Toshiba RAS-13SKHP-ES2, RAS-13S2AH-ES2 SERVICE MANUAL

SERVICE MANUAL
AIR CONDITIONER
SPLIT WALL TYPE
FILE NO. SVM-10026
RAS-13SKHP-ES2 / RAS-13S2AH-ES2
February, 2010
CONTENTS
1. SPECIFICATIONS
2. CONSTRUCTION VIEWS
2-1 Indoor Unit
2-2 Outdoor Unit
3. WIRING DIAGRAM
4.
SPECIFICATION OF ELECTRICAL PARTS
5. REFRIGERATION CYCLE DIAGRAM
6. CONTROL BLOCK DIAGRAM
7. OPERATION DESCRIPTION
7-1 Remote Control
7-2 Outline of Air Conditioner Control 7-3 Description of Operation Mode 7-4 Drescription of Safety and Reliability Prevention Function 7-5 One-Touch Operation 7-6 Hi POWER Operation 7-7 QUIET Operation 7-8 ECO Operation 7-9 COMFORT SLEEP Operation 7-10 FILTER Check lamp 7-11 Auto Restart Function 7-12 Self-Cleaning Operation
FILE NO. SVM-10026
8. INSTALLATION PROCEDURE
8-1 Safety Cautions 8-2 Installation Diagram of Indoor and Outdoor Units 8-3 Installation 8-4 Indoor Unit 8-5 Outdoor Unit 8-6 How to Set Remote Control Selector Switch 8-7 Others
9. TROUBLESHOOTING CHART
9-1 Troubleshooting Procedure 9-2 Basic Check Items 9-3 Primary Judgement 9-4 Self-Diagnosis by Remote Control (Check Code) 9-5 Troubleshooting Flowcharts
9-6 Troubleshooting for Remote Control (Including the Indoor P.C. Board)
10. PART REPLACEMENT
10-1 Indoor Unit 10-2 Outdoor Unit
11. EXPLODED VIEWS AND PARTS LIST
11-1 Indoor Unit (E-Parts Assy) 11-2 Indoor Unit
11-3 Outdoor Unit

1. SPECIFICATIONS

/
/
/
/
FILE NO. SVM-10026
MODEL
ITEM
Capacity
kW
Phase
Power source
V
Hz Power consumption kW Power factor % Running Indoor A Current Outdoor A Starting current A Moisture removal lit/h Noise Indoor (H/M+/M/L+/L) dB
Outdoor (220-240V) dB
Refrigerant Name of refrigerant
Rated amount kg Refrigerant control Interconnection Gas side size mm pipe Connection type
Liquid side size mm
Connection type
Maximum length
(One way)
Maximum height
difference
m
m
INDOOR UNIT
Dimensions Height mm
Width mm
Depth mm Net weight kg Evaporator type Indoor fan type Airflow volume High fan
Medium fan
Low fan
3
m
3
m
3
m Fan motor output W Air filter
OUTDOOR UNIT
Dimensions Height mm
Width mm
Depth mm Net weight kg Condenser type Outdoor fan type Airflow volume
3
m Fan motor output W Compressor Model
Output W Safety device Louver type Usable outdoor temperature range °C
RAS-13SKHP-ES2 / RAS-13S2AH-ES2
Cooling
220V 240V
3.73 3.78 4.15
Heating
220V 240V
4.25
1
220 240
50
1.14 96
1.19
88
1.14 1.18 96 86
0.15
5.25
5.65 5.25 5.60 22
2.0
41/38/35/33/31
50 51 50 51
R410A
1.05
Capillary tube
12.7
Flare connection
6.35
Flare connection
1
15*
6
RAS-13SKHP-ES2
275 790 205
9
Finned tube
Cross flow fan
h h h
600 430 380
620 520 400
20
Filter (RB-A620DE)
RAS-13S2AH-ES2
550 780 290
34
Finned tube
Propeller fan
h
2120 2200 2120 2200
42
PA145G1C-4FT1
1100
Fuse, Overload relay
Automatic louver
15 ~ 43
10 ~24
2
Note : 1
·
Capacity is based on the following temperature conditions.
FILE NO. SVM-10026
Temperature
Indoor unit inlet air temperature
Outdoor unit inlet air temperature
Note : 2
*1 No need to charge extra refrigerant.
Condition
Cooling Heating
(DB) 27°C20°C
(WB) 19°C15°C
(DB) 35°C7°C
(WB) 24°C6°C
JIS C9612
- 3 -
2-1. Indoor Unit
FILE NO. SVM-10026

