Please read this Installation Manual carefully before installing the Air Conditioner.
• This Manual describes the installation method of the indoor unit.
• For installation of the outdoor unit, follow the Installation Manual attached to the outdoor unit.
Installation Manual
ADOPTION OF NEW REFRIGERANT
This Air Conditioner is a new type which adopts a new refrigerant HFC (R410A) instead of the
conventional refrigerant R22 in order to prevent destruction of the ozone layer.
• Ensure that all Local, National and International regulations are satisfied.
• Read this “PRECAUTIONS FOR SAFETY” carefully before Installation.
• The precautions described below include the important items regarding safety.
Observe them without fail.
• After the installation work, perform a trial operation (test run) to check for any problem.
Follow the Owner’s Manual to explain how to use and maintain the unit to the customer.
• Turn off the main power supply switch (or breaker) before the unit maintenance.
• Ask the customer to keep the Installation Manual together with the Owner’s Manual.
WARNING
• Ask an authorized dealer or qualified installation professional to install (including moving)/
maintain the air conditioner.
Inappropriate installation may result in water leakage, electric shock or fire.
• Be sure to connect earth wire. (grounding work)
Incomplete grounding cause an electric shock.
Do not connect ground wires to gas pipes, water pipes, lightning rods or ground wires for telephone
wires.
• Turn off the main power supply switch or breaker before attempting any electrical work.
Make sure all power switches are off. Failure to do so may cause electric shock.
• Install the refrigerant pipe securely during the installation work before operating the air
conditioner.
If the air conditioner is operated with the valve open and without the refrigerant pipe, the compressor
sucks air and the refrigeration cycle is over pressurized, which may cause a burst or injury.
• When moving the air conditioner for the installation into another place, be very careful not to
enter any gaseous matter other than the specified refrigerant into the refrigeration cycle.
If air or any other gas is mixed in the refrigerant, the gas pressure in the refrigeration cycle becomes
abnormally high and it resultingly causes pipe burst and injuries on persons.
• Perform installation work properly according to the Installation Manual.
Inappropriate installation may result in water leakage, electric shock or fire.
• When the air conditioner is installed in a small room, provide appropriate measures to ensure
that the concentration of refrigerant leakage occur in the room does not exceed the critical level.
• Install the air conditioner securely in a location where the base can sustain the weight
adequately.
• Perform the specified installation work to guard against an earthquake.
If the air conditioner is not installed appropriately, accidents may occur due to the falling unit.
• If refrigerant gas has leaked during the installation work, ventilate the room immediately.
If the leaked refrigerant gas comes in contact with fire, noxious gas may generate.
• After the installation work, confirm that refrigerant gas does not leak.
If refrigerant gas leaks into the room and flows near a fire source, such as a cooking range, noxious gas
might generate.
• Electrical work must be performed by a qualified electrician in accordance with the Installation
Manual. Make sure the air conditioner uses an exclusive power supply.
An insufficient power supply capacity or inappropriate installation may cause fire.
• Use the specified wires for wiring connect the terminals securely fix.
To prevent external forces applied to the terminals from affecting the terminals.
• Conform to the regulations of the local electric company when wiring the power supply.
Inappropriate grounding may cause electric shock.
3-EN
–3–
SMMS High-Wall Type
• For the refrigerant recovery work (collection of refrigerant from the pipe to the compressor),
stop the compressor before disconnecting the refrigerant pipe.
If the refrigerant pipe is disconnected while the compressor is working with the valve open, the
compressor sucks air and the refrigeration cycle is over pressurized, which may cause a burst or injury.
Installation Manual
CAUTION
New Refrigerant Air Conditioner Installation
• THIS AIR CONDITIONER ADOPTS THE NEW HFC REFRIGERANT (R410A) WHICH DOES NOT
DESTROY OZONE LAYER.
• The characteristics of R410A refrigerant are; easy to absorb water, oxidizing membrane or oil, and its
pressure is approx. 1.6 times higher than that of refrigerant R22. Accompanied with the new refrigerant,
refrigerating oil has also been changed. Therefore, during installation work, be sure that water, dust,
former refrigerant, or refrigerating oil does not enter the refrigerating cycle.
• To prevent charging an incorrect refrigerant and refrigerating oil, the sizes of connecting sections of
charging port of the main unit and installation tools are changed from those for the conventional
refrigerant.
