Toshiba RAS-13UKV-E, RAS-13UAV-E SERVICE MANUAL

.ILE NO. A02-001
SPLIT TYPE
RAS-13UKV-E
RAS-13U AV-E
PRINTED IN JAPAN, Mar.,2002 ToMo
CONTENTS
1. SPECIFICATIONS ..................................................................................... 3
3. CONSTRUCTION VIEWS ........................................................................ 13
4. WIRING DIAGRAM.................................................................................. 15
5. SPECIFICATIONS OF ELECTRICAL PARTS ......................................... 17
6. REFRIGERANT CYCLE DIAGRAM ........................................................ 18
7. CONTROL BLOCK DIAGRAM ................................................................ 20
8. OPERATION DESCRIPTION................................................................... 22
9. INSTALLATION PROCEDURE................................................................ 35
10. HO W TO DIA GNOSE THE TROUBLE...................................................... 44
11. HO W TO REPLACE THE MAIN P AR TS................................................... 63
12. EXPLODED VIEWS AND PARTS LIST ................................................... 74
– 2 –
1. SPECIFICATIONS
1-1. Specifications
RAS-13UKV-E/RAS-13UAV-E
Unit model Indoor
Outdoor Current limited Cooling capacity (kW) Cooling capacity range (kW) Heating capacity (kW) Heating capacity range (kW) Power supply Electric Indoor Operation mode
characteristics
Outdoor Operation mode
COP (Cooling/Heating) Operating noise Indoor High (Cooling / Heating) (dB•A)
Outdoor (Cooling / Heating) (dB•A) Indoor unit Unit model
Dimension Height (mm)
Net weight (kg)
Fan motor output (W)
Air flow rate (Cooling / Heating) (m³/h) Outdoor unit Unit model
Dimension Height (mm)
Net weight (kg)
Compressor Motor output (W)
Fan motor output (W)
Air flow rate (Cooling / Heating) (m³/h) Piping Type
connection
Refrigerant Name of refrigerant
Wiring connection Power supply
Usable temperature range Indoor (Cooling / Heating) (°C)
Accessory Indoor unit Installation plate
Indoor unit Liquid side
Outdoor unit Liquid side
Maximum length (Per unit) (m)
Maximum chargeless length (m)
Maximum height difference (m)
Weight (kg)
Interconnection
Outdoor unit Drain nipple
Running current (A) Power consumption (W) Power factor (%)
Running current (A) Power consumption (W) Power factor (%) Starting current (A)
Medium (Cooling / Heating) (dB•A) Low (Cooling / Heating) (dB•A)
Width (mm) Depth (mm)
Width (mm) Depth (mm)
Type Model
Gas side
Gas side
Outdoor (Cooling / Heating) (°C)
Wireless remote controller Remote controller holder Flat head wood screw Purifying filter Zeolite filter Batteries Mounting screw Installation manual Owner’s manual
Twin rotary type with DC-inverter variable speed control
220 – 230 –240V – 1Ph – 50/60Hz
Cooling Heating
0.15 0.15 30 30 87 87
Cooling Heating
5.07 / 4.84 / 4.63 5.40 / 5.16 / 4.94 1060 1130
95 95
3 Wires : includes earth (Outdoor)
• The specifications may be subject to change without notice for purpose of improvement.
RAS-13UKV-E RAS-13UAV-E
3.5
0.9 – 4.0
4.2
0.9 – 6.0
5.55 / 5.31 / 5.09
3.21 / 3.62 39 / 39 33 / 34 26 / 28 48 / 50
RAS-13UKV-E
275 790 208
10 30
530 / 620
RAS-13UAV-E
550 780 270
38
750
DA91A1F-44F
43
2410 / 2410
Flare connection
Ø6.35 Ø9.52 Ø6.35 Ø9.52
15 15 10
R410A
0.8
4 Wires : includes ear th
21 – 32 / 0 – 28
10 – 43 / –10 – 24
1 1 1
2 (Ø3.1 x 16L)
1 1 2
6 (Ø4 x 25L)
1 1 1
– 3 –
1-2. Operation Characteristic Curve
<Cooling> <Heating>
7
6
RAS-13UKV-E
5
4
3
Current (A)
2
Conditions Indoor : DB 27˚C/WB 19˚C Outdoor : DB 35˚C
1
Air flow : High Pipe length : 5m 230V
0
0 20 40 60 80 100
Compressor speed (rps)
7
6
RAS-13UKV-E
5
4
3
Current (A)
2
• Conditions Indoor : DB 20˚C Outdoor : DB 7˚C/WB 6˚C
1
Air flow : High Pipe length : 5m 230V
0
0 20 40 60 80 100
Compressor speed (rps)
1-3. Capacity Variation Ratio According to Temperature
<Cooling> <Heating>
105 100
95 90 85 80 75 70
Capacity ratio (%)
65 60 55 50
32 34
Current Limited Start
RAS-13UKV-E
Conditions Indoor : DB27˚C/WB19˚C Indoor air flow : High Pipe length 5m
36 38 40 4233 35 37 39 41 43
Outdoor temp. (˚C)
120 110 100
90 80 70 60 50
Capacity ratio (%)
40 30 20 10
0
–10–9–8–7–6–5–4–3–2–1012345678910
RAS-13UKV-E
Conditions Indoor : DB 20˚C Indoor air flow : High Pipe length : 5m
Outdoor temp. (˚C)
Capacity ratio : 100% = 3.5 kW (RAS-13UKV-E)
*
– 4 –
2. REFRIGERANT R410A
This air conditioner adopts the new refrigerant HFC (R410A) which does not damage the ozone layer.
The working pressure of the new refrigerant R410A is 1.6 times higher than conventional refrigerant (R22). The refrigerating oil is also changed in accordance with change of refrigerant, so be careful that water, dust, and existing refrigerant or refrigerat­ing oil are not entered in the refrigerant cycle of the air conditioner using the new refrigerant during installation work or servicing time.
