Welcome Estía to your home!
Air-to-water Heat Pump System
World-leading energy efficiency –– COP of 4.77*
Comfortable heating and hot water supply
Versatile installation and operation
Introducing Toshiba’s super-efficient space heating and hot water supply system for homes and businesses. Estía
represents breakthrough thinking in intelligent heat pump and inverter technologies, by efficiently transferring
ambient thermal heat from outside air to heat water indoors. Based on Toshiba’s proven light commercial air
conditioning system, the Super Digital Inverter, this innovative unit features DC twin rotary compressor, DC
inverter and R410A refrigerant, providing the highest coefficient of performance (COP) in its class. This means
more power from less energy consumption, and the ideal ecological and economical solution for your home.
8 kW11 / 14 kW
Outdoor unit
Hot water cylinder Hydro unit
* 11 kW model
3
1.INTRODUCTION
Advantages
World-leading energy efficiency - COP of 4.77*
With its best in class COP performance, Estía air to water heat pump system delivers more heating
power with less energy consumption.
Estía uses high quality components and material which contribute to the overall savings in energy
consumption.
With the Toshiba advanced inverter, Estía air to water heat pump system only delivers the heating
capacity required; thus consuming only the necessary electricity.
The hot water temperature is also optimized thanks to Toshiba advanced control depending on
the outside air temperature. The milder outside, the air-to-water systems automatically produces
lower water temperature to anticipate decreased needs of space heating. The same control logic
allows to anticipate as well increasing heating needs when weather conditions become extreme;
this overall temperature management gives the best conditions of comfort.
All this s
reducing the CO
Easy
aving has a positive impact on the personal electricity bill and the whole community by
emissions in the atmosphere.
2
to installEnvironment conscious
Engineering Data book
*11kW model
Quick and easy to install. The hydro module
unit can be placed safely in the most suitable
place within the house.
There’s no need for chimney or underground
captors which require additional works on site.
The compact outdoor unit can be placed anywhere outside the
house or on a balcony, thanks to extensive piping options.
One system, multiple
solutions
Estía heat pump sys
combination with different types of emitters:
existing heating l
floor heating or fan coil units.
tems can be used in
ow temperature radiators,
he use of Toshiba Estía heat pump contribute
T
to the reduction of global CO
atmosphere and limit the use of fossil fuels or
other non-renewable energy primary sources.
Whenever required for maintenance purpose,
all the R410A refrigerant (non ozone depleting) can be
completely sucked back to the outdoor unit through the
powerful embedded Toshiba “pump down” operation.
emissions in the
2
The right temperature at the
right time
It can produce water at different temperatures
f
or several applications simultaneously.
Toshiba Estía air to water heat pump system operates smoothly
both with low outdoor air temperature down to -20 ˚C in winter
and up to 43 ˚C in the summer season. The system has a unique
anti-ice build-up protection embedded.
1
4
1.INTRODUCTION
For new houses or refurbishment Estía heat pump offers a variety of combinations, some examples are shown below:
Engineering Data book
Outdoor unit
Shower Bath Kitchen
Hydro unit
Outdoor unit
Shower Bath Kitchen
Hydro unit
Outdoor unit
Hydro unit
Floor heating
2 way valve
Hot water
tank
1 zone heating / cooling with domestic hot water
Hot water
tank
Buffer tank
Mixing
valve
Buffer
tank
2 zone heating with domestic hot water
1 zone heating
HEATING ONLY
Panel radiator
Fan coil
Panel radiator
1 zone
1 zone
HEATING
COOLING
2 zones
Floor heatingTemp. sensor
Shower Bath Kitchen
Hydro unit
Outdoor unit
Outdoor unit
Shower Bath Kitchen
Hydro unit
Outdoor unit
1 zone
Hot water tank
1 zone heating with domestic hot water
Floor heating
1 zone
Hydro unit
Conventional boiler
Buffer
tank
1 zone heating with boiler backup
Panel radiator
2 zones
Conventional boiler
Hot water
tank
Mixing valve
2 zone heating with domestic hot water and boiler backup
Panel radiator
Floor heatingTemp. sensor
Buffer tank
I
n existing dwellings already equipped with traditional gas or
fuel boilers, Toshiba Estía air to water heat pump system can be
combined with the existing heating system to cover exclusively
and in an optimized way all the heating needs, all year round.
Then, the boiler is only used as a back-up source during some
extreme weather days of the winter.
T
he intelligent Toshiba control balances the energy source in the
most efficient way.
