Toshiba LF654, LF620F User Manual

Field Intelligent Device – Mount Anywhere Series - Flanged
Electromagnetic Flowmeter
Introduction
The electromagnetic flowmeter uses Faraday’s Law of electromagnetic induction to measure the process flow. The device consists of two units: a detector, through which the fluid to be measured flows and in which low-level signals proportional to flow rates are obtained; and a converter, which supplies excitation current to the detector, and amplifies the signals from the detector and then processes and converts the signals into the 4–20 mAdc current signal or communication signal. The meter features a Mount-Anywhere magnetic field distribution technology, the meter is highly immune to upstream flow disturbances. Combined with a multi-functional converter LF620 (combined type) or LF622 (separate type) equipped with its patented Noise-Sentry original noise­suppression circuit and advanced algorithms. The LF654 has a very high tolerance to noise, giving the unit a very stable output even for slurry fluid measurement. IR (Infrared) switches enable parameter setting of the converter without removing the cover. Flow direction can be set in either way, and its unique 128 x 128 dot matrix LCD display allows the LCD to be rotated electronically to 90, 180 and 270 degrees without opening the cover.
* HART protocol (Highway Addressable Remote Transducer) is
a communication protocol for industrial sensors recommended by the HCF (HART Communication Foundation).
** DevComm2000 Smart Device Communicator available
through TIC for performing HART device configurations on PC or laptop .
* PROFIBUS is the communications protocol for factory and
process automation that the PROFIBUS Organization recommends. Instead of analog control with a conventional analog signal (4-20 mA), it is fieldbus which digitizes all signals. Flowmeters support PROFIBUS-PA.
* Modbus is the communication protocol that Modicon Inc.
developed. Physical layer is RS485.
LF654 /LF620 LF654 /LF622
1/2" to 18" (15 to 450 mm)
LF654/LF620F LF654 LF622F
Figure2. LF654 Mount-Anywhere Series
Flowmeters
Certification No. Z01207
For PU and
HR lined flowmeter
Specifications
Overall Specifications
Measurement range in terms of flow velocity:
0 –1.0 ft/s to 0 – 39.4ft/s (0 – 0.3 m/s to 0 –12 m/s). 0 – 0.3 ft/s to 0 – 1.0 ft/s (0 – 0.1 m/s to 0 – 0.3 m/s) range is available optionally.
Accuracy: < 1/2" to 18" ( 15mm to 450mm) >
±0.2 % of Rate*
* This pulse output error result is established under standard
operating conditions at Toshiba admitted flow calibration facility. (NIST Traceable)
* Individual meter measurement error may vary up to ±0.5% of
Rate at 1.64 ft/s (0.5m/s) or more and ±0.3% of rate ±0.039
inch/s (1mm/s) at 1.64 ft/s or less. * Current output: plus ± 8µA (0.05% of span.) * Refer to individual calibration data for each individual meter's
measurement error.
Combined type Se par a te t yp e
Figure1. Configuration
TIC-LF654L
TIC-LF654L
Fluid conductivity:
3µS/cm minimum
Fluid temperature:
(-
-4 to 248 °F
20 to +120 °C):
PFA lined flowmeter
-4 to 140 °F
(-
20 to +60 °C):
Polyurethane lined flowmeter
(-
23 to 176 °F
5to +80 °C):
Hard Rubber lined flowmeter
Ambient temperature:
(-
-40 to 140 °F
40 to +60 °C):
PFA lined flowmeter
-4 to 140 °F (-20 to +60 °C): PU lined and HR lined flowmeters
Structure:
Standard — IP 67 and NEMA 4X Watertight
Option IP68 and NEMA 6P Submersible type
allows for accidental submergence up to 15m for 48 hours. This option is only available when PU or HR liners are selected.
Power consumption:
Standard:10W(14VA)
at AC100V and Excitation current:0.2A
MAX:15W (22VA)
MAX:17W(24VA) with PROFIBUS
Approved hazardous location certifications:
Model: LF654/LF620F and LF654/LF622F
cFMus Nonincendive for use in
hazardous (classified) locations:
Class I, II, III, Division 2, Groups A-G
Detector and converter combination:
LF650/LF620: Combined type for standard
specification.