The next section describes the precautions for air conditioner using the new refrigerant. Conforming to contents of the next section together with the general cautions included in this manual, perform the correct and safe work.
2-1. Safety During Installation/Servicing
As R410As pressure is about 1.6 times higher than that of R22, improper installation/servicing may cause a serious trouble. By using tools and materi­als exclusive for R410A, it is necessary to carry out installation/servicing safely while taking the following precautions into consideration.
(1) Never use refrigerant other than R410A in an air
conditioner which is designed to operate with R410A.
If other refrigerant than R410A is mixed, pres­sure in the refrigeration cycle becomes abnor­mally high, and it may cause personal injury, etc. by a rupture.
(2) Confirm the used refrigerant name, and use
tools and materials exclusive for the refrigerant R410A.
The refrigerant name R410A is indicated on the visible place of the outdoor unit of the air condi­tioner using R410A as refrigerant. To prevent mischarging, the diameter of the service port differs from that of R22.
(3) If a refrigeration gas leakage occurs during
installation/servicing, be sure to ventilate fully. If the refrigerant gas comes into contact with fire,
a poisonous gas may occur.
(4) When installing or removing an air conditioner,
do not allow air or moisture to remain in the refrigeration cycle. Otherwise, pressure in the refrigeration cycle may become abnormally high so that a rupture or personal injury may be caused.
(5) After completion of installation work, check to
make sure that there is no refrigeration gas leakage.
If the refrigerant gas leaks into the room, coming into contact with fire in the fan-driven heater, space heater, etc., a poisonous gas may occur.
(6) When an air conditioning system charged with a
large volume of refrigerant is installed in a small room, it is necessary to exercise care so that, even when refrigerant leaks, its concentration does not exceed the marginal lev el.
If the refrigerant gas leakage occurs and its concentration exceeds the marginal level, an oxygen starvation accident may result.
(7) Be sure to carry out installation or removal
according to the installation manual. Improper installation may cause refrigeration
trouble, water leakage, electric shock, fire, etc.
(8) Unauthorized modifications to the air conditioner
may be dangerous. If a breakdown occurs please call a qualified air conditioner technician or electrician.
Improper repairs may result in water leakage, electric shock and fire, etc.
2-2. Refrigerant Piping Installation
2-2-1. Piping Materials and Joints Used
For the refrigerant piping installation, copper pipes and joints are mainly used. Copper pipes and joints suitable for the refrigerant must be chosen and installed. Furthermore, it is necessary to use clean copper pipes and joints whose interior surfaces are less affected by contaminants .
(1) Copper Pipes
It is necessary to use seamless copper pipes which are made of either copper or copper alloy and it is desirable that the amount of residual oil is less than 40 mg/10 m. Do not use copper pipes having a collapsed, deformed or discol­ored portion (especially on the interior surface).
Otherwise, the expansion v alve or capillary tube may become bloc ked with contaminants.
As an air conditioner using R410A incurs pressure higher than when using R22, it is necessary to choose adequate materials.
Thicknesses of copper pipes used with R410A are as shown in Table 2-2-1. Never use copper pipes thinner than 0.8 mm even when it is available on the market.
– 5 –
Table 2-2-1 Thicknesses of annealed copper pipes
Thickness (mm)
Nominal diameter
1/4 3/8 1/2 5/8
(2) Joints
For copper pipes, flare joints or soc ket joints are used. Prior to use , be sure to remove all con­taminants.
a) Flare Joints
Flare joints used to connect the copper pipes cannot be used for pipings whose outer diameter exceeds 20 mm. In such a case, socket joints can be used.
Sizes of flare pipe ends, flare joint ends and flare nuts are as shown in Tables 2-2-3 to 2­2-6 below .
Outer diameter (mm)
6.35
9.52
12.70
15.88
R410A R22
0.80 0.80
0.80 0.80
0.80 0.80
1.00 1.00
b) Socket Joints
Socket joints are such that they are brazed for connections, and used mainly for thick pipings whose diameter is larger than 20 mm.
Thicknesses of socket joints are as shown in Table 2-2-2.
Table 2-2-2 Minimum thicknesses of socket joints
Nominal diameter
1/4 3/8 1/2 5/8
Reference outer diameter of
copper pipe jointed (mm)
2-2-2. Processing of Piping Materials
When performing the refrigerant piping installation, care should be taken to ensure that water or dust does not enter the pipe interior, that no other oil other than lubricating oils used in the installed air conditioner is used, and that refrigerant does not leak. When using lubricating oils in the piping processing, use such lubricating oils whose water content has been removed. When stored, be sure to seal the container with an airtight cap or any other cover.
Minimum joint thickness
(mm)
6.35
9.52
12.70
15.88
(1) Flare Processing Procedures and Precautions
a) Cutting the Pipe
By means of a pipe cutter, slowly cut the pipe so that it is not deformed.
b) Removing Burrs and Chips
If the flared section has chips or burrs, refrigerant leakage may occur. Carefully remove all b urrs and clean the cut surface before installation.
c) Insertion of Flare Nut
0.50
0.60
0.70
0.80
– 6 –
d) Flare Processing
Make certain that a clamp bar and copper pipe have been cleaned.
By means of the clamp bar, perform the flare processing correctly.
Use either a flare tool for R410A or conven­tional flare tool.
Flare processing dimensions differ according to the type of flare tool. When using a conventional flare tool, be sure to secure dimension A by using a gauge for size adjustment.
