Toshiba Eagle T1 Series PLCs User Manual

In Touch With Tomorrow
Analog Inputs
Analog Outputs
Eagle
0201
Eagle 0404
Eagle 0800
I
nputs
Also
Programmable Controllers
TOSHIBA INTERNATIONAL CORPORATION
13131 West Little York Road
PH. 800 231- 1412, 713-466 -0277 FAX 713-466-8773
Houston, TX 77041
PRODUCT INFORMATION October 2002
More Analog Inputs for T1 µPLCs
Toshiba Houston offers the Eagle analog I/O for the T1 Series µPLCs. The Eagle I/O is universal analog I/O. Eagle I/O allows T1 PLCs to work with the following analog signals.
For the analog inputs, the Eagle I/O performs the A to D (analog to digital) conversion and loads a digital value directly into a T1 register. For analog outputs, the Eagle I/O reads a digital value out of a T1 register and performs a D to A (digital to an alog conversion). Analog signal types and PLC registers are defined using the included simple setup software.
Simple process control has never been easier or more cost effective. Now the analog values of temperature, pressure, flow, weight, etc. can be included into the sequencing, interlocking and
permissive control performed by the PLC.
For more information contact your nearest Toshiba programmable controller distributor, or visit the Toshiba Houston Industrial website, www.tic.toshiba.com.
8 Analog
Available
2 Analog Inputs 1 Analog Output
4 Analog Inputs 4 Analog Output
Thermocouples 0-20 mA 4-20 mA RTDs 4-20 mA 0-100 mV 0-50 mV 0-100 mV 0-10 Vdc
SPECIFICATIONS
Input Range: Voltage
ANALOG INPUTS
ITEM SPECIFICATION Part Number: See Order Numbers Below I/O Registers Assigned: None (Uses Data Registers, 1 Register per Channel Designated by Sfwr) Input Range: Thermocouple
Resolution
Input Range: RTD
Resolution
Current
Resolution
ANALOG OUTPUTS
ITEM SPECIFICATION Part Number: See Order Numbers Below I/O Registers Assigned: None (Uses Data Registers, 1 Register per Channel Designated by Sfwr ) Output Range: Voltage
Current
GENERAL
ITEM SPECIFICATION Communication Ports: PLC
Temperature: Humidity: 10% to 90% Non condensing Immunity to ESD: Level 3 per IEC 61000-4-2 Immunity to Transients: Level 3 per IEC 61000-4-4 Radiated Susceptibility: Level 3 per IEC 61000-4-3 Emissions: EN55011 CISPR A Certifications: CE, CSA Isolation: Analog isolated from Digital, no isolation between channels. Size Eagle 0800 & 0404 155mm x 102mm x 48mm
Mounting: DIN rail or through hole Weight Eagle 0800 & 0404: 0.5 kg Eagle 020:1 02 kg
J, K, R, S, T, E, N, & B . 0-100 mV, Cold Junction Compens ation Error 1° maximum, 0.5°C typical. PT100 (0.00395 and 0.00385), 3 Wire Compensation, Current Sense
0.5ma. Range: -200° to 800° C 0-100 mV, 0-10 V (via PLC scaling/external shunt resistor) 0-20 mA 12 bit
0-10 V, Minimum Load = 400 4-20 mA Maximum Load = 500
Connects to T1 Programming Port
IBM
Connects to Computer for Setup Connects to OIS for PLC Access Operating: 0° to 50° C Storage: -25° to 80° C
Eagle 0201 94mm x 42mm x 47 mm
ORDER NUMBERS
ITEM DESCRIPTION Eagle0201U 2 Universal Analog Inputs, 1 Analog Output. Eagle0404U 4 Universal Analog Inputs, 4 Analog Outputs. Eagle-0800U 8 Universal Analog Inputs. TKEAGLE05T1 Cable, 50 cm, Connects T1 to Eagle Exp.Unit TKEAGLE20T1 Cable, 2 m, Connects T1 to Eagle Exp.Unit1 TKEAGLE20T2 Cable, 2 m, Connects T2 to Eagle Exp.Unit
NOTES: 1. Each Eagle unit contains setup software.
2. Connection cables must be ordered separately