Toshiba RAS-13G2KCVP-T, RAS-10G2KCVP-T, RAS-18G2ACVP-T, RAS-18G2KCVP-T, RAS-10G2ACVP-T Service Manual

...
R410A
SERVICE MANUAL
SPLIT TYPE
Indoor Unit Outdoor Unit
Revised on Oct
,
RAS-10G2KCVP-
T
RAS-13G2KCVP-
T
RAS-18G2KCVP-
T
RAS-10G2ACVP-
T
R
AS-13G2ACVP-
T
RAS-18G2ACVP-
T
FILE NO. SVM-15058-1
CONTENTS
1. SAFETY PRECAUTIONS .......................................................................... 3
2. SPECIFICATIONS ..................................................................................... 6
3. REFRIGERANT R410A ............................................................................. 8
4. CONSTRUCTION VIEWS ........................................................................ 16
5. WIRING DIAGRAM .................................................................................. 18
6. SPECIFICATIONS OF ELECTRICAL PARTS ......................................... 19
7. REFRIGERANT CYCLE DIAGRAM ........................................................ 20
8. CONTROL BLOCK DIAGRAM ................................................................ 23
9. OPERATION DESCRIPTION................................................................... 25
10.
INSTALLATION PROCEDURE ................................................................ 59
11.
HOW TO DIAGNOSE THE TROUBLE ...................................................... 74
12.
HOW TO REPLACE THE MAIN PARTS.................................................... 99
13.
EXPLODED VIEWS AND PARTS LIST .................................................. 116
FILE NO. SVM-15058
- 2 -
1. SAFETY PRECAUTIONS
Installing, staring up, and servicing air-conditioning equipment can be hazardous due to system pressures, electrical components, and equipment location (roofs, elevated structures, etc.).
Only trained, qualified installers and service mechanics should install, start-up, and service this equipment. Untrained personnel can perform basic maintenance functions such as cleaning coils. All other operations should be
performed by trained service personnel.
When working on the equipment, observe precautions in the literature and on tags, stickers, and labels attached to the equipment.
Follow all safety codes, Wear safety glasses and work gloves. Keep quenching cloth and fire extinguisher near by when brazing. Use care in handling, rigging, and setting bulky equipment.
Read these instructions thoroughly and follow all warnings or cautions included in literature and attached to the unit. Consult local building codes and National Electrical Code (NEC) for special requirements. Recognize safety information. This is the safety-alert symbol
! . When you see this symbol on
the unit and in instructions or manuals, be alert to the potential for personal injury. Understand these signal words : DANGER, WARNING, and CAUTION. These words are used with the safety-alert symbol.
DANGER identifies the most serious hazards which will result in severs personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
Before installation, please read these precautions for safety carefully.
Be sure to follow the precautions provided here to avoid safety risks. The symbols and their meanings are shown below.
WARNING : It indicates that incorrect use of this unit may cause severe injury or death. CAUTION : FAILURE TO FOLLOW THIS CAUTION may result in equipment damage or improper operation and
personal injury.
CAUTION
New refrigerant air conditioner installation
THIS AIR CONDITIONER USES THE NEW HFC REFRIGERANT (R410A), WHICH DOES NOT DESTROY THE
OZONE LAYER.
R410A refrigerant is affected by inpurities such as water and oils because the pressure of R410A refrigerant is approx.
1.6 times of refrigerant R22. ALSO NEW OILS ARE USED WITH R410A, THUS ALWAYS USE NEW REFRIGERANT PIPING AND DO NOT ALLOW MOISTURE OR DUST TO ENTER THE SYSTEM. To avoid mixing refrigerant and refrigerant machine oil, the sizes of charging port on the main unit is different than those used on R22 machines and different tools will be required.
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation. Do not bury more than 36 in. (914 mm) of refrigerant pipe in the ground. If any section of pipe is buried, there must be a 6 in. (152 mm) vertical rise to the valve connections on the outdoor units. If more than the recommended length is buried, refrigerant may migrate to the cooter buried section during extended periods of system shutdown. This causes refrigerant slugging and could possibly damage the compressor at start-up.
FILE NO. SVM-15058
- 3 -
DANGER
FOR USE BY QUALIFIED PERSONS ONLY.
TURN OFF MAIN POWER SUPPLY BEFORE.ATTEMPTING ANY ELECTRICAL WORK. MAKE SURE ALL POWER
SWITCHES ARE OFF. FAILURE TO DO SO MAY CAUSE ELECTRIC SHOCK.
CONNECT THE CONNECTING CABLE CORRECTLY. IF THE CONNECTING CABLE IS CONNECTED WRONGLY,
ELECTRIC PARTS MAY BE DAMAGED.
CHECK THE EARTH WIRE THAT IT IS NOT BROKEN OR DISCONNECTED BEFORE INSTALLATION.
DO NOT INSTALL NEAR CONCENTRATIONS OF COMBUSTIBLE GAS OR GAS VAPORS.
FAILURE TO FOLLOW THIS INSTRUCTION CAN RESULT IN FIRE OR EXPLOSION.
TO PREVENT OVERHEATION THE INDOOR UNIT AND CAUSING A FIRE HAZARD, PLACE THE UNIT WELL AWAY
(MORE THAN 2 M) FROM HEAT SOURCES SUCH AS RADIATORS, HEATERS, FURNACE, STOVES, ETC.
WHEN MOVING THE AIR CONDITIONER FOR INSTALLING IT IN ANOTHER PLACE AGAIN, BE VERY CAREFUL NOT
TO GET THE SPECIFIED REFRIGERANT (R410A) WITH ANY OTHER GASEOUS BODY INTO THE REFRIGERATION CYCLE. IF AIR OR ANY OTHER GAS IS MIXED IN THE REFRIGERANT, THE GAS PRESSURE IN THE REFRIGERATION CYCLE BECOMES ABNORMALLY HIGH AND IT RESULTINGLY CAUSES BURST OF THE PIPE AND INJURIES ON PERSONS.
IN THE EVENT THAT THE REFRIGERANT LEAK, DURING INSTALLATION WORK, IMMEDIATELY ALLOW FRESH AIR
INTO THE ROOM. IF THE REFRIGERANT GAS IS HEATED BY FIRE OR SOMETHING ELSE, IT CAUSE GENERATION OF POISONOUS GAS.
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death. Before installing, modifying, or servicing system, main electrical disconnect switch must be in the OFF position. There may be more than 1 disconnect switch. Lock out and tag switch with a suitable warning label.
Never modify this unit by removing any of the safety guards or bypassing any of the safety interlock switches.
Installation work must be purformed by qualified personnel only.
Specified tools and pipe parts for model R410A are required, and installation work must be done in accordance with the
manual. HFC type refrigerant R410A has 1.6 times more pressure than that of conventional refrigerant (R22). Use the specified pipe parts, and ensure correct installation, otherwise damage and/or injury may be caused. At the same time, water leakage, electrical shock, and fire may occur.
Be sure to install the unit in a place which can sufficiently bear its weight. If the load bearing of the unit is not enough, or
installation of the unit is improper, the unit may fall and result in injury.
