Toshiba MMD-AP0074SPH-E, MMD-AP0094SPH-E, MMD-AP0124SPH-E, MMD-AP0154SPH-E, MMD-AP0184SPH-E Installation Manual

Page 1
Installation Manual
English
Indoor Unit
Model name:
Slim Duct Type
MMD-AP0074SPH-E MMD-AP0094SPH-E MMD-AP0124SPH-E MMD-AP0154SPH-E MMD-AP0184SPH-E
AIR CONDITIONER (MULTI TYPE)
Page 2
– 1 –
SMMS Slim Duct Type
Installation Manual
SMMS Slim Duct Type
Installation Manual
Original instruction
Contents
1 Precautions for Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2 Accessory Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
3 Selection of Installation Place . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
4 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
5 Drain Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
6 Duct Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
7 Refrigerant Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
8 Electrical Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
9 Applicable Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
10 Test Run . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
11 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
12 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
13 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Please read this Installation Manual carefully before installing the Air Conditioner.
• This Manual describes the installation method of the indoor unit.
• For installation of the outdoor unit, follow the Installation Manual attached to the outdoor unit.
ADOPTION OF NEW REFRIGERANT
This Air Conditioner uses R410A an environmentally friendly refrigerant.
Thank you for purchasing this Toshiba air conditioner. Please read carefully through these instructions that contain important information which complies with the “Machinery” Directive (Directive 2006/42/EC), and ensure that you understand them. After completing the installation work, hand over this Installation Manual as well as the Owner’s Manual attached to the outdoor unit provided with the outdoor unit to the user, and ask the user to keep them in a safe place for future reference.
Generic Denomination: Air Conditioner
Definition of Qualified Installer or Qualified Service Person
The air conditioner must be installed, maintained, repaired and removed by a qualified installer or qualified service person. When any of these jobs is to be done, ask a qualified installer or qualified service person to do them for you. A qualified installer or qualified service person is an agent who has the qualifications and knowledge described in the table below.
Agent Qualifications and knowledge which the agent must have
Qualified installer
• The qualified installer is a person who installs, maintains, relocates and removes the air conditioners made by Toshiba Carrier Corporation. He or she has been trained to install, maintain, relocate and remove the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such operations by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to these operations.
• The qualified installer who is allowed to do the electrical work involved in installation, relocation and removal has the qualifications pertaining to this electrical work as stipulated by the local laws and regulations, and he or she is a person who has been trained in matters relating to electrical work on the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work.
• The qualified installer who is allowed to do the refrigerant handling and piping work involved in installation, relocation and removal has the qualifications pertaining to this refrigerant handling and piping work as stipulated by the local laws and regulations, and he or she is a person who has been trained in matters relating to refrigerant handling and piping work on the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work.
• The qualified installer who is allowed to work at heights has been trained in matters relating to working at heights with the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work.
Qualified service person
• The qualified service person is a person who installs, repairs, maintains, relocates and removes the air conditioners made by Toshiba Carrier Corporation. He or she has been trained to install, repair, maintain, relocate and remove the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such operations by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to these operations.
• The qualified service person who is allowed to do the electrical work involved in installation, repair, relocation and removal has the qualifications pertaining to this electrical work as stipulated by the local laws and regulations, and he or she is a person who has been trained in matters relating to electrical work on the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work.
• The qualified service person who is allowed to do the refrigerant handling and piping work involved in installation, repair, relocation and removal has the qualifications pertaining to this refrigerant handling and piping work as stipulated by the local laws and regulations, and he or she is a person who has been trained in matters relating to refrigerant handling and piping work on the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work.
• The qualified service person who is allowed to work at heights has been trained in matters relating to working at heights with the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work.
1-EN 2-EN
Page 3
– 2 –
SMMS Slim Duct Type
Installation Manual
EN
SMMS Slim Duct Type
Installation Manual
Definition of Protective Gear
When the air conditioner is to be transported, installed, maintained, repaired or removed, wear protective gloves and ‘safety’ work clothing. In addition to such normal protective gear, wear the protective gear described below when undertaking the special work detailed in the table below. Failure to wear the proper protective gear is dangerous because you will be more susceptible to injury, burns, electric shocks and other injuries.
Work undertaken Protective gear worn
All types of work
Protective gloves ‘Safety’ working clothing
Electrical-related work
Gloves to provide protec tion for electricians and from h eat Insulating shoes Clothing to provide protection from electr ic shock
Work done at heights (50 cm or more)
Helmets for use in industry
Transportation of heavy objects
Shoes with additional protective toe cap
Repair of outdoor unit Gloves to provide protection for electricians and from heat
Warning indications on the air conditioner unit
Warning indication Description
WARNING
ELECTRICAL SHOCK HAZARD
Disconnect all remote electric power supplies before servicing.
WARNING
Moving parts. Do not operate unit with grille removed. Stop the unit before the servicing.
CAUTION
High temperature parts. You might get burned when removing this panel.
CAUTION
Do not touch the aluminium fins of the unit. Doing so may result in injury.
CAUTION
BURST HAZARD
Open the service valves before the operation, otherwise there might be the burst.
WARNING
ELECTRICAL SHOCK HAZARD
Disconnect all remote electric power supplies before servicing.
WARNING
Moving parts. Do not operate unit with grille removed. Stop the unit before the servicing.
CAUTION
High temperature parts. You might get burned when removing this panel.
CAUTION
Do not touch the aluminum fins of the unit. Doing so may result in injury.
CAUTION
BURST HAZARD
Open the service valves before the operation, otherwise there might be the burst.
3-EN 4-EN
Page 4
– 3 –
SMMS Slim Duct Type
Installation Manual
SMMS Slim Duct Type
Installation Manual

