Toshiba GRZ100-500, GRZ100-200, GRZ100-211B, GRZ100-214B, GRZ100-216B User Manual

...
GRZ100
2
FEATURES
Fully numerical distance protection relay
High speed operation typically 20ms
zones, two reverse zones, and one non-directional zone
Zone 1 extension protection
Command protection distance schemes (PUP, POP,
BOP and UOP with week infeed and current reversal logic)
Command protection DEF schemes (POP, BOP and
UOP)
Single- and/or three-phase trip
High-resistance earth fault protection
Overcurrent backup protection
Thermal overload protection
Overvoltage and undervoltage protection
Switch-on-to-fault (SOTF) and stub protection
Broken conductor detection
Breaker failure protection
Out-of-step trip protection
Power swing blocking
VT failure detection
Single-shot (single/three/single+three phase) or
multi-shot (three phase) autoreclose
Fault location
Configurable binary inputs and outputs
Programmable logic for I/O configuration, alarms,
indications, recording, etc.
Automatic supervision
Metering and recording functions
Menu-driven user interfaces
Front-mounted RS232C port for communication to a
local PC and rear-mounted RS485, Fibre optic or Ethernet LAN serial ports for communication to a remote PC
IRIG-B port for external clock
The IEC60870-5-103 protocol is provided for
communication with substation control and automation systems.
GRZ100 can be provided with integral digital communi­cation channels for teleprotection signalling. Either one or two communication channels are provided, suitable for relay-to-relay connection via fibre-optic links, or via electrical interfaces to a digital communication network. GRZ100 can be configured using the integral communi­cation channels to support the following functions:
Phase-segregated command protection distance
schemes (PUP, POP, BOP and UOP with week infeed and current reversal logic).
Phase-segregated command protection DEF
schemes (POP, BOP and UOP).
Command protection signalling for tripping during a
power swing.
Command protection for 2- or 3-terminal applications.
Phase-segregated transfer trip (intertripping).
Transmission of binary signals for user-configurable
applications.
Transmission of measured values to be displayed at
the remote terminals.
Synchronisation of the clocks at the various terminals.
Enhanced fault-location accuracy by use of remote- end
data in the case of 3-terminal applications.
Continuous monitoring of the communication channels,
with capability to provide dual-redundant channels in the case of a 2-ended system, and automatic re-routing of signals in the event of a communi­cation channel failure in a 3-ended system.
APPLICATION
GRZ100 is a full-scheme high-speed numerical distance relay for application to transmission lines in solidly earthed networks.
GRZ100 provides the following protection schemes.
Time-stepped distance protection
Zone 1 extension protection
Command protection (distance protection using
telecommunication)
Overcurrent protection for SOTF and stub fault
Out-of-step trip protection
Breaker failure protection
As a backup protection for high-resistance earth faults, GRZ100 provides the following four functions.
Directional earth fault protection
Directional earth fault protection using
telecommunication
Directional or non-directional inverse time overcurrent
and earth fault protection
Definite time overcurrent and earth fault protection
GRZ100 can initiate high-speed single-shot autoreclose or multi-shot autoreclose.
GRZ100 provides the following metering and recording functions.
Metering
Fault recording
Event recording
Disturbance recording
GRZ100 provides the following user interfaces for relay setting or viewing of stored data.
Relay front panel; LCD, LED display and operation keys
Local PC
Remote PC
GRZ100
3
A local PC can be connected to the relay via the RS232C port on the front fascia of the relay. Either one or two rear ports (RS485 or fibre optic) are provided for connection to a remote PC and for IEC60870-5-103 communication with a substation control and automation system. Further, an Ethernet LAN port (TCP/IP) can be provided.
GRZ100 has four models which differ depending on whether or not the autoreclose or fault detector
provided with independent MPU and trip contact for fail-safe function
have been included.
Model 200 series
- With autoreclose for single breaker scheme
Model 300 series
- With autoreclose for one-and-a­half breaker scheme
Model 400 series
- With autoreclose for single breaker scheme
- With fault detector
Model 500 series
- With autoreclose for one-and-a­half breaker scheme
-With fault detector
The following GRZ100 models provide integral digital communication channels for protection signalling. These models can also be applied using standard, external teleprotection equipment.