• Accordingly the exclusive tools are required for the new refrigerant (R410A).
• For connecting pipes, use new and clean piping designed for R410A, and please care so that water or
dust does not enter.
To Disconnect the Appliance from Main Power Supply.
• This appliance must be connected to the main power supply by means of a switch with a contact
separation of at least 3 mm.
• The installation fuse must be used for the power supply line of this conditioner.
• Tighten the flare nut with a torque wrench in the specified manner.
Excessive tightening of the flare nut may cause a crack in the flare nut after a long period, which may
result in refrigerant leakage.
• Wear heavy gloves and a long sleeve shirt during the installation work to avoid injury.
EN
–4–
4-EN
SMMS High-Wall Type
Installation Manual
3SELECTION OF INSTALLATION PLACE
WARNING
• Install the air conditioner at enough strong place to withstand the weight of the unit.
If the strength is not enough, the unit may fall down resulting in injury.
CAUTION
• Do not install the air conditioner in a location subject to a risk of exposure to a combustible gas.
If a combustible gas leaks and stays around the unit, a fire may occur.
Upon approval of the customer, install the air conditioner in a place that satisfies the
following conditions.
• Place where the unit can be installed horizontally.
• Place where a sufficient servicing space can be ensured for safety maintenance and check.
• Place where drained water will not cause any problem.
Avoid installing in the following places.
• Place exposed to air with high salt content (seaside area), or place exposed to large quantities of sulfide
gas (hot spring).
(Should the unit be used in these places, special protective measures are needed.)
• A restaurant kitchen where a lot of oil is used or place near machines in a factory (Oil adhering to the
heat exchanger and resin part (cross flow fan) in the indoor unit may reduce the performance, generate
mist or dew drop, or deform or damage resin parts.)
• Place where organic solvent is used nearby.
• Place close to a machine generating high frequency.
• Place where the discharged air blows directly into the window of the neighbour house. (Outdoor unit)
• Place where noise of the outdoor unit is easily transmitted.
(When install the outdoor unit on the boundary with the neighbour, pay due attention to the level of noise.)
• Place with poor ventilation.
• Do not use the air conditioner for special purposes such as preserving food, precision instruments, or art
objects, or where breeding animals or growing plants are kept. (This may degrade the quality of
preserved materials.)
• Place where any of high-frequency appliances (including inverter devices, private power generators,
medical equipment, and communication equipment) and inverter-type fluorescent light is installed.
(A malfunction of the air conditioner, abnormal control, or problems due to noise to such appliances/
equipment may occur.)
• When the wireless remote controller is used in a room equipped with an inverter-type fluorescent light or
at a place exposed to direct sunlight, signals from the remote controller may not be received correctly.
• Place where organic solvent is used.
• Place near a door or window exposed to humid outside air (Dew dropping may form.).
• Place where special spray is used frequently.
5-EN
–5–
SMMS High-Wall Type
Installation diagram of Indoor and outdoor units
Before installing the
wireless remote
controller
1.Remove the battery
cover.
2.Insert 2 new
batteries (R03 [AAA]
type) following the
(+) and (–) positions.
Wireless
remote controller
Cover
A
C
L
Batteries
Batteries
Wireless remote
control
8
5
0
m
m
(
A
tta
c
h
to
th
Pan head wood
screw
*
2
o
r
m
o
r
e
*1
Hook
A
i
r
f
i
l
t
e
r
e
fr
o
nt
pa
n
e
l
.)
Remote control
holder
Hook
Installation plate
110mm or more
1
7
0
m
m
o
r
m
Shield pipe
Heat
insulator
o
r
e
Installation Manual
For the rear left and left piping
Wall
Insert the cushion between the
indoor unit and wall, and tilt the
indoor unit for better operation.
Do not allow the drain hose to get
slack.
Cut the piping hole
sloped slightly.
Make sure to run the drain hose
sloped downward.
The auxiliary piping can be
connected to the left, rear left, rear
right, right, bottom right or bottom
left.
Right
Rear right
Bottom right
Rear left
Bottom left
Left
EN
Installation space
The indoor unit shall be installed so that its top surface comes at a height of 2m or more.
Also it must be avoided to put anything on top of the indoor unit.
*1 Reserve space required to install the indoor unit and for service work.
Keep 110mm or more for clearance between top plate of the indoor unit and the ceiling surface.
