil deteriorates. Therefore, use a flux which does not contain chlorine.
3 When adding water to the flux, use water which
does not contain chlorine (e.g. distilled water or ion-exchange water).
4 Remove the flux after brazing.
M
Flow meter
Stop valve
Nitrogen gas
cylinder
From Nitrogen cylinder
Pipe
Rubber plug
Nitrogen gas
Fig. 2-5-1 Prevention of oxidation during brazing
12
3-1. Indoor Unit
FILE NO. SVM-03008
3. CONSTRUCTION VIEWS
Front panel
Back body
660
Knock out system
Air inlet
Air filter
790
Heat exchanger
275
Air outlet
120 80
590
Hanger
64
53
48
208
48
Knock out system
660
Drain hose (0.54m)
Hanger
45
Minimum distance to ceiling
275
1
7
0
o
r m
o
re
320
620
235 235
215 215
re
Minimum distance to ceiling
o r m
o
5
6
Hanger
– 13 –
Connecting pipe (0.43m)
(Flare 6.35) Connecting pipe (0.33m) Flare 9.52
Hanger
Hanger
150150 160160
Installation plate outline
Center line
For stud bolt (8~10)
For stud bolt (6)
26
4519040
Minimum distance to ceiling
1
7
0
o
r m
o
re
32
9090
160
57 18
Wireless remote control
3-2.Outdoor Unit
FILE NO. SVM-03008
A
A Detail drawing (Back Leg)
6 Hole
310
600 52 36
302
270
R15
R5.5
32.5
310
302
30 Drain outlet
436
530
265
FAN GUARD
115 125
2-11 x 14 Hole (For 8-10 anchor bolt)
600 780
90
102
6 Hole
11 x 14 Hole
B
62
B Detail drawing (Front Leg)
310
302
36 52
R15
310 330
COVER PV
Z
Electrical part cover
600 or more
320
100 or more
Z View
Installation dimension
600
Air inlet
Air outlet
600 or more
4 x 11 x 14 Long holes (For 8 10 anchorbolt)
600 or more
120
75
Liquid side (Flare 6.35) Gas side (Flare 9.52)
54
Service port
– 14 –
4-1.Indoor Unit
FILE NO. SVM-03008
4. WIRING DIAGRAM
Table 4-1-1 Simple Check for Failure Diagnosis
Check Item
OPERATION
1
INDICATOR
TERMINAL BLOCK
2
FUSE 3.15A
3
DC5V
4 5
DC12V DC325V
6
(DC310 to 340V)
Refer to the service data for the detailed failure diagnosis.
Check to see if the OPERATION indicator goes on and off when the main switch or breaker is turned on. (Check the primary and secondary voltage of the transformer.)
Check the power supply v oltage between 1 and 2. (Refer to the name plate.) (Check the primary and secondary voltage of the transformer.) Check the fluctuating voltage between 2 and 3. (DC15 to 60 V)
Check to see if the fuse blows out. (Check the R04 of the varistor.)
Check the voltage at the No. 4 pin on CN13 connector of the infrared receiver. (Check the transformer and the power supply circuit of the rated voltage.)
Check the voltage at the white lead of the louver motor. (Check the transformer and the power supply circuit of the rated voltage.)
Check the voltage at the No. 1 pin on CN10 connector. (Check the DB01, R05 and C03.)