Model 211B, 214B, 216B
- 2-terminal line application (one communication channel)
- With autoreclose for single breaker scheme
Model 311B
- 2-terminal line application
(one communication channel)
- With autoreclose for one-and-a-half breaker scheme
Model 221B, 224B, 226B
- 2- / 3-terminal line application
(two communication channels)
- With autoreclose for single breaker scheme
Model 321B, 323B
- 2- / 3-terminal line application
(two communication channels)
- With autoreclose for one-and-a-half breaker scheme
In the GRZ100 models provided with an integral digital communication channel for protection signaling, four communication topologies are available depending on the model. Models 211/214/216/311B support configuration (a) only in Figure 1. Models 221/224/226/321/323B can support all configurations. Configuration (b) and (d) offer security against failure of a communication link.
RELAY B RELA Y A
Ch1 Ch1
(a) Two-ended system, single channel
RELAY B RELAY A
Ch1 Ch1
Ch2 Ch2
(b) Two-ended system, dual redundant channels
RELAY A
RELAY B RELAY C
Ch1
Ch1
Ch1
Ch2
Ch2
Ch2
(c) Three-ended system, chain topology
RELA Y A
RELAY B RELA Y C
Ch1
Ch1
Ch1
Ch2
Ch2
Ch2
(d) Three-ended system, ring topology
Figure 1 Communication System Topologies
RELAY FUNCTIONS
Time-Stepped Distance Protection
GRZ100 provides maximum four-zone distance protection (Z1, Z2, Z3, ZF) for forward faults, two-zone distance protection (ZR1, ZR2) for reverse faults and one non­directional distance protection (ZND) for both forward and reverse faults.
GRZ100 provides individual phase-fault measuring elements and earth-fault measuring elements for all types of fault. Direction measurement in GRZ100 is based on cross polarization with voltage memory to ensure dependable fault detection. GRZ100 uses an advanced distance measurement algorithm which achieves accurate fault impedance measurement over a wide range of frequencies. This superior algorithm also minimizes the effect of CT saturation and gives stable performance with CVT transients.
The GRZ100 provides measuring zones with mho-based characteristics or quadrilateral characteristics, as shown in Figures 2 and 3.
As shown in Figure 2, mho-based characteristics are composed of mho element, offset mho element, reactance element, and blinder element for phase fault protection and earth fault protection.
GRZ100
4
(a) Phase fault measuring element
(b) Earth fault measuring element
Figure 2 Mho-based Characteristics
As shown in Figure 3, quadrilateral characteristics are composed of reactance element, directional element and blinder element. Reverse zones for phase fault use the offset directional element to ensure reverse close-up fault detection.
Z1 is applied to Zone 1 protection. The reactance line of Z1 can be configured to take a negative gradient when the terminal is sending power, which prevents Z1 from overreaching for remote end faults.
To ensure that GRZ100 can provide reliable time-delayed tripping for close-up three-phase faults, the phase fault elements are reverse offset following Z1 operation.
Z2 is applied to Zone 2 which provides protection for the rest of the protected line not covered by Zone1 and backup protection for the remote end busbar.
Z3 is applied to Zone 3 which provides remote back-up protection for adjacent lines. Z3 is also used for detection of forward faults in command protection. If Z3 is dedicated to command protection, then ZF can be used for Zone 3 instead of Z3 in time-stepped distance protection.
(a) Phase fault measuring element
(b) Earth fault measuring element
Figure 3 Quadrilateral Characteristics
ZR1 and ZR2 are reverse looking elements applied to Reverse Zone 1 and Zone 2, and used for local back-up protection for busbar faults or transformer faults.
Z4 is used for detection of reverse faults in command protection.
Z4S has an offset characteristic in order to assure detection of close-up phase faults.
Zone 1 Extension
When telecommunications cannot be applied, a Zone 1 extension (Z1X) protection is provided for high-speed protection of any fault along the whole length of the protected line.
The reactance line of Zone 1 extension can take a negative gradient when the terminal is sending loads, which prevents Zone 1 extension from overreaching.
Command protection
The following four schemes are available for distance protection using telecommunication.
