Toshiba GRL100-701B, GRL100-702B, GRL100-711B, GRL100-712B Instruction Manual

6 F 2 S 0 8 5 0
INSTRUCTION MANUAL
LINE DIFFERENTIAL RELAY
GRL100 - 7∗∗B
All Rights Reserved.
( Ver. 0.3 )
www . ElectricalPartManuals . com
1
6 F 2 S 0 8 5 0
Safety Precautions
Before using this product, please read this chapter carefully.
This chapter describes the safety precautions recommended when using the GRL100. Before installing and using the equipment, this chapter must be thoroughly read and understood.
Explanation of symbols used
Signal words such as DANGER, WARNING, and two kinds of CAUTION, will be followed by important safety information that must be carefully reviewed.
Indicates an imminently hazardous situation which will result in death or
serious injury if you do not follow the instructions.
Indicates a potentially hazardous situation which could result in death or
serious injury if you do not follow the instructions.
CAUTION Indicates a potentially hazardous situation which if not avoided, may result
in minor injury or moderate injury.
CAUTION Indicates a potentially hazardous situation which if not avoided, may result
in property damage.
DANGE
R
WARNING
www . ElectricalPartManuals . com
2
6 F 2 S 0 8 5 0
Current transformer circuit
Never allow the current transformer (CT) secondary circuit connected to this equipment to be opened while the primary system is live. Opening the CT circuit will produce a dangerously high voltage.
Exposed terminals
Do not touch the terminals of this equipment while the power is on, as the high voltage generated is dangerous.
Residual voltage
Hazardous voltage can be present in the DC circuit just after switching off the DC power supply. It takes approximately 30 seconds for the voltage to discharge.
Fiber optic
Invisible laser radiation Do not view directly with optical instruments. Class 1M laser product (Transmission distance: 30km class)
- the maximum output of laser radiation: 0.2 mW
- the pulse duration: 79.2 ns
- the emitted wavelength(s): 1310 nm
CAUTION
Earth
The earthing terminal of the equipment must be securely earthed.
CAUTION
Operating environment
The equipment must only used within the range of ambient temperature, humidity and dust detailed in the specification and in an environment free of abnormal vibration.
Ratings
Before applying AC voltage and current or the DC power supply to the equipment, check that they conform to the equipment ratings.
Printed circuit board
Do not attach and remove printed circuit boards when the DC power to the equipment is on, as this may cause the equipment to malfunction.
External circuit
When connecting the output contacts of the equipment to an external circuit, carefully check the supply voltage used in order to prevent the connected circuit from overheating.
Connection cable
Carefully handle the connection cable without applying excessive force.
DANGE
R
WARNING
www . ElectricalPartManuals . com
3
6 F 2 S 0 8 5 0
Modification
Do not modify this equipment, as this may cause the equipment to malfunction.
Short-link
Do not remove a short-link which is mounted at the terminal block on the rear of the relay before shipment, as this may cause the performance of this equipment such as withstand voltage, etc., to reduce.
Disposal
When disposing of this equipment, do so in a safe manner according to local regulations.
www . ElectricalPartManuals . com
4
6 F 2 S 0 8 5 0
Contents
Safety Precautions 1
1. Introduction 9
2. Application Notes 11
2.1 Protection Schemes 11
2.2 Current Differential Protection 12
2.2.1 Operation of Current Differential Protection 12
2.2.2 Segregated-phase Current Differential Protection 12
2.2.3 Zero-phase Current Differential Protection 13
2.2.4 Fail-safe Function 14
2.2.5 Remote Differential Trip 15
2.2.6 Transmission Data 17
2.2.7 Synchronized Sampling 17
2.2.8 Charging Current Compensation 24
2.2.9 Blind Zone Protection 25
2.2.10 Application to Three-terminal Lines 26
2.2.11 Dual Communication Mode 28
2.2.12 Application to One-and-a-half Breaker Busbar System 28
2.2.13 Communication System 29
2.2.14 Setting 35
2.3 Distance Protection 43
2.3.1 Time-Stepped Distance Protection 43
2.3.2 Command Protection 58
2.3.3 Power Swing Blocking 73
2.4 Directional Earth Fault Protection 76
2.4.1 Directional Earth Fault Command Protection 77
2.4.2 Directional Earth Fault Protection 81
2.5 Overcurrent Backup Protection 83
2.5.1 Inverse Time Overcurrent Protection 84
2.5.2 Definite Time Overcurrent Protection 86
2.6 Transfer Trip Function 87
2.7 Out-of-step Protection 88
2.8 Thermal Overload Protection 90
2.9 Overvoltage and Undervoltage Protection 93
2.9.1 Overvoltage Protection 93
2.9.2 Undervoltage Protection 97
2.10 Broken Conductor Protection 101
2.11 Breaker Failure Protection 104
2.12 Switch-Onto-Fault Protection 107
2.13 Stub Protection 109
2.13.1 STUB DIF Protection 109
2.13.2 STUB OC Protection 109
www . ElectricalPartManuals . com
5
6 F 2 S 0 8 5 0
2.13.3 Setting 110
2.14 Tripping Output 111
2.15 Autoreclose 113
2.15.1 Application 113
2.15.2 Scheme Logic 115
2.15.3 Autoreclose Output Signals 131
2.16 Characteristics of Measuring Elements 132
2.16.1 Segregated-phase Current Differential Element DIF and DIFSV 132
2.16.2 Zero-phase Current Differential Element DIFG 133
2.16.3 Distance Measuring Elements Z1, Z2, Z3, Z4, ZR and PSB 134
2.16.4 Phase Selection Element UVC 142
2.16.5 Directional Earth Fault Elements DEFF and DEFR 143
2.16.6 Inverse Definite Minimum Time (IDMT) Overcurrent Element OCI and
EFI 144
2.16.7 Thermal Overload Element 145
2.16.8 Out-of-Step Element OST 145
2.16.9 Voltage and Synchronism Check Elements OVL, UVL, OVB, UVB and
SYN 146
2.16.10 Current change detection elements OCD, OCD1 and EFD 147
2.16.11 Level Detectors 147
2.17 Fault Locator 149
2.17.1 Application 149
2.17.2 Starting Calculation 149
2.17.3 Displaying Location 149
2.17.4 Distance to Fault Calculation 150
2.17.5 Setting 154
3. Technical Description 158
3.1 Hardware Description 158
3.1.1 Outline of Hardware Modules 158
3.1.2 Transformer Module 161
