4-1 Indoor Unit
4-2 Outdoor Unit (RAS-13UAH-E3)
4-3 Outdoor Unit (RAS-10UAH-E3)
4-4 Outdoor Unit (RAS-07UAH-E3)
4-5 Indoor Unit (RAS-13NKD-E, RAS-10NKD-E, RAS-07NKD-E)
4-6 Outdoor Unit (RAS-13UA-E3)
4-7 Outdoor Unit (RAS-10UA-E3)
4-8 Outdoor Unit (RAS-07UA-E3)
7-1 Outline of Air Conditioner Control
7-2 Description of Operation Circuit
7-3 Hi POWER Mode
7-4 High-Temperature Limit Control
7-5 Low-Temperature Limit Control
7-6 Defrost Operation (NKHD Series only)
7-7 Current Limit Control (NKHD Series only)
7-8 Auto Restart Function
7-9 Filter Check Lamp
7-10 Self-Cleaning function
– 1 –
8.INSTALLATION PROCEDURE
8-1 Safety Cautions
8-2 Installation Diagram of Indoor and Outdoor Units
8-3 Installation
8-4 Indoor Unit
8-5 Outdoor Unit
8-6 How to Set Remote Control Selector Switch
8-7 Others
9.TROUBLESHOOTING CHART
9-1 Troubleshooting Procedure
9-2 Basic Check Items
9-3 Primary Judgement
9-4 Self-Diagnosis by Remote Control (Check Code)
9-5 Troubleshooting Flowcharts
9-6 Troubleshooting for Remote Control (Including The Indoor P.C. Board)
9-7 Troubleshooting for Air Purifier and Minus Ion
10. PART REPLACEMENT
10-1 Indoor Unit
10-2 Outdoor Unit
FILE NO. SVM-04022
11. EXPLODED VIEWS AND PARTS LIST
11-1 Indoor Unit (E-Parts Assy)
11-2 Indoor Unit
11-3 Outdoor Unit (RAS-13UAH-E3)
11-4 Outdoor Unit (RAS-10UAH-E3)
11-5 Outdoor Unit (RAS-07UAH-E3)
11-6 Outdoor Unit (RAS-13UA-E3)
11-7 Outdoor Unit (RAS-10UA-E3)
11-8 Outdoor Unit (RAS-07UA-E3)
– 2 –
FILE NO. SVM-04022
1. SPECIFICA TIONS
MODEL RAS-13NKHD-E/ RAS-13UAH-E 3 RAS-13NKD-E / RAS-13UA-E3
ITEM Cooling Heating Cooling
Capacity
Power source V 220 − 240
Power consumptionkW1.271.321.261.331.241.28
Pow er factor%989698969895
RunningIndoorA0.15
currentOutdoorA5.755.605.705.655.755.60
Starting currentA2524
Moisture removallit/h2.0
Noise
Refrigerant
Refrigerant controlCapillary tube
Interconnection
pipe
INDOOR UNIT RAS-13NKHD-E RAS-13NKD-E
Dimensions Width mm 790
Net weight kg 10
Evaporator typeFinned tube
Indoor fan typeCross flow fan
Air volumeMedium fanm3/h520550520
Fan motor outputW20
Air filterHoneycomb woven filter with PP frame
OUTDOOR UNIT RAS-13UAH-E3 RAS-13UA-E3
DimensionsWidthmm780
Net weight kg 37 34
Condenser typeFinned tube
Outdoor fan typePropeller fan
Airflow volume m3/h 2120
Fan motor outputW
Indoor (H/M/L)dB41/35/31
Outdoor (220 − 240 V)dB495149514748
Name of refrigerantR22
Rated amount kg 1.00 0.80
Gas side size mm ∅12.7
Connection typeFlare connection
Liquid side size mm ∅6.35
Connection typeFlare connection
Maximum length
(One way)
Maximum height
difference
Height mm 275
Depth mm 218
High fanm3/h630650630
Low fanm3/h430490430
Heightmm550
Depthmm270
Model PH170T2-4L2 PH225X2C-4FT
Output W1100
kW 3.55 3.60 4.40 4.45 3.70 3.75
Phase 1∅
Hz50
m
m
220 V 240 V 220 V 240 V 220 V 240 V
1
15*
6
2200
2120 2200 2030 2150
42
30
– 3 –
FILE NO. SVM-04022
MODEL RAS-10NKHD-E / RAS-10UAH-E3 RAS-10NKD-E / RAS-10UA-E3
ITEMCoolingHeatingCooling
Capacity
Power sourceV220 − 240
Power consumptionkW1.001.050.890.910.800.85
Power factor%959294919795
RunningIndoorA0.15
currentOutdoorA4.654.604.154.003.603.58
Starting currentA1916
Moisture removallit/h1.2
Noise
Refrigerant
Refrigerant controlCapillary tube
Interconnection
pipe
INDOOR UNITRAS-10NKHD-E RAS-10NKD-E
DimensionsWidthmm790
Net weightkg10
Evaporator typeFinned tube
Indoor fan typeCross flow fan
Air volumeMedium fanm3/h460520460
Fan motor outputW20
Air filterHoneycomb woven filter with PP frame
OUTDOOR UNITRAS-10UAH-E3 RAS-10UA-E3
DimensionsWidthmm780
Net weightkg3130
Condenser typeFinned tube
Outdoor fan typePropeller fan
Airflow volume m3/h174018501740185017401850
Fan motor outputW20
Indoor (H/M/L)dB39/33/26
Outdoor (220 − 240 V)dB474947494445
Name of refrigerantR22
Rated amountkg0.760.65
Gas side sizemm∅9.52
Connection typeFlare connection
Liquid side sizemm∅6.35
Connection typeFlare connection
Maximum length
(One way)
Maximum height
difference
Heightmm275
Depth mm 218
High fanm3/h570610610
Low fanm3/h340400340
Heightmm550
Depthmm270
ModelPH120T1-4CPH102T1-4CH
Output W750
kW2.702.753.123.152.652.70
Phase1∅
Hz50
m10*
m
220 V240 V220 V240 V220 V240 V
1
5
−4−
FILE NO. SVM-04022
MODEL
RAS-07NKHD-E RAS-07NKD-E
RAS-07UAH-E3 RAS-07UA-E3
ITEM Cooling Heating Cooling
Capacity
Phase1∅ı
Power sourceV220 − 240
Power consumption kW 0.69 0.76 0.60 0.65 0.60 0.64
Power factor % 98 97 97 95 92 89
RunningIndoorA0.15
current Outdoor A 3.05 3.10 2.65 2.70 2.80 2.85
Starting currentA1311
Moisture removallit/h0.8
NoiseIndoor (H/M/L)dB38/32/26
Outdoor (220-240V) dB
Refrigerant
Refrigerant controlCapillary tube
Interconnection
pipe
Name of refrigerantR-22
Rated amountkg0.620.57
Gas side sizemmı 9.52
Connection typeFlare connection
Liquid side sizemmı 6.35
Connection typeFlare connection
Maximum length
(One way)
Maximum height
difference
220V 240V 220V 240V 220V 240V
kW 2.00 2.05 2.20 2.25 2.10 2.15
Hz50
44
m10*
m 5
45 45
46
44
1
45
INDOOR UNITRAS-07NKHD-ERAS-07NKD-E
Heightmm275
DimensionsWidthmm790
Depth mm 218
Net weightkg10
Evaporator typeFinned tube
Indoor fan typeCross flow fan
High fanm3/h570610570
Air volumeMedium fanm3/h460490460
Low fanm3/h340400340
Fan motor outputW20
Air filterHoneycomb woven filter with PP frame
OUTDOOR UNITRAS-07UAH-E3RAS-07UA-E3
Heightmm530
DimensionsWidthmm660
Depthmm240
Net weightkg2726
Condenser typeFinned tube
Outdoor fan typePropeller fan
Airflow volume m3/h128013601280136012801360
Fan motor outputW20
Compressor
Safety deviceFuse, Overload relay
Louver typeAutomatic louver
Usable outdoor temperature range °C15 ~ 43−10 ~ 2415 ~ 43
ModelPH80T1-4C
Output W605
– 5 –
Note : 1
•
Capacity is based on the following temperature conditions.
FILE NO. SVM-04022
Temperature
Indoor unit inlet air temperature
Outdoor unit inlet air temperature
Note : 2
*1
No need to charge extra refrigerant.
Condition
Cooling Heating
(DB) 27°C20°C
(WB)19°C15°C
(DB) 35°C7°C
(WB)24°C6°C
JIS B8615-1
− 6 −
2-1.Indoor Unit
FILE NO. SVM-04022
2. CONSTRUCTION VIEWS
Front panel
60
6
Knock out system
Air inletAir Filter
275
Back body
Heat exchangerPlasma air purifier
790
Air outlet
64
53
12080
590
Hanger
218
60
6
48
Knock out system
48
Drain hose (0.54 m)
Hanger
45
Minimum
distance
to ceiling
275
1
7
0
o
r
m
o
r
e
320
620
235235
215215
e
r
o
Minimum
m
distance
or
to ceiling
5
6
Hanger
–7 –
Connecting pipe (0.43 m)
(Flare ∅6.35)
Connecting pipe (0.33 m)
(For 13 series ; Flare ∅12.70
For 07, 10 series ; Flare ∅9.52)
Hanger
For stud bolt (∅6)
Hanger
150150160160
9090
Installation plate outline
Center line
For stud bolt
(∅8~∅10)
26
Minimum
distance
to ceiling
1
7
0
o
r
m
o
r
e
32
4519040
163
5819
Wireless remote control
FILE NO. SVM-04022
2-2. Outdoor Unit (RAS-13UAH-E3, RAS-10UAH-E3, RAS-13UA-E3, RAS-10UA-E3)
A
A
Detail Drawing (Back Leg)
6 Hole
∅
302
310
32.5
600
52
36
270
R15
R5.5
310
302
∅
30 Drain outlet
436
∅
530
265
FAN GUARD
115125
∅
11 x 14 Hole
2(For
∅8-∅
600
780
10 anchor bolt)
∅11 x 14 Hole
90
62
B
B Detail Drawing (Front Leg)
310
102
302
∅6 Hole
36
52
310
330
R15
COVER PV
Z
Electrical
part cover
Installation dimension
B or more
325
100 or more
Z
Air outlet
View
600
Air inlet
A or more
600 or more
120
54
75
13 Series
600 mm400 mm
A
B100 mm45 mm
∅
11 Long holes (For∅8-∅10 anchor bolt)
4 x
Liquid side
(Flare ∅6.35)
Gas side
(Flare ∅9.52)
10 Series
Gas side
(Flare ∅12.7)
13 Series
Service port
10 Series
– 8 −
2-3. Outdoor Unit (RAS-07UAH-E3, RAS-07UA-E3)
A
97
A
Detail Drawing (Back Leg)
∅
6 Hole
265
273.5
50
36
660
R 15
R 5.5
530
273.5
∅
420
59.5
∅
Fan guard
25Drain outlet
2-
∅
11x14 hole
(for
∅8-∅
B
10 anchor bolt)
FILE NO. SVM-04022
B
Detail Drawing (Front Leg)
265
273.5
∅
6 Hole
∅
11x14 Hole
36
50
R 15
660
Cover PV
Z
242
Installation dimension
100 or more
325
100 or more
Air outlet
50097.5
660
View
Z
600
Air inlet
600 or more
600 or more
(11)
126
48
297
54
Service port
56
4x
∅
11x14 Long holes (for∅8-∅10 anchor bolt)
(12.5)273.5 (pitch)
Liquid side
(Flare
∅
Gas side
∅
(Flare
6.35)
9.62)
− 9 −
WIRING DIAGRAM
3.
3-1. RAS-13NKHD-E / RAS-13UAH-E3
FILE NO. SVM-04022
Power Cord
SINGLE PHASE
220-240V 50Hz
BLK
BLK
BRW
BLU
GRN & YEL
THERMO
SENSOR (TA)
BLK
HEAT EXCHANGER
SENSOR (TC)
BLK
INDOOR
TERMINAL
OUTDOOR
TERMINAL
112
CN03
112
CN01
BLOCK
BLOCK
BLK
P04
ORN
T02
C.T.
73°C
THERMAL FUSE
PNK
PNK
112
CN04
2
SG01
P01
P02
2
R22
VARISTOR
3
4
RY01
F01
T6.3A 250V
RY04RY03
CR01
Louver
Motor
YEL
54321
CN07
54321
C01
R21
VARISTOR
MAIN P.C. BOARD
MCC-5007
YEL
YEL
YEL
CN25
WHI
L01
150°C
2
BLK
1
WHI
CN01
CR02
RED
2
BLU
GRN & YEL
4
3
AC FAN MOTOR
1
2
1
2
BLU
BLU
1
2
1
2
DC12V
DC12V
DC5V
C02
C15
CN10
BLK
1
1
GRY
2
2
YEL
3
3
BRW
4
4
RED
5
5
WHI
6
6
INFRARED RAYS RECEIVE
AND INDICATION PARTS
345
345
BLU
345
345
6
6
BLU
BLU
BLU
6
6
POWER SUPPLY
CIRCUIT
R01
R26
789
789
BLU
789
789
CN13
BLU
DB01C03
R25
CR03
R27
335
5
1
1
BLU
IC03
1
10
10
BLU
10
10
CN11
11
11
WHI
11
11
CN34
BRW
1
1
BLU
2
2
BRW
4
4
BRW
3
3
BRW
2
2
RED
1
1
+
CN33
1
3
2
4
1
3
2
4
BLK
RED
1
1
331
2
2
Power supply
BRW
BRW
BRW
3
5
2
4
3
5
2
4
High-voltage
RED
WP-002
RED
BLK
6
6
RED
BLK
BLK/RED
Ion
Electrode
Air purifier
Electrode
OVERLOAD RELAY
COMPRESSOR
BLK
BLK
PNK
WHI
1(L)2(N)
RED
SOLENOID COIL
RED
RED
CAPACITOR
BLU
CAPACITOR
BLU
FAN MOTOR
43
CHASSIS
WHI
BLK
– 10−
3-2. RAS-10NKHD-E / RAS-10UAH-E3
RAS-07NKHD-E / RAS-07UAH-E3
FILE NO. SVM-04022
Power Cord
SINGLE PHASE
220-240V 50Hz
BLK
BLK
OVERLOAD RELAY
BRW
BLU
GRN & YEL
THERMO
SENSOR (TA)
BLK
HEAT EXCHANGER
SENSOR (TC)
BLK
INDOOR
TERMINAL
OUTDOOR
TERMINAL
BLK
BLOCK
BLOCK
ORN
112
CN03
112
CN01
BLK
P04
C.T.
