Engineering Data
4-way Air Discharge
Cassette Type
E08-361
Indoor Unit
MMU-AP0092H / MMU-AP0122H
MMU-AP0152H / MMU-AP0182H
MMU-AP0242H / MMU-AP0272H
MMU-AP0302H / MMU-AP0362H
MMU-AP0482H / MMU-AP0562H
Contents
1. Specifications
2. Dimensions
3. Center of Gravity
4. Electrical current characteristics
5. Sensible capacity table
6. Wiring diagram
7. Air throw distance chart
8. Sound characteristics (NC-Curve)
9. Accessories
10. Fresh air intake (Design guide)
11. Branching duct (Design guide)
4-way Air Discharge Cassette Type
1. Specifications
Engineering Data Book
50Hz
Model name MMU-
Cooling/Heating capacity (Note 1) (kW) 2.8/3.2 3.6/4.0 4.5/5.0 5.6/6.3 7.1/8.0 8.0/9.0 9.0/10.0 11.2/12.5 14.0/16.0 16.0/18.0
Power supply 1 phase 50Hz 230V (220-240V) / 1 phase 60Hz 220V (Sepatate power supply for indoor units is required.)
Electical
characteristics
Appearance
Outer
dimention
Total weight
Heat exchanger Fined tube
Soundproof / Heat-insulating material Non-flammable insulation
Fan unit
Air filter Standard filter (Long life filter)
Controller Remote controller
Connecting
pipe
Sound pressure level (Note 2)
(High/Med./Low)
Running current (A) 0.23 0.27 0.29 0.38 0.43 0.73 0.88
Power consumption (kW) 0.021 0.023 0.026 0.036 0.043 0.088 0.112
Starting current (A) 0.30 0.33 0.36 0.42 0.59 0.87 1.23 1.26
Main unit Heat-insulating material attached Zinc hot dipping steel plate
Ceiling
panel
Main unit
Ceiling
panel
Main unit (kg) 18 20 25
Ceiling panel (kg) 4.0
Fan Turbo fan
Standard air flow High
(Mid/Low)
Motor (W) 14 20 68 72
Gas pipe (mm) φ9.5 φ12.7 φ15.9
Liquid pipe (mm) φ6.4 φ9.5
Drain port (Nominal dia.mm) 25 (Polyvinyl chloride tube)
Model RBC-U31PG(W)-E
Panel color White (2.5GY9.0/0.5)
Hight (mm) 256 319
Width (mm) 840
Depth (mm) 840
Hight (mm) 30
Width (mm) 950
Depth (mm) 950
AP0092H AP0122H AP0152H AP0182H AP0242H AP0272H AP0302H AP0362H AP0482H AP0562H
(m³/h)
(dB(A)) 30/29/27 31/29/27 32/29/27 35/31/28 38/33/30 43/38/32 46/38/33 46/40/33
800
(730/680)
930
(830/790)
1050
(920/800)
1290
(920/800)
1320
(1100/850)
1970
(1430/1070)
2130
(1430/1130)
2130
(1520/1230)
Note 1 : The cooling capacities and electrical characteristics are measured under the conditions specified by JIS B 8615 based
on the reference piping.
The reference piping consists of 5 m of main piping and 2.5 m of branch piping connected with 0 meter height.
Note 2 : The sound level are measured in an anechoic chamber in accordance with JIS B 8616.
Normally, the values measured in the actual operating environment become larger than the indicated values due to the
effects of external sound.
Note : Rated conditions Cooling : Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Heating : Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB
2
4-way Air Discharge Cassette Type
Engineering Data Book
60Hz
Model name MMU-
Cooling/Heating capacity (Note 1) (kW) 2.8/3.2 3.6/4.0 4.5/5.0 5.6/6.3 7.1/8.0 8.0/9.0 9.0/10.0 11.2/12.5 14.0/16.0 16.0/18.0
Power supply 1 phase 50Hz 230V (220-240V) / 1 phase 60Hz 220V (Sepatate power supply for indoor units is required.)