Electrical work must be performed by trained, qualified installers and service mechanics in accordance with the code governing
such installation work, internal wiring regulations, and the manual. A dedicated circuit and the rated voltage must be used.
Insufficient power supply or improper installation may cause electrical shock or fire.
Use a cabtyre cable to connect wires in the indoor/outdoor units. Midway connection is not allowed. Improper connection or
fixing may cause a fire.
Wiring between the indoor unit and outdoor units must be well shaped so that the cover can be firmly placed. Improper
cover installation may cause increased heat, fire, or electrical shock at the terminal area.
Be sure to use only approved accessories or the specified parts. Failure to do so may cause the unit to fall, water leakage,
fire or electrical shock.
After the installation work. ensure that there is no leakage of refrigerant gas. If the refrigerant gas leaks out of the pipe into
the room and is heated by fire or something else from a fanheater, stove or gas range, it causes generation of poisonous gas.
Make sure the equipment is properly grounded. Do not connect the ground wire to a gas pipe, water pipe, lightning
conductor, or telephone earth wire. Improper earth work may be the cause of electrical shock.
Do not install the unit where flammable gas may leak. If there is any gas leakage or accumulation around the unit, it can
cause a fire.
Do not select a location for installation where there may be excessive water or humidity, such as a bathroom. Deterioration
of insulation nay cause electrical shock or fire.
Installation work must be performed following the instructions in this installation manual. Improper installation may cause
water leakage, electrical shock or fire. Check the following items before operating the unit.
- Be sure that the pipe connection is well placed and there are no leaks.
- Check that the service valve is open. If the service valve is closed, it may cause overpressure and result in compressor damage. At the same time, if there is a leak in the connection part, it may cause air suction and overpressure, resulting in damage to the unit or injury.
In a pump-down operation, be sure to stop the compressor unit before removing the refrigerant pipe. If removing the
refrigerant pipe while the compressor is operating with the service valve opened, it may cause air suction and overpressure, resulting in damage to the unit or injury.
Do not modity the power cable, connect the cable midway, or use a multiple outlet extension cable. Doing so may cause
contact failure, insulation failure, or excess current, resulting in fire or electrical shock.
If you detect any damage, do not install the unit. Contact your dealer immediately.
FILE NO. SVM-15058
- 4 -
CAUTION
CAUTION
Exposure of unit to water or other moisture before installation could result in electric shock. Do not store it in a wet
basement or expose to rain or water.
After unpacking the unit, examine it carefully for possible damage. Report any damages to your distributor.
Do not install in a place that can increase the vibration of the unit. Do not install in a place that can amplify
the noise level of the unit or where noise and discharged air might disturb neighbors.
Please read this installation manual carefully before installing the unit. It contains further important instructions
for proper installation.
This appliance must be connected to the main power supply by means of a circuit breaker depending on the
place where the unit is installed. Failure to do so may cause electrical shock.
Follow the instructions in this installation manual to arrange the drain pipe for proper drainage from the unit.
Ensure that drained water is discharged. Improper drainage can result is water leakage, causing water damage to furniture.
Tighten the flare nut with a torque wrench using the prescribed method. Do not apply excess torque. Otherwise,
the nut may crack after a long period of usage and it may cause the leakage of refrigerant.
Wear gloves (heavy gloves such as cotton gloves) for installation work. Failure to do so may cause personal
injury when handling parts with sharp edges.
Do not touch the air intake section or the aluminum fins of the outdoor unit. It may cause injury.
Do not install the outdoor unit in a place which can be a nest for small animals. Small animals could enter and
contact internal electrical parts, causing a failure or fire.
Request the user to keep the place around the unit tidy and clean.
Make sure to conduct a trial operation after the installation work, and explain how to use and maintain the unit
to the customer in accordance with the manual. Ask the customer to keep the operation manual along with the installation manual.
FILE NO. SVM-15058
- 5 -
2-1. Specifications
Unit model Indoor
RAS-10G2KCVP-T RAS-13G2KCVP-T RAS-18G2KCVP-T
Outdoor
RAS-10G2ACVP-T RAS-13G2ACVP-T RAS-18G2ACVP-T
Cooling capacity (kW)
2.6 3.8 5.1
Cooling capacity range (kW)
1.3-3.5 1.3-4.1
1.1-6.0
Power supply
1Ph/50Hz/220V
Electric characteristic
Indoor Operation mode
Cooling Cooling Cooling
Running current (A)
0.24 0.24 0.24
Power consumption (W)
25 25 25
Power factor (%)
47 47 47
Outdoor Operation mode
Cooling Cooling Cooling
Running current (A)
2.96 4.77 7.12
Power consumption (W)
555 1035 1555
Power factor (%)
92 99
99
Starting current (A)
2.97 5.01 7.36
COP
4.48 3.58 3.23
Operating noise
Indoor High (dB-A)
42
42
44
Medium (dB-A)
33 34 35
Low (dB-A)
24 25 26
Outdoor (dB-A)
49 50 52
Indoor unit Unit model
RAS-10G2KCVP-T RAS-13G2KCVP-T RAS-18G2KCVP-T
Dimension Height (mm)
293
Width (mm)
831
Depth (mm)
270
Net weight (kg)
14
Fan motor output (W)
30
30
Air fl ow rate (m3/min)
10.8 11.2 11.6
Outdoor unit Unit model
RAS-10G2ACVP-T RAS-13G2ACVP-T RAS-18G2ACVP-T
Dimension Height (mm)
550 550
Width (mm)
780 780
Depth (mm)
290 290
Net weight (kg)
37 36
Compressor Motor output (W)
1100
Type
750
Single rotary type with DC inverter variable
speed control
Twin rotary type with
DC inverter variable
speed control
Model
DA108X1C-23FZ DA131S1B-31FZ
Fan motor output (W)
43 43
Air fl ow rate (m3/min)
30 37.5
34.0
Piping connection
Type
Flare connection Flare connection
Indoor unit Liquid side (mm)
Ø6.35 Ø6.35
Gas side (mm)
Ø9.52 Ø12.70
Outdoor unit Liquid side (mm)
Ø6.35 Ø6.35
Gas side (mm)
Ø9.52 Ø12.70
Maximum length (m)
20 20
(m)
15 15
Maximum chargeless length Maximum height difference (m)
10 10
Refrigerant Name of refrigerant
R410A R410A
Weight (kg)
1.40
Wiring connection
Power supply
1.1
3Wires:includes earth(Outdoor)
Interconnection
4Wires:includes earth
Usable temperature range
Indoor (°C)
21~32
Outdoor (°C)
-10~43
Accessory Indoor unit Installation plate
1
Wireless remote controller
1
Batteries
2
Remote controller holder
1 Mounting screw 6(Ø4x25L) Remote controller holder
Pan head wood screw
2(Ø3.1x16L)
Installation manual
1 Owner’s manual
1
Outdoor unit Drain nipple
-
Water-proof rubber cap
-
* The specifications may be subject to change without notice for purpose of improvement.
2.