LF650/LF622: Separate type for standard
specification.
LF654/LF620F: Combined type with Ex approval of
Class I, II, III, Division 2 (cFMus).
LF654/LF622F: Separate type with Ex approval of
Class I, II, III, Division 2 (cFMus).
Mount-Anywhere Technology:
With TOSHIBA’s unique magnetic field distribution technology the meter is highly immune to upstream flow disturbances.
A minimum of 1D (one diameter) length of upstream straight pipe from the flange is required to maintain the specification performance.
Note: The test results were obtained and demonstrated at
TOSHIBA's flow calibration facility, Fuchu Japan.
Drinking water approvals:
PU and HR liner: NSF certified
Model LF654 Detector
Mounting style: Flange connection type
Fluid pressure:
-
15 psi or -1.0 bar (-0.1 MPa) to the nominal
pressure of the connection flange.
Note: Before shipping from the manufacturer, each detector
unit is tested by the following test condition. Pressure… twice of the pressure index number (ex. 300 psi in case of ASME B 16.5 class 150 flange) Time… 15 minutes
Connection flange standards:
ASME B16.5 class 150, ASME B16.5 class 300
EN1092-1 PN10, EN1092-1 PN16
JIS B 2220 10K, JIS B 2220 20K
Principal materials:
Case — carbon steel
Flange material — carbon steel
Linings
1/2” to 18” (15 to 450mm): PFA 1/2” to 18” (15 to 450mm): PU
4” to 18” (100 to 450mm): HR
Note: PFA liners are mechanically retained for full vacuum
service (65 to 450 mm).
Electrodes
Type-Super smooth, polished with self cleaning
finish, and non stick shape
316L stainless steel (std.) in case of PU and HR
lining
Hastelloy C equivalent (std.)
… in case of PFA lining
Note: Electrodes are mechanically buffed and
electro-chemically polished.
Grounding rings — 316 stainless steel (std.)
Note: See Table 4 for optional materials and other
related information.
Measuring tube material — 304 stainless steel Terminal box material — ADC12(Aluminum
alloy die casting)
Coating: Polyurethane resin coating (std.) gray colored
Dimensions and weights: See Figure 3, 4, 5 and 6.
Cable connection port: for separate type detectors.
Cable gland
LF650: Provided as standard, G 1/2 male screws. LF654(with cFMus):Not provided, 3/4–14NPT
male screws are required.
Applicable diameter —
0.433 to 0.512 inch (11 to 13mm)
2
TIC-LF654L
Model LF620 and LF622 converters
Input signals
Analog signal — the voltage signal from detector,
proportional to process flow rate (for LF622 separate type converter).
Digital input DI
Signal type: 20 to 30Vdc voltage signal Input resistance: 2.7k Number of inputs: one point
Note: DI cannot be used with the Modbus communication.
DI function — One of the following functions can
be assigned to the DI signal.
Range switching — Selects either the higher or
lower range in the unidirectional or bidirectional 2-range setting.
Totalizer control — ‘Starts and stops’ or ‘Rest and
start’ the built-in totalizer.
Fixed-value outputs —Outputs fixed-values for
current and pulse outputs for loop check.
Zero adjustment — Executes zero adjustment
(on-stream at zero flow rate).
Output signals
Current output:
4–20mAdc (load resistance 0 to 750)
Note: The current output cannot be used with the
PROFIBUS-PA communication. (Refer table 6 for details)
Digital outputs — Two points are available as
follows.
Digital output DO1:
Output type: Transistor open collector
Number of outputs: One point Output capacity: 30Vdc, 200mA maximum
Note: DO1 cannot be used if Modbus
communication connection is 3 lines. (Refer table 6 for details)
Digital output DO2 :
Output type:
Solid-state relay output (non polarity)
Number of outputs: One point
Output capacity: 150Vdc, 150mA maximum or
150Vac (peak to peak), 100mA maximum
Note: DO2 cannot be used with the Modbus
communication. (Refer table 6 for details)
DO1 and DO2 functions — One of the following
functions can be assigned to DO1 and/or DO2 .