1 Precautions for Safety

The manufacturer shall not assume any liability for the damage caused by not observing the description of this manual.
WARNING
General
• Before starting to install the air conditioner, read through the Installation Manual carefully, and follow its instructions to install the air conditioner.
• Only a qualified installer or service person is allowed to do installation work. Inappropriate installation may result in water leakage, electric shock or fire.
• Do not use any refrigerant different from the one specified for complement or replacement. Otherwise, abnormally high pressure may be generated in the refrigeration cycle, which may result in a failure or explosion of the product or an injury to your body.
• Before opening the intake grille of the indoor unit or service panel of the outdoor unit, set the circuit breaker to the OFF position. Failure to set the circuit breaker to the OFF position may result in electric shocks through contact with the interior parts. Only a qualified installer(*1) or qualified service person(*1) is allowed to remove the intake grille of the indoor unit or service panel of the outdoor unit and do the work required.
• Before carrying out the installation, maintenance, repair or removal work, set the circuit breaker to the OFF position. Otherwise, electric shocks may result.
• Place a “Work in progress” sign near the circuit breaker while the installation, maintenance, repair or removal work is being carried out. There is a danger of electric shocks if the circuit breaker is set to ON by mistake.
• Only a qualified installer(*1) or qualified service person(*1) is allowed to undertake work at heights using a stand of 50 cm or more or to remove the intake grille of the indoor unit to undertake work.
• Wear protective gloves and safety work clothing during installation, servicing and removal.
• Do not touch the aluminium fin of the unit. You may injure yourself if you do so. If the fin must be touched for some reason, first put on protective gloves and safety work clothing, and then proceed.
• Do not climb onto or place objects on top of the outdoor unit. You may fall or the objects may fall off of the outdoor unit and result in injury.
• When work is performed at heights, use a ladder which complies with the ISO 14122 standard, and follow the procedure in the ladder’s instructions. Also wear a helmet for use in industry as protective gear to undertake the work.
• Before cleaning the filter or other parts of the outdoor unit, set the circuit breaker to OFF without fail, and place a “Work in progress” sign near the circuit breaker before proceeding with the work.
• Before working at heights, put a sign in place so that no-one will approach the work location, before proceeding with the work. Parts and other objects may fall from above, possibly injuring a person below. While carrying out the work, wear a helmet for protection from falling objects.
• The refrigerant used by this air conditioner is the R410A.
• The air conditioner must be transported in stable condition. If any part of the product is broken, contact the dealer.
• When the air conditioner must be transported by hand, carry it by two or more people.
• Do not move or repair any unit by yourself. There is high voltage inside the unit. You may get electric shock when removing the cover and main unit.
Selection of installation location
• When the air conditioner is installed in a small room, provide appropriate measures to ensure that the concentration of refrigerant leakage occur in the room does not exceed the critical level.
• Do not install in a location where flammable gas leaks are possible. If the gas leak and accumulate around the unit, it may ignite and cause a fire.
• To transport the air conditioner, wear shoes with additional protective toe caps.
• To transport the air conditioner, do not take hold of the bands around the packing carton. You may injure yourself if the bands should break.
• Install the indoor unit at least 2.5 m above the floor level since otherwise the users may injure themselves or receive electric shocks if they poke their fingers or other objects into the indoor unit while the air conditioner is running.
• Do not place any combustion appliance in a place where it is directly exposed to the wind of air conditioner, otherwise it may cause imperfect combustion.
Installation
• Suction duct length must be longer than 850 mm.
• When the indoor unit is to be suspended, the designated hanging bolts (M10 or W3/8) and nuts (M10 or W3/8) must be used.
• Install the air conditioner securely in a location where the base can sustain the weight adequately. If the strength is not enough, the unit may fall down resulting in injury.
• Follow the instructions in the Installation Manual to install the air conditioner. Failure to follow these instructions may cause the product to fall down or topple over or give rise to noise, vibration, water leakage or other trouble.
• Carry out the specified installation work to guard against the possibility of high winds and earthquake. If the air conditioner is not installed appropriately, a unit may topple over or fall down, causing an accident.
• If refrigerant gas has leaked during the installation work, ventilate the room immediately. If the leaked refrigerant gas comes in contact with fire, noxious gas may generate.
• Use forklift to carry in the air conditioner units and use winch or hoist at installation of them.
• Helmet must be worn to protect your head from falling objects. Especially, when you work under an inspection opening, helmet must be worn to protect your head from falling objects from the opening.
• The unit can be accessed from the service panel shown in the figure.
Refrigerant piping
• Install the refrigerant pipe securely during the installation work before operating the air conditioner. If the compressor is operated with the valve open and without refrigerant pipe, the compressor sucks air and the refrigeration cycles is over pressurized, which may cause a injury.
• Tighten the flare nut with a torque wrench in the specified manner. Excessive tighten of the flare nut may cause a crack in the flare nut after a long period, which may result in refrigerant leakage.
• After the installation work, confirm that refrigerant gas does not leak. If refrigerant gas leaks into the room and flows near a fire source, such as a cooking range, noxious gas may be generated.
• When the air conditioner has been installed or relocated, follow the instructions in the Installation Manual and purge the air completely so that no gases other than the refrigerant will be mixed in the refrigerating cycle. Failure to purge the air completely may cause the air conditioner to malfunction.
• Nitrogen gas must be used for the airtight test.
• The charge hose must be connected in such a way that it is not slack.
Electrical wiring
• Only a qualified installer(*1) or qualified service person(*1) is allowed to carry out the electrical work of the air conditioner. Under no circumstances must this work be done by an unqualified individual since failure to carry out the work properly may result in electric shocks and / or electrical leaks.
• To connect the electrical wires, repair the electrical parts or undertake other electrical jobs, wear gloves to provide protection for electricians and from heat, insulating shoes and clothing to provide protection from electric shocks. Failure to wear this protective gear may result in electric shocks.
• Use wiring that meets the specifications in the Installation Manual and the stipulations in the local regulations and laws. Use of wiring which does not meet the specifications may give rise to electric shocks, electrical leakage, smoking and / or a fire.
• Connect earth wire. (Grounding work) Incomplete grounding causes an electric shock.
• Do not connect earth wires to gas pipes, water pipes, and lightning conductor or telephone earth wires.
• After completing the repair or relocation work, check that the earth wires are connected properly.
• Install a circuit breaker that meets the specifications in the installation manual and the stipulations in the local regulations and laws.
• Install the circuit breaker where it can be easily accessed by the agent.
• When installing the circuit breaker outdoors, install one which is designed to be used outdoors.
• Under no circumstances the power wire must not be extended. Connection trouble in the places where the wire is extended may give rise to smoking and / or a fire.
• Electrical wiring work shall be conducted according to law and regulation in the community and installation manual. Failure to do so may result in electrocution or short circuit.
5-EN 6-EN
Page 5
– 4 –
SMMS Slim Duct Type
Installation Manual
EN
SMMS Slim Duct Type
Installation Manual
Test run
• Before operating the air conditioner after having completed the work, check that the electrical parts box cover of the indoor unit and service panel of the outdoor unit are closed, and set the circuit breaker to the ON position. You may receive an electric shock if the power is turned on without first conducting these checks.
• If there is any kind of trouble (such as an error display has appeared, smell of burning, abnormal sounds, the air conditioner fails to cool or heat or water is leaking) has occurred in the air conditioner, do not touch the air conditioner yourself but set the circuit breaker to the OFF position, and contact a qualified service person. Take steps to ensure that the power will not be turned on (by marking “out of service” near the circuit breaker, for instance) until qualified service person arrives. Continuing to use the air conditioner in the trouble status may cause mechanical problems to escalate or result in electric shocks or other trouble.
• After the work has finished, use an insulation tester set (500 V Megger) to check the resistance is 1 MΩ or more between the charge section and the non-charge metal section (Earth section). If the resistance value is low, a disas ter such as a leak or electric shock is caused at user’s side.
• Upon completion of the installation work, check for refrigerant leaks and check the insulation resistance and water drainage. Then conduct a test run to check that the air conditioner is operating properly.
Explanations given to user
• Upon completion of the installation work, tell the user where the circuit breaker is located. If the user does not know where the circuit breaker is, he or she will not be able to turn it off in the event that trouble has occurred in the air conditioner.
• If the fan grille is damaged, do not approach the outdoor unit but set the circuit breaker to the OFF position, and contact a qualified service person(*1) to have the repairs done. Do not set the circuit breaker to the ON position until the repairs are completed.
Relocation
• Only a qualified installer(*1) or qualified service person(*1) is allowed to relocate the air conditioner. It is dangerous for the air conditioner to be relocated by an unqualified individual since a fire, electric shocks, injury, water leakage, noise and / or vibration may result.
• When carrying out the pump-down work shut down the compressor before disconnecting the refrigerant pipe. Disconnecting the refrigerant pipe with the service valve left open and the compressor still operating will cause air or other gas to be sucked in, raising the pressure inside the refrigeration cycle to an abnormally high level, and possibly resulting in rupture, injury or other trouble.
CAUTION
New Refrigerant Air Conditioner Installation
THIS AIR CONDITIONER ADOPTS THE NEW HFC REFRIGERANT (R410A) WHICH DOES NOT DESTROY OZONE LAYER.
• The characteristics of R410A refrigerant are; easy to absorb water, oxidizing membrane or oil, and its pressure is approx. 1.6 times higher than that of refrigerant R22. Accompanied with the new refrigerant, refrigerating oil has also been changed. Therefore, do not let water, dust, former refrigerant, or refrigerating oil enter the refrigerating cycle during installation work.
• To prevent charging an incorrect refrigerant and refrigerating oil, the sizes of connecting sections of charging port of the main unit and installation tools are changed from those for the conventional refrigerant.
• Accordingly the exclusive tools are required for the new refrigerant (R410A).
• For connecting pipes, use new and clean piping designed for R410A, and please care so that water or dust does not enter.
To Disconnect the Appliance from Main Power Supply.
• This appliance must be connected to the main power supply by means of a switch with a contact separation of at least 3 mm.
The installation fuse (all types can be used) must be used for the power supply line of this conditioner.
(*1) Refer to the “Definition o f Qualified Installer or Qualified Ser vice Person.”

2 Accessory Parts

Part name Q’ty Shape Usage
Installation Manual 1 This manual
(Hand over to customers) (For other languages that do not appear in this Installation Manual,
please refer to the enclosed CD-R.)
CD-ROM 1 Installation Manual
Heat insulating pipe 2 For heat insulation of pipe connecting section
Washer 8 For hanging-up unit (M10 × Ø34)
Hose band 1 For connecting drain pipe
Flexible hose 1 For adjustment of drain pipe centering
Heat insulator 1 For insulating drain connecting section
7-EN 8-EN
Page 6
– 5 –
SMMS Slim Duct Type
Installation Manual
SMMS Slim Duct Type
Installation Manual

3 Selection of Installation Place

Avoid installing in the following places.
Select a location for the indoor unit where the cool or warm air will circulate evenly. Avoid installation in the following kinds of locations.
• Saline area (coastal area)
• Locations with acidic or alkaline atmospheres (such as areas with hot springs, factories where chemicals or pharmaceuticals are made and places where the exhaust air from combustion appliances will be sucked into the unit). Doing so may cause the heat exchanger (its aluminum fins and copper pipes) and other parts to become corroded.
• Locations with atmospheres with mist of cutting oil or other types of machine oil. Doing so may cause the heat exchanger to become corroded, mists caused by the blockage of the heat exchanger to be generated, the plastic parts to be damaged, the heat insulators to peel off, and other such problems to result.
• Locations where vapors from food oils are formed (such as kitchens where food oils are used). Blocked filters may cause the air conditioner’s performance to deteriorate, condensation to form, the plastic parts to be damaged, and other such problems to result.
• Locations near obstructions such as ventilation openings or lighting fixtures where the flow of the blown air will be disrupted (a disruption of the air flow may cause the air conditioner’s performance to deteriorate or the unit to shut down).
• Locations where an in-house power generator is used for the power supply. The power line frequency and voltage may fluctuate, and the air conditioner may not work properly as a result.
• On truck cranes, ships or other moving conveyances.
• The air conditioner must not be used for special applications (such as for storing food, plants, precision instruments or art works). (The quality of the items stored may be degraded.)
• Locations where high frequencies are generated (by inverter equipment, in-house power generators, medical equipment or communication equipment). (Malfunctioning or control trouble in the air conditioner or noise may adversely affect the equipment’s operation.)
• Locations where there is anything under the unit installed that would be compromised by wetness. (If the drain has become blocked or when the humidity is over 80 %, condensation from the indoor unit will drip, possibly causing damage to anything underneath.)
• In the case of the wireless type of system, rooms with the inverter type of fluorescent lighting or locations exposed to direct sunlight. (The signals from the wireless remote controller may not be sensed.)
• Locations where organic solvents are being used.
• The air conditioner cannot be used for liquefied carbonic acid cooling or in chemical plants.
• Location near doors or windows where the air conditioner may come into contact with high-temperature, high­humidity outdoor air. (Condensation may occur as a result.)
• Locations where special sprays are used frequently.
Installation under high-humidity atmosphere
In some cases including the rainy season, especially inside of the ceiling may become high-humidity atmosphere (dew-point temperature: 23 °C or higher).
1. Installation to inside of the ceiling with tiles on the roof
2. Installation to inside of the ceiling with slated roof
3. Installation to a place where inside of the ceiling is used for pathway to intake the fresh air
4. Installation to a kitchen
• In the above cases, additionally attach the heat insulator to all positions of the air conditioner, which come to contact with the high-humidity atmosphere. In this case, arrange the side plate (Check port) so that it is easily removed.
• Apply also a sufficient heat insulation to the duct and connecting part of the duct.
Installation space (Unit: mm)
Reserve sufficient space required for installation or service work.
[Reference] Condensation test conditions
Indoor side:
27 °C dry bulb temperature 24 °C wet bulb temperature
Air volume: Low air volume, operation time 4 hours
<Under air intake> <Back air intake>
Air discharge
100 or more
250 or
more
5 or more
210
235 or more
5 or more
235 or more
210
50 or more
Air intake
2500 or more
Floor surface
Ceiling
Ceiling
300 or more
Floor surface
2500 or more
210
235 or more
5 or more
Air intake
9-EN 10-EN
Page 7
– 6 –
SMMS Slim Duct Type
Installation Manual
EN
SMMS Slim Duct Type
Installation Manual
Service space
Air outlet
Ceiling
50
50
945
645
645
Service door (Ceiling opening)
Air filter
Service door (Ceiling opening)
945
945
745
745
645
Arranging the to back air intake type
<Back air intake>
Filter cleaning sign term setting
The lighting term setup of the filter sign (Notification of filter cleaning) of the remote controller can be changed according to the condition of installation. For setup method, refer to “Filter sign setting” in the Applicable controls of this Manual.
Remove the cover plate and then fix it to the bottom surface.
Do surely hooking to the main unit.
Main unit
(after remover)
Air filter
Main unit
Air filter
Force
Remove the filter from the main unit while pushing down on the tabs.
11-EN 12-EN
Page 8
– 7 –
SMMS Slim Duct Type
Installation Manual
SMMS Slim Duct Type
Installation Manual