3.1.3 Signal Processing and Communication Module 162
3.1.4 Binary Input and Output Module 163
3.1.5 Human Machine Interface (HMI) Module 167
3.2 Input and Output Signals 169
3.2.1 Input Signals 169
3.2.2 Binary Output Signals 172
3.2.3 PLC (Programmable Logic Controller) Function 172
3.3 Automatic Supervision 173
3.3.1 Basic Concept of Supervision 173
3.3.2 Relay Monitoring 173
3.3.3 CT Circuit Current Monitoring 174
3.3.4 CT Circuit Failure Detection 175
3.3.5 Voltage Transformer Failure Supervision 175
3.3.6 Differential Current (Id) Monitoring 177
3.3.7 Telecommunication Channel Monitoring 178
www . ElectricalPartManuals . com
6
6 F 2 S 0 8 5 0
3.3.8 GPS Signal Reception Monitoring (For GPS-mode only) 178
3.3.9 Relay Address Monitoring 178
3.3.10 Disconnector Monitoring 178
3.3.11 Failure Alarms 179
3.3.12 Trip Blocking 180
3.3.13 Setting 180
3.4 Recording Function 181
3.4.1 Fault Recording 181
3.4.2 Event Recording 182
3.4.3 Disturbance Recording 182
3.5 Metering Function 184
4. User Interface 185
4.1 Outline of User Interface 185
4.1.1 Front Panel 185
4.1.2 Communication Ports 187
4.2 Operation of the User Interface 189
4.2.1 LCD and LED Displays 189
4.2.2 Relay Menu 192
4.2.3 Displaying Records 194
4.2.4 Displaying the Status 198
4.2.5 Viewing the Settings 204
4.2.6 Changing the Settings 205
4.2.7 Testing 225
4.3 Personal Computer Interface 232
4.4 Relay Setting and Monitoring System 232
4.5 IEC 60870-5-103 Interface 233
4.6 Clock Function 233
5. Installation 234
5.1 Receipt of Relays 234
5.2 Relay Mounting 234
5.3 Electrostatic Discharge 234
5.4 Handling Precautions 234
5.5 External Connections 235
6. Commissioning and Maintenance 237
6.1 Outline of Commissioning Tests 237
6.2 Cautions 238
6.2.1 Safety Precautions 238
6.2.2 Cautions on Tests 238
6.3 Preparations 239
6.4 Hardware Tests 240
6.4.1 User Interfaces 240
6.4.2 Binary Input Circuit 241
6.4.3 Binary Output Circuit 242
6.4.4 AC Input Circuits 243
www . ElectricalPartManuals . com
7
6 F 2 S 0 8 5 0
6.5 Function Test 244
6.5.1 Measuring Element 244
6.5.2 Timer 269
6.5.3 Protection Scheme 271
6.5.4 Metering and Recording 275
6.5.5 Fault Locator 275
6.6 Conjunctive Tests 277
6.6.1 On Load Test 277
6.6.2 Signaling Circuit Test 277
6.6.3 Tripping and Reclosing Circuit Test 279
6.7 Maintenance 281
6.7.1 Regular Testing 281
6.7.2 Failure Tracing and Repair 281
6.7.3 Replacing Failed Modules 283
6.7.4 Resumption of Service 285
6.7.5 Storage 285
7. Putting Relay into Service 286
www . ElectricalPartManuals . com
8
6 F 2 S 0 8 5 0
Appendix A Block Diagram 287
Appendix B Signal List 289
Appendix C Variable Timer List 323
Appendix D Binary Output Default Setting List 325
Appendix E Details of Relay Menu and LCD & Button Operation 329
Appendix F Case Outline 339
Appendix G Typical External Connection 347
Appendix H Relay Setting Sheet 351
Appendix I Commissioning Test Sheet (sample) 381
Appendix J Return Repair Form 387
Appendix K Technical Data 393
Appendix L Symbols Used in Scheme Logic 409
Appendix M Multi-phase Autoreclose 413
Appendix N Data Transmission Format 417
Appendix O Example of Setting 423
Appendix P Programmable Reset Characteristics and Implementation of Thermal
Model to IEC60255-8 435
Appendix Q IEC60870-5-103: interoperability 439
Appendix R Inverse Time Characteristics 453
Appendix S Failed Module Tracing and Replacement 457
Appendix S PLC Setting Sample 463
Appendix T Ordering 467
The data given in this manual are subject to change without notice. (Ver.0.3)
www . ElectricalPartManuals . com
9
6 F 2 S 0 8 5 0
1. Introduction
The GRL100 provides high-speed phase-segregated current differential protection for use with telecommunication systems, and ensures high reliability and security for diverse faults including single-phase and multi-phase faults and double-faults on double-circuit lines, evolving faults and high-impedance earth faults.
The GRL100 is used as a main protection for the following two- or three-terminal lines in EHV or HV networks:
Overhead lines or underground cables
Lines with weak infeed or non-infeed terminals
Single or parallel lines
Lines with heavy load current
Short- or long-distance lines
The GRL100 actuates high-speed single-shot autoreclose or multi-shot autoreclose.
The GRL100 can be used for lines associated with one-and-a-half busbar arrangement as well as single or double busbar arrangement.
For telecommunications using the current differential protection, dedicated optical fibres or 64 kbits/s multiplexed communication links can be employed.
Furthermore, in addition to current differential protection, the GRL100 provides distance, directional earth fault, overcurrent backup, thermal overload, under- and over-voltage, out-of-step and breaker failure protection.
The GRL100 is a member of the G-series family of numerical relays which utilise common hardware modules with the common features:
The GRL100 provides the following metering and recording functions.
- Metering
- Fault record
- Event record
- Fault location
- Disturbance record
The GRL100 provides the following menu-driven human interfaces for relay setting or viewing of stored data.
- Relay front panel; 4 × 40 character LCD, LED display and keypad
- Local PC
- Remote PC
Password protection is provided to change settings. Eight active setting groups are provided. This allows the user to set one group for normal operating conditions while other groups may be set to cover alternative operating conditions.
GRL100 provides either two or three serial ports, and an IRIG-B port for an external clock connection. A local PC can be connected via the RS232C port on the front panel of the relay. Either one or two rear ports (RS485 or fibre optic) are provided for connection to a remote PC and for IEC60870-5-103 communication with a substation control and automation system.
Further, the GRL100 provides the following functions.
- Configurable binary inputs and outputs
www . ElectricalPartManuals . com
10
6 F 2 S 0 8 5 0
- Programmable logic for I/O configuration, alarms, indications, recording, etc.
