2-2 Outdoor Unit (RAS-10GAH-E, RAS-10GA-E, RAS-10GAX, RAS-10GAX-V)
2-3 Outdoor Unit (RAS-07GAH-E, RAS-07GA-E, RAS-07GAX)
3.WIRING DIAGRAM
3-1 RAS-10GKHP-E / RAS-10GAH-E
RAS-07GKHP-E / RAS-07GAH-E
3-2 RAS-10GKP-E / RAS-10GA-E
RAS-07GKP-E / RAS-07GA-E
RAS-10GKPX / RAS-10GAX
3-3
RAS-07GKPX / RAS-07GAX
RAS-10GKPX-V / RAS-10GAX-V
4.SPECIFICATION OF ELECTRICAL PARTS
4-1 Indoor Unit (RAS-10GKHP-E, RAS-07GKHP-E)
4-2 Outdoor Unit (RAS-10GAH-E)
4-3 Outdoor Unit (RAS-07GAH-E)
4-4 Indoor Unit (RAS-10GKP-E, RAS-07GKP-E, RAS-10GKPX
RAS-07GKPX, RAS-10GKPX-V)
4-5 Outdoor Unit (RAS-10GA-E, RAS-10GAX, RAS-10GAX-V)
4-6 Outdoor Unit (RAS-07GA-E, RAS-07GAX)
7-1Outline of Air Conditioner Control
7-2Description of Operation Circuit
7-3Hi POWER Mode
7-4High-Temperature Limit Control
7-5Low-Temperature Limit Control
7-6Defrost Operation
7-7Current Limit Control
7-8Auto Restart Function
7-9 Self-Cleaning function
7-10 QUIET Mode
7-10 COMFORT SLEEP mode
8.INSTALLATION PROCEDURE
8-1Safety Cautions
8-2Installation Diagram of Indoor and Outdoor Units
8-3Installation
8-4Indoor Unit
8-5Outdoor Unit
8-6How to Set Remote Control Selector Switch
FILE NO. SVM-06037
8-7Others
9.TROUBLESHOOTING CHART
9-1Troubleshooting Procedure
9-2Basic Check Items
9-3Primary Judgement
9-4Self-Diagnosis by Remote Control (Check Code)
9-5Troubleshooting Flowcharts
9-6Troubleshooting for Remote Control
10. PART REPLACEMENT
10-1 Indoor Unit
10-2 Outdoor Unit
11. EXPLODED VIEWS AND PARTS LIST
11-1 Indoor Unit (E-Parts Assy) For Europe model
11-2 Indoor Unit (E-Parts Assy) For Asia model
11-3 Indoor Unit
11-4 Outdoor Unit (RAS-10GAH-E)
11-5 Outdoor Unit (RAS-07GAH-E)
11-6 Outdoor Unit (RAS-10GA-E, RAS-10GAX, RAS-10GAX-V)
11-7 Outdoor Unit (RAS-07GA-E, RAS-07GAX)
1 Fan motor (for indoor) MMF-240-20-4B AC Motor with 135°C thermo fuse
2Thermo sensor (TA-sensor)10k at 25 C
3 Micro power module (M01) RM1260V
4 Microcontroller unit (IC30) TMP87CM40AFG-6G61
5Heat exchanger sensor
4-4. Indoor Unit (RAS-10GKP-E, RAS-07GKP-E, RAS-10GKPX,
RAS-07GKPX, RAS-10GKPX-V)
No.Parts nameTypeSpecifications
1 Fan motor (for indoor) MMF-240-20-4B AC Motor with 135 C thermo fuse
2 Thermo sensor (TA-sensor) 10k at 25 C
3 Micro power module (M01)
4 Microcontroller unit (IC30) TMP87CM40AFG-6G61
5Heat exchanger sensor
This is a fixed capacity type air conditioner, which uses
AC motor for an indoor fan. The AC motor drive
circuit is mounted in the indoor unit. And electrical
parts which driving the compressor and the outdoor
fan motor, are mounted in the outdoor unit.
