AIR CONDITIONER
CLIMATISEUR
KLIMASYSTEM
CONDIZIONATORE D’ARIA
VOLUME-1
AIRE ACONDICIONADO
Indoor Unit
Unité intérieure
Raumeinheit
Assolutamente solo per uso commerciale
Unità interna
Unidad interior
[4-way Air Discharge Cassette Type]
[Type cassette à 4 voies de soufflage]
[4-Wege-Kassetten-Modell]
[Tipo a cassetta per mandata d'aria a 4 vie]
[Modelo de cassette con descarga de aire de 4 vías]
This Air Conditioner adopts a new HFC refrigerant
(R410A) which does not destruct the ozone layer.
We would lik e to express our deepest thanks to your purchase this Air
Conditioner.
This manual describes the details of installation method of the indoor
unit.
Prior to installation, please read this manual thoroughly to understand the
contents.
If you are an installer or a dealer , please pass this manual to the
customer and clearly explain the contents.
For piping connections such as Y-shape branch, branching joints, header
branch of the indoor and outdoor units must be selected in accordance to
the total system capacity.
These items are supplied separately as accessories.
UTILISATION DU NOUVEAU REFRIGERANT
Ce climatiseur utilise le nouveau réfrigérant HFC
(R410A), qui ne détruit pas la couche d’ozone.
VERWENDUNG EINES NEUEN KÜHLMITTELS
Dieses Klimagerät arbeitet mit dem neuen HFC
Kältemittel R410A. Dieses Kältemittel g reift die
Ozonschicht nicht an.
Nous vous remercions d’av oir choisi ce climatiseur.
Ce manuel décrit la procédure d’installation de l’unité intérieure.
Av ant de procéder à l’installation, veuillez lire attentivement ce manuel et
vous assurer d’en avoir compris le contenu.
Si vous êtes un monteur ou un revendeur, veuillez remettre ce manuel au
client en lui expliquant clairement son contenu.
Choisissez les raccords des tuyauteries, tels que les embranchements
en Y, les raccords d’embranchement, l’embranchement du collecteur des
unités intérieures et extérieures, en fonction de la puissance totale du
système.
Ces éléments sont des accessoires fournis séparément.
Wir danken Ihnen, dass Sie sich für dieses Klimagerät entschieden
haben.
In diesem Handbuch wird die Installation der Inneneinheit beschrieben.
Bevor Sie mit der Installation beginnen, lesen Sie dieses Handbuch
sorgfältig.
Wenn Sie zu einem Installationsbetrieb oder zu einem Händler gehören,
geben Sie das Handbuch an Ihren Kunden weiter und erklären ihm den
Inhalt.
Rohrleitungsverbindungen wie Y-Abzweige, Abzweiganschlüsse und
Verteiler für Innen- und Außeneinheiten müssen entsprechend der
Systemleistung ausgewählt werden.
Diese Teile werden separat als Zubehör geliefert.
IMPIEGO DI NUOVO REFRIGERANTE
Questo condizionatore d’aria impiega il nuovo
refrigerante HFC (R410A) che non distrugge lo
strato d’ozono .
ADOPCIÓN DE NUEVO REFRIGERANTE
Este acondicionador de aire utiliza el nuev o
refrigerante HFC (R410A) que no daña la capa de
ozono.
Porgiamo i nostri sinceri ringraziamenti per aver acquistato questo
condizionatore d’aria.
Questo manaule presenta informazioni dettagliate riguardo come
installare l’unità esterna.
Prima d’iniziare l’installazione, leggere attentamente questo manuale per
comprendere le istruzioni contenute.
È importante che l’installatore o il rivenditore forniscano questo manuale
al cliente e lo informino bene delle istruzioni in esso fornite.
Per il collegamento dei tubi relativi a derivazione Y, giunti di derivazione,
collettore di derivazione di unità interne ed esterne, i tubi devono essere
scelti in funzione della capacità totale del sistema.
Queste parti sono da acquistare a parte, come parti accessorie.
Gracias por haber adquirido este acondicionador de aire.
Este manual describe en detalle el método de instalación de la unidad
interior.
Antes de realizar la instalación, lea detenidamente el manual para
entenderlo por completo.
Si es un instalador o un distribuidor, hágale llegar el man ual al cliente y
explique claramente.
Para las conexiones de la tubería, como la derivación en Y, las juntas de
derivación, se deben elegir las derivaciones con colector de las unidades
interior y exterior según la capacidad total del sistema.
Estos elementos vienen por separado, en calidad de accesorios.
CONTENTS
VOLUME-1
Accessory parts and Parts to be procured locally.... 1
1
PRECAUTIONS FOR SAFETY ........................... 2
2
SELECTION OF INSTALLATION PLACE ........... 3
3
INSTALLATION OF INDOOR UNIT..................... 5
4
DRAIN PIPING WORK ........................................ 9
For heat insulation of the pipe connecting section
For checking of ceiling opening and the main unit position
For positioning of the ceiling position
(To be used with the installation pattern)
For attach the installation pattern
For heat insulation of drain connecting section
For hanging unit
For connecting drain pipe
For adjusting core-out of drain pipe
For sealing of wire connecting port
Heat insulator B
1
For sealing of wire connecting port
Refrigerant piping
• Piping material used for the conventional refrigerant cannot be used.
• Use copper pipe only with a wall thickness of 0.8 mm or more for Ø6.4, Ø9.5, Ø12.7.
• Flare nut and flare operations are also different from those of the conventional refrigerant.
Use the flare nut fitted to the indoor unit of the air conditioner.
1
1
• Ensure that all Local, National and International regulations are satisfied.
• Important safety information are describes in this installation manual.
Please ensure this manual is read thoroughly and kept for future reference.
• After the installation work, perform a trial operation to check for any problem.
Follow the Owner’s Manual to explain how to use and maintain the unit to the customer.
• Turn off the main power supply switch (or breaker) before any unit maintenance.
• Ask the customer to keep the Installation Manual together with the Owner’s Manual.
PRECAUTIONS FOR SAFETY
CAUTIONNew Refrigerant Air Conditioner Installation
• THIS AIR CONDITIONER FEATURES A NEW HFC REFRIGERANT (R410A) WHICH DOES NOT
DEPLETE OZONE LAYER.
The pressure of R410A is 1.6 times higher than that of former refrigerant R22. The refrigerating oil has also been
changed. Therefore be sure that any former refrigerant, refrigerant oil or any other contaminants do not enter the
refrigerating cycle of the air conditioner, during either installation or service work. If incorrect tools or operating
procedures are used, there is a possibility of a serious accident. Use only tools and materials that have been
designed to operate with R410A.
To prevent the risk of charging with an incorrect refrigerant, the dimensions of the charging port connections are different
to those used for conventional refrigerant. Therefore only tools designed to operate with R410A can be used.
For connecting pipes, use piping specifically designed for R410A.