2. CONSTRUCTION VIEWS

790
Front panel
63
7
Knock out system
48
275
Air filter
116
Heat exchanger
Installation plate hanger
Air inlet
62 69
193480
205
Knock out system
49
56
Wireless remote controller
48
63
7
157
19
Installation plate hanger
Connecting pipe (0.35m)
(Flare 12.7mm)
84.5
Minimum
distance
to wall
275
170 or more
40
Hanger
84.5 150 84.5
621
235
215
Hanger
Minimum
distance
to ceiling
235
215
160.5 160.5 150
Center line
- 4 -
Drain hose (0.50m)
Connecting pipe (0.40m)
6.35mm)(Flare
84.5
65 or more
Minimum
distance
to wall
170 or more
Hanger
Installation plate outline
63
Remote controller holder
45
190
40
125
26
2.2. Outdoor Unit
600
50
36
320
306
A detail Drawing (Back leg)
R5.5
R
Ø
15
6 hole
28
86
320
Ø
25 Drain outlet
FAN-GUARD
436
Ø
FILE NO. SVM-10026
A
108 125
306
320
Ø
2
-
Ø
11 x 14
(For 8 -
Ø
Hole
10 anchor bolt)
Ø
6 hole
11x14 hole
Ø
B Detail Drawing (Front leg)
36 50
R
15
COVER-PV
Z
290
550
275
320 342
Electrical part cover
Liquid side (Flare 6.35)
Ø
Gas side (Flare 12.7)
Ø
5
4
S
ervice port
Z View
9060090
69
129
84
100 or more
321
100 or more
Air outlel
600
Air intlel
600 or more
600 or more
4x 11 Long holes(For 8- 10 anchor bolt)
Ø
Ø
Ø

3. WIRING DIAGRAM

FILE NO. SVM-10026
OUTDOOR
OUTDOOR
OUTDOOR TERMINAL
TERMINAL BLOCK
BLOCK
COMPRESSOR
COMPRESSOR
BLK
BLK
BLK
BLK
BLK
BLK
BLK
BLK
PNK
PNK
WHI
WHI
(L)2(N)
(L)2(N)
(L)2(N)
(L)2(N)
(L)
(L)
1
1
1
1
1
RED
RED
(N)
(N)
2
2
BLU
BLU
BLU
BLU
BLU
BLU
SOLENOID COIL
SOLENOID COIL
CAPACITOR
CAPACITOR
RED
RED
RED
RED
CAPACITOR
CAPACITOR
CAPACITOR
CAPACITOR
CAPACITOR
CAPACITOR
3
3
3
3
313
BLU
BLU
BLU
BLU
BLU
BLU
FAN
FAN MOTOR
MOTOR
4
4
4
4
4
4
WHI
WHI
6
CHASSIS
CHASSIS
BLK
BLK
INDOOR
OUTDOOR
FILE NO. SVM-10026