73°C
THERMAL FUSE
PNK
PNK
112
CN04
2
SG01
T02
P01
P02
2
R22
VARISTOR
3
4
RY01
F01
T6.3A 250V
RY04RY03
CR01
Louver
Motor
CN07
C01
R21
VARISTOR
MAIN P.C. BOARD
MCC-5007
YEL
YEL
YEL
YEL
54321
54321
WHI
L01
150°C
2
BLK
1
1(L)2(N)
BLK
RED
WHI
RED
2
3
BLU
SOLENOID COIL
CAPACITOR
RED
RED
CN01
BLU
CR02
BLU
GRN & YEL
4
43
CHASSIS
BLK
WHI
AC FAN MOTOR
CN25
1
1
BLU
1
1
C02
1
1
2
2
3
3
4
4
5
5
6
6
INFRARED RAYS RECEIVE
AND INDICATION PARTS
345
345
BLU
345
345
DC12V
DC12V
DC5V
BLU
BLU
POWER SUPPLY
CIRCUIT
R01
6
6
BLU
6
6
2
2
BLU
2
2
R26
CR03
R27
C15
CN10
BLK
GRY
YEL
BRW
RED
WHI
335
5
789
789
BLU
789
789
CN13
DB01C03
R25
10
11
10
11
BLU
WHI
BLU
BLU
10
11
10
11
CN34
BRW
1
1
BLU
2
2
BRW
4
4
BRW
3
3
BRW
2
2
RED
1
1
+
CN33
1
3
2
4
1
3
2
4
BLK
IC03
CN11
1
2
1
1
2
331
RED
1
1
Power supply
BRW
BRW
BRW
3
5
2
4
3
5
2
4
High-voltage
RED
WP-002
RED
BLK
6
6
RED
BLK
BLK/RED
Ion
Electrode
Air purifier
Electrode
COMPRESSOR
PNK
WHI
FAN MOTOR
CAPACITOR
− 11 −
3-3. RAS-13NKD-E / RAS-13UA-E3
FILE NO. SVM-04022
Power Cord
SINGLE PHASE
220-240V 50Hz
BLK
BLK
BRW
BLU
GRN & YEL
THERMO
SENSOR (TA)
BLK
HEAT EXCHANGER
SENSOR (TC)
BLK
INDOOR
TERMINAL
OUTDOOR
TERMINAL
CN03
CN01
BLOCK
BLOCK
112
112
BLK
P04
73°C
SG01
CN04
R22
VARISTOR
3
4
PNK
112
RY01
PNK
2
THERMAL FUSE
F01
T6.3A 250V
Louver
Motor
CN07
54321
54321
C01
R21
VARISTOR
YEL
YEL
YEL
YEL
CN25
WHI
L01
MAIN P.C. BOARD
MCC-5007
2
150°C
2
WHI
BLK
1
GRN & YEL
2
AC FAN MOTOR
INFRARED RAYS RECEIVE
1
2
1
2
BLU
BLU
1
2
1
2
DC12V
DC12V
DC5V
C02
C15
CN10
BLK
1
1
GRY
2
2
YEL
3
3
BRW
4
4
RED
5
5
WHI
6
6
AND INDICATION PARTS
345
345
BLU
345
345
6
6
BLU
BLU
6
6
POWER SUPPLY
CIRCUIT
R01
R26
BLU
CN13
789
789
BLU
789
789
BLU
DB01C03
R25
CR03
R27
335
5
1
1
BLU
IC03
1
10
10
BLU
10
10
CN11
11
11
WHI
11
11
CN34
BRW
1
1
BLU
2
2
BRW
4
4
BRW
3
3
BRW
2
2
RED
1
1
+
CN33
1
3
2
4
1
3
2
4
BLK
RED
1
1
331
2
2
Power supply
BRW
BRW
BRW
3
5
2
4
3
5
2
4
High-voltage
RED
WP-002
RED
BLK
6
6
RED
BLK
BLK/RED
Ion
Electrode
Air purifier
Electrode
BLK
BLKRED
1(L)2(N)
FAN MOTOR
CAPACITOR
RED
WHI
COMPRESSOR
CHASSIS
RED
PNK
WHI
– 12 −
3-4. RAS-10NKD-E / RAS-10UA-E3
RAS-07NKD-E / RAS-07UA-E3
FILE NO. SVM-04022
Power Cord
SINGLE PHASE
220-240V 50Hz
BLK
BLK
BRW
BLU
GRN & YEL
THERMO
SENSOR (TA)
BLK
HEAT EXCHANGER
SENSOR (TC)
BLK
INDOOR
TERMINAL
OUTDOOR
TERMINAL
CN03
CN01
BLOCK
BLOCK
112
112
BLK
P04
73°C
SG01
CN04
R22
VARISTOR
3
4
PNK
112
RY01
PNK
2
THERMAL FUSE
F01
T6.3A 250V
Louver
Motor
CN07
R21
C01
VARISTOR
YEL
YEL
YEL
YEL
54321
54321
CN25
WHI
L01
MAIN P.C. BOARD
MCC-5007
2
150°C
2
WHI
BLK
1
GRN & YEL
2
AC FAN MOTOR
1
2
1
2
BLU
BLU
1
2
1
2
DC12V
DC12V
DC5V
C02
C15
CN10
BLK
1
1
GRY
2
2
YEL
3
3
BRW
4
4
RED
5
5
WHI
6
6
INFRARED RAYS RECEIVE
AND INDICATION PARTS
345
345
BLU
345
345
BLU
BLU
POWER SUPPLY
CIRCUIT
R01
R26
6
6
BLU
6
6
789
789
BLU
789
789
CN13
BLU
DB01C03
R25
CR03
R27
335
5
1
1
BLU
IC03
1
10
10
BLU
10
10
CN11
11
11
WHI
11
11
CN34
BRW
1
1
BLU
2
2
BRW
4
4
BRW
3
3
BRW
2
2
RED
1
1
+
CN33
1
3
2
4
1
3
2
4
BLK
RED
1
1
331
2
2
Power supply
BRW
BRW
BRW
3
5
2
4
3
5
2
4
High-voltage
RED
WP-002
RED
BLK
6
6
RED
BLK
BLK/RED
Ion
Electrode
Air purifier
Electrode
BLK
BLKRED
OVERLOAD
RELAY
1(L)2(N)
FAN MOTOR
BLK
CAPACITOR
RED
WHI
COMPRESSOR
CHASSIS
RED
PNK
WHI
− 13 −
FILE NO. SVM-04022
4. SPECIFICATION OF ELECTRICAL PARTS
4-1.Indoor Unit (RAS-13NKHD-E, RAS-10NKHD-E, RAS-07NKHD-E)
No.Parts nameTypeSpecifications
1 Fan motor (for indoor) SKF-220-20-4A-1 AC Motor with 150°C thermo fuse
2Thermo sensor (TA-sensor)10kΩ at 25°C
3Switching transformerSWT-77
4Microcontroller unit (IC30)TMP87CM40AN
5Heat exchanger sensor
(TC-sensor)
6Line filter (L01)LC*SS11V-0627027mH, 600mA
7Bridge rectifier (DB01)D3SBA604A, 600 V
8Capacitor (C03)KHM400VSSN47M22547μF, 400 V
9Fuse (F01)BET6.3AT6.3A, 250VAC
4-5. Indoor Unit (RAS-13 NKD-E, RAS-10NKD-E, RAS-07NKD-E)
No.Parts nameTypeSpecifications
1Fan motor (for indoor)SKF-220-20-4A-1AC Motor with 150°C thermo fuse
2Thermo sensor (TA-sensor)———10kΩ at 25°C
3Switching transformerSWT-77
4Microcontroller unit (IC30)TMP87CM40AN
5Heat exchanger sensor
(TC-sensor)
6Line filter (L01)LC*SS11V-0627027mH, 600mA
7Bridge rectifier (DB01)D3SBA604A, 600 V
8Capacitor (C03)KHM400VSSN47M22547μF, 400 V
9Fuse (F01)BET6.3AT6.3A, 250VAC
• Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor)
Ambient temp.
conditions DB/WB
(°C)
IndoorOutdoor
– 23 –
6-1. Heat Pump model
Heat Exchange sensor
6. CONTROL BLOCK DIAGRAM
Main Unit Control Panel
Functions
M.C.U.
FILE NO. SVM-04022
Operation
Display
Thermo. Sensor
Infrared Rays Signal Reciver
•ı Louver Control
•ı3-minutes Delay at Restart
for Compressor
•ıAir-purifier control
Initiallizing Circuit
Clock Frequency
Oscillator Circuit
Power Supply
Circuit
Noise FilterRelay Driver, Louver Driver
•ıMotor Revolution Control
•ıProcessing
(Temperature Processing)
•ıTimer
Compressor
ON/OFF
Signal
Outdoor Fan
ON/OFF
Signal
RY01
Relay
4-Way Valve
ON/OFF
Signal
RY03
Relay
Louver
ON/OFF
Signal
Relay
Timer
Display
Filter Sign
Display
Hi Power
Sign Display
PAP
Sign Display
Indoor Fan
Motor
Air purifier
Unit
Micro
Switch
Louver
Motor
RY04
220-240 V~ 50-60Hz
REMOTE CONTROL
Compressor4-Way Valve
Remote Control
Operation (START/STOP)
Operation Mode Selection
AUTO, COOL, DRY, HEAT
Temperature Setting
Fan Speed Selection
ON TIMER Setting
OFF TIMER Setting
Louver Auto Swing
Louver Direction Setting
ECO
Hi Power
Filter Reset
Air Purifier
Outdoor Fan Motor
Infrared Rays
SLEEP
− 24 −
6-2. Cooling model
Heat Exchange sensor
Thermo. Sensor
Infrared Rays Signal Reciver
Main Unit Control PanelM.C.U.
Functions
• Louver Control
• 3-minutes Delay at Restart
for Compressor
•ıAir-purifier control
Initiallizing Circuit
Clock Frequency
Oscillator Circuit
Power Supply
Circuit
• Motor Revolution Control
• Processing
(Temperature Processing)
• Timer
Compressor
ON/OFF
Signal
FILE NO. SVM-04022
Operation
Display
Timer
Display
Filter Sign
Display
Hi Power
Sign Display
PAP
Sign Display
Indoor Fan
Motor
Air purifier
Unit
Louver
ON/OFF
Signal
Micro
Switch
220-240 V~ 50-60Hz
REMOTE CONTROL
Noise FilterRelay Driver, Louver Driver
Relay
RY01
Compressor, Outdoor Fan Motor
Infrared Rays
Remote Control
Operation (START/STOP)
Operation Mode Selection
AUTO, COOL, DRY, FAN ONLY
Temperature Setting
Fan Speed Selection
ON TIMER Setting
OFF TIMER Setting
Louver Auto Swing
Louver Direction Setting
Louver
Motor
ECO
Hi power
Filter Reset
Air Purifier
SLEEP
– 25 –
7. OPERATION DESCRIPTION
FILE NO. SVM-04022
7-1.Outline of Air Conditioner Control
This is a fixed-capacity type of air conditioner with a
Plasma Air-Purifier consisting of an AC fan motor for
an indoor unit. Both Plasma Air-Purifier and AC motor
drive circuit are mounted in the indoor unit. The
electrical parts driving the compressor and the fan
motor for an outdoor unit are mounted in the outdoor
unit.
The air conditioner is controlled by the controller
mounted in the indoor unit. The controller operates all
components based on the commands transmitted from
the remote control and the feedback data of the sensor
is as follow:
• The temperature measurement at the air inlet of
the indoor heat exchanger by the indoor
temperature sensor
•ı The temperature measurement at the indoor
heat exchanger by the indoor heat exchanger
temperature sensor
• Plasma Air-Purifier operation control
• Indoor fan motor operation control
• Louver motor control
• LED display control
• Outdoor fan motor operation control
•
4-WAYS-VALVE operation control
• Compressor operation control
• Receiving the information of the operation
status and judging the information or the
indication of errors
7-1-1. Louver control
(1) Vertical air flow louver
Position of veritcal air flow louver is automatically
controlled according to the operation mode.
Besides, position of vertical air flow louver can be
arbitrarily set by pressing [FIX] button.
The louver position which is set by [FIX] button is
stored in the microcomputer, and the louver is
automatically set at the stored position for the next
operation.
(2) Swing
If [SWING] button is pressed when the indoor unit
is in operation, the vertical air flow louver starts
swinging. When [FIX] button is pressed, it stops
swinging.
7-1-2. Indoor fan control (AC Fan motor)
(1) The indoor fan is operated by the stepless speed
change AC motor.
(2) For air flow level, speed of the indoor fan motor is
controlled in five steps (LOW, LOW
+
, MED, MED
and HIGH). If AUTO mode is selected, the fan
motor speed is automatically controlled by the
difference between the preset temperature and
the room temperature.
LOW
MED
=
MED+HIGH
+
=
2
LOW+MED
+
2
+
OPERATION
MODE
RAS-07NKD Series
RAS-07NKHD Series
RAS-10NKD Series
Model
RAS-10NKHD Series
RAS-13NKD Series
RAS-13NKHD Series
Table 7-1-1
F AN TAP
CoolingUHHMLL-ULSL
Fan onlyHMLLDryMLL-ULSL
Heat UHHMLL-ULSL
PAP only UHHMLL-ULSL
rpm13501300 1200 1050 1000 950 900 800 750 700650
Air flow volume (m3/h)650630 570 490 460 430 400 340 310 280250
rpm1300 1200 1050 1000900800 750 700650
Air flow volume (m3/h)630 570 490 460400340 310 280250
rpm1350 1250 1050 1000 950 900 800 750 700650
Air flow volume (m3/h)650 610 490 460 430 400 340 310 280250
rpm
Air flow volume (m3/h)
rpm
Air flow volume (m3/h)
rpm
Air flow volume (m3/h)
1300 1200 1100 1000900800 750 700650
1250
610
1300
630
1250
630 570 520 460400340 310 280250
610
1350 1300 1150 1100 1050 1000 950 900 850750
650 630 550 520 490 460 430 400 370310
1350 1300 1150 1100 1050 1020 950 900 850750
650 630 550 520 490 470 430 400 370310
800
340
800
340
700
280
700
280
– 26 –
FILE NO. SVM-04022
7-2.Description of Operation Circuit
(1) When turning on the breaker, the operation lamp
blinks. This means that the power is on (or the
power supply is cut off.)