During installation, ensure pipes are clean and ensure contaminants do not enter the pipes as the system is affected
by impurities such as water, oxide scales, dirt, oil, etc. Do not use existing pipe work from previous installation as this
will cause problems due to pressure resistances and impurities within the pipe.
ENGLISH
CAUTIONTo Disconnect the Appliance from Main Power Supply.
This appliance must be connected to the main power supply by means of a switch with a contact separation of at
least 3 mm.
WARNING
• Ask an authorized dealer or qualified installation professional to install/maintain the air conditioner.
Inappropriate installation may result in water leakage, electric shock or fire.
• Turn off the main power supply switch or breaker before attempting any electrical work.
Make sure all power switches are off. Failure to do so may cause an electric shock.
• Connect all of the installation wiring correctly.
If the installation wiring is incorrect electrical parts may be damaged.
• During the transportation and installation of the air conditioning unit, ensure that gaseous matter
other than the specified refrigerant does not enter into the refrigeration cycle.
If a refrigerant becomes contaminated with foreign gases, the gas pressure within the refrigerant cycle will become
abnormally high and may result in the fracture of pipework and possible human injury.
• Do not modify this unit by removing any of the safety guards or by overriding any of the safety
interlock switches.
• Exposure of the unit to water or other forms of moisture before installation may cause a short-circuit
of the electrical parts.
Do not store it in a wet basement or expose to rain or water.
• After unpacking the unit, examine for possible damage.
• Do not install in a place that might increase the vibration of the unit.
• To avoid personal injury (with sharp edges), be careful when handling parts.
• Perform installation work properly according to the Installation Manual.
Inappropriate installation may result in water leakage, electric shock or fire.
• When the air conditioner is installed in a small room, provide appropriate measures to ensure that in
the event of a refrigerant leak the rooms does not exceed the critical level.
2
1
PRECAUTIONS FOR SAFETY
• Install the air conditioner securely in a location where the base can sustain the weight of the unit
adequately.
• Perform the specified installation work to guard against an earthquake.
If the air conditioner is not installed appropriately, accidents may occur due to the unit falling.
• If refrigerant gas has leaked during the installation work, ventilate the room immediately.
If the leaked refrigerant gas comes in contact with fire, noxious gases may be generated.
• After the installation work, confirm that refrigerant gas does not leak.
If refrigerant gas leaks into the room and flows near a fire source, such as a cooking range, noxious gases maybe
generated.
• Electrical work must be performed by a qualified electrician in accordance with the Installation
Manual. Ensure the power supply to the air conditioner is exclusive to that unit only.
An insufficient power supply capacity or inappropriate installation may cause fire.
• Use only the specified wiring during the unit installation. Ensure that all terminals are securely fixed,
so preventing any external forces having a negative effect on the terminals.
• Conform to the regulations of the local electric authority when wiring the power supply.
Inappropriate grounding may cause an electric shock.
• Do not install the air conditioner in a location that maybe subjected to a risk of exposure to a
combustible gas.
If a combustible gas leaks and becomes concentrated around the unit, a fire may occur.
2
SELECTION OF INSTALLATION PLACE
WARNING
• The air conditioner must be installed in a location that can support the weight of the unit effectively.
If the unit is not installed on a foundation that can support its weight effectively, the unit may fall down, resulting in
possible human injury.
• Where required ensure that the units installation is sufficient enough to withstand against an earthquake.
An insufficient installation could result in the unit falling, causing possible human injury.
• Install the air conditioner at a minimum height of 2.5 m from the floor.
Do not insert your hands or others into the unit while the air conditioner is operating.
CAUTION
Upon approval from the customer, install the air conditioner in a place that satisfies the following
conditions.
• A place where the unit can be installed horizontally.
• A place where a sufficient servicing space can be maintained for safety maintenance and unit check.
• A place where the drain water can be exited from the unit, without causing a problem.
Avoid installing in the following places.
• Places exposed to air with a high salt content (seaside area), or places exposed to large quantities of sulfide gas
(hot spring). (Should the unit be used in these places, special protective measures are needed.)
• Places exposed to oil, vapor, oil smoke or corrosive gas.
• Places where organic solvent is used nearby.
• Places close to a machine generating high frequency.
• Places where the discharged air blows directly into the window of the neighbouring house. (For outdoor unit)
• Places where the noise from the outdoor unit can be easily transmitted to the neighboring property.
(When installing the air conditioner on the boundary with a neighbour, pay due attention to the level of noise.)
• Places with poor ventilation.
3
Installation space
Ensure there is sufficient space to install the unit and to perform maintenance work as and when required.
Keep 15mm or more for clearance between top plate of the indoor unit and the ceiling surface.
Installation space
1000
or more
283
or more
15 or more
1000 or more
Obstacle
283
or more
15 or more
1000 or more
Ceiling height
Model MMU-
0071 to 0121 type
0151 to 0181 type
When the ceiling height exceeds the standard distance of a 4-way discharge cassette as detailed in the following
table. The air-flow may not be sufficient to heat the room. It is therefore necessary to set the unit to high ceiling
mode or adjust the direction of the ceiling discharge.
If fitting a separately supplied filter, it will also be necessary to set to high ceiling mode.
For setup of the high ceiling mode, refer to the details of Applicable controls “To incorporate a filter sold separately”
and “In case of installation to high ceiling” within this Manual.
Installable ceiling height
Up to 2.7 m
Up to 3.5 m
Installable ceiling height list
Indoor unit Capacity type
Discharge direction
Standard (At shipment)
High ceiling (2)
High ceiling (3)
0071 to 0121 type0151 type0181 type
4-way3-way2-way4-way3-way2-way4-way3-way2-way
2.7——2.9——3.2——
———3.2——3.4——
———3.5——3.5——
Setup of high ceiling
Setup data
0000
0002
0003
(Unit: m)
REQUIREMENT
• When high ceiling (1) or (3) is used with 4-way blowing, a draft is easily recognized due to drop of discharge
temperature.
The air filter cleaning signal duration (Notification of filter cleaning) on the remote controller can be changed
according to the condition of installation.
If the room is not heated due to the installation place or construction of the room, the detection temperature of
heating can be raised.
For setup method, refer to “Change of lighting term of filter sign” and “To secure better effect of heating” in the
Applicable controls of this Manual.
4
2
SELECTION OF INSTALLATION PLACE
In case of wireless type
The wireless remote controller can be operated up to a
maximum of 8 m from the infra-red receiver.
Therefore ensure that the remote controller will be
mounted and used within this stated parameter.
• To prevent malfunction do not mount or operate in a
location that is subjected to either a fluorescent lamp
or direct sunlight.
• A maximum of 6 indoor units with wireless remote
control can be installed within the same room.
8 m or less
3
INSTALLATION OF INDOOR UNIT
WARNING
The installation of the air conditioning unit must be positioned in a location that can sufficiently support its weight
and give protection against adverse environmental conditions.
Failure to do so may result in unit damage and possible human injury.