*2 Provide a space as shown for service clearance for the cross flow fan.
Installation place
• A place which provides the spaces around the indoor unit as shown in the above diagram.
• A place where there is no obstacle near the air inlet and outlet.
• A place that allows easy installation of the piping to the outdoor unit.
• A place which allows the front panel to be opened.
CAUTION
• Direct sunlight to the indoor unit’ s wireless receiver should be avoided.
• The microprocessor in the indoor unit should not be too close to RF noise sources.
(For details, see the owner’ s manual.)
–6–
6-EN
SMMS High-Wall Type
Installation Manual
Wireless remote controller
• A place where there are no obstacles such as a curtain that may block the signal from the indoor unit.
• Do not install the remote controller in a place exposed to direct sunlight or close to a heating source, such
as a stove.
• Keep the remote controller at least 1m apart from the nearest TV set or stereo equipment.
(This is necessary to prevent image disturb-bounces or noise interference.)
• The location of the remote controller should be determined as shown below.
Indoor unit
(Side view)(Top view)
7
m
°
5
7
Reception
range
Indoor unit
Reception range
Remote controller
* : Axial distance
5 m
4
5
m
°
5
5
4
°
Remote controller
* 7 m
4INSTALLATION OF INDOOR UNIT
WARNING
Install the air conditioner certainly to sufficiently withstand the weight.
If the strength is insufficient, the unit may fall down resulting in human injury.
Perform a specified installation work to guard against strong wind or earthquake.
An incomplete installation can cause accidents by the units falling and dropping.
REQUIREMENT
Strictly comply with the following rules to prevent damage of the indoor units and human injury.
• Do not put a heavy article on the indoor unit. (Even units are packaged)
• Carry in the indoor unit as it is packaged if possible. If carrying in the indoor unit unpacked by necessity,
be sure to use buffering cloth, etc. to not damage the unit.
• To move the indoor unit, do not apply force to the refrigerant pipe, drain pan, foamed parts, or resin
parts, etc.
• Carry the package by two or more persons, and do not bundle it with plastic band at positions other than
specified.
Be careful to the following items when installing the unit.
• Considering air discharge direction, select an installation place where discharge air can circulate evenly
in a room. Avoid to install the unit at place with “NO GOOD” mark in the right figure.
OKNO GOOD
Bad installation place
: Not cooled well.
Screen
7-EN
Good installation place
Cooled well all over.
–7–
SMMS High-Wall Type
Installation Manual
5CUTTING A HOLE AND MOUNTING INSTALLATION
PLATE
Cutting a hole
In case of installing the refrigerant pipes from the
rear:
1. Decide the hole position for piping at
180mm from the arrow mark (Ö) on the
installation plate and drill a hole at a slight
downward slant toward outdoor side.
Pipe hole; dia.65mm: AP007-AP018 type
Pipe hole; dia.80mm: AP024 type
80
65
1111012101
23mm
180mm
Pipe hole
dia. 65mm:
AP007-AP018 type
dia. 80mm:
AP024 type
80
65
1111012101
The centre of the pipe hole is above the arrow
NOTE
• When drilling a wall that contains a metal lath,
wire lath or metal plate, be sure to use a pipe
hole brim ring sold separately.
When the installation plate is
directly mounted on the wall
1. Securely fit the installation plate onto the
wall by screwing it in the upper and lower
parts to hook up the indoor unit.
2. To mount the installation plate on a
concrete wall with anchor bolts, utilize the
anchor bolt holes as illustrated in the above
figure.
3. Install the installation plate horizontally in
the wall.
CAUTION
When installing the installation plate with a
mounting screw, do not use the anchor bolt hole.
Otherwise the unit may fall down and result in
personal injury and property damage.
NO
GOOD
5mm dia. hole
OKNO
GOOD
Clip anchor
(local parts)
Anchor bolt
Projection
15mm or less
Mounting screw
4 × 25
EN
Mounting the installation plate
Be sure that the installation plate is fix to the wall
with screws to make the indoor unit fit to the wall.
Pipe hole
Hook
170
85
Indoor unit
Anchor bolt holes
Hook
Thread
Hook
Mounting
Screw
Weight
50
132
23
dia.65mm
Pipe hole
(dia. 65mm
dia. 80mm)
Installation
plate
40
170
CAUTION
Failure to firmly install the unit may result in
personal injury and property damage if the unit
falls.