(2) When pressing [
receiving beep sounds from the indoor unit, and
the next operation is performed together with
opening the vertical air flow louver.
(3) Once the operation mode is set, it is memorized in
the microcontroller so that the previous operation
can be effected thereafter simply by pressing [
button.
7-2-1. Fan only operation (NKD Series only)
([MODE] button on the remote control is set
to the fan only operation.)
(1) When [FAN] button is set to AUTO, the indoor fan
motor operates as shown in Fig. 7-2-1. When
[FAN] button is set to LOW, LOW
HIGH, the motor operates with a constant air flow.
°C
+3
+2.5
+2
+1.5
+1
+0.5
(Room temp.) − (Preset temp.)
Preset
temp.
0
NOTE :
*1: The values marked with *1 are calculated and
controlled by the difference in motor speed
between M+ and L–.
Fig. 7-2-1 Setting of air flow [FAN:AUTO]
(2) The Hi POWER operation cannot be set.
] button on the remote control,
+
, MED, MED+ or
M+
*1
*1
*1
L−
(Preset temp.: 22°C)
]
7-2-2. Cooling operation
([MODE] button on the remote control is set
to the cooling operation.)
(1) The compressor, outdoor fan and operation
display on the remote control are controlled as
shown in Fig. 7-2-2.
°C
ON ON
OFF OFF ON
Compressor
Outdoor fan
display
OPERATION
(Room temp.) − (Preset temp.)
Preset
temp.
0.5
0
Fig. 7-2-2
(2) When [FAN] button is set to AUTO, the indoor fan
motor operates as shown in Fig. 7-2-3. When
+
[FAN] button is set to LOW, LOW
, MED, MED+ or
HIGH, the motor operates with a constant air flow.
°C
(Room temp.) − (Preset temp.)
Preset
temp.
+3
+2.5
+2
+1.5
+1
+0.5
0
-0.5
M+
*1
*1
*1
L−
NOTE :
*1: The values marked with *1 are calculated and
controlled by the difference in motor speed
between M+ and L–.
– 27 –
Fig. 7-2-3 Setting of air flow [FAN:AUTO]
FILE NO. SVM-04022
7-2-3. Dry operation
([MODE] button on the remote control is set
to the dry operation.)
(1) The compressor, 4-way valve, outdoor fan and
operation display on the remote control are
controlled as shown in Fig. 7-2-4.
°C
ON:6min.
OFF:4min.
ON:5min.
OFF:5min.
OFF
4-way valve
Outdoor fan
−
(Room temp.) (Preset temp.)
Preset
temp.
+3
+2
+1
ON:6min.
OFF:4min.
OFF
ON:5min.
OFF:5min.
OFF
0
Compressor
Fig. 7-2-4
ON
display
OPERATION
7-2-4. Heating operation (NKHD Series only)
([MODE] button on the remote control is set
to the heating operation.)
(1) The compressor, 4-way valve, outdoor fan and
operation display on the remote control are
controlled as shown in Fig. 7-2-6.
°C
Preset
temp.
0
-0.5
−
(Room temp.) (Preset temp.)
ON
OFF
ON
Compressor
OFF
ON
4-way valve
Outdoor fan
Fig. 7-2-6
ON
display
OPERATION
(2) The microcontroller turns the compressor on and
off at the regular intervals (4 to 6 minutes).While
the compressor is turning off, the indoor fan motor
operates in the SUPER LOW position.
The pattern of operation depending on the relation
between room temperature and preset
temperatures is shown in Fig. 7-2-5.
Room temp.
Preset temp.+1
Preset temp.
Compressor
Outdoor fan
Indoor fan
ONONONON
OFFOFFOFF
L*SL
*
Super Low
L
LSLL
SL
Fig. 7-2-5
(3) [FAN] button on the remote control is set to AUTO
only.
(2) When [FAN] button is set to AUTO, the indoor fan
motor operates as shown in Fig. 7-2-7.When
[FAN] button is set to LOW, LOW
+
, MED, MED+ or
HIGH, the motor operates with a constant air flow.
Preset
temp.
°C
0
-0.5
-1
-1.5
-2
−
-5.0
-5.5
[FAN AUTO]
(Room temp.) (Preset temp.)
L
*1
*2
+
M
H
*1, *2 : The values marked with *1 and *2 are
calculated and controlled by the difference in
motor speed between M+ and L.
Fig. 7-2-7 Setting of air flow [FAN:AUTO]
(4) The Hi POWER operations cannot be set.
− 28 −
FILE NO. SVM-04022
(3) The indoor heat exchanger restricts revolving
speed of the fan motor to prevent a cold draft.
The upper limit of the revolving speed is shown in
in Fig. 7-2-8 and Table 7-2-1.
RAS-13NKHD Series
°C
424134
33
292821
20
*2
A+4
A+4
A
−
8
A− 8
*6*5
Indoor heat exchanger temperature
AUTO
*4
*3
SL
SL*1
Stop
Manual
(One of 5 steps)
−
L H (Up to
seting speed)
RAS-10NKHD Series
RAS-07NKHD Series
464534
33
323121
20
°C
AUTO
*4
Manual
(One of 5 steps)
L
−
H (Up to
seting speed)
7-2-5. Automatic operation
([MODE] button on the remote control is set
to the automatic operation.)
(1) One of 3 operations (Cooling, Fan only or Heating)
is selected according to difference between the
preset temperature and the room temperature at
which the automatic operation has started, as
shown in Fig. 7-2-9.The Fan only operation
continues until the room temperature reaches a
level at which another mode is selected.
(2) Temporary Auto
When the [ RESET ] button on the indoor unit
is pushed, the preset temperature is fixed at 24°C
and the indoor unit is controlled as shown in
Fig. 7-2-9.
°C
Cooling operation
The louver moves to the position same
as Hi POWER operation.
+4
Cooling operation
0
*3
SL
*2
A+4
A+4
A
−
8
A
−
8
*6*5
Indoor heat exchanger temperature
SL*1
Stop
Fig. 7-2-7 Cold draft preventing control
NOTES :
*1: The fan stops for 2 minutes after thermostat-OFF.
*2: A is 24°C when the preset temperature is 24°C or
more and A is the preset temperature when it is
under 24°C.
*3: SL means Super Low.
*4: Calculated from difference in motor speed
between SL and H.
*5 and *6:
Fan*5*6
speedStarting periodStabilized period
AUTOUp until 12 minutes
ManualRoom temperature
(L H)< Preset temperature
−
•
passed after starting
the unit
•
From 12 to 25 minutes
passed after starting
the unit and room
temperature is 3°C
lower than preset
temperature
•
•
Table 7-2-1
−
4°C
•
From 12 to 25 minutes
passed after starting
the unit and room
temperature is
between preset
temperature and 3°C
lower than preset
temperature
25 minutes or more
•
passed after starting
the unit
Room temperature
•
Preset temperature
−
3.5°C
Fan only operation
−
−
1
Heating operation
NKHD-SeriesNKD-Series
(Room temp.) (Preset temp.)
Fig. 7-2-9
7-2-6. Plasma Air-Purifier (PAP) operation.
Plasma Air-Purifier is able to operate together with
other operations mode of air conditioner by pressing
[PAP] button to turn ON/OFF the Plasma Air-Purifier
while other mode is on operation.
Plasma Air-Purifier is able to operate individual by
pressing [PAP] button to turn ON/OFF instead of
pressing [
For pressing the [
conditioner and Plasma Air-Purifier ON/OFF at the
same time. (depends on presetting before turning off.)
When [PAP] button is pressed,
on the display of the remote control and the Plasma
Air-Purifier operates as follows.
] button.
] button is able to turn both air
mark is indicated
−
−
29
FILE NO. SVM-04022
(1) Operation flow chat.
Less than 1 hour
1
Air-Purlfier OFF
Error after 1 minute
5
PAP LED ON
Air-Purifier OFF
6
10 minutes
8
9
!
PAP
START
OPERATION LED ON
PAP LED ON
Indoor fan ON
2
Air-Purlfier ON
Operation confirm
PAP LED ON
Air-Purifier ON
7
FILTER LED ON
Air-Purifier OFF
Reset by
1. [RESET] button
2. [FILTER] button
1 hour later
Error within 1 minute
No error
500 hours
3
FILTER LED ON
Air-Purifier OFF
Checking
Air-Purifier insertion
Inlet-Grlll assembly
Micro switch
Hi voltage unit
Reset by
1. [RESET] button
2. [FILTER] button
3. Turn unit OFF/ON
4-1 & 4-2
4-3
Case
Descriptions
In case of the first operation, after circuit breaker turns OFF/ON or after reset by case No. 4-1, 4-2, 8 and 9.
1&2
The Air-Purifier will operates after 1 hour.
For daily used, without turning OFF circuit breaker, Air-Purifier operates immediately.
By using short timer function of remote control*, Air-Purifier operates immediately.
3
4-1
4-2
4-3
5
6
7
8
9
!
In case of some error occurs within 1 minute, the above items need to be checked.
Case no 3, reset by [RESET] button on the indoor unit. Then Air-Purifier will operate again after 1 hour.
Case no 3, reset by [FILTER] button on the remote control. Then Air-Purifier will operate again after 1 hour.
Case no 3, reset by turning OFF the unit and turning ON again. Then Air-Purifier operates immediately.
In case of some error occurs after 1 minute. Air-Purifier will turn OFF but in contrast, PAP LED will keep turning
ON continuously.
Case no 5, the Air-Purifier will operate again after 10 minute.
After complete 500 hours operation, FILTER LED will turn ON and Air-Purifier will turn OFF. In addition, Air-Purifier
should be cleaned.
Case no 7, reset by [RESET] button on the indoor unit, and Air-Purifier will operate again after 1 hour.
Case no 7, reset by [FILTER] button on the remote control, and Air-Purifier will operate again after 1 hour.
Case no 7, can not reset by turning unit OFF and ON.
*Short timer is the function of the remote control that activates the setting for the sudden operation. This
function can be set as shown below.
1. Press [
] button to turn the unit OFF.
2. Use the tip of the pencil to push the [CHECK] button and hold, “00” will show on display, then press [SET]
button to make “00” disappear.
3. Press [
] button again to turn the unit ON.
4. When short timer is activated, all setting on the remote operates immediately, Besides, all LED turns ON
continuously for 2 seconds.
– 30 –
FILE NO. SVM-04022
(2) The indoor fan motor and Plasma Air-Purifier operation.
• When Plasma Air-Purifier has been operated with other operation of air conditioner mode (Fan only, AUTO,
Cooling, Dry or Heat). The speed revolution of indoor fan is based upon the operated mode of air conditioner.
In fact, Plasma Air-Purifier works continuously.
• When the Plasma Air-Purifier is activated individually and the fan speed is set to LOW, LOW+, MED, MED+, or
HIGH, the speed revolution of the indoor fan will be constant. In fact, Plasma Air-Purifier works continuously.
Moreover, when the Plasma Air-Purifier is activated individually and the fan speed is set to AUTO, the speed
revolution of the indoor fan and the operation of Plasma Air-Purifier is shown as the fig. 7-2-10
Plasma Air-Purifier
Revolution
speed of the
indoor fan.
ON
OFF
M
L
SL
ON 5 min
OFF 10 min
15 min30 min45 min60 min
ON 5 min
OFF 10 min
Operation time
Fig. 7-2-10
– 31 –
FILE NO. SVM-04022
7-3.Hi POWER Mode
([Hi POWER] button on the remote
control is pressed.)
When [Hi POWER] button is pressed while the indoor
unit is in Auto, Cooling or Heating operation, Hi
POWER mark is indicated on the display of the remote
control and the unit operates as follows.
(1) Automatic operation
The indoor unit operates in according to the
•
current operation.
(2) Cooling operation
• The setting temperature drops 3°C.
(The value of the setting temperature on the
remote control does not change.)
• If the room temperature is higher than the
setting temperature by 3.5°C or more, the
horizontal louver moves to the Hi POWER
position automatically. Then when the room
temperature is 1°C less than the setting
temperature the horizontal louver returns
automatically.
• FAN speed : [AUTO]
If the room temperature is higher than the
setting temperature by 3.5°C or more, the air
conditioner operates at maximum airflow level.
If the room temperature is higher than the
setting temperature by less than 3.5°C, the air
conditioner operates at normal airflow level.
• FAN speed : One of 5 levels
If the room temperature is higher than the
setting temperature by 3.5°C or more, the air
conditioner operates at higher consecutive
airflow level. If the room temperature is higher
than the setting temperature by less than 3.5°C,
the air conditioner operates at normal airflow
level.
(3) Heating operation (NKHD Series only)
The preset temperature increases 2°C,
•
(The value of the preset temperature on the
remote control does not change.)
The indoor unit operates in normal heating
•
mode except the preset temperature is higher
(+2°C).
(4) The Hi POWER mode can not be set in Dry or Fan
only operation.
ı
7-4.High-Temperature Limit Control
(NKHD Series only)
The microcontroller detects the indoor heat exchanger
temperature to prevent pressure of a refrigerating cycle
from increasing excessively.
The compressor and outdoor fan motor are controlled
as shown in Fig. 7-4-1.
Compressor
OFF
ON
ON
Outdoor fan
OFF
OFF
ON
Heat exchanger
temp.
(°C)
60
53
52
Fig. 7-4-1
7-5.Low-Temperature Limit Control
The microcontroller detects the indoor heat exchanger
temperature to prevent the indoor heat exchanger from
freezing.
The compressor and outdoor fan motor are controlled
as shown in Fig. 7-5-1 and 7-5-2.
RAS-13NKHD Series
RAS-13NKD Series
Heat exchanger
temperature
(°C)
6
2
Fig. 7-5-1
RAS-10NKHD Series, RAS-07NKHD Series
RAS-10NKD Series, RAS-07NKD Series
Heat exchanger
temperature
(°C)
7
5
Compressor Outdoor fan
ON
Less than 2°C continues
for 5 minutes
OFF
Compressor
Less than 5°C continues
Outdoor fan
ON
for 5 minutes
OFF
Fig. 7-5-2
32
−
−
FILE NO. SVM-04022
7-6. Defrost Operation (NKHD Series only)
During the heating operation, the outdoor heat
exchanger temperature goes down and sometimes it is
frozen.
In this case, the air conditioner stops the heating
operation and starts the defrost operation to melt ice.