Diagnosis Result
– 15 –
4-2.Outdoor Unit
FILE NO. SVM-03008
PULSE
MODULATING
VALVE
TE
THERMOSTAT FOR COMPRESSOR
121
2
121
2
REACTOR
ORN
P10
G E A
CONVERTER
MODULE
DB01
BRW
BU EU BV EV BW EW BX
IGBT MODULE
BY
BZ
Q200
BLU P18
112
2
CN600 CN500
P07 P08
P09
P19 P20
P17
TD
11223
CT
POEWR RELAY
ELECTRONIC STAR TER
P.C. BOARD
(MCC-813)
P21 P22 P23
3
TO
RED
WHI BLK
TS
112
2
C12 C13 C14
1
1
2
2
3
3
COMPRESSOR
11223311223
CN701
RELAY
CM
COIL for 4-WAY VALVE
3
BLK P06 CN703CN603CN602CN601
VARIST OR
Q300
WHI
112
SURGE ABSORBER
F04 FUSE T3.15A
PMV
YEL
ORN
BLU
RED
GRY
3
44556
2
3
F01
FUSE
T25A
6
P01
BLK ORN
P03
WHI
P02
P11 P12
P13
P14
CN300
CN301
IGBT : Insulated Gate Bipolar Transistor
121
1
1
2
2
3
3
1
1
2
2
3
3
4
4
5
5
N
L 3 2 1
2
REACTOR
PUR
FAN MOTER
RED WHI BLK
YEL
PNK GRY
POWER SUPPLY 220-240V~ 50/60Hz
TO INDOOR UNIT
FM
– 16 –
FILE NO. SVM-03008
5. SPECIFICATION OF ELECTRICAL PARTS
5-1. Indoor Unit
No. Parts name Type Specifications
1 Fan motor (for indoor) ICF-340-30-2 DC 340 V, 30 W 2 Thermo. sensor (TA-sensor) ——— 10 k at 25°C 3 DC-DC transformer (T01) SWT-70 DC 390 V, Secondary DC 15 V, 12 V, 7 V 4 Microcomputer µPD780024AGK 5 Heat exchanger sensor
(TC-sensor) 6 Line filter (L01 SS11V-06270 27mH, AC 0.6A 7 Diode (DB01) D3SBA60 4A, 600 V 8 Capacitor (C03) KMH450VNSN120M25C 120µF, 450 V 9 Fuse (F01) FCU250V, 3.15A T3.15A, 250 V
10 Power supply IC (IC01) STR-L472 11 Varistor (R21, R109) 15G561K 560 V 12 Resistor (R01) RF-5TK4R7 4.7, 5 W
13 Louver motor MP24GA
——— 10 k at 25°C
Output (Rated) 1 W,16 poles, 1 phase, DC 12 V
5-2.Outdoor Unit
No. Parts name Model name Rating
1 SC coil L01 ADR2516-0R6TB 20A, 150µH
(Noise filter) L03 ADR2520-R15TB 15A, 0.6mH
Primary side DC280V, Secondary
2 DC-DC transformer SWT-43 side 7.5 V x 1, 13 V x 1, 26.5V x 3,
16 V x 1, 15 V x 1 3 Reactor CH-57-Z-T L=10mH, 16A x 2 4 Outside fan motor ICF-140-43-1 DC140 V, 43 W 5 Suction temp. sensor
(TS sensor) Discharge temp. sensor
6
(TD sensor) Outside air temp. sensor
7
(TO sensor) Heat exchanger temp.
8
sensor (TE sensor)
9 Terminal block (6P) ——— 20A, AC 250 V
10 Fuse
11 Electrolytic capacitor LLQ2G501KHUATF, 400LISN500K35F 500µF, DC 400 V x 3 pieces 12 Transistor module 6MBI25GS-060-01 or 6MBI25GS-060-01A 25A, 600 V 13 Compressor DA91A1F-45F 3-phases 4-poles 750 W 14 Compressor thermo. PW-2AL OFF: 125 ± 4°C, ON: 90 ± 5°C
15 Converter module MP7003
For protection of switching power source 3.15A, AC 250 V
For protection of inverter input overcurrent 25A, AC 250 V
(Inverter attached) 10 k (25°C)
(Inverter attached) 62 k (20°C)
(Inverter attached) 10 k (25°C)
(Inverter attached) 10 k (25°C)
Diode: 25A, 600 V,
IGBT: 40 A, 600V
– 17 –
6. REFRIGERANT CYCLE DIAGRAM
6-1.Refrigerant Cycle Diagram
P
Pressure measurement Gauge attaching port
Vacuum pump connecting port Deoxidized copper pipe
Outer dia. : 9.52 mm Thickness : 0.8 mm
INDOOR UNIT
Indoor heat
exchanger
Cross flow fan
Deoxidized copper pipe Outer dia. : 6.35 mm Thickness : 0.8 mm
Sectional shape of heat insulator
T1
Temp. measurement
FILE NO. SVM-03008
Max. : 15 m
Allowable height
difference : 10m
Allowable pipe length
4-way valve (CHV-0213)
TS
Temp. measurement
T2
Muffler
Muffler
TD
Compressor DA91A1F-45F
Outdoor heat
exchanger
Propeller fan
OUTDOOR UNIT
TO
Split capillary
1.5 x 2001.5 x 200
TE
s
s
Strainer
Pulse modulating valve at liquid side (SEV16RC3)
Refrigerant amount : 0.9 kg
NOTE :
Gas leak check position Refrigerant flow (Cooling) Refrigerant flow (Heating)
Note :
The maximum length of the pipe for this air conditioner is 15 m. The additional charging of refrigerant is unnecessary because this air conditioner is designed with charge-less specification.