The air conditioner is controlled by the controller
mounted in the indoor unit. The controller operates all
components based on the commands trVansmitted from
the remote control and the f
is as fPollo
The temper
ature measurement at the air inlet of
the indoor heat e
temperature sensor
The temper
heat e
ature measurement at the indoor
xchanger b
temperature sensor
Indoor f
Louv
LED displa
Outdoor f
an motor oper
er motor control
y control
an motor oper
• 4-WAYS-VALVE operation control
(Heat pump model only)
Compressor oper
•
Receiving the inf
status and judging the inf
indication of errors
eedbac
k data of the sensor
xchanger b.y the indoor
y the indoor heat earxchanger
ation control
ation control
ation control
mation of the oper
ation
mation or the
7-1-1. Louver control
(1)
er
tical air flo
osition of vw:er•itcal air flo
w louv
er
w louv
er is automatically
controlled according to the operation mode
Besides
arbitr
The louv
stored in the microcontroller
automatically set at the stored position f
oper
, position of v•er
ily set b
y pressing [FIX] b•utton.
er position which is set b
ation.
tical air flo
w louv
y [FIX] b•utton is
, and the louv•er is
er can be
or the ne•xt
(2)• Swing
If [SWING] b
is in oper
s
winging.
utton is pressed when the indoor unit
ation, the vorer
tical air flo
w louv
er starorts
When [SWING] button is pressed again,
it stops swinging.
7-1-2. Indoor fan control (AC Fan motor)
(1) The indoor fan is operated by the stepless speed
change AC motor.
(2) For air flow level, speed of the indoor fan motor is
controlled in five steps (LOW, LOW
+
, MED, MED
and HIGH). If AUTO mode is selected, the fan
motor speed is automatically controlled by the
difference between the preset temperature and
the room temperature.
LOW
=
LOW+MED
+
2
MED+=
MED+HIGH
2
+
OPERATION
MODE
RAS-07GK Series
RAS-07GKH Series
Model
RAS-10GK Series
RAS-10GKH Series
Table 7-1-1
Cooling
Fan only
Dry
Heat
rpm
Air flow volume (m3/h)
rpm
Air flow volume (m3/h)
rpm
Air flow volume (m3/h)
rpm
Air flow volume (m3/h)
UHHMLL-ULSL
UHHMLL-ULSL
1300
540
1200
490
1350
560390
1350980
560390
- 23 -
FAN TAP
HMLL-
MLL-ULSL
1250 1120 1070900 800 750 700 650 500
510 450 430 350 300 270 250 220 150
1120 1070900 800 750 700 650 500
450 430350 300 270 250 220 150
1300 1180 1140 1000900 800 750 700 550
540 500 460 400350 300 270 250 180
1300 1180 1140 1000900 800 750 700 550
540 500 460 400350 300 270 250 180
950
370
950
370
980
FILE NO. SVM-06037
7-2. Description of Operation Circuit
(1) When turning on the breaker, the operation lamp
blinks. This means that the power supply is on.
(2) When pressing [ ] button on the remote control,
receiving beep sounds from the indoor unit, and
the next operation is performed together with
opening the vertical air flow louver.
(3) Once the operation mode is set, it is memorized in
the microcontroller so that the previous operation
can be effected thereafter simply by pressing
[ ] button.
7-2-1. Fan only operation
([MODE] button on the remote control is set
to the fan only operation.)
(1) When [FAN] button is set to AUTO, the indoor fan
motor operates as shown in Fig. 7-2-1. When
[FAN] button is set to LOW, LOW
HIGH, the motor operates with a constant air flow.
°C
+3
+2.5
+2
-
+1.5
+1
+0.5
(Room temp.) (Preset temp.)
Preset
temp.
0
(Preset temp.: 22°C)
NOTE :
*1: The values marked with *1 are calculated and
controlled by the difference in motor speed
between M+ and L-.
(2) The Hi POWER, ECO and COMFORT SLEEP
operation cannot be set.
Fig. 7-2-1 Setting of air flow [FAN:AUTO]
+
, MED, MED+ or
M+
*1
*1
*1
-
L
7-2-2. Cooling operation
([MODE] button on the remote control is set
to the cooling operation.)
(1) The compressor, 4-way valve, outdoor fan and
operation display on the remote control are
controlled as shown in Fig. 7-2-2.
°C
ONON
OFF OFF OFF ON
4-way valve
Compressor
Outdoor fan
OPERATION
-
(Room temp.) (Preset temp.)
Preset
temp.
0.5
0
Fig. 7-2-2
(2) When [FAN] button is set to AUTO, the indoor fan
motor operates as shown in Fig. 7-2-3. When
[FAN] button is set to LOW, LOW
+
, MED, MED+ or
HIGH, the motor operates with a constant air flow.
°C
(Preset temp.)
−
(Room temp.)
Preset
temp.
+3
+2.5
+2
+1.5
+1
+0.5
0
-0.5
M+
*1
*1
*1
L
-
NOTE :
*1: The values marked with *1 are calculated and
controlled by the difference in motor speed
between M+ and L-.
display
- 24 -
Fig. 7-2-3 Setting of air flow [FAN:AUTO]