GRZ100
5
- Permissive Underreach Protection (PUP)
- Permissive Overreach Protection (POP)
- Unblocking Overreach Protection (UOP)
- Blocking Overreach Protection (BOP)
POP and UOP are equipped with echo logic and weak infeed tripping functions and can be used in the protection of lines with weak infeed or no infeed terminals. An undervoltage element is incorporated for the weak infeed tripping function.
Earth Return and Mutual Coupling
Compensation
Z1G, Z2G, Z1XG and ZR1G for earth fault protection adopt vectorial zero sequence current compensation to eliminate distance measuring errors due to the earth return of zero sequence current. When the GRZ100 is applied to a double circuit line, in order to eliminate the influences of zero sequence mutual coupling, the zero sequence current for the parallel line can be introduced. ZR1G is not provided with zero sequence mutual coupling compensation for the parallel line.
Application to long and short lines
The large capacitance of a long transmission line can adversely affect the measurement of fault impedance. GRZ100 employs an advanced charging current compensation technique which gives significant improvement in impedance measurement for long transmission lines.
The suitability of a distance relay for application to short lines is not determined by its minimum setting but rather by its measuring accuracy for high SIR conditions. GRZ100 provides highly accurate measuring elements suitable to be applied to short lines.
Fault Phase Selection
GRZ100 provides single- and/or three-phase tripping functions.
In order to perform extremely reliable single-phase tripping, an undervoltage element with current compensation is used for fault phase selection.
The undervoltage element with current compensation can operate correctly even for a fault with a strong power source and small voltage drop at the relay installation point.
The characteristics of the phase selection element are as shown in Figure 4.
V
IZc
I
Vk
I: Fault current
Vk: Undervoltage setting
Zc: Im
p
edance setting
V: Fault volta
g
e
Figure 4 Phase selection element
Switch-on-to-fault Protection and Stub
Protection
Switch-on-to-fault (SOTF) protection is provided in order to detect faults that are present when a line or busbar is energized.
For 500 ms following circuit breaker closure, this function is effective to protect against any switch-on-to-fault. A non-directional overcurrent element or distance measuring elements perform the SOTF protection.
Stub protection operates for a fault in a stub zone using an overcurrent element.
Voltage Transformer Failure Supervision
Failure in the voltage transformer (VT) secondary circuit may cause false tripping by voltage dependent measuring elements. Therefore, the following voltage dependent protections are blocked instantaneously when VT failure is detected.
- Distance protection
- Directional earth fault protection
- Protection using telecommunications
- Out of step protection
VT failure is detected in any of the following cases.
- If residual voltage is detected when residual current is not detected.
- If undervoltage is detected when a current change is not
detected.
Power Swing Blocking
The relay provides a power swing blocking (PSB) function to prevent false tripping by distance measuring elements during a power swing.
When a power swing is detected, all distance protection zones and protection using telecommunications can be blocked independently. The non-directional zone, ZND, is not blocked.
A power swing condition is detected using two PSB elements with quadrilateral characteristics shown in Figure 5. The outer PSB element PSBOUT encloses the inner element PSBIN, the two elements being separated by a width of PSBZ. Further, GRZ100 provides PSBSZ and PSBGZ for phase fault measuring elements and earth fault measuring elements respectively. Their functions and characteristics are identical. PSBGZ provides phase-segregated characteristics.
If the impedance locus enters the PSBZ zone for more than a predetermined time (20 to 60ms), the PSB function will block the selected zones. The PSB function is reset after 500 ms when the impedance locus has moved outside the PSB elements.
GRZ100 can provide high speed tripping for faults which occur during a power swing condition, by utilising a well-proven, dedicated negative sequence directional element and any of the PUP, POP, UOP and BOP command schemes.
GRZ100
6
PSBZ
PSBZ PSBZ
0
PSBZ
PSBIN
PSBOUT
R
X
PSBZ: Impedance setting of PSB element
Figure 5 Characteristics of power swing blocking element
Out-of-step Trip Protection
The out-of-step tripping function is used to execute power system separation at the optimum point when an out-of-step occurs.