– 18 –
6-2.Operation Data
<Cooling>
FILE NO. SVM-03008
Temperature
condition (°C)
Indoor Outdoor
27/19 35/– 13UKV-E2 0.8 to 1.0 9 to 11 49 to 45 High High 77
<Heating>
Temperature
condition (°C)
Indoor Outdoor
20/– 7/6 13UKV-E2 2.5 to 2.7 42 to 44 0 to 3 High High 83
Note :
(1) Measure surface temperature of heat exchanger pipe around center of heat exchanger path U bent.
(Thermistor themometer)
(2) Connecting piping condition : 5m
Model
name
Model
name
Standard pressure
P (MPa)
Standard pressure
P (MPa)
Heat exchanger
pipe temp.
T1 (°C) T2 (°C)
Heat exchanger
pipe temp.
T1 (°C) T2 (°C)
Indoor
fan
mode
Indoor
fan
mode
Outdoor
fan
mode
Outdoor
fan
mode
Compressor
revolution
Compressor
revolution
(rps)
(rps)
19
7-1.Indoor Unit
Heat Exchanger Sensor
7. CONTROL BLOCK DIAGRAM
Indoor Unit Control Panel
M.C.U
Functions
Louver Control
FILE NO. SVM-03008
Operation
Display
Temperature Sensor
Infrared Rays Signal Receiver
Initiallizing Circuit
Infrared
Rays
36.7KHz
Clock Frequency
Oscillator Circuit
Power Supply
Remote
Control
Noise Filter
From Outdoor Unit
Circuit
3-minute Delay at Restart for Compressor
Motor Revolution Control
Processing (Temperature Processing)
Timer
Serial Signal Communication
Louver ON/OFF Signal
Louver Driver
Serial Signal Transmitter/Receiver
Serial Signal Communication
Timer
Display
Filter
Sign Display
PRE DEF.
Sign Display
Indoor
Fan Motor
Louver
Motor
Louver Motor
REMOTE CONTROL
Infrared Rays
Remote Control
Operation (START/STOP) Operation Mode Selection
AUTO, COOL, DRY, HEAT, FAN ONLY
Temperature Setting Fan Speed Selection
ON TIMER Setting
OFF TIMER Setting
Louver Auto Swing
Louver Direction Setting
ECO
Hi power
Filter Reset
– 20 –
7-2.Outdoor Unit (Inverter Assembly)
220 240 V
50/60 Hz
MICRO-COMPUTER BLOCK DIAGRAM
Over current
sensor
Driver circuit
of P.M.V.