4. SPECIFICATION OF ELECTRICAL PARTS

4-1. Indoor Unit
No. Parts name Type Specifications
1 Fan motor (for indoor) 2 Thermo sensor (TA-sensor) 10k at 25 C 3 Micro Power Module (M01) 4 Microcontroller unit (IC30) 5 Heat exchanger sensor
(TC-sensor) 6 Line filter (L01) 7 Bridge rectifier (DB01) DB105G 1A, 600 V 8 Capacitor (C03) 9 Fuse (F01) BET 6.3A T6.3A, 250VAC
10 Varistor (R06, R07) 11 Resistor (R01 ) RF-2TK5R6 5.6 , 2 W 12 Louver motor MP24Z3T 12VDC 13 Relay (Comp., RY01) 14 Relay (Fan, RY03) 15 Relay (Solenoide, RY04)
AFN-220-20-4D
GPS-9W-AA
TMP87CM40ANG
LC*SS11V-R06270
400MXC47MEFCSN20X20
SR561K14DO
G4A-1A-E-CA
202N-1AC-C E 202N-1AC-C E
Rating 3A/AC250 V, 12VDC
Rating 3A/AC250 V, 12VDC
AC Motor with 145 C thermo fuse
W
DC 390V, Secondary DC 12V
W
10k at 25 C
27mH, 600mA
47mF, 400 V
560 V
W
Rating 25A/AC250 V, 3-48VDC
°
°
°
4-2. Outdoor Unit
No. Parts name
1 Compressor
Fan motor
2
(for outdoor)
Running capacitor
3
(for fan motor) Running capacitor
4
(for compressor) Solenoid coil
(for 4-way valve)
5
(for Heat pump
model)
Type
Output (Rated) 1100W, 2poles, 1 phase, 220 240V, 50Hz
PA145G1C-4FT1
WLF-240-42A
DS451155NPQB AC 450V, 1.5µF
B32332I5306J063 AC 450V, 30µF
STF-01AJ503H1
Winding resistance (Ω ) C-R C-S
(at 20°C) 2.67 4.48 Output (Rated) 42W, 6poles, 1 phase, 220 240V, 50Hz Winding resistance () Red-Black White-Black (at 20°C) 188
AC 220 240V, 50Hz
Specifications
289

5. REFRIGERATION CYCLE DIAGRAM

FILE NO. SVM-10026
Indoor unit
Cooling
0.39 m (Connecting pipe)
Æ12.7
O.D.:12.7 mm O.D.:6.35 mm
Cooling
Heating
Heating
P
Packed valve
(Æ12.7)
Heating
4-way valve
Cooling
Compressor
PA145G1C-4FT1
Accumulator
Heat exchanger
Cross flow fan
T1
Capillary tube
Æ1.5 x 1500
Packed valve
(Æ6.35)
Capillary tube
Æ1.0 x 500
l
0.49 m
(Connecting pipe)
Æ6.35
l
Heat exchanger
Refrigerant
R410A : 1.05 kg.
Cooling Heating
Propeller fan Outdoor unit
Mark ( ) means check points of Gas Leak.
Ambient temp.
50Hz
Standard
pressure
(MPaG)
P
Surface temp. of heat
exchanger interchanging
pipe
T1
(°C)
Fan speed
(indoor)
conditions DB/WB
(°C)
Indoor Outdoor
Standard 2.72 46.9 High 20/15 7/6
Heating Overload*1
Low temperature 2.51 37.2 High 20/
3.70 59.9
Low 27/- 24/18
-10/-10
-
Standard 0.91 9.5 High 27/19 35/24
Cooling Overload 1.26 14.6 High 32/23 43/26
Low temperature 0.77 1.5 Low 21/15 21/15
Note
Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor)
·
·
*1 During heating overload operation, a value for the high temperature limit control operation is included.