SPECIFICATIONS
FILE NO. SVM-15058
- 6 -
2-2. Operation Characteristic Curve
2-3. Capacity Variation Ratio According to Temperature
100
95
90
85
80
75
70
65
60
55
50
105
32 33 34 35 36 37 38 39 40 41 42 43 44 45 46
Outdoor Temp. (°C)
Capacity Ratio (%)
Conditions Indoor: DB27°C/WB19°C Indoor air flow: High Pipe length: 7.5m
Capa
city r
atio: 100% =
2.6kW (RAS-10G2KCVP-T)
3.8kW (RAS-13G2KCVP-T)
5.1
kW (RAS-18G2KCVP-T)
RAS-10G2KCVP-T RAS-13G2KCVP-T RAS-18G2KCVP-T
0
1
2
3
4
5
6
7
8
9
10
10 20 30 40 50 60 70 80 90 100 110 120
FILE NO. SVM-15058
- 7 -
3. REFRIGERANT R410A
This air conditioner adopts the new refrigerant HFC (R410A) which does not damage the ozone layer.
The working pressure of the new refrigerant R410A is 1.6 times higher than conventional refrigerant (R22). The refrigerating oil is also changed in accordance with change of refrigerant, so be careful that water, dust, and existing refrigerant or refrigerat­ing oil are not entered in the refrigerant cycle of the air conditioner using the new refrigerant during installation work or servicing time.
The next section describes the precautions for air conditioner using the new refrigerant. Conforming to contents of the next section together with the general cautions included in this manual, perform the correct and safe work.
3-1. Safety During Installation/Servicing
As R410A’s pressure is about 1.6 times higher than that of R22, improper installation/servicing may cause a serious trouble. By using tools and materi­als exclusive for R410A, it is necessary to carry out installation/servicing safely while taking the following precautions into consideration.
1. Never use refrigerant other than R410A in an air conditioner which is designed to operate with R410A.
If other refrigerant than R410A is mixed, pressure in the refrigeration cycle becomes abnormally high, and it may cause personal injury, etc. by a rupture.
2. Confirm the used refrigerant name, and use tools and materials exclusive for the refrigerant R410A.
The refrigerant name R410A is indicated on the visible place of the outdoor unit of the air condi­tioner using R410A as refrigerant. To prevent mischarging, the diameter of the service port differs from that of R22.
3. If a refrigeration gas leakage occurs during installation/servicing, be sure to ventilate fully.
If the refrigerant gas comes into contact with fire, a poisonous gas may occur.
4. When installing or removing an air conditioner, do not allow air or moisture to remain in the refrig­eration cycle. Otherwise, pressure in the refrig­eration cycle may become abnormally high so that a rupture or personal injury may be caused.
5. After completion of installation work, check to make sure that there is no refrigeration gas leakage.
If the refrigerant gas leaks into the room, coming into contact with fire in the fan-driven heater, space heater, etc., a poisonous gas may occur.
6. When an air conditioning system charged with a large volume of refrigerant is installed in a small room, it is necessary to exercise care so that, even when refrigerant leaks, its concentration does not exceed the marginal level.
If the refrigerant gas leakage occurs and its concentration exceeds the marginal level, an oxygen starvation accident may result.
7. Be sure to carry out installation or removal according to the installation manual.
Improper installation may cause refrigeration trouble, water leakage, electric shock, fire, etc.
8. Unauthorized modifications to the air conditioner may be dangerous. If a breakdown occurs please call a qualified air conditioner technician or electrician.
Improper repair’s may result in water leakage, electric shock and fire, etc.
3-2. Refrigerant Piping Installation
3-2-1. Piping Materials and Joints Used
For the refrigerant piping installation, copper pipes and joints are mainly used. Copper pipes and joints suitable for the refrigerant must be chosen and installed. Furthermore, it is necessary to use clean copper pipes and joints whose interior surfaces are less affected by contaminants.
1. Copper Pipes
It is necessary to use seamless copper pipes which are made of either copper or copper alloy and it is desirable that the amount of residual oil is less than 40 mg/10 m. Do not use copper pipes having a collapsed, deformed or discolored portion (especially on the interior surface).
Otherwise, the expansion valve or capillary tube may become blocked with contaminants.
As an air conditioner using R410A incurs pres­sure higher than when using R22, it is necessary to choose adequate materials.
Thicknesses of copper pipes used with R410A are as shown in Table 3-2-1. Never use copper pipes thinner than 0.8 mm even when it is available on the market.
FILE NO. SVM-15058
- 8 -
Table 3-2-1 Thicknesses of annealed copper pipes
Nominal diameter
1/4
3/8
1/2
5/8
Outer diameter (mm)
6.35
9.52
12.70
15.88
Thickness (mm)
R410A R22
0.80 0.80
0.80 0.80
0.80 0.80
1.00 1.00
2. Joints
For copper pipes, flare joints or socket joints are used. Prior to use, be sure to remove all contaminants. a) Flare Joints
Flare joints used to connect the copper pipes cannot be used for pipings whose outer diameter exceeds 20 mm. In such a case, socket joints can be used.
Sizes of flare pipe ends, flare joint ends and flare nuts are as shown in Tables 3-2-3 to 3-2-6 below.
b) Socket Joints
Socket joints are such that they are brazed for connections, and used mainly for thick pipings whose diameter is larger than 20 mm.
Thicknesses of socket joints are as shown in Table 3-2-2.
Table 3-2-2 Minimum thicknesses of socket joints
Nominal diameter
1/4
3/8
1/2
5/8
Reference outer diameter of
copper pipe jointed (mm)
6.35
9.52
12.70
15.88
Minimum joint thickness
(mm)
0.50
0.60
0.70
0.80
3-2-2. Processing of Piping Materials
When performing the refrigerant piping installation, care should be taken to ensure that water or dust does not enter the pipe interior, that no other oil than lubricating oils used in the installed air-water heat pump is used, and that refrigerant does not leak. When using lubricating oils in the piping processing, use such lubricating oils whose water content has been removed. When stored, be sure to seal the container with an airtight cap or any other cover.
1. Flare processing procedures and precautions
a) Cutting the Pipe
By means of a pipe cutter, slowly cut the pipe so that it is not deformed.
b) Removing Burrs and Chips
If the flared section has chips or burrs, refrigerant leakage may occur. Carefully remove all burrs and clean the cut surface before installation.
c) Insertion of Flare Nut
FILE NO. SVM-15058
- 9 -
A
ØD
d) Flare Processing
Make certain that a clamp bar and copper pipe have been cleaned.
By means of the clamp bar, perform the flare processing correctly.
Use either a flare tool for R410A or conven­tional flare tool.
Flare processing dimensions differ according to the type of flare tool. When using a con­ventional flare tool, be sure to secure “dimen­sion A” by using a gauge for size adjustment.