• In case of block, brick, concrete or similar type
walls, make 5mm dia. holes in the wall.
• Insert clip anchors for appropriate mounting
screws.
2m or more from floor
NOTE
• Secure four corners and lower parts of the
installation plate with 6 mounting screws to
install it.
–8–
8-EN
SMMS High-Wall Type
Installation Manual
6PIPING AND DRAIN HOSE INSTALLATION
Piping and drain hose forming
* Apply heat-insulation for both refrigerant pipe and drain hose surely so that no dew generates inside of
the equipment. (Use polyethylene foam for insulating material.)
Rear right
Rear left
Bottom left
Left
Bottom right
Right
Removing
front panel
Die-cutting
front panel
slit
Changing
drain hose
Piping
preparation
1. Remove the front panel
The front panel must be removed for piping
Air inlet grille
connections in the left, bottom left, and rear
left directions.
Front panel
• Open the air inlet grille upward.
• Remove the four screws securing the
front panel.
• Slightly open the lower part of the front
panel, and then pull the upper part of the
front panel toward you to remove it from
2
1
3
the rear plate.
2. Die-cutting front panel slit
Cut out the slit on the leftward or right side of the front panel for the left or right connection and the slit on
the bottom left or right side of the front panel for the bottom left or right connection with a pair of nippers.
3. Changing drain hose
For leftward connection, bottom-leftward connection and rear leftward connection's piping, it is necessary
to change the drain hose and drain cap.
Without changing the drain hose position, the indoor unit will not fit to the wall.
How to remove the drain hose
• The drain hose can be removed by removing the screw securing the drain hose
and then pulling out the drain hose.
• When removing the drain hose, be careful of any sharp edges of steel plate. The
edges can injuries.
• To install the drain hose, insert the drain hose firmly until the connection part
contacts with heat insulator, and the secure it with original screw.
Heat insulator
Drain hose
9-EN
–9–
SMMS High-Wall Type
How to remove the drains cap
Clip the drain cap by needle-nose pliers and pull out.
How to fix the drains cap
1) Insert hexagonal wrench (dia. 4mm) in a centre head.
4mm
2) Firmly insert drains cap.
No gap
Installation Manual
Do not apply lubricating oil (refrigerant
machine oil) when inserting the drain cap.
Insert a hexagon
wrench (4 mm)
Application causes deterioration and drain
leakage from the plug.
CAUTION
Firmly insert the drain hose and drain cap; otherwise, water may leak.
How to remove the drain hose
1) Remove the front panel.
2) Remove the screws of drain hose.
3) Pull out the drain hose.
▼ In case of right or left piping
• After scribing slits of the front panel with a knife or a marking-off pin, cut them with a pair of nippers or an
equivalent tool.
How to fix the drain hose
1) Put the drain hose.
2) Screw the drain hose to the indoor unit.
3) Install the front panel.
EN
Slit
–10–
10-EN
SMMS High-Wall Type
Installation Manual
▼ In case of bottom right or bottom left piping
• After scribing slits of the front panel with a knife or a marking-off pin, cut them with a pair of nippers or an
equivalent tool.
Slit
▼ Left-hand connection with piping
Bend the connecting pipe so that it is laid within 43mm above the wall surface. If the connecting pipe is laid
exceeding 43mm above the wall surface, the indoor unit may unstably be set on the wall. When bending
the connecting pipe, make sure to use a spring bender so as not to crush the pipe.
Bend the connection pipe within a radius of 30 mm.
To connect the pipe after installation of the unit (figure)
(To the fore front of flare)
570mm
420mm
43mm
R 30 mm (Use polish polyethylene core
or the like for bending pipe.)
°
0
8
Gas side
Liquid side
Outward form of indoor unit
Use the handle of screwdriver, etc.
NOTE
If the pipe is bent incorrectly, the indoor unit may unstably be set on the wall.
After passing the connecting pipe through the pipe hole, connect the connecting pipe to the auxiliary pipes
and wrap the facing tape around them.
CAUTION
• Bind the auxiliary pipes (two) and power supply wiring and control wiring with facing tape tightly. In case
of leftward piping and rear leftward piping, bind the auxiliary pipes (two) only with facing tape.