Table 2-2-3 Dimensions related to flare processing for R410A
ØD
A
Fig. 2-2-1 Flare processing dimensions
Nominal
diameter
1/4 3/8 1/2 5/8
Nominal
diameter
1/4 3/8
Outer
diameter
(mm)
6.35
9.52
12.70
15.88
Thickness
(mm)
0.8
0.8
0.8
1.0
Flare tool for R410A
clutch type
0 to 0.5 1.0 to 1.5 1.5 to 2.0 0 to 0.5 1.0 to 1.5 1.5 to 2.0 0 to 0.5 1.0 to 1.5 2.0 to 2.5 0 to 0.5 1.0 to 1.5 2.0 to 2.5
Table 2-2-4 Dimensions related to flare processing for R22
A (mm)
A (mm)
Outer
diameter
(mm)
6.35
9.52
Thickness
(mm)
0.8
0.8
Flare tool for R410A
clutch type
0 to 0.5 0.5 to 1.0 1.0 to 1.5 0 to 0.5 0.5 to 1.0 1.0 to 1.5
Conventional flare tool
Clutch type Wing nut type
Conventional flare tool
Clutch type Wing nut type
1/2 5/8
Nominal
diameter
1/4 3/8 1/2 5/8
12.70
15.88
0.8
1.0
0 to 0.5 0.5 to 1.0 1.0 to 2.0 0 to 0.5 0.5 to 1.0 1.0 to 2.0
Table 2-2-5 Flare and flare nut dimensions for R410A
Outer
diameter
(mm)
6.35
9.52
12.70
15.88
Thickness
(mm)
0.8
0.8
0.8
1.0
ABCD
9.1 9.2 6.5 13
13.2 13.5 9.7 20
16.6 16.0 12.9 23
19.7 19.0 16.0 25
Dimension (mm)
7
Flare nut
width
(mm)
17 22 26 29
Table 2-2-6 Flare and flare nut dimensions for R22
Nominal
diameter
1/4 3/8 1/2 5/8 3/4
Outer
diameter
(mm)
6.35
9.52
12.70
15.88
19.05
Thickness
(mm)
0.8
0.8
0.8
1.0
1.0
˚ to 46
45
Dimension (mm)
Flare nut
width
ABCD
9.0 9.2 6.5 13
13.0 13.5 9.7 20
16.2 16.0 12.9 20
19.7 19.0 16.0 23
23.3 24.0 19.2 34
˚
B A
D
C
(mm)
17 22 24 27 36
Fig. 2-2-2 Relations between flare nut and flare seal surface
(2) Flare Connecting Procedures and Precautions
a) Make sure that the flare and union portions
do not have any scar or dust, etc.
b) Correctly align the processed flare surface
with the union axis.
c) Tighten the flare with designated torque by
means of a torque wrench. The tightening torque for R410A is the same as that for conventional R22. Incidentally, when the torque is weak, the gas leakage may occur.
Table 2-2-7 Tightening torque of flare for R410A [Reference values]
Nominal
diameter
Outer
diameter
(mm)
Tightening torque
N•m (kgf•cm)
43˚ to 45
˚
When it is strong, the flare nut may crack and may be made non-removable. When choos­ing the tightening torque, comply with values designated by manufacturers . Table 2-2-7 shows reference v alues.
NOTE :
When applying oil to the flare surface, be sure to use oil designated by the manufacturer. If an y other oil is used, the lubricating oils may deteriorate and cause the compressor to burn out.
Tightening torque of torque
wrenches available on the market
N•m (kgf•cm)
1/4 3/8 1/2 5/8
6.35
9.52
12.70
15.88
14 to 18 (140 to 180) 33 to 42 (330 to 420) 50 to 62 (500 to 620) 63 to 77 (630 to 770)
– 8 –
16 (160), 18 (180)
42 (420) 55 (550) 65 (650)
2-3. Tools
2-3-1. Required Tools
The service port diameter of pac ked valve of the outdoor unit in the air conditioner using R410A is changed to prevent mixing of other refrigerant. To reinforce the pressure-resisting strength, flare processing dimensions and opposite side dimension of flare nut (For Ø12.7 copper pipe) of the refrigerant piping are lengthened.
The used refrigerating oil is changed, and mixing of oil may cause a trouble such as generation of sludge, clogging of capillary, etc. Accordingly, the tools to be used are classified into the following three types.
(1) Tools exclusive for R410A (Those which cannot be used for conventional refrigerant (R22)) (2) Tools exclusive for R410A, but can be also used for conventional refrigerant (R22) (3) Tools commonly used for R410A and for conventional refrigerant (R22) The table below shows the tools exclusive for R410A and their interchangeability.
Tools exclusive for R410A (The following tools for R410A are required.)
Tools whose specifications are changed for R410A and their interchangeability
Conventional air
conditioner installation
Whether new equipment can be used with conventional refrigerant
¡
(Note 1)
*
X
X
¡
¡
X
¡
X
No.
1
2
3 4
5 6
7 8
9
10
Used tool
Flare tool Copper pipe gauge for
adjusting projection margin
Torque wrench (For Ø12.7)
Gauge manifold Charge hose
Vacuum pump adapter Electronic balance for
refrigerant charging Refrigerant cylinder Leakage detector Charging cylinder
Usage
Pipe flaring Flaring by
conventional flare tool
Connection of flare nut
Evacuating, refrigerant charge, run check, etc.
Vacuum evacuating Refrigerant charge
Refrigerant charge Gas leakage check Refrigerant charge
Yes
Yes
Yes
Yes
Yes Yes
Yes Yes
R410A
Whether conventional equipment can be used
(Note 1)
*
(Note 1)
*
air conditioner installation
Existence of new equipment for R410A
(Note 2)
X
X
X X
X X X
(Note 1) When flaring is carried out for R410A using the conventional flare tools, adjustment of projection
margin is necessary. For this adjustment, a copper pipe gauge, etc. are necessary.
(Note 2) Charging cylinder for R410A is being currently developed.
General tools (Conventional tools can be used.)
In addition to the above e xclusive tools, the following equipments which serve also for R22 are necessary as the general tools.
(1) Vacuum pump
Use vacuum pump by
attaching vacuum pump adapter. (2) Torque wrench (For Ø6.35, Ø9.52) (3) Pipe cutter (4) Reamer
(5) Pipe bender (6) Level vial (7) Screwdriver (+, –) (8) Spanner or Monkey wrench (9) Hole core drill (Ø65)
(10) Hexagon wrench
(Opposite side 5mm)
(11) Tape measure (12) Metal saw
Also prepare the following equipments for other installation method and run chec k.