6. CONTROL BLOCK DIAGRAM

FILE NO. SVM-10026
Heat Exchange sensor
Thermo. Sensor
Current Sensor
(Compressor Current)
Infrared Rays Signal Reciver
Main Unit Control Panel
Functions
 Louver Control
3-minutes Delay at Restart
for Compressor
Initiallizing Circuit
Clock Frequency Oscillator Circuit
Power Supply
Circuit
Noise Filter Relay Driver, Louver Driver
Motor Revolution Control
Processing
(Temperature Processing)
Timer
Compressor
ON/OFF
Signal
Outdoor Fan
Relay
RY01
M.C.U.
ON/OFF
Signal
Relay
4-Way Valve
ON/OFF
Signal
RY03
Operation
Display
Timer
Display
Filter Sign
Display
Hi Power
Sign Display
PRE DEF.
Sign Display
Indoor Fan
Motor
Louver
ON/OFF
Signal
Louver
Motor
Relay
RY04
220-240 V~, 50Hz
REMOTE CONTROL
Operation Mode Selection
AUTO, COOL, DRY, HEAT, FAN ONLY
Compressor 4-Way Valve
Remote Control
Operation ( )
Temperature Setting
Fan Speed Selection
ON TIMER Setting
OFF TIMER Setting
Louver Auto Swing
Louver Direction Setting
ECO
Hi power
TIMER 1.3.5.9H
COMFORT SLEEP
QUIET
Outdoor Fan Motor
Infrared Rays
9