Over current
sensor
Heat exchanger
temp.sensor
Suction temp.
sensor
Outdoor air
temp. sensor
Discharge
temp. sensor
Inddor unit
send/receive
circuit
Relay
circuit
Noise
Filter
Converter
(AC DC)
Clock
frequency
16MHz
High Power
factor Correction
circuit
Input current
sensor
Rotor position
detect circuit
Rotor position
detect circuit
PWM synthesis function
Input current release control
IGBT over-current detect control
Outdoor fan control
High power factor correction control
Inverter output frequency control
A/D converter function
P.M.V. control
Discharge temp. control
4-way valve control
Signal communication to indoor unit
P.M.V : Pulse Modulating Valve
M.C.U : Micro Control Unit
M.C.U
For INDOOR UNIT
4-way
valve
P.M.V.
Inverter
(DC AC)
Over current
detect circuit
Gate drive
circuit
Gate drive
circuit
Over current
sensor
Inverter
(DC AC)
Outdoor
Fan motor
Compressor
MCC813 (P.C.B)
OUTDOOR UNIT
FILE NO. SVM-03008
21
8. OPERATION DESCRIPTION
FILE NO. SVM-03008
8-1.Outlined of Air Conditioner Control
This air conditioner is a capacity-variable type air conditioner, which uses DC motor for the indoor fan motor and the outdoor fan motor. And the capacity proportional control compressor which can change the motor speed in the range from 13 to 110 rps is mounted. The DC motor drive circuit is mounted to the indoor unit. The compressor and the inverter to control fan motor are mounted to the outdoor unit. The entire air conditioner is mainly controlled by the indoor unit controller.
The indoor unit controller drives the indoor fan motor based upon command sent from the remote control, and transfers the operation command to the outdoor unit controller.
The outdoor unit controller receives operation command from the indoor unit side, and controls the outdoor fan and the pulse modulating valve. (P.M.V) Besides, detecting revolution position of the compressor motor, the outdoor unit controller controls speed of the compressor motor by controlling output voltage of the inverter and switching timing of the supply power (current transfer timing) so that motors drive according to the operation command. And then, the outdoor unit controller transfers reversely the operating status information of the outdoor unit to control the indoor unit controller.
As the compressor adopts four-pole brushless DC motor, the frequency of the supply power from inverter to compressor is two-times cycles of the actual number of revolution.
(1) Role of indoor unit controller
The indoor unit controller judges the operation commands from the remote controller and assumes the following functions.
Judgment of suction air temperature of the indoor heat exchanger by using the indoor temp. sensor (TA sensor)
Temperature setting of the indoor heat exchanger by using heat exchanger sensor (TC sensor) (Prevent-freezing control)
Louver motor control
Indoor fan motor operation control
LED (Light Emitting Diode) display control
Transferring of operation command signal
(Serial signal) to the outdoor unit
Reception of information of operation status (Serial signal including outside temp. data) to the outdoor unit and judgment/display of error
(2) Role of outdoor unit controller
Receiving the operation command signal (Serial signal) from the indoor controller, the outdoor unit performs its role.
Compressor operation control
Operation control of outdoor fan motor
P.M.V. control
Detection of inverter input current and current
release operation
Over-current detection and prevention operation to IGBT module (Compressor stop function)
Compressor and outdoor fan stop function when serial signal is off (when the serial signal does not reach the board assembly of outdoor control by trouble of the signal system).
Transferring of operation information (Serial signal) from outdoor unit to indoor unit
Detection of outdoor temperature and operation revolution control
Defrost control in heating operation (Temp. measurement by outdoor heat exchanger and control for 4-way valve and outdoor fan)
Operations followed to judgment of serial signal from indoor side.
– 22 –
FILE NO. SVM-03008
(3) Contents of operation command signal (Serial
signal) from indoor unit controller to outdoor unit controller The following three types of signals are sent from the indoor unit controller.
Operation mode set on the remote control
Compressor revolution command signal
defined by indoor temperature and set tem­perature (Correction along with variation of room temperature and correction of indoor heat exchanger temperature are added.)
For these two types of signals ([Operation mode] and [Compressor revolution]), the outdoor unit controller monitors the input current to the inverter, and performs the followed operation within the range that current does not exceed the allowable value.