- Automatic supervision
The GRL100 has the following models:
Relay Type and Model
Relay Type:
- Type GRL100; Numerical current differential relay
Relay Model:
- For two terminal line, With distance protection and autoreclose
Model 701; 25 binary inputs, 19 binary outputs, 6 binary outputs for tripping
Model 702; 28 binary inputs, 37 binary outputs, 6 binary outputs for tripping
- For three terminal line, With distance protection and autoreclose
Model 711; 25 binary inputs, 19 binary outputs, 6 binary outputs for tripping
Model 712; 28 binary inputs, 37 binary outputs, 6 binary outputs for tripping
Table 1.1 GRL100 Models
Model 701B 702B 711B 712B
2- or 3-terminal line application 2-terminal 2-terminal 3-terminal 3-termnal
Segregated-phase current differential protection (DIF) x x x x
Zero-phase current differential protection (DIFG) x x x x
Charging current compensation (CCC) x x x x
Distance protection (DZ) x x x x
Power swing blocking (PSB) x x x x
Directional earth fault protection (DEF) x x x x
Switch-on-to-fault protection (SOTF) x x x x
Stub protection (STUB) x x x x
Phase overcurrent protection (OC) x x x x
Earth fault overcurrent protection (EF) x x x x
Thermal overload protection (THM) x x x x
Undervoltage protection (UV) x x x x
Overvoltage protection (OV) x x x x
Broken conductor detection (BCD) x x x x
Breaker failure protection (BF) x x x x
Out-of-step protection (OST) x x x x
Autoreclose (ARC) x x x x
Fault location (FL) x x x x
CT failure detection (CTF) x x x x
VT failure detection (VTF) x x x x
www . ElectricalPartManuals . com
11
6 F 2 S 0 8 5 0
2. Application Notes
2.1 Protection Schemes
The GRL100 provides the following protection schemes (Appendix A shows block diagrams of the GRL100-700 series):
Segregated-phase current differential protection
Zero-phase current differential protection
Three-stepped distance protection and command protection
Directional earth fault protection
SOTF and Stub protection
Overcurrent backup protection
Thermal overload protection
Overvoltage and undervoltage protection
Broken conductor detection
Out-of-step protection
Breaker failure protection
Transfer trip protection
Zero-phase current differential protection enables sensitive protection for high-impedance earth faults.
Overcurrent backup protection provides both inverse time overcurrent and definite time overcurrent protection for phase faults and earth faults.
Out-of-step protection performs phase comparison of the local and remote voltages and operates only when the out-of-step loci cross the protected line.
Furthermore, the GRL100 incorporates autoreclose functions, charging current compensation for cable or long-distance lines and fault location. The autoreclose mode can be selected from single-phase, three-phase, single- and three-phase and multi-phase modes.
The current differential protection utilises with the microwave or fibre optic digital telecommunication systems to transmit instantaneous current values sampled synchronously at each terminal.
www . ElectricalPartManuals . com
12
6 F 2 S 0 8 5 0
2.2 Current Differential Protection
GRL100 is applicable to telecommunication systems which employ dedicated optical fibre, 64 kbit/s multiplexed communication channels or microwave links.
2.2.1 Operation of Current Differential Protection
Current differential protection compares the currents flowing into and out of the protected line. The difference of the currents, that is, the differential current, is almost zero when a fault is external or there is no fault, and is equal to the fault current when the fault is internal. The differential protection operates when the difference of the currents exceeds a set value.
The GRL100 relay installed at each line terminal samples the local currents every 7.5 electrical degrees and transmits the current data to other terminals every four samples via the telecommunication system. The GRL100 performs master/master type current differential protection using the current data from all terminals.
As synchronized sampling of all terminals is performed in the GRL100, the current data are the instantaneous values sampled simultaneously at each terminal. Therefore, the differential current can be easily calculated by summing the local and remote current data with the identical sampling address. Thus, compensation of transmission delay time is not required.
The GRL100 utilises the individual three phase currents and residual current to perform segregated-phase and zero-phase current differential protection.
2.2.2 Segregated-phase Current Differential Protection
The segregated-phase differential protection transmits the three phase currents to the remote terminal, calculates the individual differential currents and detects both phase-to-phase and phase-to-earth faults on a per phase basis.
Figure 2.2.2.1 shows the scheme logic of the segregated-phase current differential protection. Output signals of differential elements DIF-A, -B and -C can perform instantaneous tripping of the breaker on a per phase basis and start the incorporated autoreclose function.
Note: For the symbols used in the scheme logic, see Appendix L.
DIF.FS-A_TP
DIF.FS-B_TP
DIF.FS-C_TP
DIF-A
&
41
&
82: DIF-A_TRIP
&
401
DIF-B
&
42
&
83: DIF-B_TRIP
&
DIF-C
&
Communication failure, etc.
43
&
1
CRT_BLOCK
1544
84: DIF-C_TRIP
&
DIF-A_FS
1616
DIF-B_FS
1617
DIF-C_FS
1618
403
402
1
400
DIF.FS_TRIP
43C ON
&
TELEPROTECTION OFF
(
from IEC103 command)
DIFFS
1
DIF_BLOCK
1585
DIF BLOCK
Figure 2.2.2.1 Scheme Logic of Segregated-phase Current Differential Protection
www . ElectricalPartManuals . com
13
6 F 2 S 0 8 5 0
Tripping output signals can be blocked by the PLC command DIF_BLOCK and CRT_BLOCK. The output signals of DIF-A, DIF-B and DIF-C are also blocked when a communication circuit failure is detected by the data error check, sampling synchronism check or interruption of the receive signals. For DIF-A_FS, DIF-B_FS and DIF-C_FS signals, see Section 2.2.4.
The differential elements DIF have a percentage restraining characteristic with weak restraint in the small current region and strong restraint in the large current region, to cope with CT saturation. (For details of the characteristic, see Section 2.16.)
Erroneous current data may be transmitted from the remote terminal when the remote relay is out-of-service for testing or other purposes. To prevent false operation in this case, the relay sets the receiving current data to zero in the differential current calculation upon detecting that the remote terminal is out-of-service.
If the relay is applied to a three-terminal line, the zero setting is performed only for the current data received from an out-of-service terminal.
Figure 2.2.2.2 shows the remote terminal out-of-service detection logic. The local terminal detects that the remote terminal is out-of-service by receiving a signal LOCAL TEST which is transmitted when the scheme switch [L. TEST] is set to "ON" at the terminal under test. As an alternative means, the local terminal can detect it by using the circuit breaker and disconnector status signal CBDS-A, B and C transmitted from the remote out-of-service terminal. The signal CBDS-A is "1" when both the circuit breaker and disconnector are closed. Thus, out-of-service is detected when either the circuit breaker or disconnector is open in all three phases.