Fig. 3-2-1 Flare processing dimensions
Table 3-2-3 Dimensions related to flare processing for R410A
Nominal
diameter
1/4
3/8
1/2
5/8
Outer
diameter
(mm)
6.35
9.52
12.70
15.88
Thickness
(mm)
0.8
0.8
0.8
1.0
A (mm)
Flare tool for R410A
clutch type
0 to 0.5
0 to 0.5
0 to 0.5
0 to 0.5
Conventional flare tool
Clutch type Wing nut type
1.0 to 1.5 1.5 to 2.0
1.0 to 1.5 1.5 to 2.0
1.0 to 1.5 2.0 to 2.5
1.0 to 1.5 2.0 to 2.5
Table 3-2-4 Dimensions related to flare processing for R22
Nominal
diameter
1/4
3/8
1/2
5/8
Outer
diameter
(mm)
6.35
9.52
12.70
15.88
Thickness
(mm)
0.8
0.8
0.8
1.0
A (mm)
Flare tool for R22
clutch type
0 to 0.5
0 to 0.5
0 to 0.5
0 to 0.5
Conventional flare tool
Clutch type Wing nut type
0.5 to 1.0 1.0 to 1.5
0.5 to 1.0 1.0 to 1.5
0.5 to 1.0 1.5 to 2.0
0.5 to 1.0 1.5 to 2.0
Table 3-2-5 Flare and flare nut dimensions for R410A
Nominal
diameter
1/4
3/8
1/2
5/8
Outer diameter
(mm)
6.35
9.52
12.70
15.88
Thickness
(mm)
0.8
0.8
0.8
1.0
Dimension (mm)
ABCD
9.1 9.2 6.5 13
13.2 13.5 9.7 20
16.6 16.0 12.9 23
19.7 19.0 16.0 25
Flare nut width
(mm)
17
22
26
29
FILE NO. SVM-15058
- 10 -
43° to 45°
45° to 46°
B A
C
D
Table 3-2-6 Flare and flare nut dimensions for R22
Nominal
diameter
1/4
3/8
1/2
5/8
3/4
Outer diameter
(mm)
6.35
9.52
12.70
15.88
19.05
Thickness
(mm)
0.8
0.8
0.8
1.0
1.0
Dimension (mm)
ABCD
9.0 9.2 6.5 13
13.0 13.5 9.7 20
16.2 16.0 12.9 20
19.7 19.0 16.0 23
23.3 24.0 19.2 34
Flare nut width
(mm)
17
22
24
27
36
Fig. 3-2-2 Relations between flare nut and flare seal surface
2. Flare Connecting Procedures and Precautions
a) Make sure that the flare and union portions do not have any scar or dust, etc. b) Correctly align the processed flare surface with the union axis. c) Tighten the flare with designated torque by means of a torque wrench. The tightening torque for R410A is
the same as that for conventional R22. Incidentally, when the torque is weak, the gas leakage may occur. When it is strong, the flare nut may crack and may be made non-removable. When choosing the tighten-
ing torque, comply with values designated by manufacturers. Table 3-2-7 shows reference values.
NOTE :
When applying oil to the flare surface, be sure to use oil designated by the manufacturer. If any other oil is used, the lubricating oils may deteriorate and cause the compressor to burn out.
Table 3-2-7 Tightening torque of flare for R410A [Reference values]
Nominal
diameter
1/4
3/8
1/2
5/8
Outer diameter
(mm)
6.35
9.52
12.70
15.88
Tightening torque
N•m (kgf•cm)
14 to 18 (140 to 180)
33 to 42 (330 to 420)
50 to 62 (500 to 620)
63 to 77 (630 to 770)
Tightening torque of torque
wrenches available on the market
N•m (kgf•cm)
16 (160), 18 (180)
42 (420)
55 (550)
65 (650)
FILE NO. SVM-15058
- 11 -
3-3. Tools
3-3-1. Required Tools
The service port diameter of packed valve of the outdoor unit in the air-water heat pump using R410A is changed to prevent mixing of other refrigerant. To reinforce the pressure-resisting strength, flare processing dimensions and opposite side dimension of flare nut (For Ø12.7 copper pipe) of the refrigerant piping are lengthened.
The used refrigerating oil is changed, and mixing of oil may cause a trouble such as generation of sludge, clogging of capillary, etc. Accordingly, the tools to be used are classified into the following three types.
1. Tools exclusive for R410A (Those which cannot be used for conventional refrigerant (R22))
2. Tools exclusive for R410A, but can be also used for conventional refrigerant (R22)
3. Tools commonly used for R410A and for conventional refrigerant (R22) The table below shows the tools exclusive for R410A and their interchangeability.
Tools exclusive for R410A (The following tools for R410A are required.)
Tools whose specifications are changed for R410A and their interchangeability
No.
1
2
3
4
5
6
7
8
9
10
Used tool
Flare tool
Copper pipe gauge for adjusting projection margin
Torque wrench (For Ø12.7)
Gauge manifold
Charge hose
Vacuum pump adapter
Electronic balance for refrigerant charging
Refrigerant cylinder
Leakage detector
Charging cylinder
Usage
Pipe flaring
Flaring by conventional flare tool
Connection of flare nut
Evacuating, refrigerant charge, run check, etc.
Vacuum evacuating
Refrigerant charge
Refrigerant charge
Gas leakage check
Refrigerant charge
R410A
air-water heat pump installation
Existence of new equipment for R410A
Ye s
Ye s
Ye s
Ye s
Ye s
Ye s
Ye s
Ye s
(Note 2)
Whether conven­tional equipment can be used
*(Note 1)
*(Note 1)
×
× ×
× ×
× ×
Conventional air-water
heat pump installation
Whether new equipment can be used with conventional refrigerant
¡
*(Note 1)
×
×
¡
¡
×
¡
×
(Note 1) When flaring is carried out for R410A using the conventional flare tools, adjustment of projection
margin is necessary. For this adjustment, a copper pipe gauge, etc. are necessary.
(Note 2) Charging cylinder for R410A is being currently developed.
General tools (Conventional tools can be used.)
In addition to the above exclusive tools, the following equipments which serve also for R22 are necessary as the general tools.
1. Vacuum pump Use vacuum pump by attaching vacuum pump adapter.
2. Torque wrench (For Ø6.35, Ø9.52)
3. Pipe cutter
4. Reamer
5. Pipe bender
6. Level vial
7. Screwdriver (+, –)
8. Spanner or Monkey wrench
9. Hole core drill (Ø65)
10. Hexagon wrench (Opposite side 4mm)
11. Tape measure
12. Metal saw
Also prepare the following equipments for other installation method and run check.
1. Clamp meter
2. Thermometer
3. Insulation resistance tester
4. Electroscope
FILE NO. SVM-15058
- 12 -
Connect the charge hose to packed valve service port at the outdoor unit’s gas side.
Recover the refrigerant, and check no refrigerant remains in the equipment.
(For refrigerant charging, see the figure below.)
Connect the charge hose to the vacuum pump adapter.
Open fully both packed valves at liquid and gas sides.
Place the handle of the gauge manifold Low in the fully opened position, and turn on the vacuum pump’s power switch. Then, evacuating the refrigerant in the cycle.
When the compound gauge’s pointer has indicated –0.1 Mpa (–76 cmHg), place the handle Low in the fully closed position, and turn off the vacuum pump’s power switch.
Keep the status as it is for 1 to 2 minutes, and ensure that the compound gauge’s pointer does not return.
Set the refrigerant cylinder to the electronic balance, connect the connecting hose to the cylinder and the connecting port of the electronic balance, and charge liquid refrigerant.
