Toshiba MITOS VT6 AIR User Manual

02/10/2015
Manual_MITOS_VT6_AIR_ver3p3_eng
MITOS VT6 AIR
02/10/2015
2 / 17
Manual_MITOS_VT6_AIR_ver3p3_eng
Summary:
GENERAL DESCRIPTION ............................................................................................................................................. 3
GENERAL FEATURES ................................................................................................................................................... 3
FUNCTIONING PARAMETERS .................................................................................................................................... 4
FUNCTIONING MODE OF THE “MITOS VT6 AIR ..................................................................................................... 7
FUNCTIONING JUST DISPLAY ................................................................................................................................. 7
FUNCTIONING “MANUAL” ........................................................................................................................................... 8
FUNCTIONING “AUTOMATIC PID” ............................................................................................................................. 9
PRESSURE / VELOCITY / FLOW RESET .................................................................................................................. 11
RESET INVERTER ALARM ........................................................................................................................................ 11
SELECTION OF SERIAL COMMUNICATION TTL/RS485 ...................................................................................... 11
CONNECTION FOR PRESSURE MEASURE / REGULATION ................................................................................. 12
CONNECTION FOR FLOW OR VELOCITY MEASURE/REGULATION ................................................................ 14
MECHANICAL DIMENSIONS .................................................................................................................................... 15
APPENDIX ..................................................................................................................................................................... 16
02/10/2015
3 / 17
Manual_MITOS_VT6_AIR_ver3p3_eng
GENERAL DESCRIPTION
MITOS VT6 AIR is a measure, visualization and control device for pressure, velocity and flow. It has got a temperature sensor (internal) and a differential pressure sensor with two possible range:
+/-999mmH
2
O +/-1% F.S.
+/-2999mmH
2
O +/-1% F.S.
The precision of the pressure measurement is optimized by the compensation in function of the temperature. It is equipped with 6 buttons and 1 LCD 16x2 lines display (2 lines and 16 fonts each line). It is also programmable by a menu. The control is done by a VF-S11, VF-FS1, VF-AS1 VF-NC3, VF-MB1, VF-S15 or VF-PS1 Toshiba inverter, using a simple TTL serial connection (VF-S11 inverter) or RS485 (other inverter) and it can be manual or automatic. The selection of the type of serial connection can be selected by a dip-switch placed on the back of the box. Manual control allow to command run/stop and/or the inverter frequency. The frequency sent is fixed and is programmable from the display menu. Automatic control commands run/stop and also regulate the frequency sent to the inverter in order to keep the pressure, velocity or flow (selectable) at a fixed level, programmable from the display menu. Automatic control uses a PID regulation characterized by proportional, integrative and derivative parameters, changeable from the programming menu. MITOS VT6 AIR can also visualize some functioning parameters of the inverter, such as current and power delivered, input and output voltage, frequency, hours of functioning, historic of the last four alarms. Available scales for pressure, velocity and flow are:
Pressure: mmH
2
O; mbar; Pascal; Kpascal. Velocity: second meter Flow: hundreds of cube meters per hour; cube meters per second; litres per second.
GENERAL FEATURES
MITOS VT6 AIR has got the following features
Case: Material: ABS. IP65 protection degree Alimentation: The alimentation is directly taken by the inverter through the serial connecting cable.
The current consumption is: 25mA @ 24 VDC
Working temperature: From -5 to +50 °C Box dimensions: 120 x 65 x 35 mm. Weight: 350g. Input: 1 differential pressure gauge with two possible range
+/-999mmH2O +/-1% F.S. +/-2999mmH2O +/-1% F.S.
User interfaces: Monocromatic graphic display 2x32 types, 6 buttons (START, MAN/AUTO, UP, DOWN,
MON, STOP/RESET)
02/10/2015
4 / 17
Manual_MITOS_VT6_AIR_ver3p3_eng
FUNCTIONING PARAMETERS
The parameters programming menu is accessible in the normal functioning menu, by pushing MON button for at least 3 seconds. After the 3 seconds, it is necessary to insert a password. With UP and DOWN, you can change the number referred to the password, between 0 and 999. Once set the correct value, press MON to confirm. Each wrong password value allows to view just a part of the available parameters, the first eight in the following pattern. In the programming menu, you can select the parameter with the buttons UP and DOWN. Then, when the parameter is selected, the parameter will flash pressing the button MON. Value can be changed through buttons UP and DOWN. To store the new value, you need to press again MON (the parameter stops flashing). To quit the programming menu, just press MAN/AUTO. Here follow all the functioning parameters of MITOS VT6 AIR.
PARAMETER
FUNCTION
POSSIBLE VALUES
Hysteresis
If the PID control is enabled, this act only if:
V >
Set point PID + Hysteresis
or
V <
Set point PID - Hysteresis
where V is the value measured by the controlled variable
min = 0; max (
2
) appendix
Constant PID Kp
PID control proportional constant
0.0 ÷ 300.0
Constant PID Ki
PID control integrative constant
0.0 ÷ 300.0
Constant PID Kd
PID control derivative constant
0.0 ÷ 300.0
ACC manual
Value of the ACC parameter sent to the inverter when Type command = MANUAL.