Pulse output (available only for DO1, DO2)
Pulse rate: MAX 10kHz (10000pps)(DO1)
MAX 100Hz (100pps)(DO2)
(Over 1kpps, auto-setting)
Pulse width: 0.5 to 500ms (but less than half of the period for 100% flow rate)
Note: The same and simultaneous pulse is not available
between DO1 and DO2.)
• Multi-range selection outputs (Note 1)
• High, High high, Low, and/or Low low alarm outputs (Note 2)
• Empty pipe alarm output (Note 2)
• Preset count output
• Converter failure alarm output
Note 1: Two outputs (DO1 and DO2) are needed for 4-range
switching and forward/reverse 2-range switching.
Note 2: Normal Open (default set) or Normal Close is selected
for alarm outputs when programming. When power failure occurs, unit will be fault to Normal Open.
Communications output:
• HART (std.) — Digital signal is superimposed on
4–20mAdc current signal as follows: Conforms to HART protocol
Load resistance: 240 to 750 Load capacitance: 0.25µF maximum Load inductance: 4mH maximum
• PROFIBUS (opt.)
Protocol: PROFIBUS-PA Baud rate: 31.25kbps Bus voltage: 9-30VDC
Consumption electric current of bus: less than 16mA
Manufacture Ident-No.: 093B Standard Ident-No.: 9740
HEX
HEX
Slave address: 0-126 (Default address is 126) Profile: Profile Ver.3.01 for Process Control
Devices
Function blocks: AI(Flow)×1 , Totalizer×1
• MODBUS (opt.)
Physical layer : RS485 Protocol : Modbus Mode : RTU Baudrate : 4800, 9600, 19200bps Data length : 8bit Parity bit : None, Odd, Even Stop bit : 1bit, 2bit Error check : CRC-16 Max. station number : 32(with Master device) Max. cable length : 1.2km (Note)
Note: This length is specification of 3 line
connection.
3
TIC-LF654L
LCD display:
Full dot-matrix 128×128 dot LCD display (back–light provided) A parameter change will rotate the display.
Parameter settings — Parameters can be set as
follows:
• IR Switches: Three key switches are provided to set configuration parameters.
• Digital communication: HART, PROFIBUS or Modbus is needed to set parameters.
• Zero adjustment: Zero point adjustment can be started by pressing the switch in the converter.
• Damping: 0.1 to 60 seconds (selectable in one second increments)
“Field re-verification”
Mag-Prover– Toshiba’s
Zero span calibration tool allows unit to be re-calibrated and verified using an internal software program (For more information contact Toshiba International Corp.)
Conditions when power fails:
Parameter setting values are stored in non–volatile memory and the values will be restored when the
power returns to normal condition.The outputs and
display will remain as follows when power fails.
• Current output: 0mAdc
• Digital output: OFF
• LCD display: No display
• HART: No communication
• PROFIBUS: No communication
• Modbus: No communication
Power supply:
One of the following can be selected:
• 100 to 240Vac, 50/60Hz (allowable voltage 80 to 264Vac)
110Vdc (allowable voltage 90 to 130Vdc)
• 24Vdc (allowable voltage 18 to 36Vdc)
Surge protection:
Arresters are installed in the power supply and a current signal output circuit to help protect the meter from lightning and improve personnel safety.
Case: Aluminum alloy (equal to IP 67)
Coating:
Acrylic resin-baked coating, pearlgray colored
Cable connection port:
Cable glands
LF620 and LF622 without cFMus Approval:
Provided as standard, outer diameter of cableφ
11~13mm Material Nylon 66 G (PF) 1/2 male threads.
LF620F and LF622F with cFMus Approval:
Not provided, 1/2–14NPT male threads are required.
Applicable diameter
0.433 to 0.512 inch (11 to 13mm)
Note: When PROFIBUS option is specified, cable gland size is
φ68mm for signal cable, φ1113mm for power
cable
Vibration resistance:
No resonance to the following levels of vibration:
2
• 10 to 150Hz with acceleration of 9.8m/s
• Vibration of 30Hz with 29.4 m/s
2
in 4h in each
direction will not cause any defect to unit.