4 Installation

CAUTION
Strictly comply with the following rules to prevent damage of the indoor units and human injury.
• Do not put a heavy article on the indoor unit or let a person get on it. (Even units are packaged)
• Carry in the indoor unit as it is packaged if possible. If carrying in the indoor unit unpacked by necessity, use buffering cloth or other material to not damage the unit.
• To move the indoor unit, hold the hooking brackets (4 positions) only. Do not apply force to the other parts (refrigerant pipe, drain pan, foamed parts, resin parts or other parts).
• Hanging bolt pitch of air inlet chamber side is different (centre position), make sure not to make mistake to install the setting direction.
• Carry the package by two or more persons, and do not bundle it with plastic band at positions other than specified.
External dimensions (Unit: mm)
803 (inside)
Refrigerant piping
845
805 910
Air filter
Fresh air inlet (knock-out hole)
Hung-up plate
Drain-up port
33
4-Ø4
168
(inside)
210
57
67
511
67
645
80
168
120
21
80
59
103
21
20
40
359
372
422
502
19
21
21
163
Ø92
31
Installation of hanging bolt
• Consider the piping / wiring after the unit is hung to determine the location of the indoor unit installation and orientation.
• After the location of the indoor unit installation has been determined, install hanging bolts.
• For the dimensions of the hanging bolt pitches, refer to the external view.
• When a ceiling already exists, lay the drain pipe, refrigerant pipe, control wires, and remote controller wires to their connection locations before hanging the indoor unit.
Procure hanging bolts washer and nuts for installing the indoor unit (these are not supplied).
Installation of hanging bolt
Use M10 hanging bolts (4 pcs, to be local procure). Matching to the existing structure, set pitch according to size in the unit external view as shown below.
Hanging bolt M10 or W3/8 4 pieces
Nut M10 or W3/8 12 pieces
New concrete slab
Install the bolts with insert brackets or anchor bolts.
Steel flame structure
Use existing angles or install new support angles.
Existing concrete slab
Use a hole-in anchors, hole-in plugs, or a hole-in bolts.
Rubber
Anchor bolt
(Blade type bracket)
(Slide type bracket)
(Pipe hanging anchor bolt)
Hanging bolt
Hanging bolt
Support angle
13-EN 14-EN
Page 9
SMMS Slim Duct Type
Installation Manual
EN
SMMS Slim Duct Type
Installation Manual
– 8 –
Installation of indoor unit
Treatment of ceiling
The ceiling differs according to structure of building. For details, consult your constructor or interior finish contractor. In the process after the ceiling board has been removed, it is important to reinforce ceiling foundation (frame) and to keep horizontal level of installed ceiling correctly in order to prevent vibration of ceiling board.
• Attach the nuts and the M10 flat washers to the hanging bolt.
• Put washers at up and down of the hanging bracket of the indoor unit to hang down the indoor unit.
• Check that four sides are horizontal with a level gauge. (Horizontal degree: Within 5 mm)
Installation of remote
controller (Sold separately)
For installation of the wired remote controller, follow the Installation Manual attached with the remote controller.
• Pull out the remote controller cord together with the refrigerant pipe or drain pipe. Pass the remote controller cord through upper side of the refrigerant pipe and drain pipe.
• Do not leave the remote controller at a place exposed to the direct sunlight and near a stove.
Wireless remote controller
The sensor of indoor unit with wireless remote controller can receive a signal by distance within approx. 8 m. Based upon it, determine a place where the remote controller is operated and the installation place.
• Operate the remote controller, confirm that the indoor unit receives a signal surely, and then install it.
• Keep 1 m or more from the devices such as television, stereo. (Disturbance of image or noise may generate.)
• To prevent a malfunction, select a place where is not influenced by a fluorescent light or direct sunlight.
• Two or more (Up to 6 units) indoor units with wireless type remote controller can be installed in the same room.
Nut
(W3/8 or M10)
M10 flat washer (Accessory)
M10 flat washer (Accessory)
Hanging bolt
(W3/8 or M10)
Nut (W3/8 or M10)
8
m
o
r
l
e
s
s

5 Drain Piping

CAUTION
Following the Installation Manual, perform the drain piping work so that water is properly drained, and apply a heat insulation so as not to cause a dew drop. Inappropriate piping work may result in water leakage in the room and wet of furniture.
Piping / Heat insulating material
Require the following materials for piping and heat insulating at site.
Flexible hose
Use the attached flexible hose to adjust centre discrepancy of the hard vinyl chloride pipe or to adjust the angle.
• Do not use the flexible hose as stretched, or do not deform it more extent than that in the following figure.
• Fix the soft end of the flexible hose with the attached hose band.
• Use the flexible hose on a horizontal level.
REQUIREMENT
• Perform heat insulation of the drain pipes of the indoor unit.
• Perform heat insulation of the connecting part with the indoor unit. An incomplete heat insulation causes dew drop.
• Set the drain pipe with downward slope (1/100 or more), and do not make swelling or trap on the piping. It may cause an abnormal sound.
• For length of the traversing drain pipe, restrict to 20 m or less. To use a long pipe, provide support brackets with interval of 1.5 - 2 m in order to prevent waving.
• Set the collective piping as shown in the below figure.
• Do not apply force to the connecting part of the drain pipe.
• The hard vinyl-chloride pipe cannot be directly connected to the drain pipe connecting port of the indoor unit. For connection with the drain pipe connecting port, fix the attached flexible hose with the hose band, otherwise a damage or water leak is caused on the drain pipe connecting port.
Piping
Hard vinyl chloride pipe VP25 (Outer dia.: Ø32 mm)
Heat insulator
Foam polyethylene: Thickness 10 mm or more
OK
NO GOOD
max 45°
max 45°
90° Bend
Riser (Trap)
Top view
Side view
Side view
Air outlet
Side view
Air outlet
Air outlet
Support bracket
1/100 or more downward
Heat insulator
1.5 - 2 m Arched shape
Trap
NO
GOOD
VP25
As long as possible (100 mm)
Downward slope 1/100 or more
VP30 or more
VP25
VP25
15-EN 16-EN
Page 10
– 9 –
SMMS Slim Duct Type
Installation Manual
SMMS Slim Duct Type
Installation Manual
Connecting drain pipe
• Connect a hard socket (locally procured) to the hard socket of the attached supplied flexible hose.
• Connect a drain pipe (locally procured) to the connected hard socket.
REQUIREMENT
• Connect hard vinyl chloride pipes securely using an adhesive for vinyl chloride to avoid water leakage.
• It takes some time until the adhesive is dried and hardened (refer to the manual of t he adhesive). Do not apply stress to the joint with the drain pipe during this time period.
Drain up
When a down-gradient cannot be secured for the drainpipe, drain-up piping is possible.
• The height of the drain pipe must be 850 mm or less from the bottom of the ceiling.
• Take the drain pipe out of the drain pipe joint with the indoor unit in 300 mm or less, and bend up the pipe vertically.
• Immediately after the pipe is bent up vertically, lay the pipe making a down-gradient.
• Set downward grading immediately after raising up vertically.
Check the draining
In the test run, check that water drain is properly performed and water does not leak from the connecting part of the pipes. Check draining also when installed in heating period. By using a pitcher or hose, pour water (1500 - 2000 cc) into the discharge port before installation of the ceiling panel. Pour water gradually so that water does not spread on the motor of the drain pump.
CAUTION
Pour water gently so that it does not spread around inside the indoor unit, which may cause a malfunction.
Drain pipe connecting port (Transparent)
Adhesive inhibited:
Use the attached flexible hose and hose band for connecting the drain hose to the clear drain socket. If applying the adhesive, socket will be damaged and cause water leakage.
Align the attached hose band to the end of hose, set the tightening position upward, and then tighten it.
Flexible hose (Accessory)
Socket for VP25 vinyl chloride pipe (locally procured)
Drain pipe connecting port (Hard socket)
VP25 vinyl chloride pipe (locally procured)
Attached hose band
Attached flexible hose
Soft socket
Hard socket
Socket for VP25 (locally procured)
VP25 vinyl chloride pipe (locally procured)
Indoor unit
Indoor unit
Rising up 687 mm
or less
Underside of ceiling
Indoor unit
300 mm or less
Rising up 850 mm or less
CAUTION
Pour water gently so that it does not spread around inside the indoor unit, which may cause a malfunction.
• After the electric work has finished, pour water during COOL mode operation.
• If the electric work has not yet finished, pull out the float switch connector (CN34: Red) from the electrical control box, and check draining by plugging the single phase 220 - 240 V power to the terminal blocks R (L) and S (N). If doing so, the drain pump motor operates.
• Test water drain while checking the operation sound of the drain pump motor. (If the operation sound changes from continuous sound to intermittent sound, water is normally drained.) After the check, the drain pump motor runs, connecting the float switch connector. (In case of check by pulling out the float switch connector, be sure to return the connector to the original position.)
Pump
Insert the edge of hose into the drain pan and bend it downward.
Water (1500 cc ~ 2000 cc)
Vessel
Cover plate
L N
Pull out connector CN34 (Red) from P.C. board.
CN34 (RED)
Black
Black
Red
White
Power terminals
220 - 240 V, 50 Hz 220 V, 60 Hz
17-EN 18-EN
Page 11
– 10 –
SMMS Slim Duct Type
Installation Manual
EN
SMMS Slim Duct Type
Installation Manual
Perform heat insulating
• As shown in the figure, cover the flexible hose and hose band with the attached heat insulator up to the bottom of the indoor unit without gap.
• Cover the drain pipe seamlessly with a heat insulator to be procured locally so that it overlaps with the attached heat insulator of the drain connecting section.
* Direct the slits and seams of the heat insulator upward to avoid water leakage.
Wrap the attached heat insulator seamlessly from the surface of the indoor unit.
Flexible hose
Hose band
Attached heat insulator
Heat insulator to be procured locally
Hard vinyl chloride pipe