(Indoor unit)
(Outdoor unit)
Opened
Opened
Refrigerant cylinder
(with siphon)
Check valve
Open/close valve for charging
Electronic balance for refrigerant charging
Opened
Closed
Service port
3-4. Recharging of Refrigerant
When it is necessary to recharge refrigerant, charge the specified amount of new refrigerant according to the following steps.
1. Never charge refrigerant exceeding the specified amount.
2. If the specified amount of refrigerant cannot be charged, charge refrigerant bit by bit in COOL mode.
3. Do not carry out additional charging. When additional charging is carried out if refrigerant leaks, the refrigerant composition changes in the
refrigeration cycle, that is characteristics of the air conditioner changes, refrigerant exceeding the specified amount is charged, and working pressure in the refrigeration cycle becomes abnormally high pressure, and may cause a rupture or personal injury.
Fig. 3-4-1 Configuration of refrigerant charging
FILE NO. SVM-15058
- 13 -
Gauge manifold
[ Cylinder with siphon ] [ Cylinder without siphon ]
OUTDOOR unit
Gauge manifold
OUTDOOR unit
Refrigerant
cylinder
Electronic
balance
Refrigerant
cylinder
Electronic
balance
Siphon
1. Be sure to make setting so that liquid can be charged.
2. When using a cylinder equipped with a siphon, liquid can be charged without turning it upside down.
It is necessary for charging refrigerant under condition of liquid because R410A is mixed type of refrigerant. Accordingly, when charging refrigerant from the refrigerant cylinder to the equipment, charge it turning the cylinder upside down if cylinder is not equipped with siphon.
R410A refrigerant is HFC mixed refrigerant. Therefore, if it is charged with gas, the composi­tion of the charged refrigerant changes and the characteristics of the equipment varies.
3-5. Brazing of Pipes
3-5-1. Materials for Brazing
1. Silver brazing filler
Silver brazing filler is an alloy mainly composed of silver and copper. It is used to join iron, copper or copper alloy, and is relatively expensive though it excels in solderability.
2. Phosphor bronze brazing filler
Phosphor bronze brazing filler is generally used to join copper or copper alloy.
3. Low temperature brazing filler
Low temperature brazing filler is generally called solder, and is an alloy of tin and lead. Since it is weak in adhesive strength, do not use it for refrigerant pipes.
1. Phosphor bronze brazing filler tends to react with sulfur and produce a fragile compound water solution, which may cause a gas leakage. Therefore, use any other type of brazing filler at a hot spring resort, etc., and coat the surface with a paint.
2. When performing brazing again at time of servicing, use the same type of brazing filler.
3-5-2. Flux
1. Reason why flux is necessary
• By removing the oxide film and any foreign matter on the metal surface, it assists the flow of brazing filler.
• In the brazing process, it prevents the metal surface from being oxidized.
• By reducing the brazing filler’s surface tension, the brazing filler adheres better to the treated metal.
Fig. 3-4-2
FILE NO. SVM-15058
- 14 -
Nitrogen gas
cylinder
Pipe
Flow meter
M
Stop valve
From Nitrogen cylinder
Nitrogen gas
Rubber plug
2. Characteristics required for flux
• Activated temperature of flux coincides with the brazing temperature.
• Due to a wide effective temperature range, flux is hard to carbonize.
• It is easy to remove slag after brazing.
• The corrosive action to the treated metal and brazing filler is minimum.
• It excels in coating performance and is harm­less to the human body.
As the flux works in a complicated manner as described above, it is necessary to select an adequate type of flux according to the type and shape of treated metal, type of brazing filler and brazing method, etc.
3. Types of flux
• Noncorrosive flux
Generally, it is a compound of borax and boric acid. It is effective in case where the brazing tem­perature is higher than 800°C.
• Activated flux
Most of fluxes generally used for silver brazing are this type. It features an increased oxide film removing capability due to the addition of compounds such as potassium fluoride, potassium chloride and sodium fluoride to the borax-boric acid compound.
4. Piping materials for brazing and used brazing filler/flux
1. Do not enter flux into the refrigeration cycle.
2. When chlorine contained in the flux remains within the pipe, the lubricating oil deteriorates. Therefore, use a flux which does not contain chlorine.
3. When adding water to the flux, use water which does not contain chlorine (e.g. distilled water or ion-exchange water).
4. Remove the flux after brazing.
3-5-3. Brazing
As brazing work requires sophisticated techniques, experiences based upon a theoretical knowledge, it must be performed by a person qualified.
In order to prevent the oxide film from occurring in the pipe interior during brazing, it is effective to proceed with brazing while letting dry Nitrogen gas (N2) flow.
Never use gas other than Nitrogen gas.
1. Brazing method to prevent oxidation
1) Attach a reducing valve and a flow-meter to the Nitrogen gas cylinder.
2) Use a copper pipe to direct the piping mate­rial, and attach a flow-meter to the cylinder.
3) Apply a seal onto the clearance between the piping material and inserted copper pipe for Nitrogen in order to prevent backflow of the Nitrogen gas.
4) When the Nitrogen gas is flowing, be sure to keep the piping end open.
5) Adjust the flow rate of Nitrogen gas so that it is lower than 0.05 m3/Hr or 0.02 MPa (0.2kgf/cm2) by means of the reducing valve.
6) After performing the steps above, keep the Nitrogen gas flowing until the pipe cools down to a certain extent (temperature at which pipes are touchable with hands).
7) Remove the flux completely after brazing.
Fig. 3-5-1 Prevention of oxidation during brazing
Piping material
Copper - Copper
Copper - Iron
Iron - Iron
Used brazing filler
Phosphor copper
Silver
Silver
Used flux
Do not use
Paste flux
Vapor flux
FILE NO. SVM-15058
- 15 -
4. CONSTRUCTION VIEWS
4-1. Indoor Unit
831
293
Air filter
Heat exchanger
Plasma ion charger (Air purifier)
Picoion generator
62
64 64
62
70.5 38
590
225 225
137 104
45
293
46
69
174
35
156 156
102 174
65
198
46
Outline of indoor unit
HangerHanger
Installation plate outline
Center line
Hanger
Minimum distance to wall
Minimum distance
to wall
Minimum distance
to wall 52mm
or more
190mm
or more
225mm
or more
62
64
6
Front panel
Knock out system
270
6 64
62
Knock out system
104.3
312
150 150 150 150
131.5 99
Drain hose (0.6m)
Connecting pipe(0.37m) (For 25, 35 Series : Flare
9.52mm)
Connecting pipe(0.41m) Flare
6.35mm
HangerHanger
63
Remote controller holder
149
26
57
Wiress remote controller
20
188
FILE NO. SVM-15058
- 16 -
4-2. Outdoor Unit
320
306
30
ZView
600
A detail Drawing (Back leg)
320
306
2
-
11 x 14
Hole
(For
10 anchor bolt)
B Detail Drawing (Front leg)
Ø
25 Drain outlet
FAN-GUARD
COVER-PV
Liquid side (FlareØ6.35)
Gas side (Flare Ø 9.52 for RAS-10, 13) (Flare Ø 12.7 for RAS-18)
Service port
2 - Ø11 x 14 Long holes (For Ø8- Ø10 anchor bolt)
Installation dimension
Air outlel
100 or more
100 or more
600 or more
600 or more
Air intlel
Ø
Ø
8-
Ø
Ø
6 hole
86
Ø
6 hole
Ø
11x14 hole
R
15
28
A
320
R5.5
36
108 125
50
137
92
54
600
320
9060090
275
290
550
Ø
436
Z
R15
50
36
320
342
69
2 - R5-5 x 17L Ushape (For
Ø
8 - Ø10 anchor bolt)
FILE NO. SVM-15058
- 17 -
5.