5
2. SYSTEM OVERVIEW
6
2.SYSTEM OVERVIEW
Engineering Data book
2-1. System Combination
Combination
Outdoor Unit
Hydro Unit
HWS-803XWHM3-Ez––––––––~, 3kW
HWS-803XWHT6-Ez––––––––3N ~, 6kW
HWS-803XWHD6-Ez––––––––3~, 6kW
HWS-803XWHT9-Ez–––––––3N~, 9kW
HWS-1403XWHM3-E–zzzzzzzz~, 3kW
HWS-1403XWHT6-E–zzzzzzzz3N~, 6kW
HWS-1403XWHD6-E–zz ––––––3~, 6kW
HWS-1403XWHT9-E–zzzzzzzz3N~, 9kW
Hydro unit
HWS-
803H-E
HWS-803XWHM3-E
HWS-803XWHT6-E
HWS-803XWHD6-E
HWS-803XWHT9-E
HWS-1403XWHM3-E
HWS-1403XWHT6-E
HWS-1403XWHD6-E
HWS-1403XWHT9-E
HWS-
1103H-E
Single phase model3 phase model3 phase with bottom plate heater
HWS-
1403H-E
HWS-
1103H8-E
HWS-
1403H8-E
HWS-
1603H8-E
HWS-
1103H8R-E
HWS-
1403H8R-E
HWS-
1603H8R-E
Hot water cylinder
HWS-1501
CSHM3-E
HWS-2101
CSHM3-E
HWS-3001
CSHM3-E
HWS-1501
CSHM3-UK
HWS-2101
CSHM3-UK
z
Backup
heater
HWS-3001
CSHM3-UK
2-2. Hydro Unit
80 class
Hydro UnitHWS-803XWHM3-EHWS-803XWHT6-E
Back up heater capacity3.06.09.0
for back up heater220-230V ~ 50Hz380-400V 3N~ 50Hz220-230V 3~ 50Hz380-400V 3N~ 50Hz
Power supply
Leaving water
temperature
for hot water cylinder heater
(option)
Heating(°C)20-55
Cooling(°C)10-25
220-230V ~ 50Hz
112,140,160 class
Hydro UnitHWS-1403XWHM3-EHWS-1403XWHT6-E
Back up heater capacity3.06.09.0
for back up heater220-230V ~ 50Hz380-400V 3N~ 50Hz220-230V 3~ 50Hz380-400V 3N~ 50Hz
Power supply
Leaving water
temperature
for hot water cylinder heater
(option)
Heating(°C)20-55
Cooling(°C)10-25
220-230V ~ 50Hz
HWS-803XWHD6-E
HWS-1403XWHD6-E
HWS-803XWHT9-E
HWS-1403XWHT9-E
7
2.SYSTEM OVERVIEW
Engineering Data book
2-3. Outdoor Unit
Single Phase model
Outdoor unitHWS-803H-EHWS-1103H-EHWS-1403H-E
Power supply220-230V ~ 50Hz
TypeINVERTER
FunctionHeating & Cooling
Capacity(kW)8.011.214.0
Heating
Cooling
RefrigerantR410A
DimensionHxWxD(mm)890x900x3201,340x900x320
3 Phase model
Power supply380-400V 3N~ 50Hz
TypeINVERTER
FunctionHeating & Cooling
Heating
Cooling
RefrigerantR410A
DimensionHxWxD(mm)1,340x900x320
Bottom plate heater(W)–75
Input(kW)1.822.353.11
COP(W/W)4.404.774.50
Capacity(kW)6.010.011.0
Input(kW)2.133.524.08
EER(W/W)2.822.842.70
with bottom plate heater
Outdoor unit
Capacity(kW)11.214.016.011.214.016.0
Input(kW)2.393.213.722.393.213.72
COP4.694.364.304.694.364.30
Capacity(kW)10.011.013.010.011.013.0
Input(kW)3.524.084.803.524.084.80
EER2.842.702.712.842.702.71
HWS-
1103H8-E
HWS-
1403H8-E
HWS-
1603H8-E
HWS-
1103H8R-E
1403H8R-E
HWS-
HWS-
1603H8R-E
2
2-4. Hot Water Cylinder
Hot water cylinder (option)
HWS-1501CSHM3-E
HWS-1501CSHM3-UK
Water volumelitres150210300
Max water temperature(°C)75
Electric heater(kW)2.75 (230 V ~)
Height(mm)1,0901,4742,040
Diameter(mm)550
MaterialStainless steel
8
HWS-2101CSHM3-E
HWS-2101CSHM3-UK
HWS-3001CSHM3-E
HWS-3001CSHM3-UK
2.SYSTEM OVERVIEW
Engineering Data book
2-5. Options
No.Part nameModel nameApplicationRemarks
1External output board TCB-PCIN3E
2External input boardTCB-PCMO3E
Second Remote
3
Controller
HWS-AMS11E
Boiler-linked output, Alarm output
Defrost signal output, compressor operation signal
output
Cooling/heating thermostat input
Forced-stop signal input