Zero setting of the receive current data is also performed at the terminal under test. If the scheme switch [L. TEST] is set to "ON" or the signal R.DATA_ZERO is input by PLC, all the receive current data transmitted from the in-service terminal is set to zero and this facilitates the local testing. The zero setting of the receive current data is not performed by the alternative way as mentioned above.
The out-of-service detection logic can be blocked by the scheme switch [OTD].
REM1_IN_SRV: Remote 1 in-service
REM1_OFF_SRV: Remote 1 out-of-service
REM1_NON_USE: Remote 1 not used
1
1
REM1_OFF_SRV
LOCAL_TEST1
CBDS-A
CBDS-B
CBDS-C
[OTD]
"ON"
(+)
&
[Open1]
"ON"
(+)
1
1
1
REM1_NON_USE
REM1_IN_SRV
207
208
209
1
R.DATD_ZERO
1623
1
() Out-of-service detection logic for the remote 2 is same as above.
Figure 2.2.2.2 Out-of-Service Detection Logic
Note: When a communication circuit is disconnected or communication circuit failure occurs, do
not close the circuit breaker. When closing it, make sure that the DIF element is blocked. (Otherwise, it may cause malfunction.)
2.2.3 Zero-phase Current Differential Protection
The GRL100 provides sensitive protection for high-impedance earth faults by employing zero-phase current differential protection. For more sensitive protection, residual current is introduced through an auxiliary CT in the residual circuit instead of deriving the zero-phase current from the three phase currents.
The zero-phase current differential element has a percentage restraining characteristic with weak
www . ElectricalPartManuals . com
14
6 F 2 S 0 8 5 0
restraint. For details of the characteristic, see Section 2.16.
The scheme logic is shown in Figure 2.2.3.1. The output signal of the differential element DIFG performs time-delayed three-phase tripping of the circuit breaker with the tripping output signal DIFG.FS_TRIP. DIFG.FS_TRIP can start the incorporated autoreclose function when the scheme switch [ARC-DIFG] is set to "ON". The DIFG can trip instantaneously by PLC command DIFG_INST_TP.
Tripping output signal can be blocked by the PLC command DIFG_BLOCK and CRT_BLOCK. The output signal is also blocked when a communication circuit failure is detected by data error check, sampling synchronism check or interruption of the receive signals. For DIFG_FS signal, see Section 2.2.4.
Since the DIFG is used for high-impedance earth fault protection, the DIFG output signal is blocked when zero-phase current is large as shown in the following equation:
Σ I
01 ≥ 2 pu or Σ I02 ≥ 2 pu
where,
Σ I
01: Scalar summation of zero-phase current at local terminal relay
Σ I
02: Scalar summation of zero-phase current at remote terminal relay
pu: per unit value
In GPS-mode setting and backup mode (refer to 2.2.7.2), DIFG is blocked.
DIFG
DIFG.FS_TRIP
"ON"
&
1
ΣI01≥2PU
ΣI02≥2PU
1
Communication failure, etc.
1
DIFG_BLOCK
1586
85
44
DIFG_FS
1619
&
404
43C ON
86
DIFG_TRIP
DIFGFS
DIFG_INST_TP
1632
1
&
+
[DIFG]
t 0
TDIFG
0.0-10.0s
&
Figure 2.2.3.1 Scheme Logic of Zero-phase Current Differential Protection
2.2.4 Fail-safe Function
GRL100 provides OC1, OCD and EFD elements. These are used for fail-safe to prevent unnecessary operation caused by error data in communication failure. OC1 is phase overcurrent element and its sensitivity can be set. OCD is phase current change detection element, and EFD is zero-sequence current change detection element. Both of the OCD and EFD sensitivities are fixed. The scheme logic is shown in Figure 2.2.4.1.
The outputs of DIF.FS_OP and DIFG.FS_OP signals are connected to DIF-A_FS, DIF-B_FS, DIF-C_FS and DIFG_FS respectively by PLC function. These are connected at the default setting.
The fail-safe functions are disabled by [DIF-FS] and [DIFG-FS] switches. In the [DIF-FS], OC1 or OCD or both elements can be selected. If these switches are set to “OFF”, the signals of DIF.FS_OP and DIFG.FS_OP are “1” and the fail-safe is disabled.
www . ElectricalPartManuals . com
15
6 F 2 S 0 8 5 0
DIF.FS-A_OP
OC1-A
OC1-B
OC1-C
OCD-A
OCD-B
OCD-C
[DIF-FS]
"BOTH"
"OCD"
"
OFF"
"OC"
+
&
&
&
&
1
1
&
&
1
1
1
409
DIF.FS-B_OP
410
DIF.FS-C_OP
411
DIF.FS_OP
408
EFD
&
1
DIFG.FS_OP
412
[DIFG-FS]
"ON"
+
"OFF"
DIFG_FS (see Fig. 2.2.3.1.)
DIF-A_FS DIF-B_FS DIF-C_FS (see Fig. 2.2.2.1.)
1
Figure 2.2.4.1 Fail-safe Logic
2.2.5 Remote Differential Trip
Note: This function is available only when the three-terminal protection is applied by
setting the scheme switch [TERM] to “3-TERM”. In the case of A-MODE setting, this function is not available.
When one of the telecommunication channels fails, the terminal using the failed channel is disabled from performing current differential protection, as a result of the failure being detected through by the telecommunication channel monitoring.
Figure 2.2.5.1 Protection Disabled Terminal with Channel Failure
The remote differential trip (RDIF) function enables the disabled terminal to trip by receiving a trip command from the sound terminal, which continues to perform current differential protection.
Figure 2.2.5.2(a) and (b) show the RDIF scheme logic at RDIF command sending terminal (= sound terminal) and command receiving terminal (= disabled terminal). The sound terminal
GRL100
GRL100
GRL100
www . ElectricalPartManuals . com
16
6 F 2 S 0 8 5 0
sends the command when the tripping signals RDIF-A-S, RDIF-B-S, RDIF-C-S or RDIF-S are output locally and the scheme switches [RDIF] and [TERM] are set to “ON” and “3-TERM” respectively. The RDIF command is sent to the remote terminal via the 64kb/s digital link together with other data and signals.
The receiving terminal outputs a local three-phase trip signal RDIF-TRIP under the conditions that when the command RDIF1 or RDIF2 is received from either of the remote terminals, local differential protection does not operate, the scheme switches [RDIF] and [TERM] are set to “ON” and “3-TERM” respectively and no communication channel failure exists in the channel which received the RDIF command.