WIRING DIAGRAM
FILE NO. SVM-15058
- 18 -
6.SPECIFICATIONS OF ELECTRICAL PARTS
6-1. Indoor Unit
6-2. Outdoor Unit
No.
Fan motor (for indoor)
2 Room temp. sensor (TA-sensor)
10k
at 25°C
3 Heat exchanger temp. sensor (TC-sensor)
10kat 25°C
4
5
Louver motor Output (Rated) 1W, 16 poles, DC12V
( - )
(
-
)
MP24Z4N
MF-340-30-3
DC250~370V, 30W
Parts n ame
1
Specif icatio nsType
Heat exchanger temp. sensor (TCJ-sensor)
10kat 25°C
(
-
)
No. Parts name Model name Rating
1 Reactor CH-69-Z-T L = 19mH, 10A 2 Outdoor fan motor ICF-140-43-4R DC140V, 43W 3 (Inverter attached) 10kΩ (25°C) 4 (Inverter attached) 62kΩ (20°C) 5
Suction temp. sensor (TS sensor) Discharge temp. sensor (TD sensor) Outside air temp. sensor (TO sensor) (Inverter attached) 10kΩ (25°C)
6 Terminal block (5P)
JXO-5B
20A, AC250V
7 Compressor
(10,13k)
DA108X1C-23FZ 3-phases 4-poles 750W
(18k)
DA131S1B-31FZ
3-phases 4-poles 1100W
8
Coil for PMV
CAM-MD12TCTH-5
DC12V
FILE NO. SVM-15058
- 19 -
7. REFRIGERANT CYCLE DIAGRAM
7-1. Refrigerant Cycle Diagram
RAS-10G2KCVP-T / RAS-10G2ACVP-T RAS-13G2KCVP-T / RAS-13G2ACVP-T
NOTE :
• The maximum pipe length of this air conditioner is 20m. When the pipe length exceeds 15m, the additional charging of refrigerant, 20g per 1m for the part of pipe exceeded 15m is required. (Max. 100g)
Deoxidized copper pipe
Outer dia. : 9.52mm
Thickness : 0.8mm
NOTE :
Gas leak check position Refrigerant flow
T1
Temp. measurement
INDOOR UNIT
Indoor heat
exchanger
Cross flow fan
Deoxidized copper pipe Outer dia. : 6.35mm Thickness : 0.8mm
Sectional shape of heat insulator
Allowable height
difference : 10m
Allowable pipe length
P Pressure measurement Gauge attaching port
Vacuum pump connecting port
Strainer
Pulse Modulating valve at liquid side
Compressor DA108X1C-23FZ
Outdoor heat
exchanger
Propeller fan
Refrigerant amount : 1.10kg
OUTDOOR UNIT
TC
TA
Max. : 20m
Min. : 1m Chargeless : 15m
Charge : 20g/m (16 to 20m)
TS
TD
Muffler
Temp. measurement
Ø1.2 x 80s Ø1.2 x 80s
TO Split capillary
TCJ
FILE NO. SVM-15058
- 20 -
RAS-18G2KCVP-T / RAS-18G2ACVP-T
NOTE :
Deoxidized copper pipe Outer dia. : 12.7mm Thickness : 0.8mm
NOTE :
Gas leak check position Refrigerant flow
T1
TO
Temp. measurement
TC
TA
INDOOR UNIT
Indoor heat
exchanger
Cross flow fan
Deoxidized copper pipe Outer dia. : 6.35mm Thickness : 0.8mm
Sectional shape of heat insulator
Allowable height
difference : 10m
Allowable pipe length
P Pressure measurement Gauge attaching port
Vacuum pump connecting port
Strainer
Pulse Modulating valve at liquid side
Compressor
DA131S1B-31FZ
Outdoor heat
exchanger
Refrigerant amount : 1.40kg
Propeller fan
OUTDOOR UNIT
Max. : 20m
Min. : 3m Chargeless : 15m
Strainer
Charge : 20g/m (16 to 20m)
The maximum pipe length of this air conditioner is 20 m. When the pipe length exceeds 15m, the additional
charging of refrigerant, 20g per 1m for the part of pipe exceeded 15m is required. (Max. 100g)
Muffler
Accumulater tank
TD
TS
Muffler
FILE NO. SVM-15058
- 21 -
7-2. Operation Data
<Cooling>
Temperature
condition (°C)
Model name
Standard pressure
P (MPa)
Heat
exchanger pipe temp.
Indoor fan mode
Outdoor fan mode
Compressor
revolution
(rps)
Indoor Outdoor T1 (°C)
27/19 35/-
RAS-10G2KCVP-T
0.9 to 1.1 14 to 17 High High
40
RAS-13G2KCVP-T
0.9 to 1.1 10 to 13 High High
66
RAS-18G2KCVP-T
0.9 to 1.1 10 to 13 High High
73
NOTES :
1. Measure surface temperature of heat exchanger pipe around center of heat exchaner path U bent. (Thermistor themometer)
2. Connecting piping condition 7.5 m
FILE NO. SVM-15058
- 22 -
8. CONTROL BLOCK DIAGRAM
8-1. Indoor Unit
M.C.U.
Indoor Unit Control Unit
Power Supply
Serial Signal Communication
(Operation Command and Information)
Serial Signal Transmitter/Receiver
Micro Switch
Converter
(D.C circuit)
Noise Filter
Indoor
Air purifier
unit
Louver
Motor
Louver Motor Drive Control
Indoor Fan
Motor Control
Initializing Circuit
Clock Frequency
Oscillator Circuit
Power Supply
Circuit
Heat Exchanger Sensor (TC)
Room Temperature Sensor (TA)
Infrared Rays Signal Receiver
and Indication
Functions
· Cold draft preventing Function
· 3-minute Delay at Restart for Compressor
· Fan Motor Starting Control
· Processing
(Temperature Processing)
· Timer / Weekly Timer
· Serial Signal Communication
· Clean Function
· Power Selection
Indoor
Fan Motor
Heat Exchanger Sensor (TCJ)
Infrared Rays, 36.7kHz
Remote Controller
Fan Speed Selection
ON TIMER Setting
OFF TIMER Setting
Louver AUTO Swing
Louver Direction Setting
Operation Mode Selection
REMOTE CONTROLLER
ECO
Hi-POWER
COMFORT SLEEPPOWER-SEL
WEEKLY ON / OFF
Operation ( )
COMFORT SLEEP
PURE
FILE NO. SVM-15058
- 23 -
AUTO, COOL, DRY
Thermo. Setting
8-2. Outdoor Unit (Inverter Assembly)
OUTDOOR UNIT
For INDOOR UNIT
220 V ~50Hz
MCC5009 (P.C.B)
MICRO-COMPUTER BLOCK DIAGRAM
Compressor
Outdoor
Fan motor
Current
detect
Current
detect
Gate drive
circuit
M.C.U.