Any incomplete installation may also cause possible risk of human injury.
• Unpack the package, take out the product and then place it
on the floor so that the same surface directs underneath as
it is placed in the package.
If the both sides are turned over, a deformation of mounting
metal of the ceiling panel which is sold separately, etc may
be caused. Accordingly the product may be damaged and
the installation becomes impossible in some cases.
REQUIREMENT
Strictly comply to the following rules to prevent damage of the indoor units and human injury.
• Do not place heavy objects on the indoor unit. (Even when units are still packaged)
• Always carry the unit as packaged from the factory wherever possible.
If carrying in the indoor unit unpacked by necessity, be sure to use buffering cloth, etc. to prevent damaging
the unit.
• To move the indoor unit, hold the hanging brackets (4 positions) only.
Do not apply force to other parts (refrigerant pipe, drain pan, foamed parts, or resin parts etc.).
• To be carried by two or more persons. Do not strap the unit in positions other than that stated.
OKNO GOOD
5
Dimensional view
200
1000 or more
15 or more
1000 or more
Obustacle
1000 or more
15 or more
Space required for
installation and servicing
149
175
207
64
Knockout for flesh
145.5
93
105
air intake Ø100
Bottom face
of ceiling
70
595 to 660 Ceiling open dimension
14264368.5
29
700 Panel external dimension
595 to 660 Ceiling open dimension
525 Hanging bolt pitch
Check port
( 450)
Check port
(o 450)
200
Check port
( 450)
Drain-up standing-up size
Indoor unit
627.5
or less
Stand-up
Bottom face
of ceiling
Stand-up
850 or less
Note)
595 to 660 Ceiling open dimension
As ABS is used for the drain discharge port of the main unit,
the vinyl chlor paste cannot be used.
Use the flexible hose (Band fix) included in the package.
M5 × 16L screws (Attached)
These screws are exclusive to the
installation pattern. When installing
the ceiling panel, the other exclusive
screws attached to the ceiling panel
(sold separately) are used.)
Indoor unit
Installation pattern
(Attached)
Cut off the installation
pattern along slit of
the main unit.
3
INSTALLATION OF INDOOR UNIT
Ceiling opening and installation of hanging bolts
• Evaluate and determine the piping and wiring requirements inside the ceiling prior to the hanging of the unit.
• After installation place of the indoor unit has been determined, create opening in ceiling and install the hanging
bolts.
• For the ceiling opening size and pitch for hanging bolts refer to the dimensional drawing and the supplied
installation pattern.
• Once the ceiling void has been created, ensure that the drain pipe, refrigerant pipes, inter-connecting wires and all
control wires are in place prior to installing the actual indoor unit.
Please procure the hanging bolts and nuts for
Hanging bolt
M10 or W3/8
installation of the indoor unit at local site.
Nut
M10 or W3/8
How to use the supplied installation pattern
The installation pattern is enclosed within the packaging of the air conditioner.
Existing ceiling void
Use the pattern to determine the position and size of the opening and location of the hanging bolts.
New ceiling void
Use the pattern to determine the position of the new ceiling opening.
Cut off slit section of the main unit of the installation pattern.
Cut off the outside of the pattern according to size of the ceiling
opening. (There is a slit on the standard opening size section.)
• Install the indoor unit after installation of the hanging bolts.
• Using the supplied pattern attach it to the indoor unit using the
supplied fixing screws (M5 × 16L 4off). (Screw pattern to the ceiling
panel hanging brackets of the indoor unit)
• When creating the opening ensure it is as per the outer dimensions
of the supplied pattern.
4 pieces
12 pieces
Opening a ceiling and installation of hanging bolts
Treatment of ceiling
The ceiling differs according to the structure of the building. For details, consult your architect.
In the process after the ceiling panels have been removed, it is important to reinforce the ceiling construction and
ensure the ceiling remains in a horizontal position. This is to prevent possible vibration of the ceiling panels.
1. Cut and remove the ceiling material.
2. Reinforce the cut surface of the ceiling construction and add support for fixing the end of ceiling panel.
Installation of hanging bolt
Use M10 hanging bolts (4 off, locally procured).
When mounting the unit, set the pitch of the hanging bolts according to the size of the unit as detailed on the
dimensional drawing.
New concrete slab
Install the bolts with insert brackets or anchor
bolts.
(Blade type
bracket)
(Slide type
bracket)
Anchor bolt
(Pipe hanging
anchor bolt)
Reinforcing
steel
Steel flame structure
Use existing angles or install new
support angles.
Hanging bolt
Hanging boltSupport angle
7
Existing concrete slab
Use a hole-in anchors, hole-in
plugs, or a hole-in bolts.
Installation of indoor unit
• Attach the nut (M10 or W3/8: Procured locally) and washer (Ø34 mm)
to the hanging bolt.
• Put washers at either side of the T-groove on the hanging bracket of
the indoor unit in order to hang the unit.
• Using a spirit level, check that all four sides are horizontal.
(Horizontal positioned within 5 mm)
• Cut off the installation gauge from the installation pattern.
• Using the installation gauge check and adjust clearance between the
indoor unit and the ceiling opening (1) (10 to 42 mm on each side).
Ensure that the unit is level to the ceiling and within a distance of (2)
23 mm to 28 mm below.
The installation gauge has details of how to use printed on it.
Note) Install the indoor unit so that the end part of opening does not
come into contact with the drain socket piping.
Hanging bolt
(W3/8 or M10)
Nut
(W3/8 or M10)
Nut
(W3/8 or M10)
(1) M10 washer supplied, all other material
must be procured locally.
(2) To ensure that the unit is mounted safely, the
hanging bolt must be positioned just below
the hanging bracket as shown in the diagram.
(1)
M10 flat washer
(Accessory)
(2)
M10 flat washer
(Accessory)
Level vial (Horizontal: within 5 mm)
Indoor unit
Hanging
metal
10 to 42
Installation gauge
mm (2)
Hanging bolt
23 to 28
Ceiling board
Indoor unit
mm (1)
Ceiling board
REQUIREMENT
Before installation of the indoor unit be sure to
remove the transportation cushion found between
the fan and the bell mouth.
Running the unit without removing the cushion
may damage the fan motor.
Be sure to remove the cushion for transportation
between the fan and the bell mouth.
1) 23 to 28 mm
Installation gauge2) 10 to 42 mm
Installation of ceiling panel
(Sold separately)
Install the ceiling panel after completion of the
installation of the indoor unit, including all piping and
wiring.
Install the ceiling panel as per the supplied Installation
Manual.
Check the installation dimensions of the indoor unit
and the ceiling opening are correct and then install.
REQUIREMENT
Ensure the ceiling panel is mated to the ceiling
surface or the indoor unit.
If the panel and unit are not mated together this
may result in the formation of dew condensation
causing a possible water leak.
First remove the 4 corner caps from the ceiling
panel and fit to the indoor unit.
