Manual_MITOS_VT6_AIR_ver3p3_eng
MITOS VT6 AIR
USER MANUAL

Manual_MITOS_VT6_AIR_ver3p3_eng
Summary:
GENERAL DESCRIPTION ............................................................................................................................................. 3
GENERAL FEATURES ................................................................................................................................................... 3
FUNCTIONING PARAMETERS .................................................................................................................................... 4
FUNCTIONING MODE OF THE “MITOS VT6 AIR” ..................................................................................................... 7
FUNCTIONING “JUST DISPLAY” ................................................................................................................................. 7
FUNCTIONING “MANUAL” ........................................................................................................................................... 8
FUNCTIONING “AUTOMATIC PID” ............................................................................................................................. 9
PRESSURE / VELOCITY / FLOW RESET .................................................................................................................. 11
RESET INVERTER ALARM ........................................................................................................................................ 11
SELECTION OF SERIAL COMMUNICATION TTL/RS485 ...................................................................................... 11
CONNECTION FOR PRESSURE MEASURE / REGULATION ................................................................................. 12
CONNECTION FOR FLOW OR VELOCITY MEASURE/REGULATION ................................................................ 14
MECHANICAL DIMENSIONS .................................................................................................................................... 15
APPENDIX ..................................................................................................................................................................... 16

Manual_MITOS_VT6_AIR_ver3p3_eng
GENERAL DESCRIPTION
MITOS VT6 AIR is a measure, visualization and control device for pressure, velocity and flow. It has got a temperature
sensor (internal) and a differential pressure sensor with two possible range:
+/-999mmH
2
O +/-1% F.S.
+/-2999mmH
2
O +/-1% F.S.
The precision of the pressure measurement is optimized by the compensation in function of the temperature. It is
equipped with 6 buttons and 1 LCD 16x2 lines display (2 lines and 16 fonts each line). It is also programmable by a
menu.
The control is done by a VF-S11, VF-FS1, VF-AS1 VF-NC3, VF-MB1, VF-S15 or VF-PS1 Toshiba inverter, using a
simple TTL serial connection (VF-S11 inverter) or RS485 (other inverter) and it can be manual or automatic. The
selection of the type of serial connection can be selected by a dip-switch placed on the back of the box.
Manual control allow to command run/stop and/or the inverter frequency. The frequency sent is fixed and is
programmable from the display menu.
Automatic control commands run/stop and also regulate the frequency sent to the inverter in order to keep the pressure,
velocity or flow (selectable) at a fixed level, programmable from the display menu. Automatic control uses a PID
regulation characterized by proportional, integrative and derivative parameters, changeable from the programming
menu.
MITOS VT6 AIR can also visualize some functioning parameters of the inverter, such as current and power delivered,
input and output voltage, frequency, hours of functioning, historic of the last four alarms.
Available scales for pressure, velocity and flow are:
Pressure: mmH
2
O; mbar; Pascal; Kpascal.
Velocity: second meter
Flow: hundreds of cube meters per hour; cube meters per second; litres per second.
GENERAL FEATURES
MITOS VT6 AIR has got the following features
Case: Material: ABS. IP65 protection degree
Alimentation: The alimentation is directly taken by the inverter through the serial connecting cable.
The current consumption is: 25mA @ 24 VDC
Working temperature: From -5 to +50 °C
Box dimensions: 120 x 65 x 35 mm.
Weight: 350g.
Input: 1 differential pressure gauge with two possible range
+/-999mmH2O +/-1% F.S.
+/-2999mmH2O +/-1% F.S.
User interfaces: Monocromatic graphic display 2x32 types, 6 buttons (START, MAN/AUTO, UP, DOWN,
MON, STOP/RESET)

Manual_MITOS_VT6_AIR_ver3p3_eng
FUNCTIONING PARAMETERS
The parameters programming menu is accessible in the normal functioning menu, by pushing MON button for at least 3
seconds. After the 3 seconds, it is necessary to insert a password. With UP and DOWN, you can change the number
referred to the password, between 0 and 999. Once set the correct value, press MON to confirm. Each wrong password
value allows to view just a part of the available parameters, the first eight in the following pattern. In the programming
menu, you can select the parameter with the buttons UP and DOWN. Then, when the parameter is selected, the
parameter will flash pressing the button MON. Value can be changed through buttons UP and DOWN. To store the new
value, you need to press again MON (the parameter stops flashing). To quit the programming menu, just press
MAN/AUTO.
Here follow all the functioning parameters of MITOS VT6 AIR.
If the PID control is enabled, this act only if:
Set point PID + Hysteresis
Set point PID - Hysteresis
where V is the value measured by the controlled
variable
PID control proportional constant
PID control integrative constant
PID control derivative constant
Value of the ACC parameter sent to the inverter
when Type command = MANUAL.
Value of the DEC parameter sent to the inverter
when Type command = MANUAL.
Value of the ACC parameter sent to the inverter
when Type command = AUTOMATIC.
Value of the DEC parameter sent to the inverter
when Type command = AUTOMATIC.
MITOS VT6 AIR can be used as a simple
display, but it can also send run and/or frequency
variation commends to the Inverter
Type of variable where the control PID is
performed
Pressure Unit of measurement
Velocity Unit of measurement
Set the set-point of the variable where the PID
control is performed

Manual_MITOS_VT6_AIR_ver3p3_eng
- PID proport.-integr.-derivative
-
- PD proportional.-derivative
In AUTOMATIC mode, Inverter starts working
through ACC/DEC ramps equal to ACC
MANUAL/DEC MANUAL. When the
controlled variable reaches the set
ACC/DEC are automatically set to the values
ACC AUTOMATIC / DEC AUTOMATIC.
This configuration remains till the stop of the
Inverter.
If the controlled variable does not reach the setpoint within PID ACC/DEC
seconds from
the start, ACC/DEC are set to the values ACC
AUTOMATIC/DEC AUTOMATIC
Type of velocity calculation.
The setting AIR has to be used in case the fluid
present in the pipe is air. Otherwise, you may use
the GENERIC setting. During velocity
calculation with the section AIR, you need to set
also the fluid temperature in °C, through the
parameter
The calculation of the velocity with GENERIC
setting is base on the following formula::
(settable) and P is
the differential pressure in mmHH
Circular pipe diameter (mm)
Rectangular pipe’s side 1 size (mm)
Circular pipe’s side 1 size (mm)
Temperature of the fluid in the pipe (°C)
0
Sets the constant value in the generic formula for
Sets the language of the menu
MITOS VT6 AIR is enabled to send
commands to the inverter (
COMMAND) and it has the complete control of
the inverter (run
stop and frequency variation
(
parameter determines the
way the commands are sent

Manual_MITOS_VT6_AIR_ver3p3_eng
Sets the monitor variable shown in the first line
of the normal functioning display menu.
will be visualized only in the
MITOS VT6 AIR has only the run/stop
Sets the monitor variable shown in the second
line of the normal functioning display menu.
Var. monitor2 will always be visualized and can
be changed pushing UP and DOWN buttons
while keeping F2 key pushed. But
in this case the
selection will be kept only until the device is on
Sets the value of the frequency sent to the
inverter in MANUAL functioning. This value
can be modified from the normal functioning
menu
It allows to store automatically or not the set
point variation chosen with the UP and DOWN
keys.
Selecting YES, the set point variation (of the
frequency or of the variable regulated in the PID
control) from the normal functioning menu, is
automatically stored.
Selecting NO, the set point variation is not
automatically stored and when you turn on the
device again the value reloaded is the one saved
using the parameters programming menu.