6 Duct Design

Arrangement (Unit: mm)
Referring to the following dimensions, manufacture duct at the local site.
<Under air intake>
<Back air intake>
805
100
100
100
100
100
100
100
100
12.5
12.5
45.3
100
100
41.5
8.2 or less
286.8
266
825
170
44.3
44.3
100
188
805
825
100
100
100
100
100
100
100
100
12.5
12.5
19-EN 20-EN
Page 12
– 11 –
SMMS Slim Duct Type
Installation Manual
SMMS Slim Duct Type
Installation Manual
Mount an air filter to the air intake side; otherwise decrease of capacity may be caused.
<Under air intake> <Back air intake>
Remove the cover plate and then fix it to the bottom surface.
Main unit
Air filter
Push
Remove the filter from the main unit while pushing down on the tabs.
Take out this cover plate.
Connecting method of the duct
CAUTION
Incomplete heat insulation of the supply air flange and sealing may occur dewing resulted in falling of water drop.
Flange (locally procured)
Aluminum tape (locally procured)
Aluminum tape (locally procur ed)
Under surface
Cover a screw
Heat insulator with sticking materi al (100 mm-width locally procured)
Aluminum tape (locally procured)
Air discharge side
Indoor unit
Air intake side
Connect a duct to the inside of the flange
Heat insulator with sticking mater ial (100 mm - width locally procured )
Aluminum tape (locally procured)
Duct: Insulation materia (locally procured)
Flange
21-EN 22-EN
Page 13
– 12 –
SMMS Slim Duct Type
Installation Manual
EN
SMMS Slim Duct Type
Installation Manual
Fan characteristics
No filter
AP007 AP009
AP012
AP015 AP018
0
10
20
30
40
50
60
300 400 500 600 700
Standard air volume: 540 m3/h
Upper limit of external
static pressure(50 Pa)
High (50 Pa)
High (35 Pa)
Low (50 Pa)
High (20 Pa)
Low (35 Pa)
Low (20 Pa)
High (10 Pa)
Low (10 Pa)
Upper limit of
external static
pressure(35 Pa)
Upper limit of external static
pressure(20 Pa)
Upper limit of external static
pressure(10 Pa)
Lower limit of external static pressure (50 Pa)
Lower limit of external static pressure (35Pa)
Lower limit of external static pressure (20Pa)
External static pressure (Pa)
Air Volume (m3/h)
0
10
20
30
40
50
60
300 400 500 600 700
Standard air volume: 600 m3/h
Upper limit of
external static
pressure(50Pa)
High (50Pa)
High (35Pa)
Low (50Pa)
High (20Pa)
Low (35Pa)
Low (20Pa)
High (10Pa)
Low (10Pa)
Upper limit of
external static
pressure
(35Pa)
Upper limit of
external static
pressure
(20Pa)
Upper limit of
external static
pressure(10Pa)
Lower limit of external static pressure (50Pa)
Lower limit of external static pressure (35Pa)
Lower limit of external static pressure (20Pa)
External static pressure (Pa)
Air Volume (m3/h)
0
10
20
30
40
50
60
400 500 600 700 800
Standard air volume: 690 m3/h
Upper limit of external
static pressure(50Pa)
High (50Pa)
High (35Pa)
Low (50Pa)
High (20Pa)
Low (35Pa)
Low (20Pa)
High (10Pa)
Low (10Pa)
Upper limit of
external static
pressure(35Pa)
Upper limit of
external static
pressure(20Pa)
Upper limit of
external static
pressure(10Pa)
Lower limit of external static pressure (50Pa)
Lower limit of external static pressure (35Pa)
Lower limit of external static pressure (20Pa)
External static pressure (Pa)
Air Volume (m3/h)
0
10
20
30
40
50
60
400 500 600 700 800 900
Standard air volume: 780 m3/h
Upper limit of
external static
pressure(50 Pa)
High (50 Pa)
High (35 Pa)
Low (50 Pa)
High (20 Pa)
Low (35 Pa)
Low (20 Pa)
High (10 Pa)
Low (10 Pa)
Upper limit of
external static
pressure(35 Pa)
Upper limit of
external static
pressure(20 Pa)
Upper limit of
external static
pressure(10 Pa)
Lower limit of external static pressure (50 Pa)
Lower limit of external static pressure (35 Pa)
Lower limit of external static pressure (20 Pa)
External static pressure (Pa)
Air Volume (m3/h)
Filter attached
AP007 AP009
AP012
AP015 AP018
0
10
20
30
40
50
60
300 400 500 600 700
Standard air volume: 540 m3/h
Upper limit of
external static
pressure(50 Pa)
High (50 Pa)
Lower limit of externa static pressure (50 Pa)
Low (50 Pa)
High (20 Pa)
Low (35 Pa)
Low (20 Pa)
High (10 Pa)
Low (10 Pa)
Upper limit of
external static
pressure(35 Pa)
Upper limit of
external static
pressure(20 Pa)
Upper limit of
external static
pressure(10Pa)
Lower limit of external static pressure (35 Pa)
Lower limit of externa static pressure (20 Pa)
Standard filter pressure loss
External static pressure (Pa)
Air Volume (m3/h)
0
10
20
30
40
50
60
300 400 500 600 700
Standard air volume: 600 m3/h
Upper limit of external static pressure(50 Pa)
High (50 Pa)
High (35
Pa)
Low (50 Pa)
High (20
Pa)
Low (35 Pa)
Low (20Pa)
High
(10Pa)
Low (10Pa)
Upper limit of
external static
pressure(35Pa)
Upper limit of
external static
pressure(20Pa)
Upper limit of external
static pressure(10Pa)
Lower limit of external static pressure (50Pa)
Lower limit of external static pressure (35Pa)
Lower limit of external static pressure (20Pa)
External static pressure (Pa)
Air Volume (m3/h)
Standard filter pressure loss
0
10
20
30
40
50
60
400 500 600 700 800
Standard air volume: 690 m3/h
Upper limit of external
static pressure(50Pa)
High (50Pa)
High (35Pa)
Low (50Pa)
High (20Pa)
Low (35Pa)
Low (20Pa)
High (10Pa)
Low (10Pa)
Upper limit of external
static pressure(35Pa)
Upper limit of
external static
pressure(20Pa)
Upper limit of
external static
pressure(10Pa)
Lower limit of external static pressure (50Pa)
Lower limit of external static pressure (35Pa)
Lower limit of external static pressure (20Pa)
External static pressure (Pa)
Air Volume (m3/h)
Standard filter pressure loss
0
10
20
30
40
50
60
400 500 600 700 800 900
Standard air volume: 780 m3/h
Upper limit of external static pressure(50Pa)
High (50Pa)
High (35Pa)
Low (50Pa)
High (20Pa)
Low (35Pa)
Low (20Pa)
High (10Pa)
Low (10Pa)
Upper limit of external static pressure(35Pa)
Upper limit of
external static
pressure(20Pa)
Upper limit of
external static
pressure(10Pa)
Lower limit of external static pressure (50Pa)
Lower limit of external static pressure (35Pa)
Lower limit of external static pressure (20Pa)
External static pressure (Pa)
Air Volume (m3/h)
Standard filter pressure loss
23-EN 24-EN
Page 14
– 13 –
SMMS Slim Duct Type
Installation Manual
SMMS Slim Duct Type
Installation Manual

7 Refrigerant Piping

CAUTION
When the refrigerant pipe is long, provide support brackets at intervals of 2.5 m to 3 m to clamp the refrigerant pipe. Otherwise, abnormal sound may be generated. Use the flare nut attached with the indoor unit or R410A flare nut.
Permissible piping length and
height difference
They vary depending on the outdoor unit. For details, refer to the Installation Manual attached to the outdoor unit.
Pipe size
Connecting refrigerant piping
Flaring
1. Cut the pipe with a pipe cutter.
Remove burrs completely. (Remaining burrs may cause gas leakage.)
2. Insert a flare nut into the pipe, and flare the pipe.
Use the flare nut provided with the unit or the one used for the R410A refrigerant. The flaring dimensions for R410A are different from the ones used for the conventional R22 refrigerant. A new flare tool manufactured for use with the R410A refrigerant is recommended, but the conventional tool can still be used if the projection margin of the copper pipe is adjusted to be as shown in the following table.
Projection margin in flaring: B (Unit: mm)
Flaring diameter size: A (Unit: mm)
* In case of flaring for R410A with the conventional
flare tool, pull it out approx. 0.5 mm more than that for R22 to adjust to the specified flare size. The copper pipe gauge is useful for adjusting projection margin size.
• The sealed gas was sealed at the atmospheric pressure so when the flare nut is removed, there will no “whooshing” sound: This is normal and is not indicative of trouble.
• Use two wrenches to connect the indoor unit pipe.
Model MMD-
Pipe size (mm)
Gas side Liquid side
AP007 to AP012 Ø9.5 Ø6.4
AP015 to AP018 Ø12.7 Ø6.4
Outer dia. of copper pipe
R410A tool used
Conventional
tool used
6.4, 9.5 0 to 0.5 1.0 to 1.5
12.7, 15.9
Outer dia. of copper pipe A
+0 –0.4
6.4 9.1
9.5 13.2
12.7 16.6
15.9 19.7
Work using double spanner
• Use the tightening torque levels as listed in the table below.
• Tightening torque of flare pipe connections. Pressure of R410A is higher than that of R22. (Approx. 1.6 times) Therefore, using a torque wrench, tighten the flare pipe connecting sections which connect the indoor and outdoor units of the specified tightening torque. Incorrect connections may cause not only a gas leak, but also a trouble of the refrigeration cycle.
CAUTION
Tightening with an excessive torque may crack the nut depending on installation conditions.
Airtight test / Air purge, etc.
For air tightness test, vacuum drying and adding refrigerant, refer to the Installation Manual attached to the outdoor unit.
CAUTION
Do not supply power to the indoor unit until the airtight test and vacuuming are completed. (If the indoor unit is powered on, the pulse motor valve is fully closed, which extends the time for vacuuming.)
Open the valve fully
Open the valve of the outdoor unit fully.
Heat insulation process
Apply heat insulation for the pipes separately at liquid side and gas side.
• For the heat insulation to the pipes at gas side, use the material with heat-resisting temperature 120 °C or higher.
• To use the attached heat insulation pipe, apply the heat insulation to the pipe connecting section of the indoor unit securely without gap.
REQUIREMENT
• Apply the heat insulation to the pipe connecting section of the indoor unit securely up to the root without exposure of the pipe. (The pipe ex posed to the outside causes water leak.)
• Wrap heat insulator with its slits facing up (ceiling side).
Outer dia. of connecting
pipe (mm)
Tightening torque (N•m)
6.4 14 to 18 (1.4 to 1.8 kgf•m)
9.5 33 to 42 (3.3 to 4.2 kgf•m)
12.7 50 to 62 (5.0 to 6.2 kgf•m)
15.9 63 to 77 (6.3 to 7.7 kgf•m)
Indoor unit
Union
Heat insulation pipe (Accessory)
Flare nut
Heat insulator of the pipe
25-EN 26-EN
Page 15
SMMS Slim Duct Type
Installation Manual
EN
SMMS Slim Duct Type
Installation Manual
– 14 –