Installation of remote controller (Sold separately)
For installation of the wired remote controller, follow the Installation Manual supplied with the remote controller.
• Do not expose remote controller to direct sunlight or excessive heat.
• When using a wireless type remote controller check receiver on the indoor unit receives a signal.
• For a wireless type controller ensure that it is used and mounted a minimum distance of 1m apart from any other
electrical devices (TV, Stereo, etc). As this may cause interference with the devices.
8
4
As long as possible (10cm)
VP30 or more
Downward slope
1/100 or more
VP25
VP25
VP25
(Collective pipes)
Riser (Trap)
90˚ Bend
max
45˚
max
45˚
OK
NO GOOD
Socket for VP25 vinyl chloride pipe
(To be local procure)
Align the attached hose band to the
end of hose, set the tightening
position upward, and then tighten it.
Indoor unit body
Drain pipe
connecting port
(Transparent)
Flexible hose
(Accessory)
VP25 vinyl chloride pipe
(To be local procure)
DRAIN PIPING WORK
CAUTION
• Install the drain piping so that the water
drains effectively.
• Apply heat insulation to prevent dew
condensation from forming.
• Incorrectly installed pipework may result
in a water leak.
Pipe material/Insulator and size
The following materials for piping work and insulation
are to be procured locally.
Hard vinyl chloride pipe socket for VP25
Pipe material
Insulator
Hard vinyl chloride pipe VP25
(Outer diameter Ø32 mm)
Foamed polyethylene foam, thickness:
10 mm or more
REQUIREMENT
• Ensure insulating of the drain pipes and connecting parts on the indoor units.
• The drain pipe should have a downward slope of at least 1/100 and ensure
there are no swells or blockages as this will cause abnormal sounds.
• The maximum traverse length of drain pipe is 20 m. Provide support
brackets at intervals of 1.5 to 2 m where necessary to prevent movement.
• Install the combined piping as shown in the illustration.
• Do not create an air purge in the pipework,
as the water would leak from this point.
Heat
insulator
1.5m to 2m
1/100 or more
downward
Arched
shape
Trap
Support
bracket
NO
GOOD
• The hard vinyl-chloride pipe cannot be connected
• Adhesive agent cannot be used for the pipe
Connection of flexible hose
• Insert the soft socket of the supplied flexible hose
into the connecting port of the drain pipe.
• Align the supplied hose band to the pipe connecting
port end, and tighten.
• Fix the soft socket with the supplied hose
• The supplied flexible hose can bend up to
directly to the drain pipe connecting port of the indoor unit.
For connection with the drain pipe connecting port,
ensure that the supplied flexible hose is fitted.
connecting port (hard socket) on the indoor unit.
Be sure to use the supplied hose band for fixing,
otherwise there is a risk of damage or water
leakage from the drain pipe connecting port.
REQUIREMENT
band, tighten at the upper position of the
unit.
a maximum of 45°
Drain pipe connecting port
(Hard socket)
Attached hose band
Soft socketHard socket
Adhesive agent prohibited
VP25 vinyl chloride pipe
(Procured locally)
Attached flexible hose
Socket for VP25
(Procured locally)
9
Connection of drain pipe
Check the draining
• Connect the hard socket (Procured locally) to the
hard socket side of the supplied flexible hose which
has been installed.
• Connect the drain pipes (Procured locally) in turn to
the connected hard sockets.
REQUIREMENT
• Using a adhesive agent for vinyl chloride,
connect the hard vinyl chloride pipes so that
water does not leak.
• Allow sufficient time for the adhesive to set and
harden. (Refer to the instructions of the
adhesive.)
Drain up
When it is not possible to achieve a natural downward
slope on the drain pipe, you can create a vertical lift
(Drain up) on the pipe.
• Set the height of the drain pipe within 850 mm from
the bottom surface of the ceiling.
• The drain pipe should be piped from the drain pipe
connecting port horizontally for a maximum of
300 mm and then piped vertically.
• After piping the vertical lift, ensure the pipework is
set to a downward gradient.
After completion of drain piping,
Check water drains away and that no water leaks from
any of the connecting parts. At the same time check
for any abnormal sounds from the drain pump.
Ensure drainage is checked during cooling mode.
When the electric work has finished:
• Before installing the ceiling panel, pour water as
shown in the following figure, check water drains
from the drain pipe connecting port (Transparent) in
COOL mode and then check there are no water
leaks from the drain pipes.
When the electric work has not finished:
• Pull out the float switch connector (3P: Red) from
P.C. board connector (CN34: Red) of the electric
parts box. (Ensure the power is turned off.)
• Connect the single-phase 220-240V, 1N, 50Hz (or
220V, 1N, 60Hz) power to the terminal blocks R (L)
and S (N). (Never apply 220-240V to (A), (B), (U1)
and (U2).)
• Pour water referring to the figure.
(Amount: 1500 cc to 2000 cc)
• When the power is turned on, the drain pump motor
drives automatically. Check water is drained from
the drain pipe connecting port (Transparent), and
then check there is no water leak from the drain
pipes.
• After checking for water leaks on the drain, turn off
the power supply, and re-attach the float switch
connector to the original position (CN34) on the P.C.
board and refit the electric parts box.
Indoor unit
300mm
or less
Rising up
627.5mm or less
Rising up 850mm or less
Underneath of ceiling
10
CN34
(RED)
220–240V, 1N ~, 50Hz
220V 1N ~, 60Hz
R(L)S(N)
Red
Black
Pull out connector CN34 (Red) from P.C. board.
Black
White
4
DRAIN PIPING WORK
Thermal insulating process
• After checking of the draining, using the supplied thermal insulation fit to the flexible hose leaving no clearance at
the connecting port of the indoor unit.
• Fit locally procured thermal insulation to the drain pipe leaving no clearance between the supplied insulation.
Flexible hose
Attached heat insulator
Hose band
Heat insulator to be
procured locally
Hard vinyl chloride pipe
CAUTION
Ensure water is poured slowly.
To reduce risk of water spreading throughout the
unit, resulting in a possible fault.
Air
discharge area
Drain pan
Check panel
Insert the leading part of the
hose between the heat
exchanger and the drain pan,
and then bend it downward.
Polyethylene hand pump for
pouring water in drain pan
Vessel
Water (1500cc to 2000cc)
11
5
REFRIGERANT PIPING
WARNING
• If refrigerant gas leaks during the installation work, ventilate the room immediately.
• If the leaked refrigerant comes in contact with fire, noxious gas may generate.
• After the installation work, confirm that refrigerant does not leak.
• If refrigerant gas leaks into the room and flows near to a source of fire, noxious gas maybe generated.
REQUIREMENT
When using long lengths of refrigerant piping. Provide support brackets at intervals of 2.5 m to 3 m.
If the pipes are not fixed abnormal sounds maybe generated.
Ensure the supplied R410A flare nuts are used.
Permissible pipe length and permissible height difference
This differs depending on the outdoor units. For details, refer to the Installation Manual supplied with the outdoor
unit.