Note: Avoid using the flowmeter in an environment with
constant vibration.
Dimensions and Weights:
See Figure 7 (for Separate type)
MTBF:
Converter: 220,000 hours (25 years) at 77 °F (25 °C)
based on strict military specification MIL-HDBK-217F
Detector: 350,000 hours (40 years) at 77 °F (25 °C)
based on strict military specification MIL-HDBK-217F
4
Installation
Dimensions
TIC-LF654L
Unit: inch (mm)
Note1: Eye bolts are provided at the top for flowmeters sized 8" (200mm) or above, and further, a roll-prevention base is provided for
flowmeters sized 10" (250mm) or larger.
Note2: Cable glands are not provided for LF654 of cFMus approved type. Refer to the cable connection port at converter.
ASME B 16.5 class 150 dimensions:
Meter size
(inch)
1/2 5.51 8.07 9.84 4 approx. 11.0
1 6.30 8.31 10.43 4 approx. 16..0 1-1/4 7.87 8.62 10.94 4 approx. 20.0 1-1/2 6.69 8.66 11.18 4 approx. 20.0
2 7.09 9.09 12.09 4 approx. 29.0 2-1/2 7.87 9.29 12.80 4 approx. 38.0
3 9.06 9.69 13.43 4 approx. 45..0
4 9.45 10.28 14.80 8 approx. 64.0
5 9.84 10.71 15.71 8 approx. 73.0
6 10.24 11.34 16.85 8 approx. 93.0
8 11.81 12.24 19.02 8 approx. 139.0.
10 13.78 13.15 21.14 12 approx. 207.0 12 15.75 14.65 24.13 12 approx. 315.0 14 17.72 14.88 25.39 12 approx. 403.0 16 19.69 15.79 27.20 16 approx. 509.0 18 21.65 16.69 29.21 16 approx. 617.0
L1
(inch)
L2
(inch)
L3
(inch)
No. of
bolts
Weight
(lbs)
EN 1092-1 PN 16 dimensions:
Meter size
(mm)
15 140 203 251 4 approx. 6.0 25 160 209 272 4 approx. 7.5 32 200 217 285 4 approx. 10.0 40 170 218 288 4 approx. 10.5 50 180 232 310 4 approx. 14.5 65 200 237 325 4 approx. 16.5
80 230 255 347 8 approx. 21.5 100 240 262 367 8 approx. 26.5 125 250 273 399 8 approx. 31.0 150 260 285 425 8 approx. 37.5 200 300 310 475 12 approx. 54.0 250 350 335 535 12 approx. 78.0 300 400 3 65 588 12 approx. 117.0 350 450 3 74 619 16 approx. 156.5 400 500 3 97 677 16 approx. 202.5 450 550 4 20 730 20 approx. 249.5
L1
(mm)
L2
(mm)
L3
(mm)
No. of
bolts
Weight
(kg)
JIS B 2220 10K dimensions:
Meter size
(mm)
15 140 203 251 4 approx. 6.0 25 160 209 272 4 approx. 8.5 32 200 217 285 4 approx. 10.5 40 170 218 288 4 approx. 10.0 50 180 232 310 4 approx. 13.5
65 200 237 325 4 approx. 16.5
80 230 255 347 8 approx. 18.0 100 240 262 367 8 approx. 23.5 125 250 273 399 8 approx. 30.0 150 260 285 425 8 approx. 37.0 200 300 310 475 12 approx. 48.5 250 350 335 535 12 approx. 74.0 300 400 365 588 16 approx. 102.0 350 450 374 619 16 approx. 127.0 400 500 397 677 16 approx. 175.0 450 550 420 730 20 approx. 217.0
Note 3 : 1 inch = 25.4 mm
L1
(mm)
L2
(mm)
L3
(mm)
No. of
bolts
Weight
(kg)
Figure 3. LF650/LF620 and LF654/LF620F
combined type flowmeters Meter Sizes 1/2" (15) to 18" (450mm) for Toshiba lay length
5
Loading...
+ 9 hidden pages