When the RDIF function is applied, the command sending signals and receiving signals must be assigned by PLC function.
DIF-A_TRIP
[RDIF]
+
“ON”
&
&
&
DIF-B_TRIP
DIF-C_TRIP
451
1
1
1
452
DIF-G_TRIP
&
453
RDIF-A-S
RDIF-B-S
RDIF-C-S
1
RDIF-S
454
(a) Sending terminal
RD.FS-A TP
456
&
455
457
458
1
1
1
RDIF-A-R1
1684
RDIF-B-R1
1685
RDIF-C-R1
1686
1
1
RDIF_BLOCK
1598
RDIF-R1
1687
&
&
&
&
&
&
RDIF_3PTP
1649
1
1
1
RD.FS-B TP
RD.FS-C TP
RD.FS_TRIP
RD.FS-A_ TRIP
Receiving signal from Remote Terminal 1
1
1
1
1
1
1
RDIF-A-R2
1716
RDIF-B-R2
1717
RDIF-C-R2
1718
RDIF-R2
1719
Receiving signal from Remote Terminal 2
43C ON
+
“ON”
[RDIF]
[TERM]
+
“3-TERM”
&
RD.FS-B_ TRIP
RD.FS-C_ TRIP
RDIF-A_FS
1624
RDIF-B_FS
1625
RDIF-C_FS
1626
DIF elements not operated
DIF.FS_OP
(b) Receiving Terminal
Figure 2.2.5.2 Remote Differential Trip
www . ElectricalPartManuals . com
17
6 F 2 S 0 8 5 0
2.2.6 Transmission Data
The following data are transmitted to the remote terminal via the 64kb/s digital link. The data depends on the communication mode and whether a function is used or not. The details are shown in Appendix N.
A-phase current
B-phase current
C-phase current
Residual current
Positive sequence voltage
A-phase differential element output signal
B-phase differential element output signal
C-phase differential element output signal
A-phase breaker and disconnector status
B-phase breaker and disconnector status
C-phase breaker and disconnector status
Scheme switch [LOCAL TEST] status
Scheme switch [TFC] status
Reclose block command
Sampling synchronization control signal
Synchronized test trigger signal
User configurable data
Current and voltage data are instantaneous values which are sampled every 30 electrical degrees (12 times per cycle) and consist of eleven data bits and one sign bit. This data is transmitted every sample to the remote terminal.
Three differential element outputs and the transfer trip command are related to remote terminal tripping and are transmitted every sampling interval.
Other data is transmitted once every power cycle.
The data transmission format and user configurable data are also shown in Appendix N.
A synchronized test trigger signal is used to test the differential protection simultaneously at all terminals. For details, see Section 6.5.3.
In addition to the above data, cyclic redundancy check bits and fixed check bits are transmitted to monitor the communication channel. If a channel failure is detected at the local terminal, all the local and remote current and voltage data at that instant are set to zero and outputs of the differential protection and out-of-step protection are blocked, and these protections of remote terminal are also blocked because the channel failure is also detected at the remote terminal.
2.2.7 Synchronized Sampling
The GRL100 performs synchronized simultaneous sampling at all terminals of the protected line. Two methods are applied for the sampling synchronization; intra-system synchronization and GPS-based synchronization. The former is applied to communication modes A-MODE and
www . ElectricalPartManuals . com
18
6 F 2 S 0 8 5 0
B-MODE, and the latter is applied to GPS-MODE.
The intra-system synchronization keeps the sampling timing error between the terminals within ±10µs or ±20µs and the GPS-based system keeps it within ±5µs or ±10µs for two- or three-terminal applications.
In both methods, the sampling synchronization is realized through timing synchronization control and sampling address synchronization control. These controls are performed once every two power cycles.
2.2.7.1 Intra-system Synchronized Sampling for A-MODE and B-MODE
The synchronized sampling is realized using sampling synchronization control signals transmitted to other terminals together with the power system data. This synchronized sampling requires neither an external reference clock nor synchronization of the internal clocks of the relays at different terminals. The transmission delay of the channel is corrected automatically.
Timing synchronization
One of the terminals is selected as the time reference terminal and set as the master terminal. The other terminal is set as the slave terminal. The scheme switch [SP.SYN] is used for the settings.
Note: The master and slave terminals are set only for the convenience of the sampling timing
synchronization. The GRL100s at all terminals perform identical protection functions and operate simultaneously.
To perform timing synchronization for the slave terminal, the sampling time difference between master and slave terminals is measured. The measurement principle of the sampling time difference T is indicated in Figure 2.2.7.1. The master terminal and slave terminal perform their own sampling and send a signal that becomes the timing reference for the other terminal.
t
t
Master terminal
TM
T
Slave terminal
T
d2
Td1
Sampling timing
T
F
Figure 2.2.7.1 Timing Synchronization
Each terminal measures the time TM and TF from its own sampling instant to the arrival of the
signal from the other terminal. As is evident from the figure, the times TM and TF can be
obtained by equation (1) and (2) where Td1 and Td2 are the transmission delay of the channel in each direction. The sampling time difference T can be obtained from the resulting equation (3).
TM = T
d1
T (1)
TF = T
d2
+ T (2)
T = {(TF T
M
) + (T
d1
T
d2
)}/2 (3)
The slave terminal advances or retards its sampling timing based on the time T calculated from equation (3), thereby reducing the sampling time difference with the master terminal to zero. This adjustment is performed by varying the interval of the sampling pulse generated by an
www . ElectricalPartManuals . com
19
6 F 2 S 0 8 5 0
oscillator in the slave terminal.
The difference of the transmission delay time Tdd (= T
d1
T
d2
) is set to zero when sending and
receiving take the same route and exhibit equal delays. When the route is separate and the sending and receiving delays are different, Tdd must be set at each terminal to be equal to the
sending delay time minus the receiving delay time. The maximum Tdd that can be set is 10ms.
(For setting, see Section 4.2.6.7. The setting elements of transmission delay time difference are TCDT1 and TCDT2.)
The time TM measured at the master terminal is sent to the slave terminal together with the current data and is used to calculate the ∆T.
The permissible maximum transmission delay time of the channel is 10ms.
In case of the three-terminal line application, the communication ports of the GRL100 are interlinked with each other as shown in Figure 2.2.7.2, that is, port CH1 of one terminal and port CH2 of the other terminal are interlinked. For the setup of the communication system, see Section 2.2.13.3.
When terminal A is set as the master terminal by the scheme switch [SP.SYN], the synchronization control is performed between terminals A and B, and terminals B and C. The terminal B follows the terminal A and the terminal C follows the terminal B. The slave terminals perform the follow-up control at their communication port CH2.