An out-of-step is detected by using two distance measuring elements with quadrilateral characteristics as shown in Figure 5. The element operates when the out-of-step locus passes from Zone A Æ Zone B Æ Zone C (or Zone C Æ Zone B Æ Zone A) and remains in Zones A and C for the detection time (TOST).
X
Impedance locus
OSTX
F
Zone A
OSTR
2
OSTR1
OSTXB
Zone B
Zone C
R
Figure 6 Characteristics of out of step trip element
Breaker Failure Protection
When an overcurrent element remains in operation longer than a pre-determined length of time following the output of a trip signal the associated circuit breaker is judged to have failed and adjacent circuit breakers can be tripped as a back-up measure.
Two independent timers are available, one of which can be used to control the RETRIP of the original circuit breaker(s). The second timer is used to control the backtripping of adjacent circuit breakers.
For high-speed protection, an overcurrent element with high-speed reset time is used to prevent a spurious re-trip or backtrip following a successful trip or re-trip action.
Overcurrent Backup Protection
The IDMT(inverse definite minimum time) overcurrent element is provided for non-directional inverse time overcurrent protection. The IDMT element is available in conformity with either of three IEC Standard characteristics (Standard inverse, Very inverse, Extremely inverse) or a Long-time inverse.
The characteristics of each IDMT are shown in Figure 8.
The IDMT element has a reset feature with definite time reset.
If the reset time is set to instantaneous, then no intentional delay is added. As soon as the energising current falls below the reset threshold, the element returns to its reset condition.
If the reset time is set to some value in seconds, then an intentional delay is added to the reset period. If the energising current exceeds the setting for a transient period without causing tripping, then resetting is delayed for a user-definable period. When the energising current falls below the reset threshold, the integral state (the point towards operation that it has travelled) of the timing function (IDMT) is held for that period.
This does not apply following a trip operation, in which case resetting is always instantaneous.
Definite time overcurrent protection
Definite time overcurrent protection is enabled by the instantaneous overcurrent element and pick-up delay timer.
Broken Conductor Detection
The unbalance condition caused by an open circuited conductor is detected by the broken conductor detection function. An unbalance threshold with programmable definite time delay is provided.
High-resistance Earth Fault Protection
This protection provides high-resistance earth fault protection using the directional earth fault (DEF) element and the earth fault overcurrent element as follows.
Directional Earth Fault Protection
DEF element is used for time-delayed backup protection for high-resistance faults.
Directional Earth Fault Protection using
Telecommunication
High-speed DEF protection using telecommunications is provided by using a forward looking DEF element and a reverse looking DEF element. POP, UOP, and BOP schemes can be selected with DEF protection using telecommunications.
To enable single phase tripping for a high impedance earth fault, GRZ100, when equipped with the optional integral communication channels, is provided with phase selection logic to obtain phase segregated trip permission signals.
The characteristics of the forward and reverse looking DEF elements are as shown in Figure 7.
-3V
0
Backward DEF
Forward DEF
3I
0
Figure 7 Characteristics of directional earth fault element
GRZ100
7
Inverse Time Overcurrent Earth Fault
Protection
Directional or non-directional inverse time overcurrent earth fault protection is provided using a combination of the IDMT (inverse definite minimum time) overcurrent earth fault element and DEF element. The IDMT element is available in conformity with either of three IEC Standard characteristics (Standard inverse, Very inverse, and Extremely inverse) or a Long-time inverse.
The characteristics of each IDMT are shown in Figure 8.
The IDMT element for earth fault also has a reset feature with definite time reset.
Figure 8 IDMT operating time characteristics
Definite Time Overcurrent Earth Fault
Protection
Definite time overcurrent earth fault protection is provided using the instantaneous overcurrent element and pickup­delay timer.
The definite time earth fault (EF) can be configured to issue either an alarm and/or trip signal.
Thermal Overload Protection
The thermal overload feature provides protection for cables and other plant against the effects of prolonged operation under excess load conditions. A thermal replica algorithm is applied to create a model for the thermal characteristics of the protected plant. Tripping times depend not only on the level of overload current, but also on the level of prior load current, the thermal replica providing ‘memory’ of previous conditions.