Temperature of indoor heat exchanger by indoor heat exchanger sensor (Minimum revolution control)
(4) Contents of operation command signal (Serial
signal) from outdoor unit controller to indoor unit controller The following signals are sent from the outdoor unit controller.
The current operation mode
The current compressor revolution
Outdoor temperature
Existence of protective circuit operation
For transferring of these signals, the indoor unit controller monitors the contents of signals, and judges existence of trouble occurrence. Contents of judgment are described below.
Whether distinction of the current operation status meets to the operation command signal
Whether protective circuit operates When no signal is received from the outdoor unit controller, it is assumed as a trouble.
8-1-1. Capacity control
The cooling and heating capacity is varied by changing compressor motor speed. The inverter changes compressor motor speed by changing AC 220-240 V power to DC once, and controls capac­ity by changing supply power status to the compressor with transistor module (includes 6 transistors). The outline of the control is as follows:
The revolution position and revolution speed of the motor are detected by detecting winding electromotive force of the compressor motor under operation, and the revolution speed is changed so that the motor drives based upon revolution speed of the operation command by changing timing (current transfer timing) to exchange inverter output voltage and supply power winding.
Detection of the revolution position for controlling is performed 12 times per 1 revolution of compressor. The range of supply power frequency to the compressor differs according to the operation status (COOL, HEAT, DRY).
Table 8-1-1 Compressor revolution range
Operation Model
mode name
COOL
HEAT
8-1-2. Current release control
The outdoor main circuit control section (Inverter assembly) detects the input current to the outdoor unit. If the current value with compressor motor speed instructed from indoor side exceeds the specified value, the outdoor main circuit control section controls compressor motor speed by reducing motor speed so that value becomes closest to the command within the limited value.
13UKV-E2
Compressor
revolution (rps)
13 to 88
16 to 110
8-1-3. Power factor improvement control
Power factor improvement control is performed mainly aiming to reduce the current on much power consump­tion of cooling/heating operation. Controlling starts from the time when input power has reached at a certain point. To be concrete, IGBT of the power factor improvement circuit is used, and the power factor is improved by keeping IGBT on for an arbitrary period to widen electro-angle of the input current.
– 23 –
FILE NO. SVM-03008
8-1-4. Prevent-freezing control
The indoor heat exchanger sensor detects refrigerant vapor temperature in COOL/DRY operation. If the temperature is below the specified value, compressor motor speed is reduced so that operation is performed in temperature below the specified value to prevent­freezing of indoor heat exchanger.
8-1-5. P.M.V. (Pulse Modulating Valve)
Using P.M.V., refrigerant flow of refrigeration cycle is varied for the optimum temperature.
After the power has been turned on, when a serial operation signal is received from indoor at the first time, or when PMV alarm is detected and the equip­ment is reactivated, move the valve once until it hits on the stopper for positioning of the valve. In this case, ticktack sound may be heard.
8-1-6. Louver control
(1) Vertical air flow louvers
Positions of vertical air flow louvers are automatically controlled according to the operation status (AUTO (A), COOL ( ), DRY ( ), HEAT( ) and FAN ONLY ( ). Besides, positions of vertical air flow louvers can be arbitrarily set by pushing the [FIX] button.
(2) Swing
If the [SWING] button is pressed during running operation, vertical air flow louvers start swinging. When the [FIX] button is pushed, swinging stops.
8-1.7. Indoor fan control (DC fan motor)
(1) The indoor fan is operated by the stepless speed
change DC motor.
(2) For air flow level, speed of the indoor fan motor is
controlled in five steps (LOW, LOW+, MED, MED and HIGH). If AUTO mode is selected, the fan motor speed is automatically controlled by the difference between the preset temperature and the room temperature.