Piping material and dimensions
Piping material
Indoor unit capacity type MMU-
Pipe size (mm)
• Use new and clean pipe, ensuring that the pipes are not contaminated with dust, oil, moisture, etc.
Gas side
Liquid side
Phosphor deoxidization seamless pipe for air conditioner
0071 to 0121 type0151 to 0181 type
Ø9.5Ø12.7
Ø6.4Ø6.4
Pipe flaring
Flaring
1. Cut the pipe with a pipe cutter.
• Flaring diam. meter size :
A (Unit : mm)
NO GOODOK
90˚
2. Place flare nut onto the pipe, and flare the pipe.
(Use the flare nut fitted to the unit or one that is
R410A compatible)
As the flaring sizes of R410A differ from that used
on R22. It is recommended to use a dedicated
R410A flaring tool. However a conventional flare
tool can be used, by adjustment of the projection of
the copper pipe.
Obliquity RoughnessWarp
Outer diam. of copper pipe
6.4
9.5
12.7
15.9
In case of flaring for R410A with the conventional
*
flare tool, make a margin of 0.5 mm longer than that
of R22 pipe so that the flare size matches with the
specified size.
The copper pipe gauge is useful for adjusting the
projection margin size.
A
+0
A
- 0.4
R410A
9.1
13.2
16.6
19.7
12
5
REFRIGERANT PIPING
• Projection margin in flaring :
B (Unit : mm)
Rigid (Clutch type)
Outer diam. of
copper pipe
6.4
9.5
12.7
15.9
R410A tool used
R410AR22
0 to 0.5 (Same as left)
0 to 0.5 (Same as left)
0 to 0.5 (Same as left)
0 to 0.5 (Same as left)
Conventional tool used
R410AR22
1.0 to 1.50.5 to 1.0
1.0 to 1.50.5 to 1.0
1.0 to 1.50.5 to 1.0
1.0 to 1.50.5 to 1.0
Imperial (Wing nut type)
Outer diam. of copper pipe
6.4
9.5
12.7
15.9
R410AR22
1.5 to 2.01.0 to 1.5
1.5 to 2.01.0 to 1.5
2.0 to 2.51.5 to 2.0
2.0 to 2.51.5 to 2.0
Connection of refrigerant pipe
Connect all the refrigerant pipes with the flare
connection method
• As the unit is sealed to atmospheric pressure.
It is not abnormal that no “Push....” sound will be
heard upon the removal of the flare nut.
• Ensure use of two spanners for the connecting of the
pipework to the indoor unit.
B
Airtight test/Air purge, etc.
For carrying out airtight test, air purge, gas leak check
and addition of refrigerant refer to the Installation
Manual supplied with the outdoor unit.
Open fully valves of the outdoor unit
Gas leak check
Using a leak detector or soapy water, check for gas
leaks at the connecting pipework and the caps on the
service valves.
REQUIREMENT
Use a leak detector designed specifically for HFC
refrigerant (R410A, R134a, etc.).
Heat insulating process
Fit heat insulation to the gas and liquid pipes
separately.
During cooling mode, the temperature of the liquid and
the gas pipes are reduced. Therefore ensure sufficient
insulation is fitted to prevent dew condensation.
• On the gas side ensure that the heat insulation used
is heat resistant to a minimum temperature of 120°C
• Using the supplied heat insulation. Insulate the
interconnecting parts of the indoor unit, ensuring that
there is no exposure of any refrigerant pipework.
As detailed in the below illustration.
Work using double spanner
• Refer to the following table for tightening torque.
Connecting pipe
outer dia. (mm)
Ø6.4
Ø9.5
Ø12.7
Ø15.9
Tightening torque
(N•m)
14 to 18
(1.4 to 1.8 kgf•m)
33 to 42
(3.3 to 4.2 kgf•m)
50 to 62
(5.0 to 6.2 kgf•m)
68 to 82
(6.8 to 8.2 kgf•m)
Re-tightening
torque (N•m)
18
(1.8 kgf•m)
42
(4.2 kgf•m)
50
(5.0 kgf•m)
68
(6.8 kgf•m)
REQUIREMENT
Apply the thermal insulation to the pipe connecting
section of the indoor unit securely up to the root
without exposure of the pipe. (The pipe exposed to
the outside causes water leak.)
Set notching upward.
Pipe side
Main unit
Attached heat insulating pipe
13
(Required at the site)
6
ELECTRIC WORK
WARNING
1. Using the specified wires, ensure the wires are connected and securely fixed so that no
external force can transmit to the connecting part of the terminals.
Poor connection may cause risk of fire, etc.
2. Ensure connection of earth wire. (Grounding work)
Do not connect the earth wire to a gas pipe, mains water pipe, lightning rod, or the earth wire of a telephone.
Incorrect earthing will cause risk of an electric shock.
3. For electrical installation work, strictly follow the Local and national Regulations of each
country and the Installation Manual. A designated power supply must be used.
Capacity shortage of the power supply or incomplete installation may cause an electric shock or a fire.
CAUTION
Ensure an earth leakage breaker is installed.
Failure to install, may result in a electric shock.
REQUIREMENT
• For power supply wiring, strictly conform to the Local authorities in each country.
• For wiring of the power supply of the outdoor units, follow to the outdoor unit Installation Manual.
• Never connect 220–240V control wiring to the terminal blocks (U1, U2, U3, U4, U5, U6) fault will be. (Caused.)
• Arrange the electrical wiring so that they do not come into contact with high-temperature parts of the pipework;
this is to prevent the risk of insulation melting and causing a possible accident.
• After connecting wires to the terminal block. Secure wiring with cable clamp.
• Store wiring Install control wiring and refrigerant piping within the same line.
• Do not turn on power of the indoor unit until vacuuming of the refrigerant pipe has finished.
14
6
ELECTRIC WORK
Power supply specifications
Power supply wiring and communication wiring are to be procured locally.
For the power supply specification, follow the table below. Ensure power supply is adequate. An insufficient power
supply could result in unit failure.
For specification of the power capacity of the outdoor unit and the power supply wires, refer to the Installation
Manual supplied with the outdoor unit.
220–240V, 1N ~ 50Hz
220V, 1N ~ 60Hz
(Up to 1000 m) Twist wire : 1.25 mm²
(Up to 2000 m) Twist wire : 2.00 mm²
(Up to 1000 m) Twist wire : 1.25 mm²
(Up to 2000 m) Twist wire : 2.00 mm²
Indoor unit power supply (*1)
Communication line
Power supply
Power supply switch/Earth leakage breaker or power supply wiring/fuse rating for indoor
units should be selected by the accommodated total current values of the indoor units.