The thermal characteristics of the system are defined by entering settings for full load current and thermal time constant. The GRZ100 issues a trip according to the ‘cold’ and ‘hot’ curves specified in IEC60255-8 (see Figure 9), to prevent the protected system from exceeding its thermal capacity. The cold curve tripping times are applicable when the system is first energised, while the hot curves are relevant when the system has already been carrying some prior load for a period of time. An alarm output is also available to give early warning of high load current, set as a percentage of thermal capacity.
IEC60255-8 Thermal Characteristics
Therm al Curves (Cold Cur ve - no
prior load)
0.01
0.1
1
10
100
1000
110
Overload Current (Multiple of k.I
FLC
)
Operate Time (minutes)
τ
=1
τ
=2
τ
=5
τ
=10
τ
=20
τ
=50
τ
=100
Thermal Curves (Hot Curve - 90%
prior lo ad)
0.001
0.01
0.1
1
10
100
1000
110
Overload Current (Multiple of k.I
FLC
)
Operate Time (minutes)
τ
=100
τ
=50
τ
=20
τ
=10
τ
=5
τ
=2
τ
=1
()
 
  
=
2
2
2
.
.
FLC
IkI
I
Lnt
τ
;
()
 
  
=
2
2
22
.
.
FLC
P
IkI
II
Lnt
τ
IEC60255-8 ‘Cold’ Curve
IEC60255-8 ‘Hot’ Curve
t = time to trip for constant overload current I (seconds) I = overload current (largest phase current) (pu) I
P
= previous load current (pu)
k.I
FLC
(or Iθ) = thermal overload current setting (pu)
τ
= thermal time constant (seconds)
Ln = natural logarithm
Figure 9 IEC60255-8 thermal characteristics
Overvoltage and Undervoltage Protection
GRZ100 provides two-stage overvoltage protections for both phase-to-phase voltage input and phase-to-neutral voltage input. The first stage can be set for inverse time or definite time operation, and the second stage set for definite time operation. In total, therefore, GRZ100 provides four independent overvoltage thresholds.
GRZ100 also provides four independent undervoltage thresholds with two-stage undervoltage protection for phase-to-phase voltage input and two-stage undervoltage protection for phase-to-neutral voltage input. The undervoltage protection is provided with an
undervoltage blocking function to prevent undervoltage tripping in the case of a dead line.
GRZ100
8
Overvoltage Inverse Time Curve
s
0.100
1.000
10.00 0
100.000
1000.000
11.5 22.53
Applied Volta ge ( x Vs)
Operating Time (se cs)
TMS = 1
TMS = 2
TMS = 5
TMS = 10
Undervol tage Inver se Time Curv es
1.000
10.000
100.000
1000.000
00.20.40.60.81
Applied Voltage (x Vs)
Operating Time (secs)
TMS = 10
TMS = 5
TMS = 2
TMS = 1
()
xTMS
Vs
V
t
11−
=
()
xTMS
Vs
V
t−=
1
1
Figure 10 Inverse time characteristics
Autoreclose
Most faults on HV and EHV overhead transmission lines are transient faults, which are removed following line de-energization. After a short time, the hot gases disperse and the air de-ionizes. After clearing the fault and deionizing the fault arc, reclosing can be performed. GRZ100 provides two autoreclose schemes, single-shot autoreclose and multi-shot autoreclose.
The GRZ100 autoreclose function can be initiated by any of the following high-speed protections.
- Protection using telecommunication
- Zone1 extension protection
Single-shot autoreclose
Single-shot reclosing can provide any of three auto­reclose modes; single-phase autoreclose, three-phase autoreclose, and single-and three-phase autoreclose.
In the single-phase autoreclose mode, only a faulted phase is tripped, and then reclosed if a single-phase earth fault occurs.
In the three-phase autoreclose mode, all three phases are tripped, and then reclosed regardless of the fault mode, whether a single-phase fault or a multi-phase fault has occurred.
In the single- and three-phase autoreclose mode, the single-phase is reclosed if a single-phase is tripped and the three phases are reclosed if three phases are tripped.
Multi-shot autoreclose
In a multi-shot autoreclose, two- to four-shot reclosing can be selected. The first shot is selected from any of the four autoreclose modes available in the single-shot autoreclose scheme.
