Toshiba BMS-LSV6E Installation Manual

Page 1
Model: BMS-LSV6E
INSTALLATION MANUAL
INTELLIGENT SERVER
CONTENTS
Precautions for Safety.................................................................................................................... 1
Before Installation .......................................................................................................................... 1
1 CF (Compact Flash) card Installation ....................................................................................... 3
2 Setting .......................................................................................................................................... 3
3 Installation.................................................................................................................................... 4
4 Cable Connection ....................................................................................................................... 6
• Thank you very much for purchasing this TOSHIBA INTELLIGENT SERVER.
• Please read this manual carefully beforehand for proper installation of the SERVER.
Page 2
1
Precautions for Safety
• Read these “Precautions for Safety” carefully before installation.
• The precautions described below include important items regarding safety. Observe them without fail.
• After the installation work, perform a trial operation to check for any problem.
• Ask an authorized dealer or qualified installation professional to install or reinstall the software.
• Perform installation work properly according to this Installation Manual.
• Do not modify the unit.
This may cause malfunction.
• Perform wiring correctly in accordance with specified the current capacity.
Failure to do so may result in short-circuiting, overheating, or fire.
• Connect the specified cables for the terminals securely to prevent external forces from affecting them.
Failure to do so may result in disconnection, overheating, or fire.
• When providing services, perform the task after you confirm that you turned off the main power supply, removed the power cord from the AC inlet, and the power was off.
CAUTION
Before Installation
No.
1
2
3
4
Quantity
1
1
1
2
Item
INTELLIGENT SERVER
Installation Manual
Cable
Closed end wire joint
Remarks
RS-485 cable for Intelligent Server
No.
1
2
Type
Wire size
Length
Type
Length
Signal line
For RS-485
For ethernet
Description
2-core shield wire
1.25 mm2, 500 m max. (total length)
LAN cable (higher than Category 5, UTP) The appropriate use of straight cable/cross cable should be done depending on your system used.)
100 m max
Use the following wiring materials to connect signal lines. (Procured on site)
Check the following package contents.
Prepare the following software (sold separately) before using the server.
Available software
Intelligent Server Software BMS-STCC
E ( is 06 or higher)
BACnet Software BMS-STBN
E ( is 06 or higher)
NOTE
Page 3
2
Intelligent Server Specifications
Names of each parts
VGA
LAN2PS/2LAN1
USB
COM1
SDRRNL3OFFS1ONL2L1
L1 LED L2 LED S1 switch L3 LED
Ethernet port2 (LAN2) Ethernet port1 (LAN1) CF CARD slot Serial port1 (COM1)
RUN LED Shut down switch
POWER switch
AC inlet (AC IN)
Specifications
Power Supply
Current
Operating temperature/humidity
Storage temperature
Dimension
Mass
COM port
LAN
220-240 VAC 50/60 Hz
0.2 A
0 to 40 °C, 10 to 90 %RH (no condensation)
-20 to 60 °C
250 (W) × 70 (H) × 145 (D) mm (292 (W) including the fixing metal plate)
1.5 kg
RS-485 (9-pin, D-SUB)
10BASE-T/100BASE-TX
External view
70
69.5
19
3.2
145
105
9
125
11
250
292
280
4-Ø4.6
Page 4
3
1
CF (Compact Flash) card Installation
• Do not insert or remove the CF (Compact Flash) card during power on of the Intelligent Server. Doing so may cause a failure.
• If the CF (Compact Flash) card is not inserted properly, the Intelligent Server will not work.
REQUIREMENT
Insert the CF card (with the software sold separately) Push the CF card fully into the slot.
2
Setting
CF card
Rating label
(1)Remove two screws and the cover plate and the CF card slot appears. (2)Insert the CF card with its rating label attached surface upward.
Confirm the CF card is surely pushed into the slot.
The setting is not required. S1 is set to “OFF”.