Power supply wiring
Indoor/Outdoor inter-unit wiring (*2)
Central control line wiring (*3)
Remote controller wiring (*4)
20 m or lessTwist wire : 2.0 mm²
50 m or lessTwist wire : 3.5 mm²
Q’ty2
Wire size
Q’ty2
Wire size
Q’ty2
Wire sizeTwist wire : 0.5 to 2.0 mm²
Indoor unit power supply (*1)
• Indoor unit power supply, must have a dedicated supply and be separate to that of the outdoor unit.
• Arrange the power supplies to the indoor and outdoor units, so that a common earth leakage breaker and main
switch can be used.
• Power supply cable specification : Cable 3-core 2.5 mm², in conformity with Design 60245 IEC 57.
Indoor/Outdoor inter-unit wiring, Central controller wiring (*2) (*3)
• Use a 2 core non polarity cable.
• To prevent any possible noise issues, use a shielded 2 core wire.
• The total stated length of communication wiring is determined by the interconnecting length of indoor to outdoor
cable plus the length of the central control communication cable.
Remote controller wiring (*4)
• For wiring remote controllers a 2 core polarity cable must be used.
Total wire length of remote controller
wiring and remote controller inter-unit
wiring = L + L1 + L2 + … Ln
Total wire length of remote controller inter-unit wiring = L1 + L2 + … Ln
Indoor unit
Remote
controller
wiring
Remote
controller
Twist wire: 0.5mm
In case of wired type only
In case of wireless type included
Indoor unit
L1L2Ln
Remote controller inter-unit wiring
2
to 2.0 mm2 × 2
Indoor unitIndoor unit
Up to 500 m
Up to 400 m
Up to 200 m
(Max. 8 units)
The remote controller wire
(Communication line) and AC220–
240V (Power supply) wires cannot
be parallel to contact each other
and cannot be stored in the same
conduits. If doing so, a trouble
may be caused on the control
system due to noise, etc.
15
Cable connection
REQUIREMENT
• Be sure to locate the cable through the cable connection port of the indoor unit.
• Ensure additional wire length of approximately 100 mm at the indoor unit electric parts box.
This is to enable ease of any service work in the future.
• The low-voltage circuit is provided for the remote controller.
• Remove the cover of the electric parts box by removing the mounting screws (3 off) and push the hooking section.
(The cover of the electric parts box remains hanged to the hinge.)
• Tighten the screws on the terminal block and secure the cables with cord clamp fitted to the electric parts box.
(Do not apply tension to the connecting section of the terminal block.)
• Using the supplied thermal insulation for the sealing of the cable connecting port, seal the cable connecting port.
(Otherwise dew condensation may be caused.)
• Mount the cover of the electric parts box ensuring the cables are not pinched.
(Mount the cover after the ceiling panel has been wired to the electric box.)
• Strip approximately 14 mm of insulation off of the connecting wires.
• As the remote controller wire has no polarity, there is no problem if connections to indoor unit terminal blocks A
and B are reversed.
Wiring diagram
Terminal block for remote controller
wiring of indoor unit
Terminal block
A
B
Remote controller wire (Field supply)
Wiring between indoor and outdoor units
Outdoor power supply
Earth
Indoor unit
Earth
LN
Header outdoor unit
U1U1U3 U4 U5U6
Control wiring between indoor and outdoor units
Control wiring between indoor units
U2U1A B
Outdoor power supply
Earth
Control wiring between outdoor units
Indoor unit
Earth
LNU2U1A B
Follower outdoor unit
U1U1U3 U4 U5U6
Indoor unit
U2U1A B
A
Remote
B
controller unit
NOTE
A outdoor unit that is
inter-connected to the
indoor units automatically
becomes the header unit.
Connection of shield wire closed terminal
Indoor unit
Earth
LNU2U1A B
Earth
LN
BA
Indoor power supply
220-240V, 1N ~5Hz
220V, 1N ~60Hz
Earth leakage
breaker
Power switch
Pull box
Remote
controller
Pull box
Address setup
Set up the addresses as per the Installation Manual
supplied with the outdoor unit.
Wiring on the ceiling panel
As per the Installation Manual of the ceiling panel,
connect the connector (2P: Red) of the ceiling panel to
the connector (5P: White) onto the P.C. board within
the electric parts box.
Remote
controller
17
BA
Remote controller
Pull box
BA
[Group control]
7
T
T
T
T
T
T
APPLICABLE CONTROLS
NOTIFICATION
When using the equipment for the first time, the remote controller will not accept any commands for a short
period of time.
• Automatic address
• While automatic addressing no operations can be performed on the remote control.
• Automatic addressing will take a maximum duration of 10 minutes (generally 5 minutes).
• Upon turning on the unit after completion of automatic addressing, a maximum period of
10 minutes (generally 3 minutes) are required prior to the start up operation of the outdoor unit.
All indoor units are shipped from factory as standard. Change if necessary.
To change the setup use the main remote controller (wired remote controller).
* The setup change for wireless remote controller, sub remote controller or a unit without a controller (Centrally
controlled.) is not possible. In such cases, temporarily install a separate main remote controller.
Applicable control setup
Basic operation procedure for setup change
Change the setup while operation of the equipment is stopped.
(Be sure to stop the operation of a set.)
Procedure
1
2
Push the
as shown in the figure.
Check that the displayed item code is [10].
• If the item code indicates any characters other than [10], push the
button to erase the display and retry the operation from the first step.
(For some time after the
of the remote controller cannot be accepted.)
(In a group control, the firstly displayed
indoor unit No. becomes the center unit.)
Each time the
Select the indoor unit that requires a change to the setup.
During this time the indoor unit that is selected can be
confirmed as the louver and fan will be operated.
Using
SET
, CL and
TEMP.
the buttons, select the item code [**].
TES
buttons simultaneously for 4 seconds or more, after a while, the display part flashes
TES
button has been pushed, the operation
UNIT
button is pressed, the indoor unit No. in the group control is displayed consecutively.
Description
3
TIME
buttons, select set data [
SET
button. During this time, if the display changes from flashing to permanently on, the setup is
CL
button clears the set up contents which has been set. In this case, restart from Procedure 2.
TES
TES
button deletes the display and returns the status to the
TES
button. (The setup is configured.)
button has been pushed, the remote
****
].
4
5
6
Using the
Push the
complete.
• To change the setup of an indoor unit that is not selected, restart operation from Procedure 2.
• To change to a different setup within the selected indoor unit, restart operation from Procedure
Pushing the
When the setup is finished, push the
Pushing the
normal stopped status.
(For a period of time after the
controller will not accept any commands.)
6
1
6
CODE No.
UNIT No.
R.C. No.
TEMP.
TIMER SET
FILTER
TEST
RESET
TES
(* The display changes according
to the indoor unit model.)
∗
∗∗
SWING/FIXTIME
SETTING
ON / OFF
FAN
MODE
VENT
UNITSET CL
UNIT No.
R.C. No.
UNIT No.
∗∗∗∗∗
∗
R.C. No.
3
3
2
5
CODE No.
CODE No.
∗∗
.
