1
Precautions for Safety
• Read these “Precautions for Safety” carefully before installation.
• The precautions described below include important items regarding safety. Observe them without fail.
• After the installation work, perform a trial operation to check for any problem.
• Ask an authorized dealer or qualified installation professional to install or reinstall the
software.
• Perform installation work properly according to this Installation Manual.
• Do not modify the unit.
This may cause malfunction.
• Perform wiring correctly in accordance with specified the current capacity.
Failure to do so may result in short-circuiting, overheating, or fire.
• Connect the specified cables for the terminals securely to prevent external forces from
affecting them.
Failure to do so may result in disconnection, overheating, or fire.
• When providing services, perform the task after you confirm that you turned off the main
power supply, removed the power cord from the AC inlet, and the power was off.
CAUTION
Before Installation
No.
1
2
3
4
Quantity
1
1
1
2
Item
INTELLIGENT SERVER
Installation Manual
Cable
Closed end wire joint
Remarks
RS-485 cable for Intelligent Server
No.
1
2
Type
Wire size
Length
Type
Length
Signal line
For RS-485
For ethernet
Description
2-core shield wire
1.25 mm2, 500 m max. (total length)
LAN cable (higher than Category 5, UTP)
The appropriate use of straight cable/cross cable should be done
depending on your system used.)
100 m max
Use the following wiring materials to connect signal lines. (Procured on site)
Check the following package contents.
Prepare the following software (sold separately) before using the server.
Available software
Intelligent Server Software BMS-STCC
E ( is 06 or higher)
BACnet Software BMS-STBN
E ( is 06 or higher)
NOTE