8 Electrical Connection

WARNING
Use the specified wires for wiring connect the
terminals. Securely fix them to prevent external forces applied to the terminals from affecting the terminals.
Incomplete connection or fixation may cause a fire or other trouble.
Connect earth wire. (grounding work) Incomplete grounding cause an electric shock. Do not connect earth wires to gas pipes, water pipes, lightning conductor or telephone earth wires.
Appliance shall be installed in accordance with
national wiring regulations.
Capacity shortage of power circuit or incomplete installation may cause an electric shock or a fire.
CAUTION
• If incorrect / incomplete wiring is carried out, it will cause an electrical fire or smoke.
• Install an earth leakage breaker that is not tripped by shock waves. If an earth leakage breaker is not installed, an electric shock may be caused.
• Use the cord clamps attached to the product.
• Do not damage or scratch the conductive core and inner insulator of power and inter-connecting wires when peeling them.
• Use the power cord and Inter-connecting wire of specified thickness, type, and protective devices required.
• Do not connect 220 V – 240 V power to the terminal blocks ( , , , ) for control wiring. (Otherwise, the system will fail.)
• Do not damage or scratch the conductive core and inner insulator of power and inter-connecting wires when peeling them.
• Perform the electric wiring so that it does not come to contact with the high-temperature part of the pipe. The coating may melt resulting in an accident.
REQUIREMENT
• For power supply wiring, strictly conform to the Local Regulation in each country.
• For wiring of power supply of the outdoor units, follow the Installation Manual of each outdoor unit.
• Perform the electric wiring so that it does not come to contact with the high-temperature part of the pipe.The coating may melt resulting in an accident.
• After connecting wires to the terminal blocks, provide a trap and fix wires with the cord clamp.
• Run the refrigerant piping line and control wiring line in the same line.
• Do not turn on the power of the indoor unit until vacuuming of the refrigerant pipes completes.
Power supply wire and
communication wires specifications
Power supply wire and communication wires are procured locally. For the power supply specifications, follow to the table below. If capacity is little, it is dangerous because overheat or burnout may be caused. For specifications of the power capacity of the outdoor unit and the power supply wires, refer to the Installation Manual attached to the outdoor unit.
Indoor unit power supply
• For the power supply of the indoor unit, prepare the exclusive power supply separated from that of the outdoor unit.
• Arrange the power supply, circuit breaker, and main switch of the indoor unit connected to the same outdoor unit so that they are commonly used.
• Power supply wire specification: Cable 3-core 2.5 mm², in conformity with Design 60245 IEC 57.
U
1
U
2
A
B
Power supply
Control wiring, Central controller wiring
• 2-core with polarity wires are used for the Control wiring between indoor unit and outdoor unit and Central controller wiring.
• To prevent noise trouble, use 2-core shield wire.
• The length of the communication line means the total length of the inter-unit wire length between indoor and outdoor units added with the central control system wire length.
Communication line
Remote controller wiring
• 2-core with non-polarity wire is used for wiring of the remote controller wiring and group remote controllers wiring.
CAUTION
The remote controller wire (Communication line) and AC 220 – 240 V wires cannot be parallel to contact each other and cannot be stored in the same conduits. If doing so, a trouble may be caused on the control system due to noise or other factor.
Power supply
220 V – 240 V ~, 50 Hz
220 V ~, 60 Hz
Power supply switch / circuit breaker or power supply wiring / fuse rating for indoor units should be selected by the accumulated total current values of the indoor units.
Power supply wiring Below 50 m 2.5 mm
2
Control wiring between indoor units, and outdoor unit (2-core shield wire)
Wire size
(Up to 1000 m) 1.25 mm²
(Up to 2000 m) 2.0 mm²
Central control line wiring (2-core shield wire)
Wire size
(Up to 1000 m) 1.25 mm²
(Up to 2000 m) 2.0 mm²
Remote controller wiring, remote controller inter-unit wiring
Wire size: 0.5 mm² to 2.0 mm²
Total wire length of remote controller wiring and remote controller inter-unit wiring = L + L1 + L2 + … Ln
In case of wired type only Up to 500 m
In case of wireless type
included
Up to 400 m
Total wire length of remote controller inter-unit wiring = L1 + L2 + … Ln Up to 200 m
L1
L
L2 Ln
Indoor unit
Remote controller inter-unit wiring
Indoor unit Indoor unit Indoor unit
Remote
controller
(Max. 8 units)
Remote controller wiring
27-EN 28-EN
Page 16
– 15 –
SMMS Slim Duct Type
Installation Manual
SMMS Slim Duct Type
Installation Manual
Wiring between indoor and outdoor units
NOTE
An outdoor unit connected with control wiring between indoor and outdoor units wire becomes automatically the header unit.
Wiring example
U1 U2
U1 U2 U3 U4L1 L2 L3 N U5 U6
LN AB
AB
U1 U2 U3 U4L1 L2 L3 N U5 U6
U1 U2LN AB
AB
U1 U2LN AB
AB
U1 U2LN AB
Outdoor Power supply 380 V - 415 V ~, 50 Hz 380 V ~, 60 Hz
Circuit breaker, Power switch
Remote controller
Indoor unit
Outdoor Power supply 380 V - 415 V ~, 50 Hz 380 V ~, 60 Hz
Remote controller Remote controller
Indoor unit Indoor unit Indoor unit
Circuit breaker Circuit breaker
Header outdoor unit
Follower outdoor unit
Control wiring between outdoor units
Control wiring between indoor and outdoor units
Control wiring between indoor units
Indoor power supply 220 V - 240 V ~, 50 Hz 220 V ~, 60 Hz
Earth Earth Earth Earth
Group control
Pull boxPull boxPull box
Earth terminal
Earth terminal
Wire connection
REQUIREMENT
• Connect the wires matching the terminal numbers. Incorrect connection causes a trouble.
• Pass the wires through the bushing of wire connection holes of the indoor unit.
• Keep a margin (Approx. 100 mm) on a wire to hang down the electrical control box at servicing or other purpose.
• The low-voltage circuit is provided for the remote controller. (Do not connect the high-voltage circuit)
• Before remove the electrical control box cover, remove the cover plate and air filter.
• Remove the cover of the electrical control box by taking off the mounting screws (2 positions) and pushing the hooking section. (The cover of the electrical control box remains hanged to the hinge.)
• Tighten the screws of the terminal block, and fix the wires with cord clamp attached to the electrical control box. (Do not apply tension to the connecting section of the terminal block.)
• Set a loop for the connecting wire of the storing part of the indoor unit electric parts; otherwise the electrical control box cannot be drawn out in service time.
• Mount the cover of the electrical control box without pinching wires.
R(L)
S(N)
BA
S(N)R(L)
Air filter
Screw
(2 positions)
Cover plate
Remote controller wire
Cable cramp
Control wire
Electrical control box
Electrical
control box
cover
Power supply cord
R
(L)S(N)
10
10
30
70
Earth wire
Power supply wire
29-EN 30-EN
Page 17
SMMS Slim Duct Type
Installation Manual
EN
SMMS Slim Duct Type
Installation Manual
– 16 –
Remote controller wiring
Strip off approx. 9 mm the wire to be connected.
Wiring diagram
Address setup
Set up the addresses as per the Installation Manual supplied with the outdoor unit.
A B
A B
Terminal block
Remote controller unit
Terminal block for remote controller wiring of indoor unit
Remote controller wire (Locally procured)

9 Applicable Controls

REQUIREMENT
When the air conditioner is used for the first time, it will take some moments after the power has been turned on before the remote controller becomes available for operations: This is normal and is not indicative of trouble.
• Concerning the automatic addresses (The automatic addresses are set up by performing operations on the outdoor interface circuit board.) While the automatic addresses are being set up, no remote controller operations can be performed. Setup takes up to 10 minutes (usually about 5 minutes).
• When the power is turned on after automatic address setup It takes up to 10 minutes (usually about 3 minutes) for the outdoor unit to start operating after the power has been turned on.
Before the air conditioner was shipped from the factory, all units are set to [STANDARD] (factory default). If necessary, change the indoor unit settings. The settings are changed by operating the wired remote controller. * The settings cannot be changed using only a wireless
remote controller, simple remote controller or group control remote controller by itself so install a wired remote controller separately as well.
Basic procedure for changing
settings
Change the settings while the air conditioner is not working. (Stop the air conditioner before making
settings.)
CAUTION
Set only the CODE No. shown in the following table: Do NOT set any other CODE No. If a CODE No. not listed is set, it may not be possible to operate the air conditioner or other trouble with the product may result. * The displays appearing during the setting process
differ from the ones for previous remote controllers (AMT21E, AMT31E). (There are more CODE No.)
1 Push and hold button and “TEMP.”
button simultaneously for at least 4 seconds. After a while, the display flashes as shown in the figure. Confirm that the CODE No. is [01].
If the CODE No. is not [01], push button to clear the display content, and repeat the procedure from the beginning. (No operation of the remote controller is accepted for a while after button is pushed.) (While air conditioners are operated under the group control, “ALL” is displayed first. When
is pushed, the indoor unit number
displayed following “ALL” is the header unit.)
1
6
1 3
2
5
4
(* Display content varies with the indoor unit model.)
31-EN 32-EN
Page 18
– 17 –
SMMS Slim Duct Type
Installation Manual
SMMS Slim Duct Type
Installation Manual
2 Each time button is pushed, indoor
unit numbers in the control group change cyclically. Select the indoor unit to change settings for.
The fan of the selected unit runs and the louvers start swinging. The indoor unit for change settings can be confirmed.
3 Specify CODE No. [ ] wi th “TEMP.” /
buttons.
4 Select SET DATA [ ] with “TIME” /
buttons.
5 Push button. When the display changes
from flashing to lit, the setup is completed.
• To change settings of another indoor unit,
repeat from Procedure 2.
• To change other settings of the selected indoor
unit, repeat from Procedure 3.
Use button to clear the settings. To make settings after button was pushed, repeat from Procedure 2.
6 When settings have been completed, push
button to determine the settings.
When button is pushed, flashes and then the display content disappears and the air conditioner enters the normal stop mode. (While is flashing, no operation of the remote controller is accepted.)
External static pressure settings
Set up a tap change based upon the external static pressure of the duct to be connected. To set up a tap change, follow to the basic operation procedure (1 2 3 4 5 6).
• Specify [5d] to the CODE No. in procedure 3.
• For the SET DATA of procedure 4, select a SET DATA of the external static pressure to be set up from the
following table.
<Change on wired remote controller>
With a remote controller-less system (group control)
Besides the switching method using the wired remote controller as a way to establish the external static pressure switching is also possible by changing over the jumper block settings on the indoor P.C. board as shown in the following table. * However, once these settings are changed, it is necessary to reset the SET DATA to 0000 that placing the
jumper block back to the factory default position and rewriting the SET DATA back to 0000 with wired remote controller (sold separately).
• Change over the jumper blocks on the indoor P.C. board, and select the desired setting.
Jumper block positions (CN112, CN111 and CN110 from the left)
SET DATA External static pressure
0000 10 Pa Standard (Factory default)
0001 20 Pa High static pressure 1
0003 35 Pa High static pressure 2
0006 50 Pa High static pressure 3
Jumper block
position
SET DATA 0000 0001 0003 0006
External static
pressure
10 Pa 20 Pa 35 Pa 50 Pa
Standard
(Factory default)
High static Pressure 1 High static Pressure 2 High static Pressure 3
Short
Open
CN112 CN111 CN110
CN112 CN111 CN110
CN112 CN111 CN110
CN112 CN111 CN110
33-EN 34-EN
Page 19
SMMS Slim Duct Type
Installation Manual
EN
SMMS Slim Duct Type
Installation Manual
– 18 –
Filter sign setting
According to the installation condition, the filter sign term (Notification of filter cleaning) can be changed. Follow to the basic operation procedure (123456).
• For the CODE No. in Procedure 3, specify [01].
• For the [SET DATA] in Procedure 4, select the SET
DATA of filter sign term from the following table.
To secure better effect of
heating
When it is difficult to obtain satisfactory heating due to installation place of the indoor unit or structure of the room, the detection temperature of heating can be raised. Also use a circulator or other machinery to circulate heat air near the ceiling. Follow to the basic operation procedure (123456).
• For the CODE No. in Procedure 3, specify [06].
• For the set data in Procedure 4, select the SET
DATA of shift value of detection temperature to be set up from the following table.
Remote controller sensor
The temperature sensor of the indoor unit senses room temperature usually. Set the remote controller sensor to sense the temperature around the remote controller. Select items following the basic operation procedure (1 2 3 4 5 6 ).
• Specify [32] for the CODE No. in Procedure 3.
• Select the following data for the SET DATA in
Procedure 4.
When flashes, the remote controller sensor is defective. Select the SET DATA [0000] (not used) or replace the remote controller.
Group control
In a group control, a remote controller can control up to maximum 8 units.
• The wired remote controller only can control a group control. The wireless remote controller is unavailable for this control.
• For wiring procedure and wires of the individual line (Identical refrigerant line) system, refer to “Electrical Connection” in this Manual.
• Wiring between indoor units in a group is performed in the following procedure.
• Connect the indoor units by connecting the remote controller wires from the remote controller terminal blocks (A, B) of the indoor unit connected with a remote controller to the remote controller terminal blocks (A, B) of the other indoor unit. (Non-polarity)
• For address setup, refer to the Installation Manual attached to the outdoor unit.
SET DATA Filter sign term
0000 None
0001 150 H
0002
2500 H
(Factory default)
0003 5000 H
0004 10000 H
SET DATA Detection temperature shift value
0000 No shift
0001 +1 °C
0002
+2 °C
(Factory default)
0003 +3 °C
0004 +4 °C
0005 +5 °C
0006 +6 °C
SET DATA 0000 0001
Remote controller sensor
Not used
(Factory default)
Used