Indoor unit
Auxiliary pipes
Installation plate
Power supply wiring
Control wiring
11-EN
• Carefully arrange pipes so that any pipe does not stick out of the rear plate of the indoor unit.
• Carefully connect the auxiliary pipes and connecting pipes to one another and cut off the insulating tape
wound on the connecting pipe to avoid double-taping at the joint, moreover, seal the joint with the vinyl
tape, etc.
• Since dew results in a machine trouble, make sure to insulate both the connecting pipes.
(Use polyethylene foam as insulating material.)
• When bending a pipe, carefully do it, not to crush it.
–11–
SMMS High-Wall Type
Installation Manual
7INDOOR UNIT FIXING
1. Pass the pipe through the hole in the wall,
and hook the indoor unit on the installation
plate at the upper hooks.
2. Swing the indoor unit to right and left to
confirm that it is firmly hooked up on the
installation plate.
3. While pressing the indoor unit onto the wall,
hook it at the lower part on the installation
plate. Pull the indoor unit toward you to
confirm that it is firmly hooked up on the
installation plate.
Hook here
1
Installation plate
2
Hook
Press
(unhook)
• For detaching the indoor unit from the installation
plate, pull the indoor unit toward you while
pushing its bottom up at the specified parts.
8DRAINAGE
1. Run the drain hose sloped downwards.
NOTE
• Hole should be made at a slight downward slant
on the outdoor side.
2. Put water in the drain pan and make sure
that the water is drained out of doors.
3. When connecting extension drain hose,
insulate the connecting part of extension
drain hose with shield pipe.
Do not rise the drain hose.
50 mm
or more
Do not put the
drain hose end
into water.
Shield pipe
Do not form the drain hose
into a wavy shape.
Do not put the
drain hose end
in the drainage
ditch.
EN
PushPush
REQUIREMENT
The lower part of indoor unit may float, due to the
condition of piping and you cannot fix it to the
installation plate. In that case, use the screws
provided to fix the unit and the installation plate.
Especially when the pipes are pulled out from
the left side, the unit must be screwed to the
installation plate.
screwscrew
Drain hose
Inside the
room
Extension drain hose
CAUTION
Arrange the drain pipe for proper drainage from
the unit.
Improper drainage can result in dew-dropping.
This air conditioner has the structure designed to
drain water collected from dew, which forms on the
back of the indoor unit, to the drain pan.
Therefore, do not store the power cord and other
parts at a height above the drain guide.
Wall
Drain guide
Space for pipes
–12–
12-EN
SMMS High-Wall Type
9REFRIGERANT PIPING
Installation Manual
Refrigerant Piping
1. Use copper pipe with 0.8 mm or more
thickness. (In case pipe size is dia. 15.9,
with 1.0mm or more.)
2. Flare nut and flare works are also different
from those of the conventional refrigerant.
Take out the flare nut attached to the main
unit of the air conditioner, and use it.
REQUIREMENT
When the refrigerant pipe is long, provide support
brackets at intervals of 2.5 to 3m to clamp the
refrigerant pipe. Otherwise, abnormal sound may
be generated.
CAUTION
IMPORTANT 4 POINTS FOR PIPING WORK
1. Remove dust and moisture from the inside of
the connecting pipes.
2. Tight connection (between pipes and unit)
3. Evacuate the air in the connecting pipes using
VACUUM PUMP.
4. Check the gas leakage. (Connected points)
Pipe size
(dia.: mm)
MMK-
Gas side9.512.715.9
Liquid
side
AP007 to
AP012 type
6.46.49.5
AP015 to
AP018 type
AP024 type
Permissible Piping Length and
Height Difference
They vary according to the outdoor unit.
For details, refer to the Installation Manual attached
to the outdoor unit.
Flaring
• Cut the pipe with a pipe cutter.
Remove burrs completely.
Remaining burrs may cause gas leakage.
• Insert a flare nut into the pipe, and flare the pipe.
As the flaring sizes of R410A differ from those of
refrigerant R22, the flare tools newly
manufactured for R410A are recommended.
However, the
conventional tools can
be used by adjusting
projection margin of the
copper pipe.
▼ Projection margin in flaring: B (Unit: mm)
Rigid (Clutch type)
Outer dia. of
copper pipe
6.4 , 9.5
12.7 , 15.9
R410A tool used
R410AR410A
0 to 0.51.0 to 1.5
Conventional
tool used
▼ Flaring dia. meter size: A (Unit: mm)
0
+
A
Outer dia. of copper pipe
6.49.1
9.513.2
12.716.6
15.919.7
-0.4
R410A
B
13-EN
* In case of flaring for R410A with the
conventional flare tool, pull it out
approx.