If reclosing by the first shot fails, three-phase tripping and reclosing is applied for the second to fourth shots.
Synchronism Check
For the correct operation of three-phase autoreclose, voltage
and synchronism check are necessary. Characteristics of the synchronism check element are shown in Figure 11.
VL: Line voltage V
B
: Busbar voltage θ: Synchronism check angle
θ
θ
0 deg
Operating zone
VL
V
B
OV
θ
θ
Figure 11 Synchronism check element
A detected slip cycle is determined by the following equation:
where,
f: slip cycle
θ: synchronism check angle setting
TSYN: synchronism check timer setting
One-and-a-half Breaker Scheme (Models 300
and 500)
GRZ100 performs two-breaker autoreclose in a one-and­a-half breaker scheme.
Only single-shot autoreclose is available in Models 300 and
500. Single-phase autoreclose, three-phase autoreclose or single and three-phase autoreclose can be applied to the two circuit breakers.
Fault Detector (Models 400 through 500)
For ultra-critical applications, where security is the over­riding concern and a two-out-of-two tripping philosophy is specified, GRZ100 can be provided with an independent fault detector. This fault detector contains its own main processing unit (MPU) and trip contacts. The trip contacts of the main protection are connected in series with the fault detector trip contacts to ensure completely fail-safe operation.
The fault detector incorporates the following six fault detection elements.
- Multi-level overcurrent element
- Current change detection element
- Earth fault overcurrent element
- Undervoltage element for earth fault detection
- Undervoltage element for phase fault detection
- Undervoltage change detection element
Interfaces for Integral Communication
GRZ100 can be provided with the following interface(s) and linked to a dedicated optical fibre communication circuit or multiplexed communication circuit (multiplexer) shown in Figure 12.
The electrical interface supports CCITT G703-1.2.1, -1.2.2,
-1.2.3, X.21(RS530) and RS422. Twisted pair cable is used for connecting the relay and multiplexer. In the case of an
f =
180°ХTSYN
θ
GRZ100
9
optical link via a multiplexer, the optical interface unit G1IF1 (optical to electrical converter) is required for connecting to the multiplexer. The electrical interface between the converter and the multiplexer supports CCITT G703 -1.2.1,
-1.2.2, -1.2.3, and X.21(RS530).
b) Optical interface using multiplexer
Multi­plexer
Optical
I/F
Unit
G1IF1
GRZ100
Opt. I/F
CCITT-G703. ITUT-X.21 Bit rate: 64kbps
GI Opt. Fibre < 2km SWL, 64kbps
GRZ100
Elec. I/F
c) Electrical interface using multiplexer
Multi­plexer
Twisted pair wire CCITT-G703. ITUT-X.21 RS422 Bit rate: 64kb
p
s
a) Optical interface
GRZ100
Opt. I/F
Optical Fibre 64kbps
(Option)
Figure 12 Telecommunication system
METERING AND RECORDING
Metering and Monitoring
The following power system data is measured continuously and can be displayed on the LCD on the relay fascia, at the local PC, and the remote PC when connected.
- Voltages (phase, phase to phase, symmetrical components)
- Currents (phase, phase to phase, symmetrical components)
- Active power and reactive power
- Frequency
Currents and voltages can be indicated as primary or secondary values. Active power and reactive power are indicated as primary values.
The user can monitor the following output and status on the LCD and at local/remote PCs.
- Relay element output
- Binary input/output
- CB status
Event Record
The most recent 480 time-tagged events are stored with 1ms resolution.
The event recorder can be triggered by a Trip signal, by Overcurrent trigger elements (OC) and by Undervoltage trigger elements (UV). In case of 'Trip', the trigger is performed whenever tripping occurs. In case of OC/UV, On(used) or Off(not used) is selectable.
Event trigger is freely selectable by using PLC.
Events recorded are as follows.
- Tripping and reclosing
- Alarms
- Change of binary input signal
- Change of relay setting
- Relay failure
Fault Record
A relay trip initiates fault recording. Time-tagged fault data can be stored for the 8 most recent faults. Fault record items are as follows.