Page 5
4
Intelligent Server Installation Method and Orientation
There are 2 types of setting methods and directions available for the server. Use the fixing metal plates attached when installing the server.
3
Installation
(1)Surface mount
(2)Wall mount
Mount the server with the front face upward.
AC inlet side
(Unit : mm)
4 x Ø4.6
19
66
21 105
280
145
Fixing screw hole positions
Do not install the unit in any of the following places.
• Humid or wet place
• Dusty place
• Place exposed to direct sunlight
• Place where there is a TV set or radio within one meter
• Place exposed to rain (outdoors, under eaves, etc.)
REQUIREMENT
Page 6
5
3
Installation (continued)
Installation Space and Maintenance Space
The installation space and the maintenance space must be determined before installation. These spaces depend on installation method.
Installation Space
The values in the following table are required for installation space in each direction. Select an installation place that allows good air ventilation.
Item
Installation space
Direction
Top
Bottom
Front
Rear
Right side
Left side
Surface mount
100
0
100
50
50
(*1) “Location adjacent to wall permitted” means that the unit can be installed close to the wall on that side.
Maintenance Space
Maintenance space is required for installation and maintenance of the unit.
Front
INTELLIGENT
SERVER
1000
1000
:
Maintenance Space
:
Installation Space
(Unit: mm)
Rear
(unit: mm)
Top
Rear
Left side
Right side
Front
Wall mount – type A
50
0
100
100
100
Wall mount – type B
100
0
100
100
100
Location adjacent to wall permitted (*1)
Page 7
6
4
Cable Connection
Power cable is not supplied for the Intelligent Server. Insert a three core power cord applicable to the standard of the country you use. Be sure to connect the earth line of the power cable securely.
REQUIREMENT
• Insert an AC power cable into the AC inlet of the unit.
• Connect the power cord plug to an outlet (220 V - 240 V, AC).
• Disconnect the appliance from the main power supply. Connect this appliance to the main power supply by a circuit breaker or a switch with a contact separation of at least 3mm.
• Make sure that the outlet is earthed.
REQUIREMENT
Ethernet wire Connection
Serial Port (RS-485) Connection
• Confirm that the power supply for the intelligent server is shut off.
• Connect RS-485 cable (packaged with the intelligent server) to Serial port 1 (COM1). Fix the cable to the Intelligent Server by the fixing screws (two locations on both sides) attached to the connector on RS-485 cable.
Connection to the TCS-NET Relay Interface
• TxRx(+) Connection Connect three of the four wires of RS-485 wire (red wire/orange wire/wire from the terminal board RS­485 A of the TCS-NET Relay Interface) together with the closed end wire joint. The red and orange wires can be connected directly to the terminal board RS-485 A of the Relay Interface.
• TxRx(-) Connection Connect three of the four wires of RS-485 wire (brown wire/yellow wire/wire from the terminal board RS­485 B of the TCS-NET Relay Interface) together with the closed end wire joint. The brown and yellow wires can be connected directly to the terminal board RS-485 B of the Relay Interface.
The RS-485 signal wire has polarity. If connected with incorrect polarity, the unit will not work.
Do not connect or disconnect the wire during control operation. Doing so may cause a malfunction.
NOTE
• Insert the Ethernet wire into the Ethernet port1 (LAN1).
AB
TCS-NET Relay Interface
TCS-NET Relay Interface
Intelligent Server
RS-485 cable
Brown/Yellow
Red/Orange
Shield wire open (insulated)
Shield wire earth connection
RS-485
RS-485
AB
RS-485
Connect the shield wires of the 2 wires
Closed end wire joint
AC Power Cable Connection
Page 8
7
• • •
Trademarks:
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •
• BACnet is a registered trademark of ASHRAE(American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.).
• Compact Flash and CF are trademarks of SanDisk Corporation.
• Ethernet is a registered trademark of Xerox Corporation.
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •
EH99861301