7-6-1. Condition to start the defrost operation
The defrost operation starts whichever below
conditions are satisfied.
(1) When the cumulative compressor operating time is
longer than 40 or 90 minutes and difference
between the indoor heat exchanger temperature
and the room temperature is less than the
specified value. (This value is decided by the
microprocessor.) (Control example is shown in
Fig. 7-6-1. In case of B or C, the defrost operation
starts.)
(2) When the current limit control or the high
temperature limit control is performed for total of
90 minutes.
<In case of C>
(1) The heating operation is performed for at least 90
minutes.
(2) The defrost operating time is 10 minutes.
7-6-3. Ending condition at defrost operation
(1) When the compressor current becomes 7.5A or
more during defrost operation, the defrost
operation stops and the heating operation restarts.
(The current sensor detects the compressor
current.)
(2) The defrost operation continues for at most
6 minutes or 10 minutes.
D
A
Indoor heat exchanger temp
- Room temp
Fig. 7-6-1 (Indoor fan speed : M)
7-6-2. Defrost operation time control
<In case of B>
(1) The heating operation is performed for at least
40 minutes.
(2) The maximum defrost operating time is 6 minutes.
The defrost operating time for the 4th cycle is
10 minutes. (When the outdoor temperature is
very low, however, the defrost operating time is
10 minutes.)
minutes
minutes
40
B
C
minutes
40
minutes
40
40
Cumulative
compressor
operating time
Heating
Defrost
Heating
Max 6 minutes
Defrost
Heating
1 cycle
Fig. 7-6-2
Defrost
Heating
10 minutes
Defrost
− 33 −
7-7. Current Limit Control (NKHD Series only)
The microcontroller detects the input current so as to
prevent it exceeds a specified value by means of
controlling the outdoor fan control as described in (1)
and (2).
(1) Current limit control (Cooling operation)
Control is performed as shown below by detecting
the compressor operating current with a current
sensor (C.T).
RAS-13NKHD Series / RAS-10NKHD Series, RAS-07NKHD Series
FILE NO. SVM-04022
Input current
13.5A/ 19.2A I4
12.5A/ 17.8A I3
Fig. 7-7-1
(2) Current limit control (Heating operation)
Control is performed as shown in Fig. 7-7-2
RAS-13NKHD Series / RAS-10NKHD Series, RAS-07NKHD Series
Input current
13.5A/ 19.2A I4
12.5A/ 17.8A I3
CompressorOutdoor fan
More than I4 continues for 3 seconds
OFF
More than I3 continues for 5 seconds
OFF
ON
CompressorOutdoor fan
More than I4 continues for 3 seconds
OFF
More than I3 continues for 5 seconds
OFF
10A/ 15.6A I2
9A/ 15.0A I1
ONOFF
ON
Fig. 7-7-2
Remark :
This function is available only for heat pump model (Cooling models have no a current sensor (C.T.)).
− 34 −
FILE NO. SVM-04022
7-8.Auto Restart Function
The indoor unit is equipped with an automatic
restarting function which allows the unit to restart
operating with the set operating conditions in the event
of power supply being accidentally shut down. The
operation will resume without warning three minutes
after power is restored.
This function is not set to work when shipped from the
factory. Therefore it is necessary to set it to work.
7-8-1. How to set auto restart function
To set the auto restart function, proceed as follows:
The power supply to the unit must be on; the function
will not set if the power is off.
Push the [RESET] button located in the center of the
front panel continuously for three seconds.
The unit receives the signal and beeps three times.
The unit then restarts operating automatically in the
event of power supply being accidentally shut down.
When the unit is on standby (Not operating)
OperationMotions
Push [RESET] button for moreThe unit is on standby.
than three seconds.
The unit starts to operate.The green lamp is on.
0
RESETHi POWER FILTER PAP TIMER
3S
The unit beeps three timesThe lamp changes from
and continues to operate.green to orange.
→
→
If the unit is not required to operate at this time, push [
once more or use the remote control to turn it off.
After approx. three seconds,
RESET
] button
When the unit is in operation
OperationMotions
Push [RESET] button for moreThe unit is in operation.The green lamp is on.
than three seconds.
RESETHi POWER FILTER PAP TIMER
The unit stops operating.The green lamp is turned off.
0
3S
The unit beeps three times.
If the unit is required to operate at this time, push [
→
→
After approx. three seconds,
RESET
once more or use the remote control to turn it on.
•While this function is being set, if the unit is in
operation, the orange lamp is on.
•While the filter check lamp is on, the [RESET]
button has the function of filter reset button.
•This function can not be set if the timer operation
has been selected.
•When the unit is turned on by this function, the
louver will not swing even though it was swinging
automatically before shutting down.
] button
– 35 –
7-8-2. How to cancel auto restart function
To cancel auto restart function, proceed as follows:
Repeat the setting prodedure: the unit receives the
signal and beeps three times.
The unit will be required to be turned on with the
remote control after the main power supply is turned
off.
When the unit is on standby (Not operating)
OperationMotions
Push [RESET] button for moreThe unit is on standby.
→
than three seconds.
The unit starts to operate.The orange lamp is on.
→
FILE NO. SVM-04022
After approx. three seconds,
The unit beeps three timesThe lamp changes from
and continues to operate.orange to green.
If the unit is not required to operate at this time, push [
RESET
RESETHi POWER FILTER PAP TIMER
0
3S
once more or use the remote control to turn it off.
When the unit is in operation
OperationMotions
Push [RESET] button for moreThe unit is in operation.The orange lamp is on.
→
than three seconds.
The unit stops operating.The orange lamp is turned off.
→
After approx. three seconds,
0
RESETHi POWER FILTER PAP TIMER
3S
•While this function is being set, if the unit is in
operation, the orange lamp is on.
7-8-3. Power failure during timer operation
When the unit is in Timer operation, if it is turned off
because of power failure, the timer operation is
cancelled. Therefore, set the timer operation again.
The unit beeps three times.
If the unit is required to operate at this time,
push [
once more or use the remote control to turn it on.
7-9.Filter Check Lamp
When the operation time of Plasma Air-Purifier
reaches 500 hours, the filter check lamp indicates.
After cleaning the Plasma Air-Purifier, turn off the filter
check lamp.
7-9-1. How to turn off filter check lamp
RESET
] button
] button
Press [FILTER] button on the remote control.
OR push [RESET] button on the indoor unit.
Note :
If [RESET] button is pushed while the filter check lamp
is not indicating, the indoor unit will start the Automatic
Operation.
– 36 –
FILE NO. SVM-04022
7-10.Self-Cleaning function
Self-Cleaning function is designed to reduce humidity that causes mold to form inside the air conditioning unit.
This advanced, efficient system reduces moisture in the coil. When air conditioner is turned off, the internal fan
activates and dries the moisture in the coil for 20 minutes, then it turns off automatically.
Operation displayONOFFOFF
FCU fan
FCU louverOPENCLOSECLOSE
Timer display
Compressor
CDU fanON or OFF
rpm is depend on presetting.rpm is SUPER LOW speed.
depend on presetting of timer function.depend on presetting of timer function.
depend on presetting per room temperature.
depend on presetting per room temperature.
Cool mode or dry mode
operation more than 10 mins.
ONON
ON or OFF
ON or OFF
8
Self-Cleaning mode
Turn off by remote controller or
timer-off function.
ON
OFFOFF
OFFOFF
8
operate 20 mins.
Automatically turn-off.
• The Self-Cleaning function is set as default at ex-factory.
• Self-Cleaning operation can stop manually by press [
7-10-1. How to cancel Self-Cleaning function
To cancel the Self-Cleaning function, proceed as
follows:
•
Press [RESET] button one time or use remote
control to turn on air conditioner. The OPERATION
display will show in orange color (When AUTORESTART is ON) or green color (When AUTORESTART is OFF).
•
Hold down the [RESET] button for more than
20 seconds. (The air conditioner will stop suddenly
when the [RESET] is pressed but keep holding it
continue. The will beep 3 times in the first
3 seconds but it is not related to Self-Cleaning
function)
•
After holding about 20 seconds, the air conditioner
will beep 5 times without any blinking of display.
•
The Self-Cleaning Operation had been cancelled.
] button of the remote control one more time.
7-10-2. How to set Self-Cleaning function.
To set the Self-Cleaning function, proceed as follows.
•
Press [RESET] button one time or use remote
control to turn on air conditioner. The OPERATION
display will show in orange color (When AUTORESET is ON) or green color (When AUTORESTART is OFF).
•
Hold down the [RESET] button for more than
20 seconds. (The air conditioner will stop suddenly
when the [RESET] is pressed but keep holding it
continue. Then will beep 3 times is the first 3
seconds but it is not related to Self-Cleaning
function)
•
After holding about 20 seconds, the air conditioner
will beep 5 times and OPERATION display blinks
5 times.
•
The Self-Cleaning function had been set.
OFF
ON or OFF
-
Operation time
Remarks
•
Per setting of Self-Cleaning function above, AUTORESTART function had been cancelled. To set
AUTO-RESTART again, please follow item 7-8-1.
Remarks
•
Per setting of Self-Cleaning function above, AUTORESTART function had been cancelled. To set
AUTO-RESTART again, please follow item 7-8-1.
RESETHi POWER FILTER PAPTIMER
– 37 –
FILE NO. SVM-04022
8. INSTALLATION PROCEDURE
8-1.Safety Cautions
For general public use
Power supply cord of parts of appliance for Indoor use shall be at least polychloroprene sheathed flexible
cord (design H07 RN-F), or cord designation 245 IEC66.
CAUTION
This appliance must be connected to the main power supply by means of a circuit breaker or a switch with a
contact separation of at least 3 mm.
If this is not possible, a power supply plug with earth must be used. This plug must be easily accessible after
installation. The plug must be disconnected from the power supply socket in order to disconnect the
appliance completely from the mains.
To Disconnect the Appliance from the Main Power Supply
DANGER
• FOR USE BY QUALIFIED PERSONS ONLY.
• TURN OFF MAIN POWER SUPPLY BEFORE ATTEMPTING ANY ELECTRICAL WORK. MAKE SURE
ALL POWER SWITCHES ARE OFF. FAILURE TO DO SO MAY CAUSE ELECTRIC SHOCK.
• CONNECT THE CONNECTING CABLE CORRECTLY. IF THE CONNECTING CABLE IS CONNECTED
WRONGLY, ELECTRIC PARTS MAY BE DAMAGED.
• CHECK THE EARTH WIRE THAT IT IS NOT BROKEN OR DISCONNECTED BEFORE INSTALLATION.
• DO NOT INSTALL NEAR CONCENTRATIONS OF COMBUSTIBLE GAS OR GAS VAPORS.
FAILURE TO FOLLOW THIS INSTRUCTION CAN RESULT IN FIRE OR EXPLOSION.
• TO PREVENT OVERHEATING THE INDOOR UNIT AND CAUSING A FIRE HAZARD, PLACE THE UNIT
WELL AWAY (MORE THAN 2 M) FROM HEAT SOURCES SUCH AS RADIATORS, HEATORS,
FURNACE, STOVES, ETC.
• WHEN MOVING THE AIR-CONDITIONER FOR INSTALLING IT IN ANOTHER PLACE AGAIN, BE VERY
CAREFUL NOT TO GET THE SPECIFIED REFRIGERANT WITH ANY OTHER GASEOUS BODY INTO
THE REFRIGERATION CYCLE. IF AIR OR ANY OTHER GAS IS MIXED IN THE REFRIGERANT, THE
GAS PRESSURE IN THE REFRIGERATION CYCLE BECOMES ABNORMALLY HIGH AND IT
RESULTINGLY CAUSES BURST OF THE PIPE AND INJURIES ON PERSONS.
• IN THE EVENT THAT THE REFRIGERANT GAS LEAKS OUT OF THE PIPE DURING THE
INSTALLATION WORK, IMMEDIATELY LET FRESH AIR INTO THE ROOM. IF THE REFRIGERANT GAS
IS HEATED BY FIRE OR SOMETHING ELSE, IT CAUSES GENERATION OF POISONOUS GAS.
WARNING
• Never modify this unit by removing any of the safety guards or bypassing any of the safety interlock
switches.
• Do not install in a place which cannot bear the weight of the unit.
Personal injury and property damage can result if the unit falls.
• Before doing the electrical work, attach an approved plug to the power supply cord.
Also, make sure the equipment is properly earthed.
• Appliance shall be installed in accordance with national wiring regulations.
If you detect any damage, do not install the unit. Contact your TOSHIBA dealer immediately.
CAUTION
• Exposure of unit to water or other moisture before installation could result in electric shock.
Do not store it in a wet basement or expose to rain or water.
• After unpacking the unit, examine it carefully for possible damage.
• Do not install in a place that can increase the vibration of the unit. Do not install in a place that can amplify
the noise level of the unit or where noise and discharged air might disturb neighbors.
• To avoid personal injury, be careful when handling parts with sharp edges.
• Please read this installation manual carefully before installing the unit. It contains further important instruc-
tions for proper installation.
– 38 –
FILE NO. SVM-04022
REQUIREMENT OF REPORT TO THE LOCAL POWER SUPPLIER
Please make absolutely sure that the installation of this appliance is reported to the local power supplier
before installation. If you experience any problems, or if the installation is not accepted by the supplier, the
service agency will take adequate countermeasures.
– 39 –
8-2.Installation Diagram of Indoor and Outdoor Units
170 m
m
or m
ore
Hook
65 mm or more
1 Installation
plate
FILE NO. SVM-04022
For the rear left and left
piping
Wall
4 Zeolite-plus
filter
Before installing the
wireless remote control
• With the remote control cover
open, load the batteries supplied
correctly, observing their
polarity.
2 Wireless remote control
Cover
A
ir
f
ilt
(A
tta
c
h
to
th
e
fr
o
n
t p
a
6 Plasma air purifier
2 Wireless remote control
Ho
ok
170 mm or more
Insert the cushion between
the indoor unit and wall,
er
and tilt the indoor unit for
better operation.
Shield
n
e
l.)
pipe
Do not allow the drain hose
to get slack.
Cut the piping hole
sloped slightly
Make sure to run the drain
hose sloped downward.
The auxiliary piping can be
connected the left, rear left,
rear right, right, bottom right
or bottom left.
3 Batteries
13 series07, 10 series
A600 mm400 mm
B100 mm45 mm
1
00 m
Right
Vinyl tape
Apply after
carrying out a
or more
B mm
600 mm or more
m
o
r m
ore
re
o
m
r
o
m
m
A
drainage test.