(1) Clamp meter (2) Thermometer
(3) Insulation resistance tester (4) Electroscope
– 9 –
2-4. Recharging of Refrigerant
When it is necessary to recharge refrigerant, charge the specified amount of new refrigerant according to the following steps .
Recover the refrigerant, and check no refrigerant remains in the equipment.
Connect the charge hose to packed valve service port at the outdoor units gas side.
Connect the charge hose to the vacuum pump adapter.
Open fully both packed valves at liquid and gas sides.
When the compound gauge’s pointer has indicated –0.1 Mpa (–76 cmHg), place the handle Low in the fully closed position, and turn off the vacuum pump’s power switch.
Keep the status as it is for 1 to 2 minutes, and ensure that the compound gauges pointer does not return.
Set the refrigerant cylinder to the electronic balance, connect the connecting hose to the cylinder and the connecting port of the electronic balance, and charge liquid refrigerant.
Place the handle of the gauge manifold Low in the fully opened position, and turn on the vacuum pumps power switch. Then, evacuating the refrigerant in the cycle.
(For refrigerant charging, see the figure below.)
(1) Never charge refrigerant exceeding the specified amount. (2) If the specified amount of refrigerant cannot be charged, charge refrigerant bit by bit in COOL mode. (3) Do not carry out additional charging.
When additional charging is carried out if refrigerant leaks, the refrigerant composition changes in the refrigeration cycle, that is characteristics of the air conditioner changes, refrigerant exceeding the specified amount is charged, and working pressure in the refrigeration cycle becomes abnormally high pressure, and may cause a rupture or personal injury.
(INDOOR unit)
(Liquid side)
(OUTDOOR unit)
Opened
Refrigerant cylinder
(With siphon pipe)
Check valve
Open/Close valve
for charging
Electronic balance for refrigerant charging
Fig. 2-4-1 Configuration of refrigerant charging
(Gas side)
Closed
Service port
– 10 –
(1) Be sure to make setting so that liquid can be charged. (2) When using a cylinder equipped with a siphon, liquid can be charged without turning it upside down.
It is necessary for charging refrigerant under condition of liquid because R410A is mixed type of refrigerant. Accordingly, when charging refrigerant from the refrigerant cylinder to the equipment, charge it turning the cylinder upside down if cylinder is not equipped with siphon.
[ Cylinder with siphon ] [ Cylinder without siphon ]
Gauge manifold
OUTDOOR unit
Refrigerant
cylinder
Gauge manifold
OUTDOOR unit
cylinder
Refrigerant
Electronic
balance
R410A refrigerant is HFC mixed refrigerant. Therefore, if it is charged with gas, the composi­tion of the charged refrigerant changes and the characteristics of the equipment varies.
2-5. Brazing of Pipes
2-5-1. Materials for Brazing
(1) Silver brazing filler
Silver brazing filler is an alloy mainly composed of silver and copper. It is used to join iron, copper or copper alloy, and is relatively expen­sive though it excels in solderability.
Electronic
balance
Siphon
Fig. 2-4-2
(1) Phosphor bronze brazing filler tends to react
with sulfur and produce a fragile compound water solution, which may cause a gas leakage. Therefore, use any other type of brazing filler at a hot spring resort, etc., and coat the surface with a paint.
(2) When performing brazing again at time of
servicing, use the same type of brazing filler.
(2) Phosphor bronze brazing filler
Phosphor bronze brazing filler is generally used to join copper or copper alloy.
(3) Low temperature brazing filler
Low temperature brazing filler is generally called solder, and is an alloy of tin and lead. Since it is weak in adhesive strength, do not use it for refrigerant pipes.
2-5-2. Flux
(1) Reason why flux is necessary
By removing the oxide film and any foreign matter on the metal surface, it assists the flo w of brazing filler.
In the brazing process, it prevents the metal surface from being oxidiz ed.
By reducing the brazing fillers surface tension, the brazing filler adheres better to the treated metal.
– 11 –
(2) Characteristics required for flux
Nitrogen gas
cylinder
Pipe
Flow meter
M
Stop valve
From Nitrogen cylinder
Nitrogen gas
Rubber plug
Activated temperature of flux coincides with the brazing temperature.
Due to a wide effective temperature range, flux is hard to carbonize.
It is easy to remove slag after brazing.
The corrosive action to the treated metal and
brazing filler is minimum.
It excels in coating performance and is harm­less to the human body.
As the flux works in a complicated manner as described above, it is necessary to select an adequate type of flux according to the type and shape of treated metal, type of brazing filler and brazing method, etc.
(3) Types of flux
Noncorrosive flux
Generally, it is a compound of borax and boric acid. It is effective in case where the br azing tem­perature is higher than 800°C.
Activated flux
Most of fluxes generally used for silver brazing are this type. It features an increased o xide film remo ving capability due to the addition of compounds such as potassium fluoride, potassium chloride and sodium fluoride to the borax-boric acid compound.
(4) Piping materials for brazing and used braz-
ing filler/flux
2-5-3. Brazing
As brazing work requires sophisticated techniques, experiences based upon a theoretical knowledge, it must be performed by a person qualified.
In order to prevent the oxide film from occurring in the pipe interior during brazing, it is effective to proceed with brazing while letting dry Nitrogen gas (N2) flow .
Never use gas other than Nitrogen gas.
(1) Brazing method to prevent oxidation
1) Attach a reducing valve and a flow-meter to the Nitrogen gas cylinder.
2) Use a copper pipe to direct the piping mate­rial, and attach a flow-meter to the cylinder.
3) Apply a seal onto the clearance between the piping material and inserted copper pipe for Nitrogen in order to prevent backflow of the Nitrogen gas.
4) When the Nitrogen gas is flowing, be sure to keep the piping end open.
5) Adjust the flow rate of Nitrogen gas so that it is lower than 0.05 m3/Hr or 0.02 MPa (0.2kgf/ cm2) by means of the reducing valv e.