When the master terminal is out-of-service in A-MODE, the slave terminal that is interlinked with port 1 of the master terminal takes the master terminal function. In the case shown in Figure
2.2.7.2, terminal B takes the master terminal function when the master terminal A is out-of-service. In B-MODE and GPS-MODE, even if the master terminal is out-of-service, the master terminal is not changed. If DC power supply of the out-of-service terminal is “OFF”, differential elements at all terminals are blocked. Therefore, the [TERM] setting change from “3TERM” to “2TERM” is required.
GRL100
Terminal B
Terminal A
Terminal C
CH1
Communication port
GRL100
GRL100
Master
Slave
Slave
CH2
CH1
CH2
CH1 CH2
Figure 2.2.7.2 Communication Link in Three-terminal Line
Sampling address synchronization
The principle of sampling address synchronization control is indicated in Figure 2.2.7.3. After time synchronization has been established, the slave terminal measures the time from sending its own timing reference signal until it returns from the master terminal. The transmission delay time Td1 from slave to master terminal can be calculated from equation (4).
www . ElectricalPartManuals . com
20
6 F 2 S 0 8 5 0
Td = ({T
o
(T TM)}/2 + T
dd
)/2 (4)
The calculated transmission delay time Td1 is divided by the sampling interval T. The mantissa
is truncated and the quotient is expressed as an integer. If the integer is set to P, the reception at the slave terminal of the signal sent from the master terminal occurs at P sampling intervals from the transmission. Accordingly, by performing control so that the sampling address of the slave terminal equals integer P when the sampling address = 0 signal is received from the master terminal, the sampling address of the slave terminal can be made the same as the master terminal.
t
t
Master terminal
T
M
Slave terminal
T
T
d2
T
d1
T
O
T
F
Figure 2.2.7.3 Sampling Address Synchronization
2.2.7.2 GPS-based Synchronized Sampling for GPS-MODE
The relays at all terminals simultaneously receive the GPS clock signal once every second. Figure 2.2.7.4 shows the GPS-based synchronized sampling circuit at one terminal. The GPS clock signal is received by the GPS receiver HHGP1 and input to a time difference measurement circuit in the GRL100. The circuit measures the time difference T between the GPS clock and the internal clock generated from the crystal oscillator. The oscillator is controlled to synchronize with the GPS clock using the measured ∆T and outputs 2,400 Hz (50Hz rating) sampling signals to the current sampling circuit (analog to digital converter).
Figure 2.2.7.4 GPS Clock-based Sampling
GPS
GPS receiver
HHGP1
Time difference measurement
Crystal oscillator
Analog/digital converter
Synchronous control
ΔT
Lead/lag control
GRL100
Line
www . ElectricalPartManuals . com
21
6 F 2 S 0 8 5 0
Timing synchronization
When the GPS signal is received normally at every line terminal, the GRL100 performs synchronized sampling based on the received clock signal. The GRL100 can provide a backup synchronization system if the GPS signal is interrupted at one or more terminals, and perform synchronized sampling without any external reference clock. The backup system becomes valid by setting the scheme switch [GPSBAK] to "ON".
In the backup modes, the percentage restraint in the small current region can be increased from the normal 16.7% ((1/6)Ir in Figure 2.16.1.1) in accordance with the PDTD setting which is the probable transmission delay time difference between send and receive channels.
Backup modes, Mode 1, 2A and 2B are initialised when the backup system is set valid.
If the GPS signal interruption occurs when the backup is set invalid, the sampling runs based on the local clock. When the arrival time of the remote signal measured from local sampling instant deviates from a nominal time, the protection is blocked.
Mode 0: When the GPS signal is received normally, the sampling is performed synchronizing with the received clock signal thus realizing synchronized sampling at all terminals. Difference of the transmission delay time for the channel in each direction and fluctuation of the delay time can be permitted.
The GRL100 performs the protection based on the nominal current differential characteristics.
When the GPS signal has interrupted for more than ten seconds at any of the terminals, the mode changes to Mode 1 at all terminals.
Mode 1: The terminal which loses its GPS signal first functions as the slave terminal. If all terminals lose their signals simultaneously, then the scheme switch [SP.SYN] setting determines which terminal functions as the slave or master. The slave terminal adjusts the local sampling timing to synchronize the sampling with other terminal which is receiving the GPS signal regularly or with the master terminal.
Note: When two terminals are receiving the GPS signal regularly, the slave terminal
synchronizes with the terminal that is interlinked with port 2 of the slave terminal.
When the GPS signal has been restored, the mode shifts from Mode 1 back to Mode 0.
If, during Mode 1 operation, a failure occurs in the communication system, the sampling timing adjustment is disabled and each terminal runs free. If the free running continues over the time determined by the PDTD setting or the apparent phase difference exceeds the value determined by the PDTD setting, the mode shifts from Mode 1 to Mode 2A at all terminals.
Mode 2A: In this mode, the intra-system synchronization described in 2.2.7.1 is applied assuming that the transmission delay time for the channel in each direction is identical. Fluctuation of the delay time can be permitted.
The current differential protection is blocked in this mode.
When the GPS signal has been restored, the mode shifts from Mode 2A to Mode 0.
If the GPS signal interruption occurs a set period following energisation of the relay power supply or the mode returned to Mode 0 from Mode 1, 2A or 2B, then the transmission delay time measurement will not be completed in Mode 0, and the mode changes to Mode 2A.
When the apparent current phase difference has stayed within the value determined by the PDTD setting, the scheme switch [AUTO2B] for automatic mode change is set to "ON" and [TERM] is set to "2TERM", the mode changes from Mode 2A to Mode 2B at both terminals.
The mode can be changed to Mode 2B manually through a binary input signal "Mode 2B initiation" or user interface. Before this operation, it must be checked that the transmission delay
www . ElectricalPartManuals . com
22
6 F 2 S 0 8 5 0
time difference between send and receive terminals is less than the PDTD setting and the SYNC ALARM LED is off. If these conditions are not satisfied, the operation may cause a false tripping.
Note: The mode change with the binary input signal is performed by either way:
If the binary input contact is such as to be open when the relay is in service, set
the BI to "Inv" (inverted). The mode changes when the contact is closed more than 2 seconds and then open.
If the binary input contact is such as to be closed when the relay is in service, set
the BI to "Norm" (normal). The mode changes when the contact is open more than 2 seconds and then closed.
For the BISW4, see Section 3.2.1.