0.5 mm more than that for R22 to
adjust to the specified flare size.
The copper pipe gauge is useful for
adjusting projection margin size.
–13–
A
SMMS High-Wall Type
Installation Manual
Tightening connection
CAUTION
• Do not apply excessive torque. Otherwise, the
nut may crack depending on the conditions.
(Unit: N•m)
Outer dia. of copper pipeTightening torque
6.4 mm (dia.)14 to 18 (1.4 to 1.8 kgf•m)
9.5 mm (dia.)33 to 42 (3.3 to 4.2 kgf•m)
12.7 mm (dia.)50 to 62 (5.0 to 6.2 kgf•m)
15.9 mm (dia.)68 to 82 (6.8 to 8.2 kgf•m)
▼ Tightening torque of flare pipe connections
Pressure of R410A is higher than that of R22.
(Approx. 1.6 times) Therefore, using a torque
wrench, tighten the flare pipe connecting sections
which connect the indoor and outdoor units of the
specified tightening torque.
Incorrect connections may cause not only a gas
leak, but also a trouble of the refrigeration cycle.
Align the centres of the connecting pipes and
tighten the flare nut as far as possible with your
fingers. Then tighten the nut with a spanner and
torque wrench as shown in the figure.
Heat insulation
Heat insulation for the pipes should be done
separately for the liquid side and gas side. Because
both of the liquid and gas side pipes become a low
temperature during cooling operation, sufficient
heat insulation should be done to prevent
condensation.
• Heat insulator with a heat resistance of 120°C or
more must be used for the gas side pipe.
• The pipe connection section of the indoor unit
must be heat insulated securely and compactly
with the attached heat insulator.
Fix with vinyl tape
Heat insulator
(attached)
Local side pipe
Airtight test/Air purge, etc.
For airtight test, air purge, addition of refrigerant,
and gas leak check, follow the Installation Manual
attached to the outdoor unit.
EN
Work using double spanner
REQUIREMENT
Tightening with an excessive torque may crack the
nut depending on installation conditions.
Tighten the nut within the specified tightening
torque.
Piping with outdoor unit
• Shape of valve differs according to the outdoor
unit.
For details of installation, refer to the Installation
Manual of the outdoor unit.
Open fully valves of the outdoor
unit
Gas leak check
Check with a leak detector or soap water whether
gas leaks or not, from the pipe connecting section
or cap of the valve.
REQUIREMENT
Use a leak detector manufactured exclusively HFC
refrigerant (R410A, R134a, etc.).
–14–
14-EN
SMMS High-Wall Type
10 ELECTRIC WORK
WARNING
1. Using the specified wires, ensure to
connect the wires, and fix wires securely so
that the external tension to the wires do not
affect the connecting part of the terminals.
Incomplete connection or fixation may cause a
fire, etc.
2. Be sure to connect earth wire. (grounding
work)
Incomplete grounding cause an electric shock.
Do not connect ground wires to gas pipes,
water pipes, lightning rods or ground wires for
telephone wires.
3. Appliance shall be installed in accordance
with national wiring regulations.
Capacity shortage of power circuit or
incomplete installation may cause an electric
shock or a fire.
Installation Manual
• Run the refrigerant piping line and control wiring
line in the same line.
• Do not turn on the power of the indoor unit until
vacuuming of the refrigerant pipes completes.
CAUTION
• If incorrect/incomplete wiring is carried out, it
will cause an electrical fire or smoke.
• Be sure to install an earth leakage breaker that
is not tripped by shock waves.
If an earth leakage breaker is not installed, an
electric shock may be caused.
• Be sure to use the cord clamps attached to the
product.
• Do not damage or scratch the conductive core
and inner insulator of power and interconnecting wires when peeling them.
• Use the power cord and Inter-connecting wire
of specified thickness, type, and protective
devices required.
• Never connect 220–240V power to the terminal
blocks (, , , , etc.) for control
wiring.
(Otherwise, the system will fail.)
REQUIREMENT
• For power supply wiring, strictly conform to the
Local Regulation in each country.