Electical
characteristics
Appearance
Outer
dimention
Total weight
Heat exchanger Fined tube
Soundproof / Heat-insulating material Non-flammable insulation
Fan unit
Air filter Standard filter (Long life filter)
Controller Remote controller
Connecting
pipe
Sound pressure level (Note 2)
(High/Med./Low)
Running current (A) 0.24 0.28 0.30 0.39 0.45 0.76 0.92
Power consumption (kW) 0.021 0.023 0.026 0.036 0.043 0.088 0.112
Starting current (A) 0.30 0.33 0.36 0.42 0.59 0.87 1.23 1.26
Main unit Heat-insulating material attached Zinc hot dipping steel plate
Ceiling
panel
Main unit
Ceiling
panel
Main unit (kg) 18 20 25
Ceiling panel (kg) 4.0
Fan Turbo fan
Standard air flow High
(Mid/Low)
Motor (W) 14 20 68 72
Gas pipe (mm) φ9.5 φ12.7 φ15.9
Liquid pipe (mm) φ6.4 φ9.5
Drain port (Nominal dia.mm) 25 (Polyvinyl chloride tube)
Model RBC-U31PG(W)-E
Panel color White (2.5GY9.0/0.5)
Hight (mm) 256 319
Width (mm) 840
Depth (mm) 840
Hight (mm) 30
Width (mm) 950
Depth (mm) 950
AP0092H AP0122H AP0152H AP0182H AP0242H AP0272H AP0302H AP0362H AP0482H AP0562H
(m³/h)
(dB(A)) 30/29/27 31/29/27 32/29/27 35/31/28 38/33/30 43/38/32 46/38/33 46/40/33
800
(730/680)
930
(830/790)
1050
(920/800)
1290
(920/800)
1320
(1100/850)
1970
(1430/1070)
2130
(1430/1130)
2130
(1520/1230)
Note 1 : The cooling capacities and electrical characteristics are measured under the conditions specified by JIS B 8615 based
on the reference piping.
The reference piping consists of 5 m of main piping and 2.5 m of branch piping connected with 0 meter height.
Note 2 : The sound level are measured in an anechoic chamber in accordance with JIS B 8616.
Normally, the values measured in the actual operating environment become larger than the indicated values due to the
effects of external sound.
Note : Rated conditions Cooling : Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Heating : Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB
3
4-way Air Discharge Cassette Type
2. Dimensions
MMU-AP0092H, AP0122H
Take-in port of wiring
44
112
172
Refrigerant pipe connecting port
Ø6.4 (Liquid side)
Refrigerant pipe connecting port
Ø9.5 (Gas side)
Bottom face of ceiling
129
77
10 5
74
Ø162
106.5
Electric parts box
860 to 910 Ceiling open dimension
30
77
105
74
397.5
157
72 241.5
950 Panel external dimension
780 Hanging bolt pitch
105 337.5
263
323
Engineering Data Book
15 or more
1000 or more
15 or more
The space that is necessary
for equipping and service
860 to 910 Ceiling open dimension
Bottom face of ceiling
129
189
Indoor unit
Drain pipe
connecting port
(Material: PP)
For branch duct knockout square hole Ø150
Hanging bolt M10 or Ø3/8(procured by locally)
Drain upstanding size
256
132
300 or less
Bottom face of ceiling
1000 or more
An obstacle
1000 or more
Standing
661 or less
Standing
850 or less
80
105
Ø162
For branch duct knockout
square hole Ø150
(2 positions)
For branch duct knockout
square hole Ø150
Bottom face of ceiling
408
105 287.5
135105207.5
240
840 Unit external dimension
269
840 Unit external dimension
362.5 105 372.5
7477
105
5
129
74
416.5
690 ± 20 Hanging bolt pitch
45
950 Panel external dimension
57
28.5
187
64
155
Indoor unit
Z