18
7
APPLICABLE CONTROLS
In case of installation to high ceiling
When the unit is to be installed at a height that exceeds the standard value, adjustment to the air volume is
necessary.
• For the operation procedure, refer to the item “To incorporate a filter sold separately”.
• For the “Setup data” in Procedure 4 , select from the “Installable ceiling height list”.
In case of remote controller-less (Group control)
To set the unit to high ceiling operation, there is a method that requires the changing of the short plugs on the indoor
P.C. board. The details are shown in the below table.
This method is only to be used where a standard wired remote controller (Group control) is not used.
∗ Upon changing the high ceiling setting
• Select setting by the changing of the short plugs
on the indoor P.C. board.
Short plug position
Short
CN112 CN111 CN110
CN112 CN111 CN110
CN112 CN111 CN110
Open
Set
data
0000
0002
0003
Filter sold separately
Standard filter (At shipment)
High ceiling (2)
High ceiling (3)
• Short plug position
(CN112, CN111, CN110 from the left)
19
Change of lighting time of filter sign
Group control
Depending on the conditions of the installation, the
time period of the filter clean sign can be changed.
Follow to the basic operation procedure
(1 → 2 → 3 → 4 → 5 → 6 ).
• For the item code in Procedure 3 , specify [01].
• For the [Set data] in Procedure 4 , select the setup
data of filter sign lighting time from the following
table.
Setup data
0000
0001
0002
0003
0004
Filter sign lighting time
None
150H
2500H (At shipment from factory)
5000H
10000H
Increased heating effect
In a group control, a remote controller can control up
to a maximum of 8 units.
• For cabling procedure and cables of the individual
line (Identical refrigerant line) system, refer to
“Electric work” in this Manual.
• Wiring between indoor units in a group is performed
in the following method.
Connect the indoor units by connecting the remote
ontroller inter-unit cables from the remote controller
terminal blocks (A, B) of the indoor unit connected
with a remote controller to the remote controller
terminal blocks (A, B) of the other indoor unit.
(No polarity)
• For address setup, refer to the Installation Manual
supplied with the outdoor unit.
If it is not possible to achieve satisfactory heating due
to the installation environment or the structure of the
room. The detected temperature can be increased.
Also use a circulator, etc to circulate hot air near the
ceiling.
Follow to the basic operation procedure
(1 → 2 → 3 → 4 → 5 → 6 ).
• For the item code in Procedure 3 , specify [06].
• For the set data in Procedure 4 , select the setup
data of the required temperature shift value from the
below table.
Setup data
0000
0001
0002
0003
0004
0005
0006
Detection temp shift value
No shift
+1°C
+2°C (At shipment from factory)
+3°C
+4°C
+5°C
+6°C
20
8
T
T
TEST RUN
Before test operation
• Before turning on the power supply, carry out the following
procedures.
1) Using 500V-megger, check there is 1MΩ or more between the
terminal block of the power supply and the earth.
If 1MΩ or less is detected, do not run the unit.
2) Check that all the valves of the outdoor unit are fully opened.
• Never push the electromagnetic contactor to carry out a forced test operation.
(It is very dangerous because a protective device does not work.)
To protect the compressor at
startup. Ensure the power supply
is left on for 12 or more hours
before operation.
WARNING
How to execute test operation
• To carry out a fan operation in a single indoor unit, firstly turn off the power supply to the unit. Then short CN72
found on the P.C. board. Once completed turn the power to the unit back on and start the unit in FAN only mode.
Upon completion of the test do not forget to remove the short circuit on CN72.
• Using the remote controller, check the unit is in normal operation. For the operation procedure, refer to the
supplied Owner’s Manual. A forced test operation can be executed in the following procedure under the condition
of thermo.-OFF of room temperature.
In order to prevent the test operation from running continuously, the operation will cease after a period of
60 minutes. The unit will then return back to its original operation.
NOTE
Do not use a forced operation in cases other
than test operation because it applies an
excessive load onto the air conditioner.
In case of wired remote controller
Procedure
TES
button pushed down for 4 seconds or more.
ON / OFF
MODE
button.
button, select the operation mode, [COOL] or [HEAT].
1
2
3
Keep the
[TEST] is displayed on the display part and the selection of the test mode is
permitted.
Push
Using
• Do not run the air conditioner in a mode other than [COOL] or [HEAT].
• The temperature controlling function will not work during the test operation.
• Fault detection will perform as usual.
1, 5
Description
FILTER
RESET
TEMP.
TEST
TIMER SET
ON / OFF
2, 4
FAN
SWING/FIXTIME
UNITSET CL
TEST
MODE
VENT
3
ON / OFF
button to stop the operation.
4
5
After the test operation, push the
(Display part is the same as procedure 1 )
Push the
([TEST] disappears on the display part and the status returns to a normal.)
TES
button to cancel (release from) the test operation mode.
21
In case of wireless remote controller
Procedure
1
2
3
4
Description
Remove a small screw which fixes the nameplate of the receiver unit.
Remove the nameplate of the sensor section by inserting a minus screwdriver, etc into the notch at the bottom
of the plate, and set the Dip switch to [TEST RUN ON].
Execute a test operation with button on the wireless remote controller.
•, , and LED flash during test operation.
• Under status of [TEST RUN ON], the temperature adjustment from the wireless remote controller is invalid.
Do not use this method in the operation other than test operation because the equipment is damaged.
Use either COOL or HEAT operation mode for a test operation.
* The outdoor unit does not operate approx. 3 minutes after power-ON and operation stop.
After the test operation finished, stop the air conditioner from the wireless remote controller, and return Dip
switch of the receiver section as before.
(A 60-minutes timer clearing function is attached to the receiver section in order to prevent a continuous test
operation.)
Small screw
Receiver unit
M4 × 25 screw
(2 pieces)
Notch
Nameplate
Spacer
N
22
E
9
3
2
1
ON / OFF
FAN
TEMP.
SWING/FIXTIME
MODE
VENT
UNITSET CL
FILTER
RESET
TEST
TIMER SET
T
T
CODE No.
UNIT No.
R.C. No.
TROUBLESHOOTING
Confirmation and check
When a fault occurs in the air conditioner, the check
code and the indoor unit No. will appear on the display
part of the remote controller.
The check code will only be displayed while the unit is
in operation.
If the display disappears, operate the air conditioner
according to the following “Confirmation of error
history” for confirmation.
Confirmation of error history
When a fault occurs in the air conditioner, the error
history can be confirmed with the following procedure.
(The error history is stored in memory and can contain
up to 4 errors).
This history can be confirmed from either the operating
status the or the stop status.
CODE No.
UNIT No.
R.C. No.
Check codeIndoor unit No. in which
an error occurred
Procedure
1
2
3
Description
When pushing the
or more, the display similar to the one shown in the figure to the right
will appear.
If [Service Check] is displayed, the fault code will be stored in the
error history mode.
• 01 (Order of error history) is displayed in CODE No. window.