Extension
drain hose
(Option:
RB–821SW)
60
0
m
m
o
r m
ore
Saddle
Rear right
Rear left
Bottom right
Bottom left
Insulate the refrigerant
pipes separately with
insulation, not together.
6 mm thick heat resisting
polyethylene foam
Left
– 40 –
8-3.Installation
8-3-1. Optional installation parts
FILE NO. SVM-04022
Part
Parts name
Code
Refrigerant piping
Liquid side : ∅6.35 mm
A
Gas side: ∅9.52 mm (07, 10 series)
Gas side: ∅12.70 mm (13 series)
Pipe insulating material
B
(polyethylene foam, 6 mm thick)
Putty, PVC tapes
C
<Fixing bolt arrangement of outdoor unit>
125 mm115 mm
310 mm
7 mm
32.5 mm
73 mm
Air outlet
30
∅
600 mm
Air inlet
102 mm
90 mm
Drain outlet
Q’ty
One
each
1
One
each
275 mm
60 mm
Air outlet
500 mm
97 mm
Air inlet
Drain outlet
RAS-10, 13 Series
Fig. 8-3-1
RAS-07 Series
• Secure the outdoor unit with fixing bolts and nuts if the unit is likely to be exposed to a strong wind.
• Use ∅8 mm or ∅10 mm anchor bolts and nuts.
– 41 –
8-3-2. Accessory and installation parts
FILE NO. SVM-04022
Part
No.
Part name (Q’ty)
1
Installation plate x 1
2
Wireless remote control x 1
Others
Name
Part
No.
3
Battery x 2
4
Zeolite-plus filter x 1
Part name (Q’ty)
Part
No.
Part name (Q’ty)
5
Mounting screw ∅4 x 25 s x 6
6
Plasma air purifier x 1
Owner’s manual
Installation manual
This model is not equipped with an extension drain hose.
Option :
For the extension drain hose, use an optionally available RB-821SW or commercially available one.
– 42 –
FILE NO. SVM-04022
∅
8-4.Indoor Unit
8-4-1. Installation place
• A place which provides the spaces around the
indoor unit as shown in the above diagram.
• A place where there is no obstacle near the air inlet
and outlet.
• A place that allows easy installation of the piping to
the outdoor unit.
• A place which allows the front panel to be opened.
CAUTION
• Direct sunlight to the indoor unit’s wireless
receiver should be avoided.
• The microprocessor in the indoor unit should not
be too close to RF noise sources.
(For details, see the owner’s manual.)
<Remote control>
• A place where there are no obstacles such as a
curtain that may block the signal from the indoor
unit.
• Do not install the remote control in a place exposed
to direct sunlight or close to a heating source, such
as a stove.
• Keep the remote control at least 1 m apart from the
nearest TV set or stereo equipment. (This is
necessary to prevent image disturbances or noise
interference.)
• The location of the remote control should be
determined as shown below.
Remote
control
(Top view)
Indoor unit
Reception
range
* : Axial distance
Fig. 8-4-1
45
°
5 m
°
Remote control
m
5
45
Indoor unit
(Side view)
7 m
°
75
Reception
range
8-4-2. Cutting a hole and mounting installation
plate
<Cutting a hole>
When installing the refrigerant pipes from the rear.
Pipe
hole
65 mm
The center of the pipe
hole is above the arrow.
100 mm
Fig. 8-4-2
1. After determining the pipe hole position on the
mounting plate (A), drill the pipe hole (∅65 mm) at
a slight downward slant to the outdoor side.
NOTE
• When drilling a wall that contains a metal lath, wire
lath or metal plate, be sure to use a pipe hole brim
ring sold separately.
<Mounting the installation plate>
For installation of the indoor unit, use the paper pattern
on the back.
62
Installation
plate
* 7 m
170
85
Pipe hole
Indoor unit
Hook
Thread
Hook
Weight
Hook
Pipe hole
5 Mounting screw
82.5
1
– 43 –
Fig. 8-4-3
FILE NO. SVM-04022
<When the installation plate is directly mounted on
the wall>
1. Securely fit the installation plate onto the wall by
screwing it in the upper and lower parts to hook up
the indoor unit.
2. To mount the installation plate on a concrete wall
with anchor bolts, utilize the anchor bolt holes as
illustrated in the above figure.
3. Install the installation plate horizontally in the wall.
CAUTION
When installing the installation plate with a
mounting screw, do not use the anchor bolt hole.
Otherwise the unit may fall down and result in
personal injury and property damage.
Installation plate
<Keep horizontal direction>
Anchor
bolt
Projection
55
5
Mounting
55
screw
∅
4 x 25
15 mm or less
ss
s
ss
5 mm dia. hole
Clip anchor
(local parts)
Fig. 8-4-4
8-4-3. Electrical work
1. The supply voltage must be the same as the rated
voltage of the air conditioner.
2. Prepare the power source for exclusive use with the
air conditioner.
CAUTION
• This appliance can be connected to the mains in
either of the following two ways.
(1) Connection to fixed wiring:
A switch or circuit breaker which disconnects
all poles and has a contact separation of at
least 3 mm must be incorporate in the fixed
wiring. An approved circuit breaker or
switches must used.
(2) Connection with power supply plug:
Attach power supply plug with power cord
and plug it into wall outlet. An approved
power supply cord and plug must be used.
NOTE
• Ensure all wiring is used within its electrical rating.
RAS-10NKHD-E
Model
Power source 50Hz, 220 − 240 V Single phase
Maximum
running current
Plug socket &
fuse rating
RAS-10NKD-E
RAS-07NKD-E
7.5A12A
RAS-13NKHD-E
RAS-13NKD-E
16A
CAUTION
Failure to firmly install the unit may result in
personal injury and property damage if the unit falls.
• In case of block, brick, concrete or similar type
walls, make 5 mm dia. holes in the wall.
• Insert clip anchors for appropriate mounting screws
5.
NOTE
• Secure four corners and lower parts of the
installation plate with 4 to 6 mounting screws to
install it.
Power cord1 mm
2
or more
1.3 mm
2
or more
– 44 –
FILE NO. SVM-04022
8-4-4. Wiring connection
<How to connect the power cord>
For the air conditioner that does not have power
cord, connect a power cord to it as mentioned
below.
(1) Open the air inlet grille upward.
(2) Remove the four screws securing the front panel.
(3) Slightly open the lower part of the front panel then
pull the upper part of the front panel toward you to
remove it from the rear plate.
(4) After removing the front panel, remove the power
cord connect cover and the cord camp.
(5) Connect and secure the power supply cord and
secure the cord camp and the power connect
cover.
(6) Put the power supply cord through the notch.
(7) Be sure to smooth the notch with a file, etc.
Air Inlet grille
Front panel
<Stripping length of the power cord>
40 mm
10 mm
N
L
10 mm
30 mm
Fig. 8-4-6
NOTE
• Use stranded wire only.
• Wire type : More than 1.5 mm
245 IEC66) or 1.3 mm
2
2
(H07RN-F or
(AWG-16)
<Taking out the power cord>
Earth line
Notch
2
1
3
Fig. 8-4-7
Put the power supply cord through the notch.
Fig. 8-4-5
– 45 –
FILE NO. SVM-04022
1 2
3
4
1
2
<How to connect the connecting cable>
Wiring of the connecting cable can be carried out
without removing the front panel.
1. Remove the air inlet grille.
Open the air inlet grille upward and pull it toward
you.
2. Remove the terminal cover and cord clamp.
3. Insert the connecting cable (according to the local
cords) into the pipe hole on the wall.
4. Take out the connecting cable through the cable
slot on the rear panel so that it protrudes about
15 cm from the front.
5. Insert the connecting cable fully into the terminal
block and secure it tightly with screws.
6. Tightening torque : 1.2 N·m (0.12 kgf·m)
7. Secure the connecting cable with the cord clamp.
8. Fix the terminal cover, rear plate bushing and air
inlet grille on the indoor unit.
CAUTION
• Be sure to refer to the wiring system diagram
labeled inside the front panel.
• Check local electrical cords and also any specific
wiring instructions or limitations.
For RAS-07,10,13NKD-E
Terminal
cover
Connecting
cable
about 15 cm
Screw
10 mm
Stripping length of the connecting cable
Cord clamp
Screw
Screw
Fig. 8-4-10
60 mm
10 mm
50 mm
1
2
Connecting cable
Earth line
Terminal block
Earth line
For RAS-07,10,13NKHD-E
Cord clamp
Screw
10 mm
10 mm
Connecting
cable
about 15 cm
Terminal
cover
Screw
Stripping length of the connecting cable
1
2
3
Screw
Fig. 8-4-8
80 mm
70 mm
10 mm
50 mm
4
Connecting cable
Earth line
Terminal block
Earth line
Fig. 8-4-11
NOTE
ı • Use stranded wire only.
• Wire type : H07RN-F or 245 IEC66 (More than
2.0 mm
2
)
<How to install the air inlet grille on the indoor unit>
• When attaching the air inlet grille, the contrary of
the removed operation is performed.
Fig. 8-4-12
Fig. 8-4-9
– 46 –
FILE NO. SVM-04022
8-4-5. Piping and drain hose installation
<Piping and drain hose forming>
*Since dewing results in a machine trouble, make
sure to insulate both the connecting pipes. (Use
polyethylene foam as insulating material.)
Rear right
Rear left
Bottom left
Changing
Left
Bottom right
Right
Die-cutting
Front panel slit
drain hose
Piping preparation
1. Die-cutting Front panel slit
For leftward connection, cut out slit on the left side of
the front panel. (A knife will produce splinters, so use
nippers.)
2. Changing drain hose
For leftward connection, bottom leftward connection
and rear leftward connection’s piping, it is necessary to
change the drain hose and drain cap.
How to remove the drains cap
Clip drain cap by needle-nose plier, and pull out.
How to fix the drains cap
1) Insert hexagonal wrench (4 mm) in a center
head.
4 mm
Fig. 8-4-15
2) Firmly insert drains cap.
No gap
Do not apply lubricating oil
(refrigerant machine oil) when
inserting the drain cap.
Application causes deterioration
Insert a hexagon
wrench (4 mm)
and drain leakage of the plug.
Fig. 8-4-16
CAUTION
Firmly insert the drain hose and drain cap; otherwise,
water may leak.
<In case of right or left piping>
• After scribing slits of the front panel with a knife or a
making-off pin, cut them with a pair of nippers or an
equivalent tool.
Fig. 8-4-13
How to install the drain hose
Firmly insert drain hose connecting part until hitting on
a heat insulator.
Heat insulator
Drain hose
Fig. 8-4-14
Slit
Fig. 8-4-17
<In case of bottom right or bottom left piping>
• After scribing slits of the front panel with a knife or a
making-off pin, cut them with a pair of nippers or an
equivalent tool.
Slit
Fig. 8-4-18
– 47 –
FILE NO. SVM-04022
<Left-hand connection with piping>
Bend the connecting pipe so that it is laid within 43 mm
above the wall surface. If the connecting pipe is laid
exceeding 43 mm above the wall surface, the indoor
unit may unstably be set on the wall. When bending the
connecting pipe, make sure to use a spring bender so
as not to crush the pipe.
Bend the connection pipe within a radius of 30 mm.
To connect the pipe after installation of the unit (figure)
(To the forefront of flare)
270 mm
170 mm
R 30 mm (Use polisin (polyethylene)
43 mm
core or the like for bending pipe.)
0
8
Liquid side
Gas side
Outward form of indoor unit
Use the handle of screwdriver, etc.
Fig. 8-4-19
8-4-6. Indoor unit fixing
1. Pass the pipe through the hole in the wall, and hook
the indoor unit on the installation plate at the upper
hooks.
2. Swing the indoor unit to right and left to confirm that
it is firmly hooked up on the installation plate.
3. While pressing the indoor unit onto the wall, hook it
at the lower part on the installation plate. Pull the
indoor unit toward you to confirm that it is firmly
hooked up on the installation plate.
1
2
Hook
Hook here
1 Installation
plate
Press
(unhook)
Fig. 8-4-20
• For detaching the indoor unit from the installation
plate, pull the indoor unit toward you while pushing
its bottom up at the specified parts.
NOTE
If the pipe is bent incorrectly, the indoor unit may
unstably be set on the wall.
After passing the connecting pipe through the pipe
hole, connect the connecting pipe to the auxiliary pipes
and wrap the facing tape around them.
CAUTION
• Bind the auxiliary pipes (two) and connecting
cable with facing tape tightly. In case of leftward
piping and rear-leftward piping, bind the auxiliary
pipes (two) only with facing tape.
Indoor unit
Auxiliary pipes
Installation plate
• Carefully arrange pipes so that any pipe does not
stick out of the rear plate of the indoor unit.
• Carefully connect the auxiliary pipes and
connecting pipes to each other and cut off the
insulating tape wound on the connecting pipe to
avoid double-taping at the joint, moreover, seal
the joint with the vinyl tape, etc.
• Since dewing results in a machine trouble, make
sure to insulate both the connecting pipes. (Use
polyethylene foam as insulating material.)
• When bending a pipe, carefully do it, not to crush it.
Connecting cable
PushPush
Fig. 8-4-21
– 48 –
FILE NO. SVM-04022
8-4-7. Drainage
1. Run the drain hose sloped downwards.
NOTE
• Hole should be made at a slight downward slant on
the outdoor side.
Do not form the
Do not rise the
drain hose.
50 mm
or more
Do not put
the drain
hose end
into water.
drain hose into
a wavy shape.
Do not put
the drain
hose end in
the drainage
ditch.
Fig. 8-4-22
2. Put water in the drain pan and make sure that the
water is drained out of doors.
3. When connecting extension drain hose, insulate the
connecting part of extension drain hose with shield
pipe.
Shield pipe
Drain hose
Inside the room
Extension drain hose
Fig. 8-4-23
CAUTION
Arrange the drain pipe for proper drainage from the
unit.
Improper drainage can result in dew-dropping.
This air conditioner has the structure designed to drain
water collected from dew, which forms on the back of
the indoor unit, to the drain pan.
Therefore, do not store the power cord and other parts
at a height above the drain guide.
8-5.Outdoor Unit
8-5-1. Installation place
• A place which provides the spaces around the
outdoor unit as shown in the left diagram.
• A place which can bear the weight of the outdoor
unit and does not allow an increase in noise level
and vibration.
• A place where the operation noise and discharged
air do not disturb your neighbors.