7. OPERATION DESCRIPTION

FILE NO. SVM-10026
7-1. Remote control
7-1-1. Function of Push Putton
11 Infrared signal emitter
1
11
2
Start/Stop button
3
Mode select button (MODE)
4
Temperature button (TEMP)
5
Fan speed button (FAN)
6
Swing louver button (SWING)
7
Set louver button (FIX)
8
On timer button (ON) Off timer button (OFF)
9
18
10
Sleep timer button (SLEEP)
19
Timer setup button (SET)
11 12
20
Timer clear button (CLR)
13
Memory and Preset button (PRESET)
14
One Touch button (ONE-TOUCH)
15
High power button (Hi-POWER)
16
Economy button (ECO)
17
Quiet button (QUIET)
18
Comfort sleep button (COMFORT SLEEP)
19
Filter reset button (FILTER)
Clock Reset button (CLOCK)
20 21
Check button (CHK)
13
14
17
10 21
19
1
TOSHIBA
PRESET
TEMP
ONE-TOUCH
2
QUIET
SWING
FIX Hi-POWER ECO
6 7
8
TIMER
SLEEP
CHK
ON
FILTER
OFF
CLOCK
FAN
MODE
COMFORT
SLEEP
CLR
SET
5
4
3
18
15 16
12
9
11
20
10
FILE NO. SVM-10026
7-1-2. Display of Remote Control
All indications, except for the clock time indicator, are displayed by pressing the button.
1. Transmission mark
This transmission mark remote controller transmits signals to the indoor unit.
indicates when the
2. Mode indicator
Indicates the current operation mode. (A : Auto, : Cool,
: Dry, : Heat, : Fan only)
3. Temperature indicator
Indicates the temperature setting. (17°C to 30°C)
4. FAN speed indicator
Indicates the selected fan speed. AUTO or five fan speed levels
LOW , LOW+ , MED , MED+ ,
( HIGH ) can be shown.
Indicate Auto will be appear with Dry operation
( : Dry) only.
9
1
12
2
13
10
5. TIMER and clock time indicator
The time setting for timer operation or the clock time is indicated.
The current time is always indicated except during TIMER operation.
6. Hi-POWER indicator
Indicates when the Hi-POWER operation starts. Press the Hi-POWER button to start and press it
again to stop the operation.
7. (PRESET) indicator
Flashes for 3 seconds when the PRESET button is pressed during operation.
The button for more than 3 seconds while the mark is
blinks.
Press another button to turn off the mark.
mark is shown when holding down the
8. ECO indicator
Indicates when the ECO is in activated. Press the ECO button to start and press it again
to stop operation.
9. A, B change indicator remote controller
When the remote controller switching function is set, “B” appears in the remote controller display. (When the remote controller setting is “A”, there is no indication at this position.)
10. Comfort sleep
Indicates when comfort sleep is activaled. Press comfort sleep button to selectter
11
6
3
8
7
4
5
11. Quiet
Indicates when quiet is activated. Press quiet button to start and press it again to stop operation.
12. One-Touch
Indicates when one touch comfort is activated. Press one-touch button to start the operation.
13. Swing
Indicates when louver is swing. Press swing button to start the swing operation and press it again to stop the swing operation.
- 11 -
FILE NO. SVM-10026
7-2. Outline of Air Conditioner Control
This is a fixed capacity type air conditioner, which uses a AC motor for an indoor fan. The AC motor drive circuit is mounted in the indoor unit. And electrical parts which operate the compressor and the outdoor fan motor, are mounted in the outdoor unit. The air conditioner is mainly controlled by the indoor unit controller. The controller operates the indoor fan motor based upon commands transmitted by the remote control and transfers the operation commands to the outdoor unit. The outdoor unit receives operation commands from the indoor unit, and operates the outdoor fan motor and the compressor.
(1) Role of indoor unit controller
The indoor unit controller receives the operation commands from the remote control and executes them.
Temperature measurement at the air inlet of the
indoor heat exchanger by the indoor
temperature sensor
Temperature measurement of the indoor heat
exchanger by the heat exchanger sensor
Louver motor control
Indoor fan motor operation control
LED display control
Transferring of operation commands to the
outdoor unit
Receiving of information of the operation status
and judging of the information or indication of error
(2) Role of outdoor unit controller
The outdoor unit controller receives the operation commands from the indoor controller and executes them.