6) After performing the steps above, keep the Nitrogen gas flowing until the pipe cools down to a certain extent (temperature at which pipes are touchable with hands).
7) Remove the flux completely after brazing.
Copper - Copper
Copper - Iron
(1) Do not enter flux into the refrigeration cycle. (2) When chlorine contained in the flux remains
(3) When adding water to the flux, use water
(4) Remove the flux after brazing.
Piping
material
Used brazing Used
filler flux
Phosphor copper Do not use
Silver Paste flux
Iron - Iron
Silver Vapor flux
within the pipe, the lubricating oil deterio­rates. Therefore, use a flux which does not contain chlorine.
which does not contain chlorine (e.g. distilled water or ion-exchange water).
Fig. 2-5-1 Prevention of oxidation during brazing
12
3-1. Indoor Unit
RAS-13UKV-E
Air inlet Air filter Heat exchanger
275
3. CONSTRUCTION VIEWS
790
208
606
Air outlet
790
120 590 80
Hanger
Drain hose (0.54m) Connecting pipe (0.43m)
Hanger
321
(Flare Ø6.35)
Connecting pipe (0.33m) (Flare Ø9.52)
620
235 235
For stud bolt (Ø8 to Ø10) For stud bolt (Ø6)
Minimum
distance
to wall
120 or more
275
26
190 4540
Minimum
distance
to wall
120 or more
Minimum
distance
to ceiling
66 or more
215215
Hanger
45
Front panel
Back body
48
Knock out system
60
48
6
Knock out system
32
HangerHanger
90 150 160 160 150
Center line
– 13 –
40
32
90
Installation plate outline
3-2. Outdoor Unit
RAS-13UAV-E
Hanger
A leg part
310
296
(ø6 hole pitch)
(Anchor bolt long hole pitch)
B leg part
Ø4.5 embossing (Ø4STS used) (For sunshade roof attaching)
14749,5
21
540
548
270
Fan guard
600
Ø25 drain hole
115
76
90
Ø11 x 17U-shape hole
50
(For Ø8-Ø10 anchor bolt)
8-Ø6 hole (For fixing outdoor unit)
16
Ø11 x 17 long hole
(For Ø8-Ø10 anchor bolt)
115.5
Valve cover
Charging port
157
59
21
54
Z
Connecting pipe port
(Pipe dia.Ø6.35)
Connecting pipe port
(Pipe dia.Ø9.52)
4 x Ø11 x 17U-shape hole (For Ø8-Ø10 anchor bolt)
Intake
100 or
C
310
more
200 or more
8
Mounting dimensions of anchor bolt
600
50 or
more
D
Intake
Outside line of product
Outlet
B
780 61
Z
view
A
250 or more
(Minimum distance from wall)
4 x Ø11 × 17 long hole (For Ø8-Ø10 anchor bolt)
322
Earth terminal
Detailed A leg part
50 36
11
310
296
R5.5
11
310
296
36 50
Detailed B leg part
600
2-Ø6 hole
2-Ø6 hole
600
R15
Outside line of product
Outside line of product
R15
R5.5
– 14 –
4-1. Indoor Unit
RAS-13UKV-E
COLOR IDENTIFICATIONBLU
BLK : BLACK RED : RED WHI : WHITE YEL : YELLOW BLU : BLUE GRN & YEL: GREEN & YELLOW
CN01 (BLU)
BLK
121
BLK
HEAT EXCHANGER
SENSOR (TC)
BLK BLK
THERMO SENSOR
(TA)
CN25 (WHI)
1 2 3 4 5 6 7 8 9
AND INDICATING PARTS
10
INFRARED RAYS RECEIVING
MCC-861
11
10 11
BLU
1
BLU
2
BLU
3
BLU
4
BLU
5
BLU
6
BLU
7
BLU
8
BLU
9
BLU WHI
CN03 (WHI)
121
CN13 (WHI)
1 2 3 4 5 6 7 8 9
10
10
11
11
2
2
1 2 3 4 5 6 7 8 9
MAIN P.C. BOARD
1 4
FUSE
F01
T3.15A
AC 250V
MCC-867
4. WIRING DIAGRAM
21 3
WHIBLK
CN23 CN21CN24
3
RED
R04
2
LINE
FILTER
CN08
21 43
HA JEM-A
TERMINAL
BLOCK
GRN & YEL
DB01R05
C03
INDOOR
UNIT
DC5V
DC12V
OUTDOOR
UNIT
CN10
6
(WHI)
1
1
3
3
4
4
5
5
66
5
CN07 (WHI)
1
1
2
2
CIRCUIT
3
3
4
4
POWER SUPPLY
5
5
FAN MOTOR
RED
BLK WHI
DC MOTOR YEL BLU
WHI
1
YEL YEL YEL YEL
1
2
2
3
3
4
4
5
5
LOUVER MOTOR
T a ble 4-1-1 Simple check for failure diagnosis
Check items
OPERATION indicator
1
Terminal block
2
Fuse 3.15A
3
DC 5V
4
DC 12V
5
DC 325V
6
(DC310 to 340V)
Check to see if the OPERATION indicator goes on and off when the main switch or breaker is turned on. (Check the primary and secondary voltage of the transformer.)
Check the power supply voltage between and . (Refer to the name plate.) (Check the primary and secondary voltage of the transformer.) Check the fluctuating voltage between
Check to see if the fuse blows out. (Check the R04 of the varistor.)
Check the voltage at the No.4 pin on CN13 connector of the infrared receiver. (Check the transformer and the power supply circuit of the rated voltage.)
Check for voltage at the white lead of the louver motor. (Check the transformer and the power supply circuit of the rated voltage.)
Check for voltage at the No.1 pin on CN10 connector. (Check the DB01, R05 and C03.)
Refer to the service data for the detailed failure diagnosis.