• PWM synthesis function
• Input current release control
• IGBT over-current detect control
• Outdoor fan control
• High power factor correction control
• Inverter output frequency control
• A/D converter function
• PMV control
• Discharge temp. control
• Signal communication to indoor unit
Gate drive
circuit
Inverter
(DC AC)
Inverter
(DC AC)
Converter
(AC DC)
PMV : Pulse Motor Valve
M.C.U. : Micro Control Unit
Clock
frequency
4MHz
Driver circuit
of PMV
PMV
High Power
factor Correction
circuit
Input current
sensor
Indoor unit
send/receive
circuit
Noise
Filter
Discharge
temp. sensor
Outdoor air
temp. sensor
Suction
temp. sensor
FILE NO. SVM-15058
- 24 -
  
9. OPERATION DESCRIPTION
9-1. Outline of Air Conditioner Control
This air conditioner is a capacity-variable type air conditioner, which uses AC or DC motor for the indoor for motor and the outdoor fan motor. And the capacity­proportional control compressor which can change the motor speed in the range from 11 to 96 rps is mounted. The DC motor drive circuit is mounted to the indoor unit. The compressor and the inverter to control fan motor are mounted to the outdoor unit.
The entire air conditioner is mainly controlled by the indoor unit controller.
The indoor unit controller drives the indoor fan motor based upon command sent from the remote controller, and transfers the operation command to the outdoor unit controller.
The outdoor unit controller receives operation com­mand from the indoor unit side, and controls the outdoor fan and the pulse Modulating valve. (P.M.V) Besides, detecting revolution position of the compres­sor motor, the outdoor unit controller controls speed of the compressor motor by controlling output voltage of the inverter and switching timing of the supply power (current transfer timing) so that motors drive according to the operation command. And then, the outdoor unit controller transfers reversely the operating status information of the outdoor unit to control the indoor unit controller.
As the compressor adopts four-pole brushless DC motor, the frequency of the supply power from inverter to compressor is two-times cycles of the actual number of revolution.
1. Role of indoor unit controller
The indoor unit controller judges the operation commands from the remote controller and assumes the following functions.
• Judgment of suction air temperature of the indoor heat exchanger by using the indoor temp. sensor. (TA sensor)
• Judgment of the indoor heat exchanger tempera­ture by using heat exchanger sensor (TC sensor) (Prevent-freezing control, etc.)
• Louver motor control
• Indoor fan motor operation control
• LED (Light Emitting Diode) display control
• Transferring of operation command signal (Serial signal) to the outdoor unit
• Reception of information of operation status (Serial signal including outside temp. data) to the outdoor unit and judgment/display of error
• Air purifier operation control
2. Role of outdoor unit controller
Receiving the operation command signal (Serial signal) from the indoor unit controller, the outdoor unit performs its role.
• Compressor operation control
• Operation control of outdoor fan motor
• P.M.V. control
• 4-way valve control
Operations followed to judgment of serial signal from indoor side.
• Detection of inverter input current and current release operation
• Over-current detection and prevention operation to IGBT module (Compressor stop function)
• Compressor and outdoor fan stop function when serial signal is off (when the serial signal does not reach the board assembly of outdoor control by trouble of the signal system)
• Transferring of operation information (Serial signal) from outdoor unit controller to indoor unit controller
• Detection of outdoor temperature and operation revolution control
3. Contents of operation command signal (Serial signal) from indoor unit controller to outdoor unit controller
The following three types of signals are sent from the indoor unit controller.
• Operation mode set on the remote controller
• Compressor revolution command signal defined
by indoor temperature and set temperature (Correction along with variation of room tempera­ture and correction of indoor heat exchanger temperature are added.)
• Temperature of indoor heat exchanger
• For these signals ([Operation mode] and [Com-
pressor revolution] indoor heat exchanger tem­perature), the outdoor unit controller monitors the input current to the inverter, and performs the followed operation within the range that current does not exceed the allowable value.
4. Contents of operation command signal (Serial signal) from outdoor unit controller to indoor unit controller
The following signals are sent from the outdoor unit controller.
• The current operation mode
• The current compressor revolution
• Outdoor temperature
• Existence of protective circuit operation
For transferring of these signals, the indoor unit controller monitors the contents of signals, and judges existence of trouble occurrence.
Contents of judgment are described below.
• Whether distinction of the current operation status meets to the operation command signal
• Whether protective circuit operates When no signal is received from the outdoor
unit controller, it is assumed as a trouble.
FILE NO. SVM-15058
- 25 -
9-2. Operation Description
1. Basic operation ........................................................................................................... 26
1. Operation control ................................................................................................... 26
2.
Cooling operation .................................................................................................. 27
3. AUTO operation .....................................................................................................
28
4. DRY operation........................................................................................................ 28
2. Indoor fan motor control ............................................................................................. 29
3. Outdoor fan motor control........................................................................................... 31
4. Capacity control .......................................................................................................... 32
5. Current release control ............................................................................................... 32
6. Release protective control by temperature of indoor heat exchanger........................ 33
7.
8.
Louver control ............................................................................................................. 36
1) Louver position....................................................................................................... 36
2) Air direction adjustment ......................................................................................... 34
3) Swing ..................................................................................................................... 34
9.
ECO operation ............................................................................................................ 39
10.
Temporary operation................................................................................................... 40
11.
Plasma
ionizer purifier control [Detection of abno
rmality] ......................................... 40
12.
Discharge temperature control ................................................................................... 41
14.
Pulse Modulating valve (P.M.V.) control ..................................................................... 42
15.
Self-Cleaning function ................................................................................................ 43
16.
Remote-A or B selection ............................................................................................ 44
9-3. Auto Restart Function ..
9-3-1. How to Set the A uto Restart Function .............................. ........................................ 50
9-3-2. How to Cancel the Au to Restar t Function ................................................................ 51
9-3-3. Power Failure During Timer Operation ................................................................... 51
21.
POWER
selection mode
....................................................................................47
9-4. Remote Controller and Its Fuctions
9-4-1. Parts Name of Remote Contr oller .............................................................................. 52
9-4-2. Operation of remote control ...................................................................................... 52
17.
QUIET mode ............................................................................................................. 45
18.
COMFORT SLEEP mode ......................................................................................... 45
19.
Short Timer ................................................................................................................ 45
20.
Hi-POWER Mode ..................................................................................................... 46
9-4-3. Name and Functions of Indications on Remote Contr oller ........................................ 61
Outdoor Quiet Control
.........................................................................................47
F
CU Display lamp rightness control .....................................................................48
13.
FILE NO. SVM-15058
- 26 -
Item
1. Basic operation
Operation flow and applicable data, etc.
1. Operation control
Description
Receiving the user’s operation condition setup, the operation statuses of indoor/outdoor units are
controlled.
1) The operation conditions are selected by the remote controller as shown in the below.
2) A signal is sent by ON button of the remote controller.