Compressor operation
control
Operation control of
outdoor fan motor
Operations according to the commands from the indoor unit
Turning off the compressor and outdoor fan
when the outdoor unit receives the shutdown command
Defrost control in heating operation
(Temperature measurement by the Indoor heat exchanger, control the four-way valve and
outdoor fan motor control)
7-2-1. Louver control
(1) Vertical air flow louver
Position of veritcal air flow louver is automatically controlled according to the operation mode. Besides, position of vertical air flow louver can be arbitrarily set by pressing [FIX] button. The louver position which is set by [FIX] button is stored in the microcomputer, and the louver is automatically set at the stored position for the next operation.
(2) Swing
If [SWING] button is pressed when the indoor unit is in operation, the vertical air flow louver starts swinging. When [SWING] button is pressed, it stops swinging.
7-2-2. Indoor Fan Control
The operation controls the fan speed at indoor unit side. The indoor fan (cross flow fan) is operated by the phase control induction motor. The fan rotates in 5 stages in MANUAL mode, and in 5 stages in AUTO mode, respectively. (Table 7-2-3)
1) When setting the fan speed to L, L+,M, M+ or H on the remote controller, the operation is performed with the constant speed shown in Table 7-2-1 and Table 7-2-2
Table (7-2-1) Cooling
Indication
L L+
M M+
H
Fan speed
Low
(L + M) / 2
Med
(M + H) / 2
High
Table (7-2-2) Heating
Indication
L L+
M M+
H
Fan speed
Low
(L + M) / 2
Med
(M + H) / 2
High
Table 7-2-3 Indoor fan and air flow rate
Cooling UH H M
OPERATION
MODE
rpm
Air flow volume (m3/h)
Fan only
Dry
Heat HH
2) When setting the fan speed to AUTO on the remote controller, revolution of the fan motor is controlled to the fan speed level show in Table 7-2-3 according to the setup temperature, room temperature, and heat exchanger temperature.
FAN T AP
M+
H M L-
M+
M
1000
M
L+
M+
UH
M+
1250
1300
620 600 550 520 430 400 400 350
1150 1100
L+
L+
L+
L-
L UL SL
850
850
- 12 -
L-
L
L
L-
L
750 UL650 SL600
800
380
UL SL
310
280
550
260
500
240
FILE NO. SVM-10026
7-3. Description of Operation Mode
(1) When turning on the breaker, the operation lamp
blinks. This means that the power is on (or the power supply is cut off.)
(2) When pressing [ ] button on the
remote control, receiving beep sounds from the indoor unit, and the next operation is performed together with opening the vertical air flow louver.
(3) Once the operation mode is set, it is memorized in
the microcomputer so that the previous operation can be effected thereafter simply by pressing [ ] button.
7-3-1. Fan only operation
([MODE] button on the remote control is set to the fan only operation.)
(1) When [FAN] button is set to AUTO, the indoor fan
motor operates as shown in Fig. 7-3-1. When [FAN] button is set to LOW, LOW+, MED, MED+ or HIGH, the motor operates with a constant air flow.
°C
7-3-2. Cooling operation
([MODE] button on the remote control is set to the cooling operation.)
(1) The compressor, 4-way valve, outdoor fan and
operation display lamp are controlled as shown in Fig. 7-3-2.
° C
ON ON
OFF OFF OFF ON
4-way valve
Compressor
Outdoor fan
(Room temp.) (Preset temp.)
Preset temp.
0.5
0
Fig. 7-3-2
display lamp
OPERATION
+3 +2.5 +2
+1.5 +1 +0.5
(Room temp.) (Preset temp.)
Preset temp.
0
(Preset temp.: 24 °C)
NOTE 1 : *1 : Fan speed = (M + L) x 3/4 + L
*2 : Fan speed = (M + L) x 2/4 + L *3 : Fan speed = (M + L) x 1/4 + L
2 : The Hi Power, ECO and COMFORT SLEEP
operation can not be set
(Linear approximation from M+ and L)
Fig. 7-3-1 Setting of air flow [FAN:AUTO]
M+
*1 *2 *3
(2) When [FAN] button is set to AUTO, the indoor fan
motor operates as shown in Fig. 7-3-3. When [FAN] button is set to LOW, LOW+, MED, MED+ or HIGH, the motor operates with a constant air flow.
°C
(Room temp.) (Preset temp.)
Preset temp.
+3 +2.5 +2 +1.5 +1 +0.5
0
-0.5
M+
*1 *2 *3
NOTE1 : *1 : Fan speed = (M + − L) x 3/4 + L
*2 : Fan speed = (M + − L) x 2/4 + L *3 : Fan speed = (M + L) x 1/4 + L
(Linear approximation from M+ and L)
Fig. 7-3-3 Setting of air flow [FAN:AUTO]
-
13
-
FILE NO. SVM-10026
7-3-3. Dry operation
([MODE] button on the remote control is set to the dry operation.)