– 15 –
Diagnosis result
and . (DC 15 to 60V)
4-2. Outdoor Unit
RAS-13UAV-E
PULSE
MODULATING
VAL VE
TE
THERMOSTAT FOR COMPRESSOR
121
2
121
2
REACTOR
ORN
P10
G
E A
CONVERTER
MODULE
DB01
BRW
BU EU
BV EV BW EW BX
IGBT MODULE
BY BZ
Q200
BLU P18
112
2
CN600 CN500
P07 P08
P09
P19 P20
P17
TD
11223
CT
POEWR RELA Y
ELECTRONIC STARTER
P.C. BOARD
(MCC-813)
P21 P22 P23
3
TO
RED
WHI BLK
TS
112
2
C12 C13 C14
1
1
2
2
3
3
COMPRESSOR
11223311223
CN701
RELAY
CM
COIL for 4-WAY VALVE
3
BLK P06 CN703CN603CN602CN601
V ARIST OR
Q300
WHI
112
SURGE ABSORBER
F04 FUSE T3.15A
PMV
YEL
ORN
BLU
RED
GRY
3
44556
2
3
F01
FUSE
T25A
RED : RED ORN : ORANGE WHI : WHITE PUR : PURPUL BLK : BLACK YEL : YELLOW BLU : BLUE GRY : GRY BRW: BROWN PNK : PINK
6
P01
BLK ORN
P03
WHI
P02
P11 P12
P13
P14
CN300
CN301
IGBT : Insulated Gate Bipolar Transistor
COLOR IDENTIFICATIONBLU
121
1
1
2
2
3
3
1
1
2
2
3
3
4
4
5
5
N
L 3 2 1
2
REACTOR
PUR
RED WHI BLK
YEL
PNK GRY
F AN MOTER
FM
POWER SUPPLY 220-240V~ 50/60Hz
TO INDOOR UNIT
– 16 –
5-1. Indoor Unit
RAS-13UKV-E
5. SPECIFICATIONS OF ELECTRICAL PARTS
No.
1
Fan motor (for indoor)
2
Thermo. sensor (TA-sensor)
3
DC-DC transformer (T01)
4
Microcomputer Heat exchanger temp. sensor
5
(TC-sensor)
6
Line filter (L01)
7
Diode (DB01)
8
Capacitor (C03)
9
Fuse (F01)
10
Power supply IC (IC01)
11
Varistor (R21, R109)
12
Resistor (R01)
13
Louver motor
Parts name
5-2. Outdoor Unit
RAS-13UAV-E
Type
ICF-340-30-2
( – )
SWT-70
µPD780024AGK
( – )
SS11V-06270
D3SBA60
KMH450VNSN120M25C
FCU 250V, 3.15A
STR-L472
15G561K
RF-5TK4R7
MP24GA
Specifications
DC340V, 30W 10k at 25°C DC390V, Secondary DC15V, 12V, 7V
10k at 25°C
27mH, AC0.6A 4A, 600V 120µF, 450V T3.15A, 250V
560V
4.7, 5W Output (Rated) 1W, 16poles, 1phase DC12V
No.
SC coil
1
(Noise filter)
2
DC-DC transformer
3
Reactor
4
Outside fan motor Suction temp. sensor
5
(TS sensor) Discharge temp. sensor
6
(TD sensor) Outside air temp. sensor
7
(TO sensor) Heat exchanger temp. sensor
8
(TE sensor)
9
Terminal block (6P)
10
Fuse
11
Electrolytic capacitor
12
Transistor module
Parts name
L03 L01
Model name
ADR2520-R15TB ADR2516-0R6TB
SWT-43
CH-38
ICF-140-43-1
(Inverter attached)
(Inverter attached)
(Inverter attached)
(Inverter attached)
——
For protection of switching power source
For protection of inverter input overcurrent
LLQ2G501KHUATF , 400LISN500K35F
6MBI25GS-060-01 or 6MBI25GS-060-01A
Rating
15A, 0.6mH 20A, 150µH Primary side DC280V, Secondary side
7.5V x 1, 13V x 1, 26.5V x 3, 16V x 1, 15V x 1 L=10mH, 16A x 2 DC140V, 43W
10k (25°C)
62k (20°C)
10k (25°C)
10k (25°C)
20A, AC250V
3.15A, AC250V 25A, AC250V 500µF, DC400V X 3 pieces 25A, 600V
13
Compressor
14
Compressor thermo.
15
Converter module
DA91A1F-44F
US-622KXTMQO-SS
MP7003
– 17 –
3-phases 4-poles 750W OFF: 125 ± 4°C, ON: 90 ± 5° C Diode: 25A, 600V, IGBT: 40A, 600V
6. REFRIGERANT CYCLE DIAGRAM
6-1. Refrigerant Cycle Diagram
RAS-13UKV-E/RAS-13UAV-E
P
Pressure measurement Gauge attaching port
Vacuum pump connecting port
Deoxidized copper pipe
Outer dia. : 9.52mm Thickness : 0.8mm
INDOOR UNIT
Indoor heat
exchanger
Cross flow fan
Deoxidized copper pipe Outer dia. : 6.35mm Thickness : 0.8mm
Sectional shape of heat insulator
T1
Temp. measurement
Allowable height
difference : 10m
Allowable pipe length
Max. : 15m
4-way valve (CHV-0213)
TS
Temp. measurement
T2
Muffler
Muffler
TD
Compressor DA91A1F-44F
Outdoor heat
exchanger
Propeller fan
OUTDOOR UNIT
TO
Split capillary
Ø1.5 x 200 Ø1.5 x 200
TE
Strainer
Pulse modulating valve at liquid side (SEV15RC2)
Refrigerant amount : 0.8kg
NOTE :
Gas leak check position Refrigerant flow (Cooling) Refrigerant flow (Heating)
NOTE :
The maximum pipe length of this air conditioner is 15 m. The additional charging of refrigerant is unnecessary because this air conditioner is designed with charge-less specification.
– 18 –
6-2. Operation Data
<Cooling>
Temperature
condition (°C)
Indoor Outdoor
27/19 35/–
Model
name
13UKV-E
Standard
pressure
P (MPa)
0.8 to 1.0
Heat exchanger
pipe temp.