Wired Remote Controller for Room air temperature
control
Up to two boards (according
to applications)
Up to two boards (according
to applications)
9
3. SYSTEM SPECIFICATION
10
3.SYSTEM SPECIFICATION
Outdoor unitHWS-803H-EHWS-1103H-EHWS-1403H-E
Hydro unitHWS-803XWH**-EHWS-1403XWH**-E
Rated Heating
condition 1
LWT=35°C
dT=5deg
Rated Heating
condition 2
LWT=45°C
dT=5deg
Rated Cooling
condition 1
LWT=7°C
dT=5deg
Rated Cooling
condition 2
LWT=18°C
dT=5deg
Power supply1~ 230V 50Hz
Maximum currentA19.222.822.8
CapacitykW8.011.214.0
Power inputkW1.822.353.11
COPW/W4.404.774.50
Rated water flow/min22.932.1140.13
CapacitykW8.011.214.0
Power inputkW2.402.953.95
COPW/W3.333.803.54
Rated water flow/min22.932.1140.13
CapacitykW6.010.011.0
Power inputkW2.133.524.08
EERW/W2.822.842.70
Rated water flow rate/min17.228.6731.53
CapacitykW6.01011.0
Power inputkW1.422.352.65
EERW/W4.234.264.15
Rated water flow/min17.228.6731.53
Engineering Data book
* Rated condition capacity and power input are the data at rated compressor operating frequency.
* Power input does not include water pump power.
* Capacity and power input are measured in accordance with EN14511.
TO:Outdoor temperature (°C)
LWT:Leaving water temperature (°C)
dT:Delta temperature (deg)
Leaving water temperature - return water temperature (Heating)
Return water temperature - leaving water temperature (Cooling)
WPMWater pump motorTCWater heat exchanger temperature sensor
3WV3-way valve (locally procured)TWIWater inlet temperature sensor
2WV2-way valve (locally procured)TWOWater outlet temperature sensor
MIXVMixing valve (locally procured)THOHeater outlet temperature sensor
BHBooster heaterTTWHot water cylinder temperature sensor
RY01~RY06Relay01~Relay06TFIFloor heating inlet temperature sensor
LPSLow pressure sensorTBTerminal block
Backup heater1, 2, 3Heater AC230V, 3kW
1. The one-dot chain line indicates wiring at the local site, and the dashed line indicates accessories sold separately and service wires,
respectively.
2., and indicates the terminal board and the numberals indicate the terminal numbers.
3. indicates P.C. board.
* Be sure to fix the electric parts cover surely with screws. (Otherwise water enters into the box resulting in malfunction.)
20
4.HYDRO UNIT
4-4-2. Power line
Electrical connection to hydro unit
Engineering Data book
Backup heater
220-230V ~ type
(3kW type)
Input power
220-230V 50Hz
Leakage
breaker 30mA
Backup heater
380-400V 3N~ type
(6,9kW type)
Input power
220-230V
3N~ 50Hz
Leakage
breaker 30mA
Backup heater
220-230V 3~ type
breaker 30mA
L NL1 L2 L3 NL1 L2 L3
Outdoor unit to hydro unit electrical connection
(6kW type)
Input power
220-230V
3~ 50Hz
Leakage
TB 20TB02TB02
Hot water cylinder
1
2
Input power
220-230V~ 50Hz
Input power
380-400V
3N~ 50Hz
Leakage breaker
30mA
Leakage breaker
30mA
L1
L2
L3
1
TB01
TB03
2
Leakage
L
N
breaker 30
mA
Input power for
cylinder heater
230 V ~ 50 Hz
1
2
L
N
3
1
2
N
3
Hydro unitOutdoor
unit
1
2
3
1
2
TB01
3
21
4.HYDRO UNIT
Engineering Data book
55
53
51
52
WPM
TB 05
565758
54
BH
2WV
TB03
Don't apply
6B6A6D
6C
TB 06
220-240V
TF1
or
breakdown
will occur.