(1) The compressor, 4-way valve, outdoor fan and
operation display lamp are controlled as shown in Fig. 7-3-4.
° C
ON:6min.
OFF:4min.
ON
ON:5min.
OFF:5min.
OFF
4-way valve
Outdoor fan
(Room temp.) (Preset temp.)
Preset temp.
+3
+2
+1
ON:6min.
OFF:4min.
OFF
ON:5min.
OFF:5min.
OFF
0
Compressor
Fig. 7-3-4
7-3-4. Heating operation
(1) The compressor, 4-way valve, outdoor fan and
Preset temp.
display lamp
OPERATION
([MODE] button on the remote control is set to the heating operation.)
operation display lamp are controlled as shown in Fig. 7-3-6.
° C
0
0.5
(Room temp.) (Preset temp.)
ON
OFF
ON
Compressor
ON
OFF
ON
4-way valve
Outdoor fan
OPERATION
display lamp
Fig. 7-3-6
(2) The microprocessor turns the compressor on and
off at the regular intervals (4 to 6 minutes). While the compressor is turning off, the indoor fan motor operates in the SUPER LOW position. The pattern of operation depending on the relation between room temperature and preset temperatures is shown in Fig. 7-3-5.
Room temp.
Preset temp.+1
Preset temp.
Compressor
Outdoor fan
Indoor fan
ON ON ON ON
OFF OFF OFF
L. *S.L. S.L.L. L. S.L. L.
*Super Low
Fig. 7-3-5
(3) [FAN] button on the remote control is set to AUTO
only.
(4) The ECO, COMFORT SLEEP, QUIET and
Hi POWER operations can not be set.
(2) When [FAN] button is set to AUTO, the indoor fan
motor operates as shown in Fig. 7-3-7. When [FAN] button is set to LOW, LOW+, MED, MED+ or HIGH, the motor operates with a constant air flow.
Preset temp.
°C
0
-0.5
-1
-1.5
-2
-5.0
-5.5
[FAN AUTO]
(Room temp.) (Preset temp.)
L
*1 *2
+
M
H
*1 : Fan speed = (M + L) x 1/4 + L
*2 : Fan speed = (M + − L) x 2/4 + L *3 : Fan speed = (M + L) x 3/4 + L
(Calculated with Linear approximation from M+ and L+)
Fig. 7-3-7
-
14
-
FILE NO. SVM-10026
y.
c
e
c
(3) The indoor heat exchanger restricts revolving
speed of the fan motor to prevent a cold draft. The upper limit of the revolving speed is shown in Fig. 7-3-8
T
46
34
45 33
33 21 32 20
*A+0 *A+0
*A-8 *A-8
Fan speed MANUAL or AUTO in starting Fan speed AUTO in stability
* No limitation while fan speed MANUAL mode is in stabilit * A: When Tsc 24, A is 24, and when Tsc < 24, A is Ts
Tsc: Set valu
Fan speed AUTO Fan speed MANUAL
Normal AUTO
Line-approximate H and SL with Tc.
SL
Stop
L-H (Up to setting speed)
Line-approximate H and SL with Tc.
SL
Stop
[In starting and in stability]
In starting
FAN Until 12 minutes
AUTO
passed after operation start
When 12 to 25 minutes passed after operation
start and room temp. is 3°C or lower than set temp.
In stability
When 12 to 25 minutes passed after opeartion
start and room temp. is than (set )
between preset
When 25 minutes or more passed after operation start
3°C
7-3-5. Automatic operation
([MODE] button on the remote control is set to the automatic operation.)
(1) One of 3 operations (Cooling, Fan only or Heating)
is selected according to difference between the preset temperature and the room temperature at which the automatic operation has started, as shown in Fig. 7-3-9. The Fan only operation continues until the room temperature reaches a level at which another mode is selected.
(2) Temporary Auto
When the [RESET] button on the indoor unit is pushed, the preset temperature is fixed at 24°C and the indoor unit is controlled as shown in Fig. 7-3-9.
°C
Cooling operation
0
Fan only operation
-1
Heating operation
(Room temp.) (Preset temp.)
FAN Room temp. < Set
Manual
temp.–4°C
Room temp. Set temp. –3.5°C
Fig. 7-3-8 Cold draft preventing control
(4) In order to prevent cold draft when compressor
during heating operation.Then louver will move to upper position and fan speed will reduce or OFF.
-
15
Fig. 7-3-9
-
7-4. Drescription of Safety and Reliability Prevention Function
FILE NO. SVM-10026
7-4-1. Low-Temperature Limit Control
The microcontroller detects the indoor heat exchanger temperature to prevent the indoor heat exchanger from freezing. The compressor and outdoor fan motor are controlled as shown in Fig. 7-4-1.
Heat exchanger temperature
(°C)
7
5
Compressor Outdoor fan
ON
Less than 5°C continues
for 5 minutes
OFF
Fig. 7-4-1
7-4-2 High-Temperature Limit Control
7-4-3. Defrost Operation