T1 (°C) T2 (°C)
9 to 11 49 to 50
Indoor fan
mode
High
Outdoor fan
mode
High
Compressor
revolution
<Heating>
Temperature
condition (°C)
Indoor Outdoor
20/– 7/6
Model
name
13UKV-E
Standard
pressure
P (MPa)
2.5 to 2.7
Heat exchanger
pipe temp.
T1 (°C) T2 (°C)
42 to 44 0 to 3
Indoor fan
mode
High
Outdoor fan
mode
High
Compressor
revolution
NOTES :
(1) Measure surface temperature of heat exchanger pipe around center of heat exchanger path U bent.
(Thermistor themometer)
(2) Connecting piping condition : 5 m
(rps)
77
(rps)
83
– 19 –
7-1. Indoor Unit
RAS-13UKV-E
Heat Exchanger Sensor
7. CONTROL BLOCK DIAGRAM
Indoor Unit Control Panel
M.C.U
Functions
Powerful
Display
Temperature Sensor
Infrared Rays Signal Receiver
Infrared
Rays
Initializing Circuit
36.7kHz
Clock Frequency
Oscillator Circuit
Power Supply
Remote
Controller
Noise Filter
From Outdoor Unit
Circuit
Louver Control
3-minute Delay at Restart for Compressor
Motor Revolution Control
Processing
(Temperature Processing)
Timer
Serial Signal Communication
Louver ON/OFF Signal
Louver Driver
Serial Signal Transmitter/Receiver
Serial Signal Communication
Operation
Display
Timer
Display
Filter
Sign Display
PRE DEF.
Sign Display
Indoor
Fan Motor
Louver
Motor
REMOTE CONTROLLER
Infrared
Rays
Remote Controller
Operation (START/STOP)
Operation Mode Selection
AUTO, COOL, DRY, HEAT, FAN ONLY
Thermo. Setting
Fan Speed Selection
ON TIMER Setting
OFF TIMER Setting
Louver AUTO Swing
Louver Direction Setting
ECO
Hi-POWER
– 20 –
RAS-13UAV-E
7-2. Outdoor Unit (Inverter Assembly)
For INDOOR UNIT
220–230–240 V
to 50/60 Hz
MICRO-COMPUTER BLOCK DIAGRAM
MCC813 (P.C.B) OUTDOOR UNIT
Inddor unit
send/receive
circuit
M.C.U
PWM synthesis function
Input current release control
Discharge
temp. sensor
IGBT over-current detect control
Outdoor fan control
High power factor correction control
Outdoor air
temp. sensor
– 21 –
Suction temp.
sensor
Inverter output frequency control
A/D converter function
P.M.V. control
Discharge temp. control
4-way valve control
Heat exchanger
temp.sensor
Signal communication to indoor unit
Rotor position
detect circuit
Rotor position
detect circuit
Gate drive
circuit
Gate drive
circuit
Over current detect circuit
Over current
sensor
Noise
Filter
High Power
factor Correction
circuit
Input current
sensor
Driver circuit
of P.M.V.
P.M.V.
Clock
frequency
16MHz
Converter
(AC DC)
Relay circuit
4-way
valve
Over current
sensor
Over current
sensor
Inverter
(DC AC)
Inverter
(DC
AC)
P.M.V : Pulse Modulating Valve M.C.U : Micro Control Unit
Outdoor
Fan motor
Compressor
8. OPERATION DESCRIPTION
8-1. Outline of Air Conditioner Control
This air conditioner is a capacity-variable type air conditioner, which uses DC motor for the indoor fan motor and the outdoor fan motor. And the capacity­proportional control compressor which can change the motor speed in the range from 13 to 110 rps is mounted. The DC motor drive circuit is mounted to the indoor unit. The compressor and the inverter to control fan motor are mounted to the outdoor unit.
The entire air conditioner is mainly controlled by the indoor unit controller.
The indoor unit controller drives the indoor fan motor based upon command sent from the remote control­ler, and transfers the operation command to the outdoor unit controller.
The outdoor unit controller receives operation command from the indoor unit side, and controls the outdoor fan and the pulse modulating valve. (P.M.V) Besides, detecting rev olution position of the com­pressor motor, the outdoor unit controller controls speed of the compressor motor by controlling output voltage of the inv erter and switching timing of the supply power (current transfer timing) so that motors drive according to the operation command. And then, the outdoor unit controller transfers re versely the operating status information of the outdoor unit to control the indoor unit controller.
As the compressor adopts four-pole brushless DC motor, the frequency of the supply power from inverter to compressor is two-times cycles of the actual number of revolution.
(1) Role of indoor unit controller
The indoor unit controller judges the operation commands from the remote controller and assumes the following functions.
Judgment of suction air temperature of the indoor heat exchanger by using the indoor temp. sensor. (TA sensor)
Temperature setting of the indoor heat ex­changer by using heat exchanger sensor (TC sensor) (Prevent-freezing control)
Louver motor control
Indoor fan motor operation control
LED (Light Emitting Diode) display control
Transferring of operation command signal
(Serial signal) to the outdoor unit
Reception of information of operation status (Serial signal including outside temp. data) to the outdoor unit and judgment/display of error
(2) Role of outdoor unit controller
Receiving the operation command signal (Serial signal) from the indoor controller, the outdoor unit performs its role.
Compressor operation control
Operation control of outdoor fan motor
P.M.V . control
Detection of inverter input current and current
release operation
Over-current detection and prevention oper a­tion to IGBT module (Compressor stop func­tion)
Compressor and outdoor fan stop function when serial signal is off (when the serial signal does not reach the board assembly of outdoor control by trouble of the signal system)
Transferring of operation information (Serial signal) from outdoor unit to indoor unit
Detection of outdoor temperature and opera­tion revolution control
Defrost control in heating operation (Temp. measurement by outdoor heat exchanger and control for four-way valve and outdoor fan)
(3) Contents of operation command signal (Serial
signal) from indoor unit controller to outdoor unit controller
The following three types of signals are sent from the indoor unit controller.