• A place which is not exposed to a strong wind.
• A place free of a leakage of combustible gases.
• A place which does not block a passage.
• When the outdoor unit is to be installed in an
elevated position, be sure to secure its feet.
• An allowable length of the connecting pipe is up to
10 m (07, 10 series) or 15 m (13 series).
• An allowable height level is up to 5 m (07, 10 series)
or 6 m (13 series).
• A place where the drain water does not raise any
problem.
CAUTION
1. Install the outdoor unit without anything blocking
the air discharging.
2. When the outdoor unit is installed in a place
exposed always exposed to strong wind like a
coast or on a high storey of a building, secure
the normal fan operation using a duct or a wind
shield.
3. In particularly windy areas, install the unit such
as to avoid admission of wind.
4. Installation in the following places may result in
trouble.
Do not install the unit in such places.
• A place full of machine oil.
• A saline-place such as the coast.
• A place full of sulfide gas.
• A place where high-frequency waves are likely
to be generated as from audio equipment,
welders, and medical equipment.
Space for pipes
Fig. 8-4-2
Wall
4
Drain guide
– 49 –
Strong
wind
Fig. 8-5-1
FILE NO. SVM-04022
8-5-2. Refrigerant piping connection
1. Cut the pipe with a pipe cutter.
90°
Obliquity
Roughness
Fig. 8-5-2
2. Insert a flare nut into the pipe, and flare the pipe.
• Projection margin in flaring : A (Unit : mm)
A
Die
Pipe
Fig. 8-5-3
Outer dia.
of copper pipe
RigidImperial
A
6.350.5 to 1.01.0 to 1.5
9.520.5 to 1.01.0 to 1.5
Warp
Outer dia.
of copper pipe
Tightening torque
∅6.3516 to 18 (1.6 to 1.8 kgf·m)
∅9.5230 to 42 (3.0 to 4.2 kgf·m)
∅12.7050 to 62 (5.0 to 6.2 kgf·m)
Flare at indoor unit side
Flare at outdoor unit side
Fig. 8-5-4
Mark line
(Unit : N·m)
12.700.5 to 1.01.5 to 2.0
<Tightening connection>
Align the centers of the connecting pipes and tighten
the flare nut as far as possible with your fingers. Then
tighten the nut with a spanner and torque wrench as
shown in the figure.
CAUTION
• Do not apply excess torque.
• Otherwise, the nut may crack depending on the
conditions.
Fig. 8-5-5
Flare nutHalf union
Externally
threaded side
Use a wrench to secure.
Use a torque wrench to tighten.
Internally
threaded side
Fig. 8-5-6
CAUTION
• KEEP IMPORTANT 4 POINTS FOR PIPING
WORK
(1) Take away dust and moisture (Inside of the
connecting pipes.)
(2) Tight connection (between pipes and unit)
(3) Evacuate the air in the connecting pipes using
VACUUM PUMP.
(4) Check gas leak (connected points)
– 50 –
FILE NO. SVM-04022
8-5-3. Evacuating
After the piping has been connected to the indoor unit,
you can perform the air purge together at once.
AIR PURGE
Evacuate the air in the connecting pipes and in the
indoor unit using a vacuum pump. Do not use the
refrigerant in the outdoor unit.
For details, see the manual of the vacuum pump.
<Using a vacuum pump>
Be sure to use a vacuum pump with counter-flow
prevention function so that inside oil of the pump does
not flow backward into pipes of the air conditioner
when the pump stops.
1. Connect the charge hose from the manifold valve to
the service port of the gas side packed valve.
2. Connect the charge hose to the port of the vacuum
pump.
3. Open fully the low pressure side handle of the
gauge manifold valve.
4. Operate the vacuum pump to start evacuating.
Perform evacuating for about 15 minutes if the piping
length is 20 meters. (15 minutes for 20 meters)
(assuming a pump capacity of 27 liters per minute.)
Then confirm that the compound pressure gauge
reading is –101 kPa (–76 cmHg).
5. Close the low pressure side valve handle of gauge
manifold.
6. Open fully the valve stem of the packed valves
(both sides of Gas and Liquid).
7. Remove the charging hose from the service port.
8. Securely tighten the caps on the packed valves.
<Packed valve handling precautions>
• Open the valve stem all the way out; but do not try
to open it beyond the stopper.
• Securely tighten the valve stem cap with torque in
the following table:
Gas side50 to 62 N·m
(∅12.70 mm)(5.0 to 6.2 kgf·m)
Gas side30 to 42 N·m
(∅9.52 mm)(3.0 to 4.2 kgf·m)
Liquid side16 to 18 N·m
(∅6.35 mm)(1.6 to 1.8 kgf·m)
Service port
9 to 10 N·m
(0.9 to 1.0 kgf·m)
Hexagonal wrench
is required.
m
4 m
Fig. 8-5-8
Compound pressure gauge
-101 kPa (-76 cmHg)
Handle Lo
Charge hose
Connecting pipe
Service port
(Valve core (Setting pin))
Packed valve at liquid side
Pressure gauge
Manifold valve
Charge hose
Vacuum pump
adapter for
counter-flow
prevention
Vacuum
pump
Packed valve at gas side
Fig. 8-5-7
Handle Hi
(Keep full closed)
– 51 –
FILE NO. SVM-04022
Selector Switch
LED Assembly
8-5-4. Wiring connection
1. Remove the valve cover from the outdoor unit.
2. Connect the connecting cable to the terminal as
identified with their respective matched numbers on
the terminal block of indoor and outdoor unit.
3. When connecting the connecting cable to the
outdoor unit terminal, make a loop as shown in the
installation diagram of indoor and outdoor unit, to
prevent water coming in the outdoor unit.
4. Insulate the unused cords (conductors) from any
water coming in the outdoor unit.Proceed them so
that they do not touch any electrical or metal parts.
<Stripping length of connecting cable>
For RAS-13/10/07UAH-E3
Terminal block
70 mm
10 mm
10 mm
Earth line
60 mm
Terminal
screw
Connecting
cable
Screw
Cord clamp
Earth
line
8-6. How to Set Remote Control Selector
Switch
When two indoor units ae installed in seperated rooms,
there is no need to change the selector switch.
<Remote control selector switch>
•
When two indoor units are installed in the same
room or the adjacent two rooms, they may be
controlled simultaneously with a single remote
control.To prevent this, set either unit and its
remote control to B setting. (Both units are set to A
setting before shipment.)
The remote control signal is not recived when the
•
indoor unit setting is different from the remote
control one.
1. Set the remote control selector switch with the
indoor unit.
1) Turn the circuit breaker of the main power switch off
before setting the selector switch.
2) Remove the Air inlet grille and Front panel.
3) Select the terminal of selector switch from
[A position] to [B position].
Fig. 8-5-9
For RAS-13/10/07UA-E3
Terminal block
10 mm
60 mm
Earth line
10 mm
50 mm
Terminal
screw
Connecting
cable
Screw
Fig. 8-5-10
CAUTION
• Wrong wiring connection may cause some
electrical parts burn out.
• Be sure to comply with local codes on running
the wire from indoor unit to outdoor unit (size of
wire and wiring method etc.)
2. Set the remote control selector switch with the
remote control
[B] is indicated on the liquid crystal display when
setting remote control selector switch to B. [A] is
not indicated on the display even if the selector
switch is set to A.
1) Load the remote control with the batteries.
2) Press the [CHECK] button using something with
sharp point. (The preset temperature on the remote
control changes to [00].)
3) Press the [MODE] button while pressing the
[CHECK] button, [B] is indicted at the right of the
present temperature display.
• To reset the switch to the [A] setting, press the
[MODE] button again while pressing the [CHECK]
button.
A
B
8-7.Others
8-7-1. Gas leak test
Valve cover
Valve stem cap
connection
Service cap
connection
Fig. 8-7-1
• Check the flare nut connections, valve stem cap
connections and service port cap connections for
gas leak with a leak detector or soap water.
8-7-2. Test operation
To switch the TEST RUN (COOL) mode, press RESET
button for 10 sec.
(The beeper will make a short beep.)
TEMP
ECO
FAN
OFF
AUTO
PRESET
MEMO
1.3.5.9H
SLEEP
SET
FILTER
[MODE] button
PAP
MODE
HiPOWER
SWING
CLR
CLOCK
RESET
FIX
ON
CHECK
[CHECK] button
Fig. 8-6-2
3. Confirm that the indoor unit can operate with
the new setting.
RESETHi POWER FILTERPAPTIMER
RESET button
Fig. 8-7-2
8-7-3. Auto restart setting
This product is designed so that, after a power failure,
it can restart automatically in the same operating mode
as before the power failure.
Information
The product was shipped with Auto Restart function
in the off position. Turn it on as required.
<How to set the auto restart>
• Press and hold the RESET button for about
3 seconds. After 3 seconds, the electronic beeper
makes three short beeps to tell you the Auto
Restart has been selected.
• To cancel the Auto Restart, follow the steps
described in the section Auto Restart Function of
the Owner’s Manual.
– 53 –
9. TROUBLESHOOTING CHART
FILE NO. SVM-04022
9-1.Troubleshooting Procedure
9-2-2. Incorrect cable connection between Indoor
and outdoor units
Follow the details of 9-2. Basic Chec k Items .
If there is no trouble corresponding to 9-2, check
whether or not there are faulty parts following
9-4. Self-Diagnosis by Remote Control.
The indoor unit is connected to the outdoor unit with
3 cables (Cooling Only model) or 5 cables (Heat Pump
model). Check that the indoor and outdoor units have
been properly connected with terminals assigned the
same numbers. If theconnectors are not properly
9-2.Basic Check Items
9-2-1. Power supply voltage
The line voltage must be A
within this range, the air conditioner may not operate
normally.
C 220 − 240 V. If it is not
connected, the outdoor unit will not operate normally,
or OPERATION lamp and TIMER lamp will blink (5Hz).
9-2-3. Program control
The microcontroller operates as shown in Table 9-2-1
to control the air conditioner. If there are any
operational problems, check whether or not the
problems correspond to Table 9-2-1. If they correspond
to the Table, they are not problems with the air conditioner, but they are indispensable operations to control
and maintain the air conditioner properly.
Table 9-2-1
No.Operation of air conditionerDescriptions
1When the main power supply is turned on,
the OPERATION lamp on the indoor unit
blinks.
2The indoor fan motor speed does not change
in the Dry operation.
3The compressor is not turned off even though
the room temperature is in the range that the
compressor is turned off.
4The compressor is not turned on and off even
though the thermo control is operated in the
Dry operation.
5The compressor is not turned on even though
the room temperature is in the range that the
compressor is turned on.
6The operation mode changes in the
Automatic operation.
7The Fan only operation continues in the
Automatic operation.
8The Hi-POWER operation does not work.
The OPERATION lamp blinks to indicate that power is turned on.
If the [
The indoor fan motor speed is automatically controlled in the Dry
operation.
The compressor has a function that it is not turned off for
3 minutes after it is turned on even though the room temperature
is in the range that the compressor is turned off.
In the Dry operation, the compressor is turned on and off
automatically at the regular intervals, independent of the thermo
control.
The compressor is not turned on in the restart delay timer
(3-minutes timer) operation. It is also not turned on after the power
supply is turned on because of this timer operation.
In Automatic operation, the room temperature is detected all time
for control fan speed and the operation mode is changed every
15 minutes according to difference between the room temperature
and the preset temperature.
When the room temperature is in the range (Preset temperature
± 1ıC), the Fan only operation is selected.
This operation does not work when the unit is in the Dry operation
or Fan only operation.
] button is pressed, the lamp stops blinking.
– 54 –
FILE NO. SVM-04022
9-3.Primary Judgement
9-3-1. Role of indoor unit controller
The indoor unit controller receives the operation
commands from the remote control and executes
them.
• Temperature measurement at the air outlet of the
indoor heat exchanger by the indoor temperature
sensor
• Temperature setting of the indoor heat exchanger by
the heat exchanger sensor
• Louver motor control
• Indoor fan motor operation control
• LED display control
• Transferring of operation commands to the outdoor
unit
Table 9-3-1
LampsSelf-diagnosis
AOPERATION lamp is blinking. (1Hz)
BOPERATION lamp is blinking. (5Hz)
COPERATION lamp is blinking. (5Hz)
DOPERATION lamp is blinking. (5Hz)
EOPERATION lamp is blinking. (5Hz)
FOPERATION and TIMER lamps are blinking.
(5Hz)
9-3-2. Failure diagnosis
The indoor unit diagnoses the operation condition and
indicates the information of the self-diagnosis with the
lamps on the display panel of the indoor unit.
Power failure (when the power supply is turning on)
Thermo sensor (TA) short or break
Heat exchanger sensor (TC) short or break
Indoor fan motor lock or failure
Indoor P.C. board f ailure
Wrong wiring of connecting cable
GOPERATION, TIMER and PAP lamps are
blinking.
Table 9-3-2 Diagnosis by detective operation
SymptomCheckPrimary judgement
The remote control
does not work.
The outdoor fan
does not rotate.
Turn off the power supply once,
then turn it on. Try to operate
the remote control.
The compressor operates.
The compressor does not operate.
Cycle failure
• Gas shortage or other refrigerant cycle trouble
• Heat exchanger sensor open, break or short
• Overload relay or thermostat trouble of compressor
The remote control
still does not work.
The remote control
works.
The indoor unit (and/or remote
control) is/are defective .
OK.
The outdoor unit (Outdoor fan
motor) is defective .
An internal part of the
compressor or P.C. board is
defective.
– 55 –
9-4.Self-Diagnosis by Remote Control
F
(Check Code)
(1) If the lamps are indicated as shown B to G in Table
9-3-1, exchanger the self-diagnosis by the remote
control.
(2) When the remote control is set to the service
mode, the indoor controller diagnoses the
operation condition and indicate the information of
the self-diagnosis on the display of the remote
control with the check codes. If a fault is detected,
all lamps on the indoor unit will blink at 5Hz and it
will beep for 10 seconds (Pi, Pi, Pi....). The timer
lamp usually blinks (5Hz) during the self-diagnosis.
9-4-1. How to use remote control in service mode
CLR
ON
CLOCK
RESET
CHECK
FILE NO. SVM-04022
(1) Press [CHECK] button with a tip of pencil to set the
remote control to the service mode.
O
• “00” is indicated on the display of the remote
control.
• The timer lamp on the indoor unit blinks
continuously. (5 times per 1 sec.)