- Date and time
- Faulted phase
- Phases tripped
- Tripping mode
- Fault location
- Pre-fault and post-fault current and voltage data (phase, phase to phase, symmetrical components)
- Autoreclose operation
Fault Location
Fault location is initiated by relay tripping signals excluding breaker failure, overcurrent backup and out-of-step tipping. It can also be started on receipt of a start signal from external relays.
Fault location is indicated in km and % for the whole length of the protected line. The fault location is highly accurate for parallel lines due to the implementation of zero-sequence mutual impedance compensation.
The result of the fault location is stored as fault record data.
In GRZ100 with integral communication, improved fault location accuracy is achieved for 3-ended applications by use of data received from the remote terminals.
Disturbance Record
The relay can record 8 analog and 32 binary signals. The disturbance recorder is initiated by operation of the overcurrent element, undervoltage element and/or relay tripping.
In respect to analog data, phase voltage and current, residual voltage and current, and the residual current of the parallel line are recorded. The data can be transformed into the COMTRADE format.
Pre-fault recording time is fixed at 300ms, post-fault recording time can be set from 100 ms to 3 s. The maximum number of stored records depends on the post-fault recording time. In the case of a post-fault recording time of 500ms, up to 20 disturbance records can be stored. The record number of the recorded data is displayed on the LCD.
GRZ100
10
Calendar and Time
The calendar and time are provided for the time-tagging of recorded data. Synchronisation with GPS (Global Positioning System) is achieved via the IRIG-B port.
USER INTERFACE
Relay Front Panel
The relay front panel incorporates the following user interfaces. Setting the relay and viewing stored data are possible using the Liquid Crystal Display (LCD) and operation keys.
- 40 character, four line LCD with back light
- Eight Light Emitting Diodes (LED) including four that are configurable
- Operation keys
- RS232C port
- Monitoring jacks
Figure 13 shows the relay front panel.
Figure 13 Relay front panel
The following items can be displayed on the LCD.
- Setting
- Metering
- Event records
- Fault records
- The number of disturbance records
- Fault location
- Any failure code detected by the automatic supervision
Password protection can be provided from the setting menu on the LCD to provide security for relay setting changes. After the password has been set, the password must be entered to access the setting menu from a local or remote PC as well as on the LCD.
The contents of metering, fault records, and relay failures can be monitored by pressing the VIEW key. The VIEW key can be pressed without removing the relay front cover.
Arbitrary signals can be assigned to the four user configurable LEDs.
Two monitoring jacks are operable when the test mode is
selected in the LCD window. An oscilloscope can be connected to the relay through these jacks. Selection of output signals on the monitoring jacks can be set from the menu.
Local PC
The user can communicate with the GRZ100 from a local PC via the RS232C port on the relay fascia. The following data can be viewed or analysed on the local PC with RSM100 software.
- Setting
- Metering
- Event records
- Fault records
- Disturbance records
- Fault location
Relay Setting and Monitoring (RSM)
GRZ100 can be connected to the RSM system via the RS485 interface at the rear of the relay. The user can operate the relay from a remote PC in the same way as from a local PC.
Figure 14 shows the configuration of the RSM system via the protocol converter G1PR2 (option). The G1PR2 can be provided with maximum 8 ports and each port supports 32 relays addressing.
A maximum of 32 x 8 relays can be connected to the remote PC in multi-drop mode, via the protocol converter.
The RSM100 software is also used to communicate with the relay and to view or analyze disturbance records on the remote PC.
The data transmission rate between relays and the protocol converter is 64kbps.
G1PR2
Figure 14 Relay setting and monitoring system
IEC60870-5-103 Communication
The relay can support the IEC60870-5-103 communication protocol. This protocol is mainly used when the relay communicates with a control system and is used to transfer the measurand data, status data and general command from the relay to the control system.
GRZ100
11
Relay Setting
The user can input or change settings using the operation keys on the relay fascia or via a local or remote PC with the RSM system.
Password protection is provided to change settings.
Eight active setting groups are provided. This allows the user to set one group for normal operating conditions while other groups may be set to cover alternative operating conditions.
Configurable Binary Output Contacts
GRZ100 is provided with 13 to 41 user configurable normally open output contacts used for indication and alarm. The number of outputs varies according to the relay model.