32
61
Bottom face of ceiling
105 351
384
105 77
30
Bottom face of ceiling
129
For branch duct
knockout square
hole Ø150
16.5
Ceiling panel
(sold separately)
Bottom face
of ceiling
Knockout for simple
OA for Ø100
Z view
12
Unit : mm
4
4-way Air Discharge Cassette Type
MMU-AP0152H, AP0182H
860 to 910 Ceiling open dimension
Engineering Data Book
1000 or more
15 or more
An obstacle
1000 or more
15 or more
The space that is necessary
for equipping and service
1000 or more
Take-in port of wiring
112
172
Refrigerant pipe connecting port
Ø6.4 (Liquid side)
Refrigerant pipe connecting port
Ø12.7 (Gas side)
Bottom face of ceiling
129
77
10 5 74
Ø162
80
240
44
Electric parts box
408
105 287.5
135105207.5
77
74 105
397.5
157
106.5
263
72 241.5
950 Panel external dimension
780 Hanging bolt pitch
Bottom face of ceiling
30
105 337.5
For branch duct knockout square hole Ø150
323
860 to 910 Ceiling open dimension
129
Drain pipe
connecting port
(Material: PP)
416.5
Indoor unit Bottom face of ceiling
189
Hanging bolt M10 or Ø3/8 (procured locally)
74
351
105384
300 or less
Drain upstanding size
256
132
129
105 77
16.5
Standing
661 or less
Standing
850 or less
For branch duct
knockout square
hole Ø150
105
Ø162
For branch duct knockout
square hole Ø150
(2 positions)
For branch duct knockout
square hole Ø150
Bottom face of ceiling
840 Unit external dimension
840 Unit external dimension
362.5 105 372.5
129
690 ± 20 Hanging bolt pitch
45
950 Panel external dimension
269
57
28.5
187
64
155
Bottom face of ceiling
Indoor unit
Z
32
61
7477
105
5
Bottom face of ceiling
30
Knockout for simple OA for Ø100
Z view
Ceiling panel
(sold separately)
Bottom face
of ceiling
12
Unit : mm
5
4-way Air Discharge Cassette Type
MMU-AP0242H, AP0272H, AP0302H
860 to 910 Ceiling open dimension
Engineering Data Book
1000 or more
15 or more
An obstacle
1000 or more
15 or more
The space that is necessary
for equipping and service
1000 or more
Take-in port of wiring
112
172
Refrigerant pipe connecting port
Ø9.5 (Liquid side)
Refrigerant pipe connecting port
Ø15.9 (Gas side)
Bottom face of ceiling
129
4
74
77
10 5
Ø162
162
80
240
44
Electric parts box
408
135105207.5 105 287.5
77
105
74
397.5
157
106.5
263
72 241.5
950 Panel external dimension
780 Hanging bolt pitch
Bottom face of ceiling
30
105 337.5
For branch duct knockout square hole Ø150
323
860 to 910 Ceiling open dimension
129
Drain pipe
connecting port
(Material: PP)
416.5
Indoor unit
189
Hanging bolt M10 or Ø3/8 (procured locally)
74
105
300 or less
Bottom face of ceiling
Drain upstanding size
256
132
129
105 77
Standing
661 or less
For branch duct
knockout square
hole Ø150
16.5
Standing
850 or less
105
Ø162
For branch duct knockout
square hole Ø150
(2 positions)
For branch duct knockout
square hole Ø150
Bottom face of ceiling
840 Unit external dimension
269
840 Unit external dimension
362.5 105 372.5
7477
105
5
129
6
690 ± 20 Hanging bolt pitch
45
950 Panel external dimension
Z
57
32
61
28.5
155
187
Indoor unit
Bottom face of ceiling
384 351
64
Knockout for simple OA for Ø100
Bottom face of ceiling
Z view
Ceiling panel
(sold separately)
Bottom face
30
of ceiling
12
Unit : mm