PAP
MODE
HiPOWER
SWING
CLR
CLOCK
RESET
FIX
ON
CHECK
TEMP
ECO
FAN
OFF
AUTO
PRESET
MEMO
1.3.5.9H
SLEEP
SET
FILTER
(2) Press [ON 8] or [OFF 9] button.
If there is no fault with a code, the indoor unit will
beep once (Pi) and the display of the remote
control will change as follows:
00011d1E0233
• Check the unit with all 52 check codes (00 to 33).
as shown in Table 9-4-1.
• Press [ON 8] or [OFF 9] button to change the
check code backwards.
If there is a fault, the indoor unit will beep for 10
seconds (Pi, Pi, Pi...).
Note the check code on the display of the remote
control.
• 2-digits alphanumeric will be indicated on the
display.
• All lamps on the indoor unit will blink.
(5 times per 1 sec.)
(3) Press [CLR] button. After service finish for clear
service code in memory.
• “7F” is indicated on the display of the remote
control.
• Alphanumeric characters are used for the check code.
is 5.is 6.
is A.is B.
is C.is D.
– 56 –
(4) Press [
] button to release the service mode.
• The display of the remote control returns to as it
was before service mode was engaged.
(5) Time shotening method.
1. Press [SET] button while pressing [CHECK]
button.
2. Press [
] button.
Block level Diagnosis function
CheckCheck
code
Block
Indoor
P.C. board
code
SymptomConditionerCondition
Thermo. sensor
short/break.
Table 9-4-1
Continued
operation.
Air
status
Indicated
when detected
abnormal
FILE NO. SVM-04022
Judgement and action
1.Check thermo sensor.
2.If it is OK, check
P.C. board.
Cable
connection/
Thermal
fuse
Refrigerant
system
Heat exchanger
sensor
short/break.
Indoor fan lock,
abnormality of
indoor fan or
thermal fuse break.
Abnormality of other
indoor unit P.C.
board.
1) Wrong wiring or
disconnection of
connective cable.
2) Terminal fuse cut
off.
Continued
operation.
All off
All off
All off
Indicated
when detected
abnormal
Indicated
when detected
abnormal
Indicated
when detected
abnormal
Indicated
when detected
abnormal
1.Check heat exchanger
sensor.
2.If it is OK, check
P.C. board.
1.Check heat thermal
fuse is blow or not?
(Terminal block part.)
2.If the thermal fuse is
not blow, check indoor
fan m otor.
(Refer to trouble
shooting flow charts.)
Replace P.C. board.
1.Check connective
cable correct if wiring is
wrong.
2.Check thermal fuse
and T erminal blocks.
3.If it is OK, check
P.C. board.
Other parts
(including
compressor)
1) Overload relay or
thermostat for
compressor
All off
Indicated
when detected
abnormal
1.If overload relay and
break.
2.If refrigerant cycle is
3. If heat exchanger
Content detected by the check codes “
” to “
” are stored in memory of the microcomputer even if the
power supply is turned off. Theref ore, contents of operations in the past are all displayed.
– 57 –
thermostat for
compressor are OK,
check refrigerant cycle.
OK, check P.C. board.
sensor is OK, check
overload relay and
thermostat for
compressor.
9-5.Troubleshooting Flowcharts
9-5-1. Power can not be turned on (No operation at all)
<Preliminary checks>
(1) Is the supply voltage normal?
(2) Is the connection to the AC output OK.?
Shut off the power supply
from AC outlet once and
turn it on after 5 seconds.
NO
Does the OPERATION
lamp blink?
YES
FILE NO. SVM-04022
Operation
Check Items
Main cause
Countermeasure
Symptom
Does the fuse
Does the thermal
(Under PF. Terminal)
Is the indication voltage
NO
(DC12 V or 5 V) of main
P.C. board correct?
Is the voltage
across C03 measured
DC 310 ~ 340 V?
YES
(F01) blow?
NO
fuse blow?
NO
YES
NO
Does the power turn on
by pushing the
button of the
remote control?
YESYES
YES
YES
Refer to the paragraph
Pre-check , or defective circuit
before power P.C. board block.
Parts (R21, R22, SG01,
C01, C02, DB01, C03,
IC01, T01) are defective.
Wrong wiring of
AC cord or connecting
cable is defective.
Does the CN13
connector the wrong
connecting?
NONO
(No problem)
Does the transmission
indicator of remote
control flash normally
and transmit certainly?
NO
YES
P.C. board is
defective.
Remote control is
defective.
Replace the remote
control.
Replace the
thermal fuse set.
Check connection.
Replace the main
P.C. board.
Re-wiring the cable.
Is the secondary
voltage of
transformer (T01)
measured DC12V
and DC7V?
YES
* Be sure to disconnect the motor connector CN10 after shut off the power supply, or it will be a cause of damage of the motor.
NO
Shut off the power
supply once, and turn
it on again after
disconnecting the
motor connector CN10*.
Check Resistance
of Pin 1 and 5 of
Fan motor = 162 Ω
YES
NO
Replace Fan motor
and P.C. board.
Replace P.C. board.
– 58 –
9-5-2. Power cannot be turned on after replacing indoor P.C. board
<Checking Procedure>
Connect the AC
power supply
FILE NO. SVM-04022
Does the OPERATION
lamp blink?
YESYES
RAS-13NKHD-E
Blue
CN31
Brown
RY01
Is it wired as shown
in Figure below?
NONO
Black
Return the wiring of the
power relay is returned to
the normal procedure.
To the paragraph of
No Power turns on .
White
Power Cord
PC-Board
Indoor
terminal
block
4
3
21
−59 −
RAS-07NKHD-E, RAS-10NKHD-E
FILE NO. SVM-04022
Blue
CN31
PC-Board
Brown
RY01
Black
Bind Band
Double winding
2
1
Indoor
terminal
block
White
3
Power Cord
8
RAS-07NKD-E, RAS-10NKD-E, RAS-13NKD-E
BlueBrown
CN31
PC-Board
RY01
BlackWhite
PowerCord
21
Indoor
terminal
block
− 60 −
9-5-3. Outdoor unit does not operate
Shut off the power supply
from AC outlet once and turn
it on after 5 seconds.
FILE NO. SVM-04022
Does the OPERATION lamp blink?
YES
Does the power turn on by
pushing the [ ] button
of the remote control?
YES
Is AC 220 V
supplied between
terminal block
Is cable connection
between indoor and outdoor
units correct?
Check items as following procedure
in 9-5-4, 9-5-5
1−2
YES
YES
?
NO
NO
NO
NO
See Power cannot be turned on .
See Power cannot be turned on .
Relays (RY01)
or IC31 or IC30 is failure.
Correct cabling between
indoor and outdoor units.
Replace the
P.C. board.
– 61 –
9-5-4. Only compressor does not operate
Shut off the power supply
from AC outlet once and turn
it on after 5 seconds.
FILE NO. SVM-04022
Does the OPERATION lamp blink?
YES
Does the power turn on by
pushing the [ ] button
of the remote control?
YES
Is the voltage across the indoor terminal
the indoor terminal
(1 − 2) AC 220-240 V?
YES
Is cable connection between indoor
and outdoor units correct?
YES
Is the voltage across the indoor terminal
the out door terminal
(1 − 2) AC 220-240 V?
YES
Are all the cords for compressor normal?
YES
Is the compressor motor winding normal?
(Check the winding resistor.)
YES
Is the capacitor for compressor normal?
YES
Is the overload relay normal?
YES
Does the compressor start?
YES
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
See Power cannot be turned on .
See Power cannot be turned on .
Relays (RY01)
or IC31 or IC30 is failure.
Correct cabling between indoor
and outdoor units.
Cables between indoor and
outdoor units are defective.
Re-wire or replace the defective cords.
Compressor is defective.
Capacitor is defective.
Overload relay is defective.
Compressor is defective.
Replace the
P.C. board.
Compressor starts but
it stops after a while?
YES
Is the gas quantity normal?
(Check the pressure)
YES
Compressor is defective
NO
Gas shortage (Gas leakage)
– 62 –
9-5-5. Only outdoor fan does not operate
Shut off the power supply
from AC outlet once and turn
it on after 5 seconds.
FILE NO. SVM-04022
Does the OPERATION lamp blink?
YES
Does the power turn on by
pushing the [ ] button
of the remote control?
YES
Is the voltage across the indoor terminal
(
) : Heat pump model, 1 - 2 :
4
2 -
Cooling only model) AC 220-240 V?
YES
Is cable connection between indoor
and outdoor units correct?
YES
Is the voltage across the terminal
) : Heat pump model, 1 - 2 :
(
4
2 -
Cooling only model) AC 220-240 V?
YES
Are all the cords for outdoor
fan motor normal?
YES
Is the outdoor fan motor winding normal?
(Check the winding resistance)
YES
NO
NO
NO
NO
NO
NO
NO
See Power cannot be turned on .
See Power cannot be turned on .
Relays (RY01)
or IC31 or IC30 is failure.
Correct cabling between indoor
and outdoor units.
Cables between indoor and
outdoor units are defective.
Correct the wire or
replace the defective cords.
Outdoor fan motor is defective.
Replace the
P.C. board.
Is the capacitor for Fan motor normal?
YES
Outdoor fan motor is defective.
NO
Capacitor for outdoor
fan motor is defective.
– 63 –
9-5-6. Only 4-Way valve does not operate (During heating operation)
Heat Pump Model
Shut off the power supply
from AC outlet once and
turn it on after 5 seconds.
FILE NO. SVM-04022
Does the OPERATION lamp blink?
YES
Does the power turn on by
pushing the [START/STOP] button
of the remote control?
YES
Is the voltage across the indoor terminal
Is the voltage across the outdoor terminal
(
2 - 3 ) 220-240V?
YES
Is cable connection between indoor
and outdoor units correct?
YES
( 2 - 3 ) 220-240V?
YES
Is the wiring of solenoid coil for
4-way valve normal?
YES
NO
NO
NO
NO
NO
NO
See "Power can not be turned on".
See "Power can not be turned on".
Relays (RY04) or IC31
or IC30 is failure.
Correct cabling between indoor
and outdoor units.
Cables between indoor
and outddor units are defective.
Solenoid coil is defective.
Replace the P.C.
board.
4-way valve is defective.
− 64 −
9-5-7. Only the indoor fan does not operate
<Check procedure>
Shut off the
power supply once.
Turn the power supply.
FILE NO. SVM-04022
Does the fan stop in
no operating status?
YES
Start the operation
with low fan setting
in cool operation.
Does the fan rotate?
YES
Change the setting of
cooling to high fan.
Does the fan speed
become higher?
YES
NO
NO
NO
Control P.C. board is defective .
Does AC 120V
or higher voltage apply
to between red and black
lead of fan motor?
YES
Shut off the power supply.
Does the cross flow
fan rotate normally?
YES
Turn on the power supply.
Operation
stops
NO
NO
Does connecting
terminal, connecting
cable or power supply
cord completely?
Does not found the short
wire about connecting
cable and power cord?
YES
Repair the
bearing of
the fan.
Motor control circuit failure
(IC30, IC03, T01) or 12V power
circuit failure (D38, Q33).
Replace the P.C. board.
Replace the P.C. board.
NO
Thermal fuse operated
due to prevent
temperature rising cause
of incompleted connecting.
Normal
Is the rotation signal (DC+5V-0V)
output between 2 (gray lead wire)
3 (brown lead wire) of the motor
and
connector (CN11) when rotating
the cross flow fan by hand in no
operating status?
(1 pulse/one turn)
YES
Replace the control
P.C. board.
− 65−
NO
Replace the fan motor
Replace connecting
the cable (or power cord),
thermal fuse and
terminal block.
FILE NO. SVM-04022
9-6. Troubleshooting for Remote Control (Including the Indoor P.C. Board)
There is no beep from
the indoor unit.
Press the [ ] button.
The OPERATION lamp of
the air conditioner main
unit does not light.
Is there direct
sunlight on the
receptor of the
air conditioner?
YES
NO
Is there any
thyristor
fluorescent light
near by?
YES
NO
Does the transmission
YES
NONO
Is operation
possible when setting the
RESET button of the
air conditioner main unit to
TEST RUN or
TEMPORARY AUT O ?
YES
indicator blink?
Is operation
possible when the
transmitter is moved
nearer to the infrared
signal receiver of the
air conditioner?
YES
Battery life
NO
Reset the remote control
by use the tip pencil push
in the RESET hole
Press the
[ ] button
Does the
transmission
indicator light?
NO
Is there any
beep and
operation?
NO
YES
Avoid direct
sunlight.
Keep the air
conditioner away
from thyristor
fluorescent light.
Can any signal tone
be heard in a transistor
radio when transmitting
within 5 cm distance
from the radio?
YES
P.C. board is failure.
Replace
P.C. board.
Note : After battery replacement,
short circuit the metal terminal at
the side of the battery compartment
(all-clear terminal) with a pencil.
– 66 –
NO
Replace the
batteries.
Normal
YES
Remote control
is failure.
Replace remote
control.
FILE NO. SVM-04022
9-6-1. How to check the P.C. board
(1) Operating precautions
1) When removing the front panel or the P.C. board,
be sure to shut off the power supply.
2) When removing the P.C. board, hold the edge of
the P.C. board and do not apply force to the
parts.
3) When connecting or disconnecting the
connectors on the P.C. board, hold the Whole
housing.
Do not pull at the lead wire.
(2) Inspection procedures
1) When a P.C. board is judged to be defective,
check for disconnection, burning, or discoloration of the copper foil pattern or this P.C. board.
2) The P.C. board consists of the following 2 parts
a. Main P.C. board part:
Power relay, indoor fan motor drive circuit and
control circuit, C.P.U. and peripheral circuits,
buzzer drive circuit and buzzer.
b. Infrared rays receive and indication parts:
Infrared rays receiver unit and LED.
– 67 –
(3) Checking procedure
FILE NO. SVM-04022
Table 9-6-1
No.
1
Shut off the power supply and
remove the P.C. board assembly
from the electronic parts base.
Remove the connecting cable from
the terminal block.
2
Remove the connector for the motor,
and turn the power on.
If the OPERATION lamp blinks
(0.5 sec. : ON, 0.5 sec. : OFF) when
the power turning on, the checking
points described as 1-4 of right
column are not necessary to
perform.
3
Make the operation status by
pressing once the [
the status of [FAN ONLY], [ON
TIMER].
4
Start the operation with the system
which the time of the restart delay
timer is shortened.