Configurable Binary Inputs
GRZ100 is provided with 18 to 28 user configurable binary inputs.
The number of inputs varies according to the relay model.
PLC Function
GRZ100 is provided with a PLC (Programmable Logic Control) function allowing user-configurable sequence logics on binary signals. Configurable binary inputs, binary outputs and LEDs are programmed by the PLC function.
AUTOMATIC SUPERVISION
Automatic Monitoring Function
The automatic monitoring function will detect failures, should they occur, that might cause unwanted operation. The items monitored include the following:
- Analog input circuits
- Analog-to-digital converter
- Watchdog Timer
- Binary output circuits
- DC power supply circuits
- CPU
- Telecommunication circuit
- Relay address monitoring
Automatic Test Function for External
Communication
In the BOP scheme, a signal check-back test function is provided to check the integrity of the signalling channels.
Alarms
In the unlikely event that a relay failure should occur, this is detected by automatic monitoring and the LED ALARM on the relay fascia is illuminated. A binary “RELAY FAILURE” output is simultaneously operated and the date/time of any such failure would be stored in the event record.
PC DISPLAY
Metering
Event record
Fault record
Vector record
Data analysis
GRZ100
12
TECHNICAL DATA
Ratings
AC current In: 1A or 5A
AC voltage Vn: 100V, 110V, 115V, 120V
Frequency: 50Hz or 60Hz
DC power supply: 110Vdc/125Vdc (Operative range: 88 - 150Vdc)
220Vdc/250Vdc (Operative range: 176 - 300Vdc) 48Vdc/54Vdc/60Vdc (Operative range: 38.4 - 72Vdc) 24Vdc/30Vdc (Operative range: 19.2 – 36Vdc)
AC ripple on DC supply IEC60255-11 maximum 12%
DC supply interruption IEC60255-11
Permissive duration of DC supply voltage interruption to maintain normal operation: Restart time:
less than 50ms at 110V less than 10s
Binary input circuit DC voltage 110Vdc/125Vdc
220Vdc/250Vdc 48Vdc/54Vdc/60Vdc 24Vdc/30Vdc
Overload Ratings
AC current input
AC voltage input
4 times rated continuous 100 times rated for 1s
2 times rated continuous
2.5 times rated for 1s
Burden
AC current input 0.2VA per phase (at rated 5A)
0.4 VA at zero-sequence circuit (at rated 5A)
0.1VA per phase (at rated 1A)
0.3 VA at zero-sequence circuit (at rated 1A)
AC voltage input 0.1VA (at rated voltage)
DC power supply: less than15W (quiescent)
less than 25W (operation)
Binary input circuit: 0.5W/input at 110Vdc
CT Ratio Setting
CT ratio 1 to 20000 in 1 steps
Full Scale of Current for Measurement
Current 65 times rated current
Phase Fault Distance Measuring Element
Z1S, Z2S and Z1XS
Z1S
θ1
Z1S θ2
ZFS, ZR1S and ZR2S
Z3S and Z4S
Characteristic angle
Z1S and Z4S offset
ZNDS
Blinder (BFRS1, BFRS2, BFRS3, BRRS, BNDS) BRLS: Linked with BRRS Characteristic angle: (BFRS1, BFRS2, BFRS3, BRRS, BNDS) Characteristic angle (BFLS)
0.10 to 250.00 in 0.01 steps (1A relay)
0.01 to 50.00 in 0.01 steps (5A relay) 0° to 45° in 1° steps 45° to 90° in 1° steps
0.1 to 250.0 in 0.1 steps (1A relay)
0.01 to 50.00 in 0.01 steps (5A relay)
0.1 to 250.0 in 0.1 steps (1A relay)
0.01 to 50.00 in 0.01 steps (5A relay) 45° to 90° in 1° steps
7.5 fixed (1A relay)
1.5 fixed (5A relay)
0.1 to 250.0 in 0.1 steps (1A relay)
0.01 to 50.00 in 0.01 steps (5A relay)
0.5 to 100.0 in 0.1 steps (1A relay)
0.10 to 20.00 in 0.01 steps (5A relay) 75° fixed
90° to 135°
Loading...
+ 28 hidden pages