10Test Run

Before test run
• Before turning on the power supply, carry out the following procedure.
1) By using 500 V-megger, check that resistance of 1 MΩ or more exists between the terminal block L to N and the earth (grounding). If resistance of less than 1 MΩ is detected, do not run the unit.
2) Check the valve of the outdoor unit being opened fully.
• To protect the compressor at activation time, leave power-ON for 12 hours or more before operating.
• Do not press the electromagnetic contactor to forcibly perform a test run. (This is very dangerous because the protective device does not work.)
• Before starting a test run, set addresses by following the Installation Manual supplied with the outdoor unit.
Execute a test run
• When a fan operation is to be performed for an individual indoor unit, turn off the power, short CN72 on the circuit board, and then turn the power back on. (First set the operating mode to “fan,” and then operate.) When the test run has been performed using this method, do NOT forget to release the shorting of CN72 after the test run is completed.
Operate the unit with the wired remote controller as usual. For the procedure of the operation, refer to the attached Owner’s Manual to the outdoor unit. A forced test run can be executed in the following procedure even if the operation stops by thermostat­OFF. In order to prevent a serial operation, the forced test run is released after 60 minutes have passed and returns to the usual operation.
CAUTION
Do not use the forced test run for cases other than the test run because it applies an excessive load to the devices.
Wired remote controller
1 Push button for 4 seconds or more.
[TEST] is displayed on the display part and the selection of mode in the test mode is permitted.
2 Push button. 3 Select the operation mode with
button, [ Cool] or [ Heat].
• Do not run the air conditioner in a mode other than [ Cool] or [ Heat].
• The temperature controlling function does not work during test run.
• The detection of error is performed as usual.
4 After the test run, push button to
stop a test run.
(Display part is same as procedure 1.)
5 Push check button to cancel (release
from) the test run mode.
([TEST] disappears on the display and the status returns to a normal.)
2, 4 3
1,5
35-EN 36-EN
Page 20
– 19 –
SMMS Slim Duct Type
Installation Manual
SMMS Slim Duct Type
Installation Manual
Wireless remote controller
1 Remove a small screw which fixes the nameplate of the receiver unit.
Remove the nameplate of the sensor section by inserting a flat-blade screwdriver into the notch at the bottom of the plate, and set the Dip switch to [TEST RUN ON].
2 Execute a test operation with ON/OFF button on the wireless remote controller.
, , and LED flash during test operation.
• Under status of [TEST RUN ON], the temperature adjustment from the wireless remote controller is invalid. Do not use this method in the operation other than test operation because the equipment is damaged.
3 Use either Cool or Heat operation mode for a test operation.
* The outdoor unit does not operate approx. 3 minutes after power-ON and operation stop.
4 After the test operation finished, stop the air conditioner from the wireless remote controller, and
return Dip switch of the receiver section as before.
(A 60-minutes timer clearing function is attached to the receiver section in order to prevent a continuous test operation.)
Small screw
Nameplate
Notch
M4 × 25 screw (2 pieces)
Spacer
Receiver unit

11Maintenance

<Daily maintenance>
Cleaning of air filter
If is displayed on the remote controller, maintain the air filter.
1 Push the button to stop the operation, then turn off the circuit breaker. 2 Take out the air filter.
Push the tabs (Forward direction as shown in the figure) of the fir filter, and then pull out it to take out the air filter.
3 Cleaning with water or vacuum cleaner
• If dirt is heavy, clean the air filter by tepid water with neutral detergent or water.
• After cleaning with water, dry the air filter sufficiently in a shade place.
6
1,5
Air filter
Main unit
Push
Remove the filter from the main unit while pushing down on the tabs.
37-EN 38-EN
Page 21
– 20 –
SMMS Slim Duct Type
Installation Manual
EN
SMMS Slim Duct Type
Installation Manual
4 Mount the air filter.
Attach the filter to the main unit while pushing the tabs
5 Turn on the circuit breaker, then push the button on the remote controller to start the
operation.
6 After cleaning, push .
display disappears.
CAUTION
• Do not start the air conditioner while leaving air filter removed.
• Push the filter reset button. ( indication will be turn off.)
Periodic Maintenance
For environmental conservation, it is strongly recommended that the indoor and outdoor units of the air conditioner in use be cleaned and maintained regularly to ensure efficient operation of the air conditioner. When the air conditioner is operated for a long time, periodic maintenance (once a year) is recommended. Furthermore, regularly check the outdoor unit for rust and scratches, and remove them or apply rustproof treatment, if necessary. As a general rule, when an indoor unit is operated for 8 hours or more daily, clean the indoor unit and outdoor unit at least once every 3 months. Ask a professional for this cleaning / maintenance work. Such maintenance can extend the life of the product though it involves the owner’s expense. Failure to clean the indoor and outdoor units regularly will result in poor performance, freezing, water leakage, and even compressor failure.
Inspection before maintenance
Following inspection must be carried out by a qualified installer or qualified service person.
Maintenance List
Parts Inspection method
Heat exchanger
Access from inspection opening and remove the access panel. Examine the heat exchanger if there is any clogging or damages.
Fan motor Access from inspection opening and check if any abnormal noise can be heard.
Fan
Access from inspection opening and remove the access panel. Examine the fan if there are any waggles, damages or adhesive dust.
Filter Go to installed location and check if there are any stains or breaks on the filter.
Drain pan
Access from inspection opening and remove the access panel. Check if there is any clogging or drain water is polluted.
Part Unit Check (visual / auditory) Maintenance
Heat exchanger Indoor / outdoor Dust / dirt clogging, scratches
Wash the heat exchanger when it is clogged.
Fan motor Indoor / outdoor Sound
Take appropriate measures when abnormal sound is generated.
Filter Indoor Dust / dirt, breakage
• Wash the filter with water when it is contaminated.
• Replace it when it is damaged.
Fan Indoor
• Vibration, balance
• Dust / dirt, appearance
• Replace the fan when vibration or balance is terrible.
• Brush or wash the fan when it is contaminated.
Air inlet / outlet grilles Indoor / outdoor Dust / dirt, scratches
Fix or replace them when they are deformed or damaged.
Drain pan Indoor
Dust / dirt clogging, drain contamination
Clean the drain pan and check the downward slope for smooth drainage.
Ornamental panel, louvres
Indoor Dust / dirt, scratches
Wash them when they are contaminated or apply repair coating.
Exterior Outdoor
• Rust, peeling of insulator
• Peeling / lift of coat
Apply repair coating.
39-EN 40-EN
Page 22
– 21 –
SMMS Slim Duct Type
Installation Manual
SMMS Slim Duct Type
Installation Manual