0.1 ÷ 320.0 sec.
DEC manual
Value of the DEC parameter sent to the inverter when Type command = MANUAL.
0.
1 ÷ 320.0 sec.
ACC automatic
Value of the ACC parameter sent to the inverter when Type command = AUTOMATIC.
0.1 ÷ 320.0 sec.
DEC automatic
Value of the DEC parameter sent to the inverter when Type command = AUTOMATIC.
0.1 ÷ 320.0 sec.
Mode
MITOS VT6 AIR can be used as a simple display, but it can also send run and/or frequency variation commends to the Inverter
-
COMMAND
-
VISUALIZATOR
Rotation sense
Sense of engine rotation
- AHEAD
- BACK
Feedback
Type of variable where the control PID is performed
- PRESSURE
-
VELOCITY
- FLOW
Pressure unit
Pressure Unit of measurement
-
mmH2O
-
Pa
-
kPa
-
mBar
Flow unit
Flow Unit of measurement
-
m3 / h (value per 100)
-
m3 / s
-
l / s
Velocity unit
Velocity Unit of measurement
m / s
PID Set point
Set the set-point of the variable where the PID control is performed
min = 0; max (
2
) appendix
02/10/2015
5 / 17
Manual_MITOS_VT6_AIR_ver3p3_eng
PARAMETER
FUNCTION
POSSIBLE VALUES
PID Type
Type of PID control
- PID proport.-integr.-derivative
-
PI proportional.-integr
ative
-
P proportional
- PD proportional.-derivative
PID ACC/DEC delay
In AUTOMATIC mode, Inverter starts working through ACC/DEC ramps equal to ACC MANUAL/DEC MANUAL. When the controlled variable reaches the set
-point,
ACC/DEC are automatically set to the values ACC AUTOMATIC / DEC AUTOMATIC. This configuration remains till the stop of the Inverter. If the controlled variable does not reach the set­point within PID ACC/DEC
Delay
seconds from the start, ACC/DEC are set to the values ACC AUTOMATIC/DEC AUTOMATIC
0
-999 sec.
Velocity calculation
Type of velocity calculation. The setting AIR has to be used in case the fluid present in the pipe is air. Otherwise, you may use the GENERIC setting. During velocity calculation with the section AIR, you need to set also the fluid temperature in °C, through the parameter
Fluid Temperature.
The calculation of the velocity with GENERIC setting is base on the following formula::
v = k
P
[m/s]
where k =
Velocity Constant
(settable) and P is
the differential pressure in mmHH
2
O.
GENERIC AIR
Pipe type
Sets the pipe section.
- RECTANGUL.
- CIRCULAR
Pipe diameter
Circular pipe diameter (mm)
0 2000 mm
Pipe side 1
Rectangular pipe’s side 1 size (mm)
0 2000 mm
Pipe side 2
Circular pipe’s side 1 size (mm)
0 2000 mm
Fluid temperature
Temperature of the fluid in the pipe (°C) 0
200 °C
Speed constant
Sets the constant value in the generic formula for
0.01 99.99
Language
Sets the language of the menu
- GERMAN
-
ITALIAN
-
ENGLISH
- SPANISH
Command type
If the
MITOS VT6 AIR is enabled to send
commands to the inverter (
Mode =
COMMAND) and it has the complete control of the inverter (run
-
stop and frequency variation
(
1
)), the Command type
parameter determines the
way the commands are sent
-
MANUAL
-
AUTOMATIC (PID)
02/10/2015
6 / 17
Manual_MITOS_VT6_AIR_ver3p3_eng
PARAMETER
FUNCTION
POSSIBLE VALUES
Var. monitor1
Sets the monitor variable shown in the first line of the normal functioning display menu.
Var. monitor1
will be visualized only in the
following cases:
Mode
= MONITOR
or
1)
Mode = COMMAND
2) the
MITOS VT6 AIR has only the run/stop
command (
1
)
see appendix (
3
)
Var. monitor2
Sets the monitor variable shown in the second line of the normal functioning display menu. Var. monitor2 will always be visualized and can be changed pushing UP and DOWN buttons while keeping F2 key pushed. But
in this case the
selection will be kept only until the device is on
see appendix (
3
)
Set point manual
Sets the value of the frequency sent to the inverter in MANUAL functioning. This value can be modified from the normal functioning menu
0.0
500.0 Hz
Store set point
It allows to store automatically or not the set point variation chosen with the UP and DOWN keys. Selecting YES, the set point variation (of the frequency or of the variable regulated in the PID control) from the normal functioning menu, is automatically stored. Selecting NO, the set point variation is not automatically stored and when you turn on the device again the value reloaded is the one saved using the parameters programming menu.
-
YES
-
NO