• Check Code is displayed in the CHECK window.
• The indoor unit address, where the fault has occurred will be
displayed in the UNIT No. window.
When pushing the
chronological order.
The numbers displayed within the CODE No. window can vary between 1 and 4. 1 being the most recent fault
and 4 being the oldest.
CAUTION
Do not push the CL button as this will erase all of the error history for that indoor unit.
After confirmation, push the
SET
TES
and
TEMP.
buttons simultaneously for 4 seconds
buttons, the error history stored within the memory will be displayed in
TES
button. This will return the display back to its original mode.
23
Check method
On the remote controller (Main remote controller, Central control remote controller) and the interface P.C. board of
the outdoor unit, a check display LCD (Remote controller) or 7-segment display (on the outdoor interface P.C.
board) operation is provided. Therefore the operation status can be known. Using this self-diagnosis function, a fault
and the location of this fault within the air conditioning system can be located, as shown in the table below.
Check code list
The following list shows each check code. Find the check contents from the list according to part to be checked.
• In case of a fault from the indoor remote controller: See “Main remote controller display” in the list.
• In case of a fault from the outdoor unit: See “Outdoor 7-segment display” in the list.
• In case of a fault from the indoor unit with a wireless remote controller:
See “Sensor block display of receiving unit” in the list.
Comp 1 case ther mo op era tionI/F
Low pressure protective oper ationI/F
Oil level down de tec tive pro tec t ionI/F
Oil leve l de te ct ive t e mp sen sor errorI/F
Comp 2 case ther mo op era tionI/F
Oil leve l de te ct ive c ir cuit error
Magnet switch error
Overcurrent relay opera tion
SIM Indoor center unit duplicatedIndoor
SIM Outdoor line address duplicatedI/F
Duplicated indoor un its with priority
SIM
(Displayed in indo or u ni t w ith pr iority)
Duplicated indoor un its with priority
SIM
(Displayed in uni t o ther th an in door un it w i th p ri ority )
SIM Group line in individual indoor unitI ndoor
SIM Indoor group/Address unsetIndoor , I /F
SIM Indoor capacity unsetIndoor
SIM Outdoor capacity unsetI/F
SIM Duplicated central control addressesAI-NET , Indo or
SIM Over No. of connected outdoor uni tsI/F
SIM No. of IPDU errorI/F
SIM Indoor outside interlockIndoor
MG-SW
Overcurrent rela
IPDU
I/F
MG-SW
Overcurrent relay
I/F
I/F
25
Check codeWireless remote cont rolle r
g
Main
remote
controller
display
P01——11
P03P03—1E
P04P04
P05P05
P07P07
P10P10 Detected indoor addres sOb
P12——11
P13P13—47
P15P15
P17P17—bb
P19P19 Detected outdoor un it nu mberO8
P20P20—22
P22P22
P26P26
P29P29
P31P31—47
———b7By alarm devi ceALT Error in indoor groupAI-NET
———97—AI-NET communication system errorAI-NET
———99—Duplicated network adaptersAI-NET
Outdoor 7-segment display
Auxiliary code
01: Comp. 1 side
02: Comp. 2 side
01: Phase-missing detection
02: Phase error
01: Comp. 1 side
02: Comp. 2 side
01: TS condition
02: TD condition
0[: IGBT short
: Fan motor position
1
[
detective circu it err or
3[: Fan motor trouble
: TH sensor temp. error
C
[
(Heat sink overheat)
D[: TH sensor error
E
: Vdc output error
[
01: Comp. 1 side
02: Comp. 2 side
01: Comp. 1 side
02: Comp. 2 side
AI-NET central
control display
21
AF
IC
AE
1A
14
16
Sensor block display
of receiving unit
Timer Ready Flash
Operation
l
¤¤
l
¤
l
¤
l
¤
l
¤
l
¤¤
l
¤¤
l
¤¤
l
¤
l
¤
l
¤
l
¤
l
¤
l
¤
l
¤
l
¤
Check code nameJudging device
ALT Indoor fan motor errorIndoor
AL T Discharge temp. TD1 errorI/F
¤
ALT High-pressure SW syste m opera t ionIPDU
¤
ALT Phase-missing detection /Phas e e rrorI/F
¤
ALT Heat sink overheat errorIPDU, I/F
¤
ALT Indoor overflow errorIndoor
ALT Indoor fan motor errorIndoor
ALT Outdoor liquid back detection errorI/F
ALT Gas leak detectionI/F
¤
AL T Discharge temp. TD2 errorI/F
¤
ALT 4-way valve inverse errorI/F
¤
ALT High-pressure protective opera tio nI/F
¤
ALT Outdoor fan IPDU errorIP DU
¤
ALT G-TR short protection errorIPDU
¤
ALT Comp position detective circuit system errorIPDU
¤
ALT Other indoor unit error (G roup te r minal u nit error)Indoor
¤
Error detected by TCC-LINK central control device
Check codeWireless remote cont rolle r
Central
control
device
indication
C05————
C06————
C12————
P30
Outdoor 7-segment display
Auxiliary code
Differs accor din g to error c ont ent s o f unit w ith oc cur ren ce o f al ar mGroup control bra nch ing un i t er ror
——(L20 is displayed.)Duplicated central con trol addres ses
AI-NET central
control display
Sensor block display
of receiving unit
Timer Ready Flash
Operation
Terminology
TCC-LINK : TOSHIBA Carriea Cominication Link.
26
Check code nameJudging device
Sending error in TCC-LI NK c entr al c ontr ol
device
Receivin
error in TCC-LINK central control
device
Batch alarm of general-purpose equipment
control interface
TCC-LINK
TCC-LINK
General-purpose equipment
I/F
TCC-LINK
9
TROUBLESHOOTING
New check code
1. Difference between the new check code and the current system
The displaying method of the check code will change from this model onwards.
Used characters
Characteristics of code classification
Block display
Check code in current system
Hexadecimal notation, 2 digits
Few classification of communication/incorrect setup system
Indoor P.C. board, Outdoor P.C. board, Cycle, Communication
Alphabet + Decimal notation, 2 digits
Many classification of communication/incorrect setup system
Communication/Incorrect setup (4 ways), Indoor protection,
Outdoor protection, Sensor, Compressor protection, etc.
Display on sensor part of wireless remote controller
• Block display will show a combination of [] [] [] symbols.
Display on 7-segment in outdoor unit
• Unit No. and check code are displayed.
• In case of error the auxiliary code, check code and sub-code
are displayed alternately.
→
Display
A
C
E
F
H
J
L
P
Classification
Unused
Central control system error
Communication system error
Each sensor error (Failure)
Compressor protective system error
Unused
Setup error, Other errors
Protective device operation
2. Special mention
• When the air conditioner stops and the error is cleared, the check code display on the remote controller will also
disappear.
However, if the error continues after the unit has been stopped, the check code will immediately be displayed
when the unit is restarted.
27
Loading...
+ 115 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.