During the heating operation, the outdoor heat exchanger temperature goes down and sometimes it is frozen. In this case, the air conditioner stops the heating operation and starts the defrost operation to melt ice.
Condition to start the defrost operation
The defrost operation starts whichever below conditions are satisfied.
(1) When the cumulative compressor operating time is
longer than 40 or 90 minutes and difference between the indoor heat exchanger temperature and the room temperature is less than the specified value. (This value is decided by the microprocessor.) (Control example is shown in Fig. 7-4-3. In case of B or C, the defrost operation starts.)
(2) When the current limit control or the high
temperature limit control is performed for total of 90 minutes.
The microcontroller detects the indoor heat exchanger temperature to prevent pressure of a refrigerating cycle from increasing excessively. The compressor and outdoor fan motor are controlled as shown in Fig. 7-4-2.
Compressor
OFF
ON
ON
Outdoor fan
OFF
OFF
ON
Heat exchanger temp.
(°C) 60
53 52
Fig. 7-4-2
xchanger temp
A
Indoor heat e
- Room temp
Fig. 7-4-3 (Indoor fan speed : M)
D
B
C
Cumulative compressor operating time
-
16
-
Defrost operation time control
FILE NO. SVM-10026
<In case of B>
(1) The heating operation is performed for at least
40 minutes.
(2) The maximum defrost operating time is 6 minutes.
The defrost operating time for the 4th cycle is 10 minutes. (When the outdoor temperature is very low, however, the defrost operating time is 10 minutes.)
minutes
40
Heating
minutes
40
Defrost
Heating
Max 6 minutes
minutes
Defrost
1 cycle
40
Heating
minutes
40
Defrost
Heating
10 minutes
Defrost
Fig. 7-4-4
<In case of C>
(1) The heating operation is performed for at least 90
minutes.
(2) The defrost operating time is 10 minutes.
Ending condition at defrost operation
(1) When the compressor current becomes 5.40A or
more during defrost operation, the defrost operation stops and the heating operation restarts. (The current sensor detects the compressor current.)
(2) The defrost operation continues for at most
6 minutes or 10 minutes.
DEFROST LAMP :
·
During defrost operation, the PRE-DEF. lamp is on and the indoor and outdoor fans are off.
·
The compressor start protection timer is inter­looked with the PRE-DEF. lamp. So the PRE-DEF. Lamp is off (the fans stop) for about 3 minutes after the [ ] button is turned on. When the compressor is turned on, the PRE-DEF. lamp comes on. After the heat ex-changer is preheated to about 24 goes off, and the indoor fan starts.
°C or higher
, the PRE-DEF. Lamp
-
17
-
7-4-4. Current Limit Control
The microcontroller detects the input current so as to prevent it exceeds a specified value by means of controlling the outdoor fan control as described in (1) and (2).
(1) Current limit control (Cooling operation)
Control is performed as shown below by detecting the compressor operating current with a current sensor (C.T).
Input current
11.0A I4
10.0A I3
FILE NO. SVM-10026
Compressor Outdoor fan More than I4 continues for 3 seconds
OFF
More than I3 continues for 5 minutes
OFF
(2) Current limit control (Heating operation)
Control is performed as shown in Fig. 7-4-6
Input current
11.0A I4
10.0A I3
6.45A I2
5.40A I1
ON
Fig. 7-4-5
Compressor Outdoor fan
More than I4 continues for 3 seconds
OFF
More than I3 continues for 5 minutes
OFF
ON OFF
ON
Fig. 7-4-6
- 18 -
FILE NO. SVM-10026
7-5. One-Touch Operation
One touch comfort is the fully automated operation that is set according to the preferable condition in a region.
Fan Operation
AUTO
*AUTO/L
L
0
*AUTO/L : Fan operates depends on the setting temperature and room temperature.
During the One Touch Comfort mode if the indoor unit receives any signal with other operation mode, the unit will cancel the comfort mode and operates according to the signal received.
Operation description
When an indoor unit receives "One Touch Comfort Signal" from the remote controller, the indoor unit operates as following.
1) Air conditioner starts to operation when the signal is received, even if the air conditioner was OFF.
2) Operation mode is set according to room temperature, the same as AUTO mode.
3) Target temperature is 24ºC.
4) Louver position is set as stored position.
5) Fan is controlled as diagrom.
12
25
Time after operation starts (min)
-
19
-