3)
The
signal is received by a sensor of the indoor unit and processed by the indoor controllers as
shown
in the below. The power relay is tumed ON and power supply to the outdoor unit.
4) The indoor controller controls the indoor fan motor and louver motor.
5) The indoor controller sends the operation command to the outdoor controller, and sends/receives the control status with a serial signal.
6)
The
outdoor controller controls the operation as shown in the below, and also controls the
compressor, outdoor fan motor, pulse Modulating valve are controlled.
Remote controller
Control contents of remote controller
• ON/OFF (Air condi
tioner/Air purifier)
• Operation select (COOL/AUTO/DRY)
• Temperature
setup
• Air
direction
• Swing
Air
volume select (AUTO/QUIET/LOW/LOW+/MED/MED+/HIGH)
ECO
• ON
timer setup
• OFF
timer setup
• Hi-POWER
Selection of
operation
conditions
ON/OFF
COMFORT
SLEEP
QUIET
PRESET
ONE-TOUCH
POWER-SELECTION
Indoor unit control
Operation command
Power relay
signal Serial
transmission
signalSerial
Inverter
Transmission
Signal
receiving
Outdoor unit
Indoor unit control
• Command signal generating function for indoor unit operation
• Calculation function (temperature calculation)
• 3 minute delay function for compressor reactivation
• Activation compensation function for indoor fan
• Cold draft preventive function
Timer
function
• Indoor heat exchanger release control
Outdoor unit control
• Inverter output frequency control
• Waveform composite function
Calculation
function
(temperature calculation)
• AD conversion function
• Compressor reactivation delay function
• Current release function
• GTr overload protective function
• Outdoor temperature estimation
• Indoor fan motor
Louver motor
Compressor
• Outdoor fan motor
Pulse modulating valve
In
door unit
A/B
Selection
function
Contront
air
flow
(wide
angle/Right
wide/Left
wide/spot
front/spot right/spot
lift)
FILE NO. SVM-15058
- 27 -
Item
1. Basic operation
Operation flow and applicable data, etc.
2.
Description
Cooling/Heating operation
The operations are performed in the following parts by controls acc
ording to cooling conditions.
1)
Receiving the operation ON signal of the remote controller, the cooling operation signal starts being transferred form the indoor controller to the outdoor unit.
2) At the indoor unit side, the indoor fan is operated according to the contents of “2. Indoor fan motor control” and the louver according to the contents of “9. Louver control”, respectively.
3) The outdoor unit controls the outdoor fan motor, compressor, pulse Modulating valve and according to the operation signal sent from the indoor unit.
Remote control
settings
Operation ON
Indoor unit control
Operation command
signal transmission
Outdoor unit control
Power relay ON
Indoor fan motor
revolution control
Compressor revolution control Outdoor fan motor revolution control Pulse modulating valve control
FILE NO. SVM-15058
- 28 -
Item
1. Basic operation
Operation flow and applicable data, etc.
Description
4. DRY operation
DRY operation is performed according to the difference between room temperature and the setup temperature as shown below.
In DRY operation, fan speed is controlled in order to prevent lowering of the room temperature and to avoid air flow from blowing directly to persons.
1) Detects the room temperature (Ta) when the DRY operation started.
2) Starts operation under conditions in the left figure according to the temperature difference between the room tempera­ture and the setup temperature (Tsc). Setup temperature (Tsc) = Set temperature on remote controller
(Ts) + (0.0 to 1.0)
3) When the room temperature is lower 1°C or less than the setup temperature, turn off the compressor.
Tsc
+
0.5
+
1.0
[°C]
Ta
Fan speed
L– (W5)
(W5+W3) / 2
SUL (W3)
3. AUTO operation
Selection of operation mode As shown in the following figure, the operation starts by selecting automatically the status of room temperature (Ta) when starting AUTO operation.
*1. When reselecting the operation mode, the fan
speed is controlled by the previous operation mode.
1)
Detects the room temperature (Ta) when the operation started.
2) Selects an operation mode from Ta in the left figure.
3) Fan operation continues until an operation mode is selected.
4)
Ts + 1
Ta
Cooling operation
Monitoring (Fan)
In AUTO mode, when room temperature reach set temperature commpressor will stop.
FILE NO. SVM-15058
- 29 -
Item
2. Indoor fan motor control
Operation flow and applicable data, etc.
<In cooling operation>
(This operation controls the fan speed at indoor unit side.) The indoor fan
(cross flow fan) is operated by the phase­control induction motor. The fan rotates in 5 stages in MANUAL mode, and in 5 stages in AUTO mode, respec­tively. (Table 1)
Description
* Symbols
UH : Ultra High H : High M+ : Medium+ M : Medium L+ : Low+ L: Low L- : Low– UL :
Ultra Low
SUL : Super Ultra Low
* The values of fan speed and air flow
volume indicate on the table are measured when the louver is inclined downward. Fan speed and air flow volume broadly vary with position
(Fig. 1)
(Fig. 2)
+2.5
Ta
[°C]
+2.0
+1.5
+1.0
+0.5
Tsc
a
b
c
d
e
M+(WC)
*3
*4
*5
L(W7)
Air volume AUTO
L L+ M M+ H
W7
(L + M) / 2
WA
(M + H) / 2
WD
Indication
Fan speed
Fan speed setup
COOL ON
AUTO
MANUAL
*3 : Fan speed = (M + –L) x 3/4 + L
*4 : Fan speed = (M + –L) x 2/4 + L
*5 : Fan speed = (M + –L) x 1/4 + L
(Linear approximation from M+ and L)
(Table 1) Indoor fan air flow rate
Quiet
W5
of louver.
1) When setting the fan speed to L, L+, M, M+,H or Quiet on the remote controller, the operation is performed with the constant speed shown in Fig. 1.
2) When setting the fan speed to AUTO on the remote controller, revolution of the fan motor is controlled to the fan speed level shown in Fig. 2 and Table 1 according to the setup tempera­ture, room temperature, and heat exchanger temperature.
RAS-10G2KCVP-T RAS-13G2KCVP-T RAS-18G2KCVP-T
Cooling Cooling Cooling
Fan speed Air Flow rate Fan speed Air Flow rate Fan speed Air Flow rate
(rpm)
(m3/h)
(rpm)
(m3/h)
(rpm)
(m3/h)
WF
UH/H
1060 661 1100 690 1120 713
WE
UH
1060 661 1100 698 1120 713
WD
H UH
1040 647 1080 676 1120 713
WC
M+ M+ H
900 527 930 551 960 576
WB
M+
900 527 930 551 950 567
WA
M M/L+ M
760 409 780 423 800 442 W9 760 409 780 423 800 442 W8
L+ L+
690 349 710 368 730 384 W7
L L
600 274 640 305 660 322 W6
L- L
520 205 560 243 580 255 W5
UL L- L-
500 187 540 224 560 243 W4
UL
480 173 520 205 540 224 W3
SUL UL
SUL/SL-
460 155 500 187 520 205 W2
SL
450 147 480 173 500 187 W1
SL-
440 142 440 142 440 142
Fan speed
Cool PAP Dry
Level
FILE NO. SVM-15058
- 30 -
Loading...
+ 92 hidden pages