•Connects easily to the M-2001 Series Digital Tapchanger Control using
mounting screws and 24-pin connector
•Provides direct mechanical replacement of the existing regulator control
•Provides built-in CT shorting protection when the M-2001 Series Digital
Tapchanger Control is removed
The M-2299 is an adapter panel which, when combined with the M-2001 Series Digital Tapchanger
Control, provides convenient direct replacement of Toshiba TB-R800 regulators. The M-2299 mounts into
the control cabinet using the same two hinge pins which
must be saved
from the original regulator.
Interface
External connections are made via a wiring harness that connects from a fifteen-position terminal block to
the ”BT” terminal block on the existing control cabinet. An additional terminal block provides access to
auxiliary functions, including self-test alarm, user-programmable alarm, auto disable and manual raise/
lower.
Features
Separate fuses for test terminal, voltage sensing and motor power are on the front panel. Spare fuses for
each are in the fuse holder.
Binding posts on the front panel allow easy connections for test procedures.
RAISE/OFF/LOWER, AUTO/OFF/MANUAL, and VOLTAGE SOURCE switches and NEUTRAL LIGHT
are standard.
NEUTRAL LIGHT will light to indicate that the regulator is in the neutral position, for those regulators
equipped with a circuit for this purpose.
Testing Specifications
High Voltage: All input and output terminals will withstand 1500 V ac rms to chassis or instrument ground
for one minute with a leakage current not to exceed 25 mA, for all terminals to ground. Input and output
circuits are electrically isolated from each other, from other circuits and from ground.
Surge Withstand Capability: All input and output circuits are protected against system transients. Units
pass all requirements of ANSI/IEEE C.37.90.1-1989 defining surge withstand capability.
Radiated Electromagnetic Withstand Capability: All units are protected against electromagnetic radiated interference from portable communications transceivers.
Environmental
Temperature Range: Functionality is maintained from –40° to +85° C.
Humidity: Functionality is maintained under 95% relative humidity (non-condensing).
DANGEROUS VOLTAGES,capable of causing death or serious
injury, are present on the external terminals and inside the equipment. Use extreme caution and follow all safety rules when handling, testing or adjusting the equipment. However, these internal
voltage levels are no greater than the voltages applied to the external terminals.
DANGER! HIGH VOLTAGE
–This sign warns that the area is connected to a dangerous high voltage, and you
must never touch it.
PERSONNEL SAFETY PRECAUTIONS
The following general rules and other specific warnings throughout the manual must be followed during application,
test or repair of this equipment. Failure to do so will violate standards for safety in the design, manufacture, and intended
use of the product. Qualified personnel should be the only ones who operate and maintain this equipment. Beckwith
Electric Co., Inc. assumes no liability for the customer’s failure to comply with these requirements.
–This sign means that you should refer to the corresponding section of the operation
manual for important information before proceeding.
Always Ground the Equipment
To avoid possible shock hazard, the chassis must be connected to an electrical ground. When servicing
equipment in a test area, the Protective Earth Terminal must be attached to a separate ground securely
by use of a tool, since it is not grounded by external connectors.
Do NOT operate in an explosive environment
Do not operate this equipment in the presence of flammable or explosive gases or fumes. To do so would
risk a possible fire or explosion.
Keep away from live circuits
Operating personnel must not remove the cover or expose the printed circuit board while power is applied. In no case may components be replaced with power applied. In some instances, dangerous voltages may exist even when power is disconnected. To avoid electrical shock, always disconnect power and
discharge circuits before working on the unit.
Exercise care during installation, operation, & maintenance procedures
The equipment described in this manual contains voltages high enough to cause serious injury or death.
Only qualified personnel should install, operate, test, and maintain this equipment. Be sure that all personnel safety procedures are carefully followed. Exercise due care when operating or servicing alone.
Do not modify equipment
Do not perform any unauthorized modifications on this instrument. Return of the unit to a Beckwith
Electric repair facility is preferred. If authorized modifications are to be attempted, be sure to follow
replacement procedures carefully to assure that safety features are maintained.
PRODUCT CAUTIONS
Before attempting any test, calibration, or maintenance procedure, personnel must be completely familiar
with the particular circuitry of this unit, and have an adequate understanding of field effect devices. If a
component is found to be defective, always follow replacement procedures carefully to that assure safety
features are maintained. Always replace components with those of equal or better quality as shown in the
Parts List of the Instruction Book.
Avoid static charge
This unit contains MOS circuitry, which can be damaged by improper test or rework procedures. Care
should be taken to avoid static charge on work surfaces and service personnel.
Use caution when measuring resistances
Any attempt to measure resistances between points on the printed circuit board, unless otherwise noted
in the Instruction Book, is likely to cause damage to the unit.
The Beckwith Electric M-2299 Adapter Panel, used
in conjunction with the M-2001 Series Digital
Tapchanger Control, uses modern electronic digital
design and digital processing circuitry to achieve
an overall stability and resolution unattainable with
electromechanical and analog design tapchanger
controls. CMOS semiconductors are used throughout
the design.
NOTE: The hinge pins
must be saved
from the
original control. The BT terminal blocks remain in
the control cabinet.
1.0Description
Standard Features
The M-2299 Adapter Panel, with the M-2001 Series
Digital Tapchanger Control, provides a solid-state
voltage control relay designed to directly replace
the Toshiba TB-R800 control. The combination of
the Tapchanger Control and Adapter Panel includes
the following features:
1.Voltage waveform sampling and digital
processing circuitry ensure accurate rms
voltage sensing in the presence of
distortion on the input voltage and
current.
2.Accuracy exceeds the ANSI/IEEE
C57.15-1986 Class 1 specification over
the temperature range of –40° C to
+70° C.
4.Separate motor power, test terminal and
voltage sensing fuses are easily
changed from the front panel and spare
fuses are provided in their respective
fuseholders.
5.Easily tested by use of the following:
a. VOLTAGE SOURCE switch
disconnects the voltage transformer
input and connects the VOLTAGEIN binding posts to the voltage input
and motor circuit.
b. VOLTAGE IN binding posts on the
front panel allow application of a
120 V rms nominal voltage to the
unit for test procedures.
c. METER OUT binding posts on the
front panel allow reading of the input
voltage when used in conjunction
with the BIAS TEST VOLTAGE
screen of the M-2001 Series Digital
Tapchanger Control.
d. RAISE and LOWER band edge LEDs
on the M-2001 Tapchanger Control
indicate when the input voltage is
outside the voltage band.
6.NEUTRAL light illuminates when the
regulator is in the neutral tap position.
7.AUTO/OFF/MANUAL switch allows
manual operation of the control.
3.Input and output circuits are protected
against system transients. Units pass
all requirements of ANSI/IEEE C37.90.11989, which defines surge withstand
capability. All input and output terminals
will withstand 1500 V ac rms to chassis
or instrument ground for one minute with
a leakage current not to exceed 25 mA,
from all terminals to ground. Input and
output circuits are electrically isolated
from each other, from other circuits and
from ground.
–1–
Loading...
+ 17 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.