Procedure
] button, except
Check Point (Symptom)Causes
1.Is the fuse blown?
Voltage check
1.Between 3 of RY01 and CN31
(AC 220 ~ 240 V)
2.Between + and – of C03
(DC 310 ~ 340 V)
3.Between
4.Between 12V and GND
Voltage check
1.Voltage of relay coil. (DC 12 V)
Between pin 10 of IC31 and
Between pin 11 of IC31 and GND
1.All indicators light for 3 sec..
2.Indicators do not indicate normally
after approximate 3 sec..
5V and GND
GND
1. Application of shock voltage.
Overload by short-circuit of the
parts.
1. AC power cord is defective.
Poor contact of the terminal plate.
Miss wiring of the power relay.
2. Capacitor (C01, C02) is defective .
Line filter (L01) is defective.
Resistor (R01) is defective.
Diode (DB01) is defective.
3.IC01, T01, F03 are defective.
4.IC01, T01 are defective.
1.Breaking wire of the relay coil,
defective relay driver. (IC31)
Defective indicator, or poor
}
housing assembly. (CN13)
5
Make the operation status by
pressing once the [
1.The time of the restart delay timer
is shortened.
2.Cool operation
3.Air volume [AUTO]
4.Make the setting temperature lower
enough than room temperature.
5.Continuous operation.
The status of No. 5 is continued, and
6
make the following condition.
1.Heat operation
2.Make the setting temperature
higher enough than room
temperature.
7
Turn the power on after connecting
the motor connector. Start the
operation with the following
condition.
1.Operation [Cooling]
2.Airflow [High fan]
3.Continuous operation
] button.
1.Compressor does not operate.
2.OPERATION lamp blinks.
1.Compressor does not operate.
2.OPERATION lamp blinks.
1.Motor does not rotate. (The key
operation is accepted.)
2.The Motor rotates, but it vibrates
too much.
1.The temperature of the indoor
heat exchanger is abnormally
lower.
2.Poor contact of the heat
exchanger sensor. (The connector
is disconnected.) (CN01)
3.Heat exchanger sensor, main
P.C. board are defective. (Refer to
Table 9-6-2 for the judgment of
defective resistance values.)
4.Main P.C. board is defective.
1.The temperature of the heat
exchanger is abnormally high.
2.The heat exchanger sensor
connector has short-circuit. (CN01)
3.The heat exchanger sensor is
defective. (Refer to Table 9-6-2
for the judgment of defective
resistance values.)
4.P.C. board is defective.
1.Poor contact of the motor
connector.
2.P.C. board is defective.
– 68 –
FILE NO. SVM-04022
17
Table 9-6-2. Approximate resistance value of thermo sensor
Temperature0°C10°C20°C25°C30°C
Resistance value33.820.3512.5910.007.99
9-6-2. How to shorten time of restart delay timer
1 Press [SET] button while pressing [CHECK] button
with a tip of a pencil.
2 Then press [
indoor unit.
] button to transmit the signal to the
(kΩ)
TEMP
ECO
FAN
OFF
AUTO
PRESET
MEMO
1.3.5.9H
SLEEP
SET
FILTER
2
1
17
PAP
MODE
HiPOWER
SWING
CLR
CLOCK
RESET
FIX
ON
CHECK
9-6-3. How to set/cancel self cleaning function
The self cleaning function is set from a factory. To cancel this function, should keep press the RESET switch on
Indoor unit for 20 seconds till can hear the long combination sound and repeat the same procedure when need
to set.
– 69 –
9-7.Troubleshooting for Air Purifier and Minus Ion
9-7-1. How to Check Whether the Air Purifier is Good or Not
Turn off the power breaker once,
and turn on again after 10 seconds.
FILE NO. SVM-04022
Does the OPERATION lamp blink?
YES
Turn off the power breaker and
remove CN34 (Micro switch connector).
Short-circuit between 1 and 2 pin
of CN34 at PC side, and turn on the
power breaker after 10 seconds.
Is DC12V applied
1
between
(Brown/GND) of CN1 of the
micro-switch connector under
OFF status of the micro-switch
micro-switch connector under
ON status of the micro-switch
1) Check operation while short-circuiting CN34 of the main P.C. board.
2) Perform air purifying operation by the remote control.
• In this time, check that the remote control is in status which is shortened by time on
• While the air purifier operates, check that the fan speed [AUTO] is not displayed.
3) Be sure not to touch the dust collector, ionizer, or ionized wire unit with the human body.
(Red/DC12V) and
high-voltage unit?
YES
Is there conduction of
(Front panel opened)?
NO
Is there conduction of
(Front panel closed)?
YES
the reactivation preventive timer and all display lamps go on for approx. 3 seconds
when a signal is received.
If time on the reactivation preventive timer is not shortened,
( )
the high-voltage is not applied to electrode of the air purifier for approx. 1 hour.
(Because the power ON/OFF is controlled on the program)
NO
NO
YES
NO
Is DC12V applied
between
1
(+) and 2 (−)
of CN33 of the main
P.C. board (MCC-5007)?
YES
Micro-switch is stuck
Micro-switch malfunction
NO
To item Power supply is not turned on
Replace the main P.C. board (MCC-5007)
Replace micro-switch.
• Conduction check of micro-switch
Push the switch
ON
ON
Releaes the switch
OFF
Tester
Does the indoor fan rotate?
Does the plasma lamp (Blue) or
the filter lamp (Orange) go on?
go off within 2 seconds after
filter lamp (Orange) go on?
Operation checkPrimary check
Refer to items, cleaning and check
for the dust collector/ionizer/ionized
wire units.
( )
YES
YES
Does the plasma lamp
it was ON, and does the
YES
Are the dust collector
and ionizer dried?
(Electrode check)
YES
When the ionized wire is
disconnected or when dirt is
not cleaned even cleaned,
replace each unit.
NO
NO
NO
Dry the dust
collector and
ionizer.
YES
Is DC-5V to DC-10V
applied between
4 (Brown/Negative voltage)
and 2 (Brown/GND)
of CN33 of the main
P.C. board?
YES
Referring to the right figure, check the
high-output voltage of the air filter unit.
(NOTE)
Use an exclusive high voltage tester;
otherwise the tester may be broken.
YES
Is output of the ionizer
approx. 3.9kV to 4.7kV?
Is output of the collector
approx. 2.9kV to 3.7kV?
YES
Are the dust
collector/ionizer/ionized
wire units dirty?
Is an abnormal sound
(cracking noise) heard
from the electrode?
To item Only indoor fan does not operate
Replace the main P.C. board (MCC-5007).
• How to check output of the air purifier
NO
GND
Be sure not to come to
contact to the silver part
or not to touch the
[ ]
ionized cables.
NO
NO
<Caution on High Voltage!!>
Ionizer
Output
Replace the high-voltage unit.
No trouble
Collector
output
High-voltage tester
– 70 –
9-7-2. How to Check Whether the Minus Ion Generator is Good or Not
Turn off the power breaker once,
and turn on again after 10 seconds.
FILE NO. SVM-04022
Does the OPERATION lamp blink?
YES
Turn off the power breaker and remove
CN34 (Micro switch connector).
Short-circuit between 1 and 2 pin of
CN34 at PC side, and turn on the
power breaker after 10 seconds.
Is DC12V applied
between 1 (Red/DC12V) and
2 (Brown/GND) of CN1 of the
high-voltage unit in the air purifier?
YES
Is there conduction of
micro-switch connector under
OFF status of the micro-switch
(Front panel opened)?
NO
Is there conduction of
micro-switch connector under
ON status of the micro-switch
(Front panel closed)?
YES
1) Check operation while short-circuiting CN34 of the main P.C. board.
2) Perform air purifying operation by the remote control.
• In this time, check that the remote control is in status which is shortened by time on
the reactivation preventive timer and all display lamps go on for approx. 3 seconds
when a signal is received.
If time on the reactivation preventive timer is not shortened,
( )
the high-voltage is not applied to electrode of the air purifier for approx. 1 hour.
• While the air purifier operates, check that the fan speed [AUTO] is not displayed.
(Because the power ON/OFF is controlled on the program)
3) Be sure not to touch the electrode with the human body.
NO
NO
YES
NO
Micro-switch is stuck
Micro-switch malfunction
To item Power supply is not turned on
Replace the power P.C. board
(MCC-5007) or the housing assembly.
Replace micro-switch.
• Conduction check of micro-switch
Push the switch
ON
Tester
ON
Releaes the switch
OFF
Does the indoor fan rotate?
YES
Does the plasma lamp (Blue) or
the filter lamp (Orange) go on?
YES
Does the plasma lamp
go off within 2 seconds after
it was ON, and does the
filter lamp (Orange) go on?
NO
Referring to the right figure, check the
Operation checkPrimary check
high-voltage output of the air ionizer.
In this time, peel the thermal insulator, and attach
it to the original position after check operation.
NOTE :
Use an exclusive high voltage tester; otherwise
the tester may be broken.
NO
Does the electrode
output approx. −6kV?
NO
Integrated
power supply assembly
NO
NO
YES
YES
No trouble
To item Only indoor fan does not operate
Replace the main P.C. board (MCC-5007).
To item How to check whether
the air purifier is good or not
•
How to check output of minusion
<Caution on High Voltage!!>
High-voltage
unit
GND
High-voltage tester
Electrode
– 71 –
FILE NO. SVM-04022
10. PART REPLACEMENT
10-1. Indoor Unit
No.Part nameProceduresRemarks
1Front panel
How to remove the front panel
1) Stop the operation of the air conditioner and
turn off its main power supply.
2) Pull the air inlet grille toward you to open it
and remove the air inlet grille.
3) Take off the right side of air filter.
4) Pull out the plasma air purifier.
5) Remove the 4 screws fixing the front panel
before open the horizontal louver and then
remove the front panel from back body by
pulling it toward you.
How to mount the front panel
Reverse step to remove the front panel.
Push the front panel back in and make sure all
hooks are locked.
2 Air inlet grille
2
4 4 Screws
Air filter right
3
4 Plusma
air purifier (3)
4
– 72 –
5
5 Front panel
FILE NO. SVM-04022
No.Part nameProceduresRemarks
2Electrical part
How to remove the electrical part
1) Remove the front panel with procedure 1.
2) Remove the screw holding the electrical part
cover.
3) Disconnect the 2 connectors (3P) for the fan
motor, the connector (5P) for the louver
motor from the P.C. board assembly and the
connector (4P) for eletrical supply.
4) Pull out the TC sensor from the sensor
holder.
5) Remove the screw for the ground connection,
remove the screw for the electrical part box
and LED unit. Then remove the LED unit and
the electrical part box from the main unit.
How to mount the electrical part
1) To put back the electrical part box, lock it to
the upper hook of the back body.
2) Tighten the screw on the electrical part box.
3) Connect the 3 connectors and arrange the
wiring same as original condition and then
tighten the screw from the LED unit to the
back body.
4) Attach the TC sensor to the holder.
5) Tighten the screw for the ground connection.
6)
Tighten the screw on the electrical part cover.
5 Screw
3 Connector
4 TC Sensor
5 Screw
2 Screw
3
2 Connectors
3Horizontal
louver
1) Remove the front panel following procedure
1.
2) Remove the center shaft of the horizontal
louver from the back body.
3) Remove the left shaft from the back body.
4) Remove the horizontal louver from the back
body.
3 Left shaft
2 Center shaft
– 73 –
FILE NO. SVM-04022
No.Part nameProceduresRemarks
4Heat exchanger
5Cross flow fan
1) Remove the front panel, electrical part
following procedure 2.
2) Remove the pipe holder at the rear side of
main unit.
3) Remove the 2 screws on the heat exchanger
at the base bearing.
4) Remove the 2 screws on the heat exchanger
at the 2 fixed plates (upper and lower) from
the back body, and then pull out the upper
side of the heat exchanger slowly.
1) Remove the front panel, electrical part and
the heat exchanger following procedure 4.
2) Remove the 2 screws on the band motor (L)
and remove the 2 screws on the band motor
(R) and then remove the cross flow fan.
3) Loosen the set screw of the cross flow fan
then separate the fan and the fan motor.
Notice
To assemble cross flow fan and fan motor to the
unit, please turn the fan motor unit the center of
its terminal meets the lowest point of band motor
(R) (point A).
Fix the cross flow fan with the set screw at the
position where the gap between the back body
and the right surface of the cross flow fan is
6 ± 0.5 mm.
2 Pipe holder
3
2 Screws
4
2 Screws
2
2 Screws
(R)
2 2 Screws (L)
6 Set screw
Middle of the fan motor terminal
6Base bearing
1) Remove the front panel, electrical part, heat
exchanger and the cross flow fan following
procedure 5.
2) Remove the 2 screws fixing the base
bearing.
3) Remove the bearing from the base bearing. If
the housing protrudes from the base bearing,
put the housing in position and attach the
bearing to the base bearing.
– 74 –
2
2 Screws
FILE NO. SVM-04022
10-2. Outdoor Unit
No.Part nameProceduresRemarks
1Common
procedure
1) Stop the operation of air-conditioner, and
disconnect the power cord from the AC
supply.
2) Remove packed valve cover and Electric
parts cover.
(3 Screws ∅4 x 10L)
3) Remove the cord clamp (2 Screws ∅4 x 22L)
and disconnect the connecting cable.
4) Remove the upper cabinet (4 Screws ∅4 x 10L)
Pulling out upword.
5) Remove the front cabinet.
(3 Screws ∅4 x 10L)
Pull the front right portion toward you, and
remove it pulling out upward.
Cord clamp
2 Screws ∅4 x 22L
Electric
parts cover
3 Screws ∅4 x 10L
Packed valve cover
Upper
cabinet
– 75 –
Front
cabinet
FILE NO. SVM-04022
No.Part nameProceduresRemarks
2Capacitor for
compressor
3Capacitor for
fan motor
1) Perform the common procedure 1.
2) Remove the fixing screw and the capacitor
band.
(1 Screw ∅4 x 8L for 10UA, 13UA)
(1 Screw ∅4 x 10L for 07UA)
21443T11302 Pipe Shield (For 13 Series)
21543T19302 Holder Sensor
21643T49302 Plate of Eva Seal
21743T49006 Holder For Plate
21843T22002 Asm-M-Bearing
21943T39301 Base, Bearing
22043T20302 Cross Flow Fan
22143T39302 Band Motor-L
22243T21338 Motor, Fan
22343T39303 Band Motor-R
224 43T69402 Wireless Remocon