LOW+=
MED+=
LOW+MED
2
MED+HIGH
2
Table 8-1-2
Operation
mode
Fan
mode
RAS-13UKV-E2
Motor speed Air flow rate
(rpm) (m3/h)
H 1210 530
COOL M 1010 420
L 810 330
DRY 780 320
H 1290 620
HEAT M 1110 470
L 930 380
+
– 24 –
FILE NO. SVM-03008
8-1-8. Outdoor fan control (DC fan motor)
Although the outdoor fan motor drives the outdoor fan by non-step variable system of the revolution speed, the revolution speed is restricted to three steps on the convenience of controlling. If a strong wind is lashing outside of the room, the operation may be continued as the outdoor fan stops in order to protect the outdoor fan motor.
If a fan lock occurred due to entering of foreign matter, the air conditioner stops and an alarm is displayed.
<COOL, DRY>
Table 8-1-3
Model name RAS-13UAV-E2
Compressor revolution (rps) To 13.8 To 34.7 From 35.3
TO 38°C 390 840 840
Outdoor temp. sensor TO TO < 38°C 390 700 840
TO < 15°C 390 TO 38°C 390 700 840
ECONO. operation TO < 38°C 390 390 700
TO < 15°C 390
TO is abnormal 700 700 840
<HEAT>
Table 8-1-4
Model name RAS-13UAV-E2
Compressor revolution (rps) To 16.8 To 57.4 From 58.0
Outdoor temp. sensor TO
ECONO. operation
TO is abnormal 390 650 840
TO 5°C 390 650 840 TO < 5°C 650 650 840 TO 5°C 390 390 650 TO < 5°C 390 650 650
– 25 –
FILE NO. SVM-03008
8-2. Description of Operation Circuit
Turning [ON] the breaker flashes the operation lamp. (1Hz) This is the display of power-ON (or notification of power failure).
When pushing [START/STOP] button of the remote control, receive sound is issued from the main unit, and the next operations are performed together with opening the vertical air flow louvers.
8-2-1. Cooling operation
(The Remote Control MODE Button is Set to the COOL Position)
Once the setting is made, the operation mode is memorized in the microcomputer so that the same operation can be effected thereafter simply by pushing [START/STOP] button.
A cooling operation signal is transmitted to outdoor unit.
The outdoor unit controls the outdoor fan relay R01, R02 and R03, and the compressor motor speed according to the operation command signal sent from the indoor unit.
When [FAN] button is set to AUTO, the indoor fan motor operates as shown in Fig. 8-2-1. When [FAN] button is set to LOW , LOW MED , MED
+
, HIGH , the
motor operates with a constant air flow.
°C
+3 +2.5 +2 +1.5 +1
(Room temp.) (Set temp.)
+0.5
Set temp.
0
0.5
NOTE :
*1: Calculated from difference in motor speed of M+
and L, and controlled.
+
,
M+ *1 *1 *1
L
In normal operation
(1) Cooling capacity control
The cooling capacity and room temperature are controller by changing the compressor motor speed according to both the difference between the temperature detected by the room temperature sensor and the temperature set by TEMP button and also any change in room temperature.
When compressor has been activated or reactivated, it operates with Max.41 rps for 2 minutes, with Max.91 rps from 2 minutes to 3 minutes, and with Max.88 rps after 3 minutes passed.
When room temperature is lower than set temperature, indoor fan motor is oper ated at fan speed L as shown in Fig. 8-2-1 while the outdoor unit stops.
(2) Prevent-freezing control
If temperature of indoor heat exchanger detected by the indoor heat exchanger sensor is 5°C lower, compressor motor speed is gradually lowered to prevent freezing of the indoor heat exchanger. If temperature is 7°C or higher, return the operation to the above item (1).
(3) Current release control
The input current of compressor and outdoor fan motor (Precisely inverter main circuit control section) which occupy most of air conditioner input is detected by the outdoor current sensor, and compressor motor speed is gradually lowered so that current value does not exceed 9.0A if current value exceeds 9.0A. When the current value lowers to 8.5A, return the operation to the above item (1).
Comp. motor
9.0
8.5
Current value (A)
Normal control
speed down
Comp. motor speed keep
Fig. 8-2-2
Fig. 8-2-1 Setting of air flow [Fan AUTO]
– 26 –
Loading...
+ 61 hidden pages