Operation mode set on the remote control
Compressor revolution command signal
defined by indoor temperature and set tem­perature (Correction along with variation of room temperature and correction of indoor heat exchanger temperature are added.)
For these two types of signals ( [Operation mode] and [Compressor revolution] ), the outdoor unit controller monitors the input current to the inverter, and perfo rms the followed operation within the range that current does not exceed the allowable value.
Temperature of indoor heat exchanger by indoor heat exchanger sensor (Minimum revolution control)
Operations follow ed
to judgment of serial signal from indoor
side.
– 22 –
(4) Contents of operation command signal (Serial
signal) from outdoor unit controller to indoor unit controller
The following signals are sent from the outdoor unit controller.
The current operation mode
The current compressor revolution
Outdoor temperature
Existence of protective circuit operation
For transf erring of these signals, the indoor unit controller monitors the contents of signals, and judges existence of trouble occurrence.
Contents of judgment are described below.
Whether distinction of the current operation status meets to the operation command signal
Whether protective circuit operates When no signal is received from the outdoor
unit controller, it is assumed as a trouble.
8-1-2. Current Release Control
The outdoor main circuit control section (Inverter assembly) detects the input current to the outdoor unit. If the current value with compressor motor speed instructed from indoor side exceeds the specified value, the outdoor main circuit control section controls compressor motor speed by reduc­ing motor speed so that value becomes closest to the command within the limited value.
8-1-3. Power Factor Improvement Control
Po w er factor improvement control is performed mainly aiming to reduce the current on much power consumption of cooling/heating operation. Control­ling starts from the time when input power has reached at a certain point. To be concrete, IGBT of the power factor impro vement circuit is used, and the power factor is improved by keeping IGBT on f or an arbitrary period to widen electro-angle of the input current.
8-1-1. Capacity Control
The cooling and heating capacity is varied by changing compressor motor speed. The inverter changes compressor motor speed by changing AC 220–230–240V power to DC once, and controls capacity by changing supply power status to the compressor with transistor module (includes 6 transistors). The outline of the control is as follows: The revolution position and re volution speed of the motor are detected by detecting winding electromo­tive force of the compressor motor under operation, and the revolution speed is changed so that the motor drives based upon revolution speed of the operation command by changing timing (current transfer timing) to exchange in verter output voltage and supply power winding.
Detection of the revolution position f or controlling is performed 12 times per 1 revolution of compressor.
The range of supply power frequency to the com­pressor differs according to the operation status (COOL, HEAT, DRY).
Table 8-1-1 Compressor revolution range
Operation
mode
COOL
HEAT
Model
name
13UKV-E
Compressor
revolution (rps)
13 to 88
16 to 110
8-1-4. Prevent-Freezing Control
The indoor heat exchanger sensor detects refriger­ant vapor temperature in COOL/DR Y operation. If the temperature is below the specified value , compressor motor speed is reduced so that opera­tion is performed in temperature below the specified value to prev ent-freezing of indoor heat exchanger.
8-1-5. P. M. V. (Pulse Modulating Valve)
Using P.M.V., refrigerant flow of refrigeration cycle is varied for the optimum temperature.
After the power has been turned on, when a serial operation signal is received from indoor at the first time, or when PMV alarm is detected and the equipment is reactivated, move the valve once until it hits on the stopper for positioning of the valve. In this case, ticktack sound may be heard.
8-1-6. Louver Control
(1) V e rtical air flow louvers
Positions of v ertical air flow louvers are auto­matically controlled according to the operation
status (AUTO : A , COOL : , DRY : , HEAT : , FAN ONLY : ). Besides, positions
of vertical air flow louvers can be arbitrarily set by pushing the [FIX] button.
(2) Swing
If the [SWING] button is pushed during running operation, vertical air flow louvers start swinging. When the [FIX] button is pushed, swinging stops.
– 23 –
8-1-7. Indoor Fan Control (DC Fan Motor)
(1) The indoor fan is operated by the stepless speed
change DC motor.
(2) For air flow level, speed of the indoor fan motor
is controlled in five steps (LOW, LOW+, MED , MED+ and HIGH). If AUTO mode is selected, the fan motor speed is automatically controlled by the difference between the preset tempera­ture and the room temperature.
LOW+= LOW + MED
2
MED+= MED + HIGH
Operation
mode
COOL
DRY
HEAT
T ab le 8-1-2
Fan
mode
H M
L
H M
L
RAS-13UKV-E
Motor speed Air flow rate
(rpm) (m³/h)
1210 530 1010 420
810 330
780 320 1290 620 1110 470
930 380
2
8-1-8. Outdoor Fan Control (DC Fan Motor)
Although the outdoor fan motor drives the outdoor fan by non-step variable system of the re volution speed, the revolution speed is restricted to three steps on the convenience of controlling. If a strong wind is lashing outside of the room, the operation may be continued as the outdoor f an stops in order to protect the outdoor fan motor.
If a fan lock occurred due to entering of foreign matter, the air conditioner stops and an alarm is displayed.
<COOL, DRY>
Model name
Compressor revolution (rps)
TO 38°C
Outdoor temp. sensor TO TO < 38°C
TO < 15°C
TO 38°C
ECONO. operation TO < 38°C
TO < 15°C
TO is abnormal
<HEAT>
Model name
Compressor revolution (rps)
Outdoor temp. sensor TO
ECONO. operation
TO is abnormal
TO 5°C TO < 5°C TO 5°C TO < 5°C
T a ble 8-1-3
RAS-13UAV-E
To 13.8 To 34.7 From 35.3
390 840 840 390 700 840
390 390 700 840 390 390 700
390 700 700 840
T a ble 8-1-4
RAS-13UAV-E
To 16.8 To 57.4 From 58.0
390 650 840 650 650 840 390 390 650 390 650 650 390 650 840
– 24 –
Loading...
+ 54 hidden pages