12Troubleshooting

Confirmation and check
When an error occurred in the air conditioner, an error code and indoor UNIT No. appear on the display part of the remote controller. The error code is only displayed during the operation. If the display disappears, operate the air conditioner according to the following “Confirmation of error log” for confirmation.
Confirmation of error log
When an error occurred on the air conditioner, the error log can be confirmed with the following procedure. (The error log is stored in memory up to 4 errors.) The log can be confirmed from both operating status and stop status.
1 When and buttons are pushed
simultaneously for 4 seconds or more, the following display appears.
If is displayed, the mode enters in the error log mode.
•[01: Order of error log] is displayed in CODE No..
• [Error code] is displayed in CHECK.
• [Indoor unit address in which an error occurred] is displayed in Unit No..
2 Every pushing of button used to set
temperature, the error log stored in memory is displayed in order.
The numbers in CODE No. indicate CODE No. [01] (latest) [04] (oldest).
REQUIREMENT
Do not push button because all the error log of the indoor unit will be deleted.
3 After confirmation, push button to return
to the usual display.
Error code Indoor UNIT No. in
which an error occurred
3
2
1
41-EN 42-EN
Page 23
– 22 –
SMMS Slim Duct Type
Installation Manual
EN
SMMS Slim Duct Type
Installation Manual
Check method
On the wired remote controller, central control remote controller and the interface P.C. board of the outdoor unit (I/F), a check display LCD (Remote controller) or 7-segment display (on the outdoor interface P.C. board) to display the operation is provided. Therefore the operation status can be known. Using this self-diagnosis function, a trouble or position with error of the air conditioner can be found as shown in the table below.
Check code list
The following list shows each check code. Find the check contents from the list according to part to be checked.
• In case of check from indoor remote controller: See “Wired remote controller display” in the list.
• In case of check from outdoor unit: See “Outdoor unit 7-segment display” in the list.
• In case of check from AI-NET central control remote controller: See “AI-NET central control display” in the list.
• In case of check from indoor unit with a wireless remote controller: See “Sensor block display of receiving unit” in the list. : Lighting, : Flashing, : Goes off
AI-NET: Artificial Intelligence
IPDU: Intelligent Power Drive Unit ALT: Flashing is alternately when there are two flashing LED. SIM: Simultaneous flashing when there are two flashing LED.
Check code Wireless remote controller
Check code name Judging device
Wired remote
controller display
Outdoor unit 7-segment display
AI-NET central
control display
Sensor block display of receiving unit
Auxiliary code Operation Timer Ready Flash
E01
Communication error between indoor unit and remote controller (Detected at remote controller side)
Remote controller
E02 Remote controller transmission error Remote controller
E03 97
Communication error between indoor unit and remote controller (Detected at indoor unit side)
Indoor unit
E04 04
Communication circuit error between indoor / outdoor unit (Detected at indoor unit side)
Indoor unit
E06 E06
No. of indoor units in which sensor has been normally received
04 Decrease of No. of indoor units I/F
—E07
Communication circuit error between indoor / outdoor unit (Detected at outdoor unit side)
I/F
E08 E08 Duplicated indoor unit addresses 96 Duplicated indoor unit addresses Indoor unit • I/F
E09 99 Duplicated master remote controllers Remote controller
E10 CF Communication error between indoor unit MC Indoor unit
E12 E12
01:Indoor / Outdoor units communication 02:Outdoor / Outdoor units communication
42 Automatic address start error I/F
E15 E15 42 No indoor unit during automatic addressing I/F
E16 E16
00:Capacity over 01 ~:No. of connected units
89 Capacity over / No. of connected indoor units I/F
E18 97, 99 Communication error between header and follower units Indoor unit Indoor unit
E19 E19
00:No header 02:Two or more header units
96 Outdoor header units quantity error I/F
E20 E20
01:Outdoor unit of other line connected 02:Indoor unit of other line connected
42 Other line connected during automatic address I/F
E21 E21
02:No header unit 00:Multiple number of header units
42 Error in number of heat storage master units I/F
E22 E22 42 Reduction in number of heat storage units I/F
E23 E23 15
Sending error in communication between outdoor units Error in number of heat storage units (trouble with reception)
I/F
E25 E25 15 Duplicated follower outdoor addresses I/F
E26 E26
No. of outdoor units which received signal normally
15 Decrease of No. of connected outdoor units I/F
E28 E28 Detected outdoor unit number d2 Follower outdoor unit error I/F
E31 E31 Number of IPDU (*1) CF IPDU communication error I/F
43-EN 44-EN
Page 24
– 23 –
SMMS Slim Duct Type
Installation Manual
SMMS Slim Duct Type
Installation Manual
F01 0F ALT Indoor unit TCJ sensor error Indoor unit
F02 0d ALT Indoor unit TC2 sensor error Indoor unit
F03 93 ALT Indoor unit TC1 sensor error Indoor unit
F04 F04 19 ALT TD1 sensor error I/F
F05 F05 A1 ALT TD2 sensor error I/F
F06 F06
01:TE1 sensor 02:TE2 sensor
18 ALT
TE1 sensor error TE2 sensor error
I/F
F07 F07 18 ALT TL sensor error I/F
F08 F08 1b ALT TO sensor error I/F
F10 OC ALT Indoor unit TA sensor error Indoor unit
F12 F12 A2 ALT TS1 sensor error I/F
F13 F13
01:Comp. 1 side 02:Comp. 2 side 03:Comp. 3 side
43 ALT TH sensor error IPDU
F15 F15 18 ALT Outdoor unit temp. sensor miscabling (TE, TL) I/F
F16 F16 43 ALT Outdoor unit pressure sensor miscabling (Pd, Ps) I/F
F22 F22 B2 ALT TD3 sensor error I/F
F23 F23 43 ALT Ps sensor error I/F
F24 F24 43 ALT Pd sensor error I/F
F29 12 SIM Indoor unit other error Indoor unit
F31 F31 1C SIM Indoor unit EEPROM error I/F
H01 H01
01:Comp. 1 side 02:Comp. 2 side 03:Comp. 3 side
IF Compressor break down IPDU
H02 H02
01:Comp. 1 side 02:Comp. 2 side 03:Comp. 3 side
1d Compressor trouble (lock) IPDU
H03 H03
01:Comp. 1 side 02:Comp. 2 side 03:Comp. 3 side
17 Current detect circuit system error IPDU
H04 H04 44 Comp. 1 case thermo operation I/F
H05 H05 TD1 sensor miswiring I/F
H06 H06 20 Low pressure protective operation I/F
H07 H07 d7 Oil level down detective protection I/F
H08 H08
01:TK1 sensor error 02:TK2 sensor error 03:TK3 sensor error 04:TK4 sensor error 05:TK5 sensor error
d4 Oil level detective temp sensor error I/F
H14 H14 44 Comp. 2 case thermo operation I/F
H15 H15 TD2 sensor miswiring I/F
H16 H16
01:TK1 oil circuit system error 02:TK2 oil circuit system error 03:TK3 oil circuit system error 04:TK4 oil circuit system error 05:TK5 oil circuit system error
d7 Oil level detective circuit error I/F
H25 H25 TD3 sensor miswiring I/F
L03 96 SIM Indoor unit centre unit duplicated Indoor unit
Check code Wireless remote controller
Check code name Judging device
Wired remote
controller display
Outdoor unit 7-segment display
AI-NET central
control display
Sensor block display of receiving unit
Auxiliary code Operation Timer Ready Flash
45-EN 46-EN
Page 25
– 24 –
SMMS Slim Duct Type
Installation Manual
EN
SMMS Slim Duct Type
Installation Manual
L04 L04 96 SIM Outdoor unit line address duplicated I/F
L05 96 SIM Duplicated indoor units with priority (Displayed in indoor unit with priority) I/F
L06 L06 No. of indoor units with priority 96 SIM
Duplicated indoor units with priority (Displayed in unit other than indoor unit with priority)
I/F
L07 99 SIM Group line in individual indoor unit Indoor unit
L08 L08 99 SIM Indoor unit group / Address unset Indoor unit, I/F
L09 46 SIM Indoor unit capacity unset Indoor unit
L10 L10 88 SIM Outdoor unit capacity unset I/F
L17 46 SIM Outdoor unit type mismatch error I/F
L20 98 SIM Duplicated central control addresses AI-NET, Indoor unit
L26 L26 Number of heat storage units connected 46 SIM Too many heat storage units connected I/F
L27 L27 Number of heat storage units connected 46 SIM Error in number of heat storage units connected I/F
L28 L28 46 SIM Too many outdoor units connected I/F
L29 L29 Number of IPDU (*1) CF SIM No. of IPDU error I/F
L30 L30 Detected indoor unit address b6 SIM Indoor unit outside interlock Indoor unit
L31 Extended I/C error I/F
P01 11 ALT Indoor fan motor error Indoor unit
P03 P03 1E ALT Discharge temp. TD1 error I/F
P04 P04
01:Comp. 1 side 02:Comp. 2 side 03:Comp. 3 side
21 ALT High-pressure SW system operation IPDU
P05 P05
00: 01:Comp. 1 side 02:Comp. 2 side 03:Comp. 3 side
AF ALT
Phase missing detection / Power failure detection Inverter DC voltage error (comp.) Inverter DC voltage error (comp.) Inverter DC voltage error (comp.)
I/F
P07 P07
01:Comp. 1 side 02:Comp. 2 side 03:Comp. 3 side
IC ALT Heat sink overheat error IPDU, I/F
P09 P09 Detected heat storage address 47 ALT No heat storage unit water error Heat storage unit
P10 P10 Detected indoor unit address Ob ALT Indoor unit overflow error Indoor unit
P12 11 ALT Indoor unit fan motor error Indoor unit
P13 P13 47 ALT Outdoor liquid back detection error I/F
P15 P15
01:TS condition 02:TD condition
AE ALT Gas leak detection I/F
P17 P17 bb ALT Discharge temp. TD2 error I/F
P18 P18 E2 ALT Discharge temp. TD3 error I/F
P19 P19 Detected outdoor unit number O8 ALT 4-way valve inverse error I/F
P20 P20 22 ALT High-pressure protective operation I/F
P22 P22
0*:IGBT circuit 1*:Position detective circuit error 3*:Motor lock error 4*:Motor current detection C*:TH sensor error D*:TH sensor error E*:Inverter DC voltage error (outdoor unit
fan)
1A ALT
Outdoor unit fan IPDU error Note: Ignore 0 to F displayed in “*” position.
IPDU
P26 P26
01:Comp. 1 side 02:Comp. 2 side 03:Comp. 3 side
14 ALT G-TR short protection error IPDU
Check code Wireless remote controller
Check code name Judging device
Wired remote
controller display
Outdoor unit 7-segment display
AI-NET central
control display
Sensor block display of receiving unit
Auxiliary code Operation Timer Ready Flash
47-EN 48-EN
Page 26
– 25 –
SMMS Slim Duct Type
Installation Manual
SMMS Slim Duct Type
Installation Manual
Error detected by TCC-LINK central control device
TCC-LINK: TOSHIBA Carrier Communication Link.
P29 P29
01:Comp. 1 side 02:Comp. 2 side 03:Comp. 3 side
16 ALT Comp. position detective circuit system error IPDU
P31 47 ALT
Other indoor unit error (Group follower indoor unit error)
Indoor unit
b7 By alarm device ALT Error in indoor unit group AI-NET
97 AI-NET communication system error AI-NET
99 Duplicated network adapters AI-NET
*1 Number of IPDU
01: Comp. 1 02: Comp. 2 03: Comp. 1 + Comp. 2 04: Comp. 3
05: Comp. 1 + Comp. 3 06: Comp. 2 + Comp. 3 07: Comp. 1 + Comp. 2 + Comp. 3 08: Fan
09: Comp. 1 + Fan 0A: Comp. 2 + Fan 0B: Comp. 1 + Comp. 2 + Fan 0C: Comp. 3 + Fan
0D: Comp. 1 + Comp. 3 + Fan 0E: Comp. 2 + Comp. 3 + Fan 0F: Comp. 1 + Comp. 2 + Comp. 3 + Fan
Check code Wireless remote controller
Check code name Judging device
Central control device
indication
Outdoor unit 7-segment display
AI-NET central
control display
Sensor block display of receiving unit
Auxiliary code Operation Timer Ready Flash
C05 Sending error in TCC-LINK central control device TCC-LINK
C06 Receiving error in TCC-LINK central control device TCC-LINK
C12 Batch alarm of general-purpose equipment control interface
General-purpose equipment,
I/F
P30
Differs according to error contents of unit with occurrence of alarm Group control follower unit error
TCC-LINK
(L20 is displayed.) Decrease of No. of indoor units
Check code Wireless remote controller
Check code name Judging device
Wired remote
controller display
Outdoor unit 7-segment display
AI-NET central
control display
Sensor block display of receiving unit
Auxiliary code Operation Timer Ready Flash
49-EN 50-EN
Page 27
– 26 –
SMMS Slim Duct Type
Installation Manual
EN
SMMS Slim Duct Type
Installation Manual