TTW
TB01
to Outdoor unit
Sensor
connection
Outdoor unit
connection
4-4-3. Control line
3WV
1
11 12
TB 01
59
3
2
13
43
41
Hot
water
cylinder
44
42
MIXV
TB 04
31 32
HOT WATER CYLINDER
L
TB 03
Input power
220-230 V ~
50 Hz
Hot water cylinder
power supply
Mixing-Valve
type 2 for 2 zone
control
TB02
L3
N
L2L1
N
L
N
TB 02
Input power
220-230 V ~
50 Hz
Backup heater
power supply
Mixing-Valve type 1
for 2 zone control
Input power
380-400 V 3N
~ 50 Hz
L1 L2
L3
N
L1 L2
Input power
220-230 V
3 ~ 50 Hz
L3
Pump (local)
Max 12 m
230 V 100 mA
0.75 mm² or more
Booster heater
(local)
Max 12 m
230 V 1 A
0.75 mm² or more
2Way-Valve for
cooling stop
Max 12 m
230 V 1 A
0.75 mm² or more
3Way-Valve for hot
water cylinder
Alert output
(local)
4
2
3
1
TB04
1
2
3
4
TB05
5
6
7
8
CN208
OPTIONOPTION
9
PJ20
2
1
Boiler operation
(local)
4
3
Max 12 m
230 V 100 mA
0.75 mm² or more
N
CW
4
2
3
1
Max 5 m shielded wire
0.75 mm² or more
CCW
A
B
Temp sensor in hot
water cylinder
A
B
4
TB06
TB07
1
2
CN209
C
D
Temp sensor for
2 zone control
Max 50 m shielded wire
0.75 mm² or more
Max 5 m shielded
wire 0.75 mm² or
more
PJ20
2
1
3
2nd Remote control
4
Max 12 m non
voltage 0.75 mm² or
more
Defrost output
(local)
Compressor
operation output
(local)
22
4.HYDRO UNIT
4-4-4. External Device
Electrical connection for external booster heater
Booster Heater
Engineering Data book
123456789
Electrical connection for external additional pumps
Pump
01
123456789
Terminal Block 05
Terminal Block 05
23
4.HYDRO UNIT
3-way valve (diverter) connection
Required Valve Specification:
Electrical Specification: 230 V; 50 Hz; <100 mA
Valve Diameters: Port A, Port B: Ø 1 1/4"
Return Mechanism: 3 types of 3-way valve (diverter) can be used.
Set the 3-way valve in use with the DIP switch SW13-1 on the Hydro Unit board.
SW13-1
Type 12-wire spring returnOFF
Type 23-wire SPSTOFF
Type 33-wire SPDTON
Type 1: SPRING RETURNType 2: SPST
port “A” to Hot water
cylinder
Hydro Unit
port “A” to Hot water
cylinder
Engineering Data book
Hydro Unit
port “AB” to
Hydro unit
Type 3: SPDT
port “AB” to
Hydro unit
port “A” open
port “B” to Room heating or
cooling
port “A” to Hot water
cylinder
port “A”
close
open
TB 05
7
8
9
Hydro Unit
TB 05
7
8
9
port “AB” to
Hydro unit
port “A”
close
open
port “B” to Room heating or
cooling
TB 05
7
8
9
4
port “B” to Room heating or
cooling
24
4.HYDRO UNIT
Engineering Data book
3-way mixing valve connection
Required Actuator Specification
Electrical Specification:230 V; 50 Hz; <100 mA
The 3-way mixing valve is used to achieve the temperature differential needed in a 2-zone heating system.
• Connect the 3-way mixing valve to terminals 2, 3 and 4 on Terminal Block 04 (for Type 1 mixing valve) or on
terminals 1, 2 and 3 on Terminal Block 04 (for Type 2 mixing valve).
• Connect the 3-way mixing valve in accordance with the diagrams below:-
Type 1: SPDTType 2: SPST
port “A” to Zone 2 Heating
port “AB” to
Hydro unit
open
Hydro Unit
TB 04
1
2
3
port “A”
close
port “B” BLANK OFF
4
Hot water cylinder connection (optional)
2
1
12LN
Hot water cylinder
port “A” to Zone 2 Heating
port “AB” to
Hydro unit
port “B” BLANK OFF
Earth leakage breaker
INPUT Power 230 V ~ 50 Hz
Terminal block 03
port “A”
close
open
Hydro Unit
TB 04
1
2
3
4
Hot water cylinder electrical box connections
Hydro unit
25
4.HYDRO UNIT
4-5. Capacity Tables
▼Outdoor unitHWS-803H-E
Hydro unitHWS-803XWH**-E
Rated heating capacity and power input
CapacitykW8.0
Rated condition 1
LWT=35°C
dT=5deg
Rated condition 2
LWT=45°C
dT=5deg
* Rated heating capacity and power input are the data at rated compressor operating frequency
* Power input does not include water pump power.