• For wiring of power supply of the outdoor units,
follow the Installation Manual of each outdoor
unit.
• Perform the electric wiring so that it does not
come to contact with the high-temperature part
of the pipe.
The coating may melt resulting in an accident.
• After connecting wires to the terminal blocks,
provide a trap and fix wires with the cord clamp.
AB
15-EN
–15–
SMMS High-Wall Type
Installation Manual
Power supply wire and communication wires specifications
Power supply wire and communication wires are procured locally.
For the power supply specifications, follow the table below. Power supply wiring and communication wiring
are to be procured locally.
For specifications of the power capacity of the outdoor unit and the power supply wires, refer to the
Installation Manual supplied with the outdoor unit.
Indoor unit power supply
• Prepare an exclusive power supply for the indoor unit independently of the outdoor unit.
• Arrange the power supplies to the indoor and outdoor units, so that a common earth leakage breaker and
main switch can be used.
• Power supply wire specification: Cable 3-core 2.5mm², in conformity with Design H07 RN-F or 60245 IEC 57.
▼ Power supply
Power supply
Power supply switch/Earth leakage breaker or power supply wiring/fuse rating for indoor units should be selected by
the accumulated total current values of the indoor units.
Power supply wiringBelow 50m 2.5 mm²
Control wiring, Central controller wiring
• Use a 2 core non polarity wire.
• To prevent any possible noise issues, use a shielded 2 core wire.
• The total stated length of communication wiring is determined by the interconnecting length of indoor to
outdoor wire plus the length of the central control communication wire.
220–240V ~ 50Hz
220V ~ 60Hz
EN
▼ Communication line
Control wiring between indoor units, and outdoor
unit (2-core shield wire)
Central control line wiring (2-core shield wire)Wire size
Wire size
(Up to 1000m) 1.25 mm²
(Up to 2000m) 2.0 mm²
(Up to 1000m) 1.25 mm²
(Up to 2000m) 2.0 mm²
Wired remote controller wiring
This wiring is not required when using the supplied wireless remote controller.
• For wiring remote controllers a 2 core non polarity wire must be used.
Total wire length of wired remote controller wiring and remote
controller inter-unit wiring = L + L1 + L2 + … Ln
Total wire length of wired remote controller inter-unit wiring = L1 + L2 + … LnUp to 200m
In case of wired type onlyUp to 500m
In case of wireless type includedUp to 400m
CAUTION
The remote controller wire (Communication line) and AC220–240V wires cannot be parallel to contact
each other and cannot be stored in the same conduits. If doing so, a trouble may be caused on the control
system due to noise, etc.
–16–
16-EN
SMMS High-Wall Type
Installation Manual
Wired remote
controller
wiring
Indoor unit
Wired remote
controller
L1L2Ln
Remote controller inter-unit wiring
Indoor unitIndoor unitIndoor unit
(Max. 8 units)
Control wiring between indoor and outdoor units
NOTE
An outdoor unit that is interconnected to the indoor units automatically becomes the header unit.
▼ Wiring example
Outdoor Power supply
380V-415V ~, 50Hz
380V ~, 60Hz
Earth
terminal
Earth leakage
breaker
Header outdoor unitFollower outdoor unit
U1 U2 U3 U4L1 L2 L3 NU5 U6
Outdoor Power supply
380V-415V ~, 50Hz
380V ~, 60Hz
Earth
terminal
Earth leakage
breaker
U1 U2 U3 U4L1 L2 L3 NU5 U6
Control wiring between outdoor units
EarthEarth
U1 U2L NA B
A B
Remote controllerRemote controller
U1 U2L NA B
A B
Indoor unitIndoor unitIndoor unitIndoor unit
EarthEarth
Indoor power supply
220-240V, ~, 50Hz
220V ~, 60Hz
Earth leakage
breaker power
switch
Control wiring between indoor and outdoor units
Control wiring between indoor units
U1 U2
L NA B
A B
Remote controller
Pull boxPull boxPull box
Address setup
Set up the addresses as per the Installation Manual supplied with the outdoor unit.
U1 U2L NA B
17-EN
–17–
SMMS High-Wall Type
Installation Manual
Wired remote controller wiring
• As the wired remote controller wire has non-polarity, there is no problem if connections to indoor unit
terminal blocks A and B are reversed.