13Specifications

* Under 70 dBA
Model
Sound power level (dBA)
Weight (kg) Main unit
Cooling Heating
MMD-AP0074SPH-E * * 22
MMD-AP0094SPH-E * * 22
MMD-AP0124SPH-E * * 22
MMD-AP0154SPH-E * * 23
MMD-AP0184SPH-E * * 23
Declaration of Conformity
NOTE
This declaration becomes invalid if technical or operational modifications are introduced without the manufacturer’s consent.
Manufacturer: Toshiba Carrier Corporation
336 Tadehara, Fuji-shi, Shizuoka-ken 416-8521 JAPAN
Authorized Representative / TCF holder:
Nick Ball Toshiba EMEA Engineering Director Toshiba Carrier UK Ltd. Porsham Close, Belliver Industrial Estate, PLYMOUTH, Devon, PL6 7DB. United Kingdom
Hereby declares that the machinery described below:
Generic Denomination: Air Conditioner
Model / type: MMD-AP0074SPH-E, MMD-AP0094SPH-E, MMD-AP0124SPH-E,
MMD-AP0154SPH-E, MMD-AP0184SPH-E
Commercial name: Super Modular Multi System Air Conditioner
Super Heat Recovery Multi System Air Conditioner Mini-Super Modular Multi System Air Conditioner (MiNi-SMMS series)
Complies with the provisions of the “Machinery” Directive (Directive 2006/42/EC) and the regulations transposing into national law
“Declaration of incorporation of partly completed machinery”
Must not be put into service until the final machinery into which it is to be incorporated has been declared in conformity with the provisions of this Directive, where appropriate.
Complies with the provisions of the following harmonized standard:
EN 378-2: 2008+A1: 2009
51-EN 52-EN
Page 28
– 27 –
SMMS Slim Duct Type
Installation Manual
SMMS Slim Duct Type
Installation Manual
Warnings on Refrigerant Leakage
Check of Concentration Limit
The room in which the air conditioner is to be installed requires a design that in the event of refrigerant gas leaking out, its concentration will not exceed a set limit.
The refrigerant R410A which is used in the air conditioner is safe, without the toxicity or combustibility of ammonia, and is not restricted by laws to be imposed which protect the ozone layer. However, since it contains more than air, it poses the risk of suffocation if its concentration should rise excessively. Suffocation from leakage of R410A is almost non-existent. With the recent increase in the number of high concentration buildings, however, the installation of multi air conditioner systems is on the increase because of the need for effective use of floor space, individual control, energy conservation by curtailing heat and carrying power etc. Most importantly, the multi air conditioner system is able to replenish a large amount of refrigerant compared with conventional individual air conditioners. If a single unit of the multi conditioner system is to be installed in a small room, select a suitable model and installation procedure so that if the refrigerant accidentally leaks out, its concentration does not reach the limit (and in the event of an emergency, measures can be made before injury can occur). In a room where the concentration may exceed the limit, create an opening with adjacent rooms, or install mechanical ventilation combined with a gas leak detection device.The concentration is as given below.
The concentration limit of R410A which is used in multi air conditioners is 0.3 kg/m
3
.
NOTE 1
If there are 2 or more refrigerating systems in a single refrigerating device, the amounts of refrigerant should be as charged in each independent device.
For the amount of charge in this example:
The possible amount of leaked refrigerant gas in rooms A, B and C is 10 kg. The possible amount of leaked refrigerant gas in rooms D, E and F is 15 kg.
NOTE 2
The standards for minimum room volume are as follows.
1) No partition (shaded portion)
Total amount of refrigerant (kg)
Min. volume of the indoor unit installed room (m3)
Concentration limit (kg/m
3
)
e.g., charged amount (10 kg)
e.g., charged amount (15 kg)
Outdoor unit
Indoor unit
Room A Room B Room C Room D Room E Room F
2) When there is an effective opening with the adjacent room for ventilation of leaking refrigerant gas (opening without a door, or an opening 0.15 % or larger than the respective floor spaces at the top or bottom of the door).
3) If an indoor unit is installed in each partitioned room and the refrigerant piping is interconnected, the smallest room of course becomes the object. But when a mechanical ventilation is installed interlocked with a gas leakage detector in the smallest room where the density limit is exceeded, the volume of the next smallest room becomes the object.
NOTE 3
The minimum indoor floor area compared with the amount of refrigerant is roughly as follows: (When the ceiling is 2.7 m high)
Important
Refrigerant piping
Indoor unit
Outdoor unit
Outdoor unit
Very small room
Refrigerant piping
Indoor unit
Mechanical ventilation device - Gas leak detector
Small room
Medium room
Large room
0
5
10
10 20 30
15
20
25
30
35
40
m
2
kg
Min. indoor floor area
Range above the density limit of 0.3 kg/m
3
(countermeasures needed)
Range below the density limit of
0.3 kg/m
3
(countermeasures not needed)
Total amount of refrigerant
53-EN 54-EN
Page 29
– 28 –
SMMS Slim Duct Type
Installation Manual
EN
SMMS Slim Duct Type
Installation Manual
Confirmation of indoor unit setup
Prior to delivery to the customer, check the address and setup of the indoor unit, which has been installed in this time and fill the check sheet (Table below).
Data of four units can be entered in this check sheet. Copy this sheet according to the No. of the indoor units. If the installed system is a group control system,
use this sheet by entering each line system into each installation manual attached to the other indoor units.
REQUIREMENT
This check sheet is required for maintenance after installation. Fill this sheet and then pass this Installation Manual to the customers.
Indoor unit setup check sheet
Indoor unit Indoor unit Indoor unit Indoor unit
Room name Room name Room name Room name
Model Model Model Model
Check indoor unit address. (For check method, refer to APPLICABLE CONTROLS in this manual.)
*In case of a single system, it is unnecessary to enter the indoor address. (CODE NO.: Line [12], Indoor [13], Group [14], Central control [03])
Line Indoor Group Line Indoor Group Line Indoor Group Line Indoor Group
Central control address Central control address Central control address Central control address
Various setup Various setup Various setup Various setup
Have you changed high ceiling setup? If not, fill check mark [×] in [NO CHANGE], and fill check mark [×] in [ITEM] if changed, respectively.
(For check method, refer to APPLICABLE CONTROLS in this manual.) * In case of replacement of jumper blocks on indoor microcomputer P.C. board,
setup is automatically changed.
External static pressure
(CODE NO. [5d])
F NO CHANGE
F STANDARD [0000]
F HIGH STATIC 1 [0001]
F HIGH STATIC 2 [0003]
F HIGH STATIC 3 [0006]
External static pressure
(CODE NO. [5d])
F NO CHANGE
F STANDARD [0000]
F HIGH STATIC 1 [0001]
F HIGH STATIC 2 [0003]
F HIGH STATIC 3 [0006]
External static pressure
(CODE NO. [5d])
F NO CHANGE
F STANDARD [0000]
F HIGH STATIC 1 [0001]
F HIGH STATIC 2 [0003]
F HIGH STATIC 3 [0006]
External static pressure
(CODE NO. [5d])
F NO CHANGE
F STANDARD [0000]
F HIGH STATIC 1 [0001]
F HIGH STATIC 2 [0003]
F HIGH STATIC 3 [0006]
Have you changed lighting time of filter sign? If not, fill check mark [×] in [NO CHANGE], and fill check mark [×] in [ITEM] if changed, respectively.
(For check method, refer to APPLICABLE CONTROLS in this manual.)
Filter sign lighting time
(CODE NO. [01])
F NO CHANGE
F NONE [0000]
F 150H [0001]
F 2500H [0002]
F 5000H [0003]
F 10000H [0004]
Filter sign lighting time
(CODE NO. [01])
F NO CHANGE
F NONE [0000]
F 150H [0001]
F 2500H [0002]
F
5000H [0003]
F 10000H [0004]
Filter sign lighting time
(CODE NO. [01])
F NO CHANGE
F NONE [0000]
F 150H [0001]
F 2500H [0002]
F 5000H [0003]
F 10000H [0004]
Filter sign lighting time
(CODE NO. [01])
F NO CHANGE
F NONE [0000]
F 150H [0001]
F 2500H [0002]
F 5000H [0003]
F 10000H [0004]
Have you changed detected temp. shift value? If not, fill check mark [×] in [NO CHANGE], and fill check mark [×] in [ITEM] if changed, respectively.
(For check method, refer to APPLICABLE CONTROLS in this manual.)
Detected temp. shift value setup
(CODE NO. [06])
F NO CHANGE
F NO SHIFT [0000]
F +1°C [0001]
F +2°C [0002]
F +3°C [0003]
F +4°C [0004]
F +5°C [0005]
F +6°C [0006]
Detected temp. shift value setup
(CODE NO. [06])
F NO CHANGE
F NO SHIFT [0000]
F +1°C [0001]
F +2°C [0002]
F +3°C [0003]
F +4°C [0004]
F +5°C [0005]
F +6°C [0006]
Detected temp. shift value setup
(CODE NO. [06])
F NO CHANGE
F NO SHIFT [0000]
F +1°C [0001]
F +2°C [0002]
F +3°C [0003]
F +4°C [0004]
F +5°C [0005]
F +6°C [0006]
Detected temp. shift value setup
(CODE NO. [06])
F NO CHANGE
F NO SHIFT [0000]
F +1°C [0001]
F +2°C [0002]
F +3°C [0003]
F +4°C [0004]
F +5°C [0005]
F +6°C [0006]
Incorporation of parts sold
separately
Incorporation of parts sold
separately
Incorporation of parts sold
separately
Incorporation of parts sold
separately
F Others ( )
F Others ( )
F Others ( )
F Others ( )
F Others ( )
F Others ( )
F Others ( )
F Others ( )
55-EN 56-EN
Page 30
EH99879399
Loading...