* Heating capacity and power input are measured in accordance with EN14511.
TO:Outdoor temperature (DB°C) RH85%
LWT:Leaving water temperature (°C)
dT:Delta temperature (deg)
Leaving water temperature - return water temperature
Power inputkW1.82
COPW/W4.40
Rated water flow rate/min22.9
CapacitykW8.0
Power inputkW2.40
COPW/W3.33
Rated water flow rate/min22.9
Engineering Data book
4
26
4.HYDRO UNIT
Average heating capacity and power input
Engineering Data book
Capacity (kW)
TO
(°C)
Power input (kW)
TO
(°C)
LWT (°C)
303540455055
-203.933.833.74———
-154.664.544.444.27— —
-75.455.305.154.994.84—
-26.246.115.975.845.695.55
26.866.756.646.526.476.38
79.028.788.588.348.117.87
109.569.299.108.848.428.29
1210.119.819.629.358.928.87
1510.9410.6010.4110.139.689.52
2012.4211.9911.8211.5011.0310.78
LWT (°C)
303540455055
-201.701.821.90———
-151.781.902.002.13— —
-72.062.212.332.472.79—
-22.102.262.392.562.863.14
22.112.282.432.602.883.17
71.872.072.252.462.652.85
101.842.032.212.422.612.86
121.832.022.202.412.602.87
151.832.022.202.412.602.88
201.822.012.182.442.582.91
COP
TO
(°C)
303540455055
-202.322.111.97———
-152.622.382.222.00— —
-72.642.402.212.021.73—
-22.982.702.502.291.991.77
23.262.962.732.502.252.02
74.824.253.823.393.062.76
105.204.584.123.653.232.90
125.524.864.373.883.433.09
155.985.254.734.203.723.31
206.825.975.424.714.283.70
LWT (°C)
* Heating capacity and power input are include defrost cycle data.
* Heating capacity and power input are shown at maximum compressor operating frequency
* Power input does not include water pump power.
* Heating capacity and power input are measured in accordance with EN14511.
TO:Outdoor temperature (DB°C) RH85%
LWT:Leaving water temperature (°C)
27
4.HYDRO UNIT
Heating peak capacity and power input
Engineering Data book
Capacity (kW)
TO
(°C)
Power input (kW)
TO
(°C)
COP
TO
(°C)
LWT (°C)
303540455055
-204.114.013.92———
-154.874.744.624.46— —
-76.256.085.925.745.41—
-27.227.006.806.596.375.97
28.177.917.677.437.176.92
79.028.788.588.348.117.87
109.569.299.108.848.428.29
1210.119.819.629.358.928.87
1510.9410.6010.4110.139.689.52
2012.4211.9911.8211.5011.0310.78
LWT (°C)
303540455055
-201.721.852.04———
-151.831.972.172.30— —
-71.852.012.212.432.59—
-21.872.042.242.462.652.78
21.862.042.242.452.652.80
71.872.072.252.462.652.85
101.842.032.212.422.612.86
121.832.022.202.412.602.87
151.832.022.202.412.602.88
201.822.012.182.442.582.91
4
LWT (°C)
303540455055
-202.382.171.92———
-152.672.412.131.94— —
-73.373.022.682.372.09—
-23.853.433.042.682.402.15
24.393.883.433.032.712.47
74.824.253.823.393.062.76
105.204.584.123.653.232.90
125.524.864.373.883.433.09
155.985.254.734.203.723.31
206.825.975.424.714.283.70
* Heating capacity and power input are shown peak value during operation.
* Heating capacity and power input are shown at maximum compressor operating requency
* Power input does not include water pump power.
TO:Outdoor temperature (DB°C) RH85%
LWT:Leaving water temperature (°C)
28
4.HYDRO UNIT
▼Outdoor unitHWS-803H-E
Hydro unitHWS-803XWH**-E
Rated cooling capacity and power input
CapacitykW6.0
Rated condition 1
LWT=7°C
dT=5deg
Rated condition 2
LWT=18°C
dT=5deg
* Rated cooling capacity and power input are the data at rated compressor operating frequency
* Power input does not include water pump power.
* Cooling capacity and power input are measured in accordance with EN14511.
TO:Outdoor temperature (DB°C)
LWT:Leaving water temperature (°C)
dT:Delta temperature (deg)
Return water temperature - leaving water temperature
Power inputkW2.13
EERW/W2.82
Rated water flow rate/min17.2
CapacitykW6.0
Power inputkW1.42
EERW/W4.23
Rated water flow rate/min17.2
Engineering Data book
29