In the three-terminal application, the mode change to Mode 2B is available even
when one of the three communication routes is failed.
Mode 2B: The same intra-system synchronization as in Mode 2A is applied.
When the GPS signal has been restored, the mode shifts from Mode 2B to Mode 0.
If a failure occurs in the communication system, the sampling timing adjustment is disabled and each terminal runs free.
The mode shifts from Mode 2B to Mode 2A, when the apparent load current phase difference exceeds the value determined by the PDTD setting for pre-determined time.
Checking the current phase difference (For two-terminal application setting only)
The current phase difference is checked using the following equations:
I
1A cos θ < 0
I
1A I1B sin θ < I1A I1B sin θs
I
1A > OCCHK
I
1B > OCCHK
Where,
I
1A = Positive sequence component of load current at local terminal
I
1B = Positive sequence component of load current at remote terminal
θ = Phase difference of I
1B from - I1A
θs = Critical phase difference = CHKθ‐HYSθ
CHKθ =
PDTD(µs)
2
×
360°
20000(µs)
+ 8.5°
HYSθ = Margin of phase difference checking
OCCHK = Minimum current for phase difference check
If the magnitude of I
1A and I1B exceed the setting and the conditions for both equations above are
established, then the sampling is regarded to be synchronized.
If the current phase difference exceeds a set value, the "SYNC ALARM" LED on the front panel is lit.
Checking the current phase difference is enabled by setting the scheme switches [TERM] to "2TERM" and [SRCθ] to "I".
www . ElectricalPartManuals . com
23
6 F 2 S 0 8 5 0
I1A
I1B
-I1A
θ
s
θ
Figure 2.2.7.5 Current Phase Difference Check
Sampling address synchronization
The same method as described in section 2.2.7.1 is employed in Mode 0 and Mode 2A where the sampling synchronization must be established. It is not employed in Mode 1 and 2B because the sampling address synchronization has already been established in the previous mode.
2.2.7.3 Differential Current Calculation
Synchronized sampling allows correct calculation of differential current even in the presence of a transmission time delay. This processing is indicated in Figure 2.2.7.4. As indicated in the figure, sampling synchronization is established between terminals A and B, and both the sampling timing and sampling address match. The instantaneous current data and sampling address are both sent to the other terminal. The GRL100 refers to the sampling address affixed to the received data and uses local data with the same sampling address to calculate the differential current. This allows both terminals to use data sampled at the same instant to perform the differential current calculation, no matter how large the transmission time delay is.
t
t
Terminal A
Terminal B
4 3210
i
B(1)
i
A(0)
i
B(0)
i
A(1)
4 3210
Sampling address number
i
A(0)
Differential current calculation
i
B(0)
Figure 2.2.7.4 Calculation of Differential Current with Transmission Delay Time
Protection in anomalous power system operation
Even when any of the terminals is out-of-service, the GRL100 in-service terminal can still provide the differential protection using the out-of-service detection logic. For details of the out-of-service detection logic, see Section 2.2.2.
When one terminal is out-of-service in a two-terminal line, the other terminal continues the current differential protection using the local current irrespective of whether it is a master terminal or a slave terminal.
When one terminal is out-of-service in a three-terminal line, synchronized sampling is established between the remaining two terminals as follows and the differential protection is maintained.
If the master terminal is out-of-service, one of the slave terminals takes over the master
terminal synchronized sampling function and enables current differential protection
www . ElectricalPartManuals . com
24
6 F 2 S 0 8 5 0
between the remaining terminals to be performed.
If the slave terminal is out-of-service, the master and another slave terminal maintain the
differential protection.
When two terminals are out-of-service in a three-terminal line, the remaining terminal continues the current differential protection using the local current irrespective of whether it is a master terminal or a slave terminal.
2.2.8 Charging Current Compensation
When differential protection is applied to underground cables or long overhead transmission lines, the charging current which flows as a result of the capacitance of the line (see Figure
2.2.8.1) appears to the protection relay as an erroneous differential current.
GRL100 GRL100
Terminal A Terminal B
Ic
Figure 2.2.8.1 Charging Current
The charging current can be compensated for in the setting of the relay’s differential protection sensitivity but only at the expense of reduced sensitivity to internal faults. In addition, the actual charging current varies with the running voltage of the line and this must be taken into account in the setting.
In order to suppress the effect of the charging current while maintaining the sensitivity of the differential protection, GRL100 is equipped with a charging current compensation function, which continuously re-calculates the charging current according to the running line voltage and compensates for it in its differential current calculation. The running line voltage is measured by VT inputs to GRL100.
The user enters values for line charging current and for the line voltage at which that charging current was determined in the settings [DIFIC] and [Vn], and these values are used by the relay to calculate the capacitance of the line. The relays at each line end share the line capacitance between them, that is they divide by two for a two-terminal line, and by three for a three-terminal line. In the case of a three-terminal line, if the relay at one terminal is out-of-service for testing (see out-of-service terminal detection), the other two terminals are automatically re-configured to divide the line capacitance by two.
Each terminal continuously calculates its share of the charging current at the running line voltage on a sample by sample basis as follows:
Ic = C
dV
/ dt
where,
Ic = line charging current
C = line capacitance calculated from settings [DIFIC] and [Vn]
V = measured line voltage
The relay then calculates the line current compensated for the charging current on a sample by sample basis as follows:
www . ElectricalPartManuals . com
25
6 F 2 S 0 8 5 0
I = I’ - Ic
where,
I = compensated current
I’ = actual measured current
Note that since GRL100 calculates both the charging current and compensated line current on a sample by sample basis, all necessary phase information is inherently taken into account.
2.2.9 Blind Zone Protection
The GRL100 relay has “Out-of-Service Detection Logic” as described in Section 2.2.2. This logic functions automatically to detect the remote CB or DS (line disconnecting switch) opened condition as shown in Figure 2.2.9.1. If the remote CB or DS is opened, the received remote current data is set to “zero” Ampere at the local terminal, and the local relay can be operated with only local current like a simple over current relay. Therefore, this logic function is used for blind zone protection.
The zone between CB and CT at the remote terminal is the blind zone in Figure 2.2.9.1. If a fault occurs within this zone, the busbar protection should operate first and trip the CB at the remote terminal, but the fault remains and the fault current (IF) is fed continuously from the local
terminal. Since this phenomenon is an external fault for the current differential protection scheme, the blind zone fault cannot be cleared. The fault may be cleared by remote backup protection following a time delay, but there is a danger of damage being caused to power system plant. Fast tripping for this type of fault is highly desirable. The Out-of-Service Detection Logic is effective for a fault where a blind zone between CT and CB on the line exists as shown in Figure 2.2.9.1.