▼ Wiring diagram
Terminal block for
remote controller
wiring of indoor unit
Terminal block
A
B
Wired remote controller wire
(Procured locally)
A
B
Wired remote
controller unit
EN
–18–
18-EN
SMMS High-Wall Type
Installation Manual
Wiring Connection
How to connect the power supply wiring
and control wiring
The power supply wire and the control wire can be
connected without removing the front panel.
REQUIREMENT
Connect the power supply wire after connecting the
control wire for this model.
1. Remove the air inlet grille.
Open the air inlet grille upward and pull it
toward you.
2. Remove the terminal cover and the clamp
base.
3. Insert the power supply wire and control
wire (according to the local rule) into the
pipe hole on the wall.
4. Take the power supply wire out of the cable
slot on the rear panel so that it protrudes
about 150mm from the front.
5. Insert the control wire fully into the control/
wired remote controller terminal block ,
, , and secure it tightly with screws.
AB
6. Clamp the control wire with the cord clamp.
7. Install the clamp base with a screw.
8. Insert the power supply wire fully into the
terminal block and secure it tightly with
screws. Tightening torque: 1.2 N·m (0.12
kgf·m) Secure the earth line with the earth
screw.
9. Clamp the power supply wire with the cord
clamp.
10.Attach the terminal cover and the air inlet
grille to the indoor unit.
CAUTION
• Be sure to refer to the wiring diagram attached
inside the front panel.
• Check local electrical cords and also any
specific wiring instructions and limitations.
• Do not catch the control wire when installing the
clamp base.
Power supply terminal block
Terminal block for
communication/remote
controller wiring
Terminal
Cover
Screw
Power
supply wire
about
150mm
<Stripping length of the power supply wire>
Terminal block
for control/
wired remote
controller wiring
Control wire
Cord clamp
Power
supply
terminal
block
Cord
clamp
Screw
N
L
U1U2A
Clamp base
95mm
20mm
10mm
R(L)
B
R(L)
S(N)
Screw
Earth screw for
power supply wire
<Connecting control wire>
R(L) S(N)
R(L)
S(N)
Earth screw
Earth line
75mm
S(N)
Earth
wire for
shield
wire
Earth screw for
shield wire
19-EN
Terminal
block
for control/
wired remote
controller
wiring
Cord
clamp
<Connecting wired remote controller wire>
U1 U2 A
B
Wired
remote
controller
wire
–19–
Cord clamp
2
Power supply wire
<Connecting power supply wire>
ABU1U
Earth screw
Earth
wire for
power
supply
wire
Clamp
base
SMMS High-Wall Type
Installation Manual
Wiring connection for flow selector unit
How to connect the wiring of flow selector unit
Connect the power supply wire and the communication wire supplied with the flow selector unit to the indoor
unit.
1. Remove the air inlet grille.
Open the air inlet grille upward and pull it toward you.
2. Remove the four screws securing the front panel.
3. Slightly open the lower part of the front panel, and then pull the upper part of the front panel
toward you to remove it from the rear plate.
4. Remove the terminal cover and the clamp base.
5. Insert the control wire fully into the control/wired remote controller terminal block and secure
it tightly with screws.
6. Connect the control wire connector of the flow selector unit to the lead with a connector to the
left of the control/wired remote controller terminal block.
7. Clamp the control wire and the control wire of the flow selector unit with the cord clamp.
8. Install the clamp base with a screw.
9. Insert the power supply wire fully into the terminal block and secure it tightly with screws.
Tightening torque: 1.2 N·m (0.12 kgf·m)
Secure the earth line with the earth screw.
10.Clamp the power supply wire with the cord clamp.
11.Insert the power supply wire fasten terminal of the flow selector unit into the power supply
terminal.
Secure the earth line with the earth screw.
12.Clamp the power supply wire of the flow selector unit tight with the cord clamp.
13.Attach the terminal cover, the front panel and the air inlet grille to the indoor unit.
Power supply
terminal block
EN
R(L)
Control wire
from the
flow selector
Control wire
Terminal
block for
control/wired
remote
controller
wiring
Connector
Cord clamp
S(N)
2
ABU1U
Power supply wire
Earth screw
for flow
selector unit
Cord clamp
Power
supply wire
of flow
selector unit
CAUTION
Confirm that every wires are stored in the electric parts box without getting caught before attaching the
terminal cover.
–20–
20-EN
Loading...
+ 46 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.