If the CB and DS condition are introduced at the remote terminal as shown in Figure 2.2.9.1, the GRL100 relay at the local terminal can operate with only local current and the fault can be cleared, because the remote current data is automatically cancelled as explained above.
Please note the “CB Close Command” signal must be connected to the GRL100 relay to prevent unwanted operation for a CB close operation (manual close and/or autoreclose). Unwanted operation may be caused if the close timing of the CB auxiliary contact is delayed relative to the CB main contact. Therefore, the CB close command signal resets forcibly the Out-of-Service Detection Logic before the CB main contact is closed.
CB and DS status signals are input by PLC. If the out-of-service detection is not used, its logic can be blocked by the scheme switch [OTD].
www . ElectricalPartManuals . com
26
6 F 2 S 0 8 5 0
DS
IR (=IF)
IL (=IF)
LINE
REMOTE
LOCAL
52A 52C 52B
89L1
IR(Current)
IR(Current)
CBDS-C
CBDS-B
(Remote terminal closed: “0” logic)
Differential Current (Id)
Remote terminal “OPEN”
CBDS-A
Comm. Link
CBDS-A,B,C
CBDS-A,B,C
DIFF RELAY GRL100
(REMOTE)
DIFF RELAY GRL100 (LOCAL)
1
&
≧1
1
If DS or CB signals (CBDS-A, B, C) changes to “0”, remote current data (IR) is cancelled to zero (0). Therefore, differential current (Id) equals to
local current (IL).
(Cancel circuit of remote terminal current IR)
Σ
BUSBAR PROT.
CB
FAULT
1
CB CLOSE COMMAND
IR
IL
Blind Zone
Figure 2.2.9.1 Blind Zone Protection
2.2.10 Application to Three-terminal Lines
When current differential protection is applied to a three-terminal line, special attention must be paid to the fault current flowing out of the line in the case of an internal fault and CT saturation at the outflowing terminal in case of an external fault.
Fault current outflow in case of internal fault
In case of a two-terminal line, fault current never flows out from the terminals for an internal fault. But in case of a three-terminal line with an outer loop circuit, a partial fault current can flow out of one terminal and flow into another terminal depending on the fault location and magnitude of the power source behind each terminal.
Case 1 in Figure 2.2.10.1 shows a fault current outflow in a single circuit three-terminal line with outer loop circuit. J and F in the figure indicate the junction point and fault point. A part of the fault current flowing in from terminal A flows out once from terminal C and flows in again from terminal B through the outer loop.
Case 2 shows the outflow in a double-circuit three-terminal line. The outer loop is generated when one terminal is open in the parallel line. A part of the fault current flowing in from terminal A flows out from the fault line to the parallel line at terminal C and flows in again at terminal B through the parallel line.
www . ElectricalPartManuals . com
27
6 F 2 S 0 8 5 0
A
B F
Case 1
J
C
Case 2
A
J
B
F
C
Open
Figure 2.2.10.1 Fault Current Outflow in Internal Fault
The larger current outflows from terminal C when the fault location is closer to terminal B and the power source behind terminal C is weaker. In case of a double-circuit three-terminal line, 50% of the fault current flowing in from terminal A can flow out from terminal C if terminal C is very close to the junction and has no power source behind it.
These outflows must be considered when setting the differential element.
CT saturation for an external fault condition
In case of a two-terminal line, the magnitude of infeeding and outflowing currents to the external fault is almost the same. If the CTs have the same characteristics at the two terminals, the CT errors are offset in the differential current calculation.
A B
F
Case 1
J
C
Case 2
A
J
B
F
C
Open
Figure 2.2.10.2 Fault Current Distribution
www . ElectricalPartManuals . com
28
6 F 2 S 0 8 5 0
But in case of a three-terminal line, the magnitude of the current varies between the terminals and the terminal closest to the external fault has the largest magnitude of outflowing fault current. Thus, the CT errors are not offset in the differential current calculation. Thus, it is necessary to check whether any fault causes CT saturation, particularly in the terminal with outflow, and the saturation must be accommodated utilising the DIFI2 setting of the DIF element.
2.2.11 Dual Communication Mode
Three-terminal application models have dual communication mode (GRL100-∗1∗). By connecting the remote terminal with dual communication routes, even if one of the routes fails, it is possible to continue sampling synchronization and protection by the current differential relay. To set dual communication mode, select "Dual" in the TERM setting. Other settings are the same as that of the two-terminal. In GPS-MODE setting, however, the dual communication mode cannot be applied.
GRL100
GRL100
CH1
CH2
CH1
CH2
Figure 2.2.11.1 Dual Communication Mode
2.2.12 Application to One-and-a-half Breaker Busbar System
The GRL100-700 series can be used for lines connected via a one-and-a-half breaker busbar system, and have functions to protect against stub faults and through fault currents.
Stub fault
If a fault occurs at F1 or F2 when line disconnector DS of terminal A is open as shown in Figure
2.2.12.1, the differential protection operates and trips the breakers at both terminals without any countermeasures.
Terminal A
F2 F1
DS
×
× ×
Terminal B
× ×
×
Figure 2.2.12.1 Stub Fault
GRL100 provides stub protection to avoid unnecessary tripping of the breakers in these cases. For the stub protection, see Section 2.13.
Fault current outflow in case of internal fault
As shown in Figure 2.2.12.2, the fault current may outflow in case of an internal fault of double-circuit lines. The outflow at terminal A increases as the fault location F approaches terminal B. When the fault is close to terminal B, 50% of the fault current flows out to the parallel line, though it depends on the power source conditions at terminals A and B.
This outflow must be considered when setting the differential element.
www . ElectricalPartManuals . com
29
6 F 2 S 0 8 5 0
Figure 2.2.12.2 Fault Current Outflow in Internal Fault
2.2.13 Communication System
2.2.13.1 Signaling Channel
The GRL100 transmits all the local data to the remote terminal by coded serial messages. Two signaling channels are required for two-terminal line protection, six for three-terminal line protection and four for dual communication for two-terminal line as shown in Figure 2.2.13.1.
GRL100
Terminal B Terminal A
GRL100
(a) Two-terminal Line
GRL100
GRL100
Terminal B
Terminal A
Terminal C
GRL100
(b) Three-terminal Line
Terminal B Terminal A
GRL100
GRL100
(c) Dual Communication for Two-terminal Line
Figure 2.2.13.1 Signaling Channel
F
Terminal B Terminal A
www . ElectricalPartManuals . com
Loading...
+ 443 hidden pages