• Read these “Precautions for Safety” carefully before installation.
• The precautions described below include important items regarding safety. Observe them without fail.
Understand the following details (indications and symbols) before reading the body text, and follow the
instructions.
• After the installation work has been completed, perform a trial operation to check for any problems. Explain how
to use and maintain the unit to the customer.
• Ask customer to keep this Manual at accessible place for future reference.
IndicationMeaning of Indication
WARNING
CAUTION
SymbolsMeaning of Symbols
Text set off in this manner indicates that failure to adhere to the directions in the warning could result in
serious bodily harm (*1) or loss of life if the product is handled improperly.
Text set off in this manner indicates that failure to adhere to the directions in the caution could result in
serious bodily injury (*2) or damage (*3) to property if the product is handled improperly.
*1: Serious bodily harm indicates loss of eyesight, injury, burns, electric shock, bone fracture, poisoning, and other
injuries which leave aftereffect and require hospitalization or long-term treatment as an outpatient.
*2: Bodily injury indicates injury, burns, electric shock, and other injuries which do not require hospitalization or long-
term treatment as an outpatient.
*3: Damage to property indicates damage extending to buildings, household effects, domestic livestock, and pets.
“" Indicates prohibited items.
The actual contents of the prohibition are indicated by a picture or text placed inside or next to the graphic
symbol.
“" Indicates compulsory (mandatory) items.
The actual contents of the obligation indicated by a picture or text placed inside or next to the graphic
symbol.
EN
WARNING
• Ask an authorized dealer or qualified installation professional to install or reinstall this unit.
Inappropriate installation may result in electric shock or fire.
• Electrical work must be performed by a qualified electrician in accordance with this installation
manual.
The work must satisfy all local, national and international regulations.
Inappropriate work may result in electric shock or fire.
• Be sure to turn off all main power supply switches before starting any electrical work.
Failure to do so may result in electric shock.
• Do not modify the unit.
A fire or an electric shock may occur.
CAUTION
• Do not install this unit where flammable gas may leak.
If gas leaks and accumulates around the unit, it may cause a fire.
• Perform wiring correctly in accordance with specified the current capacity.
Failure to do so may result in short-circuiting, overheating or fire.
• Use predefined cable and connect them certainly. Keep the connecting terminal free from
external force.
It may cause an exothermic or a fire.
–2–
2-EN
Energy Monitoring Relay Interface
Installation Manual
2Introduction
Applications/Functions/Specifications
Applications
• The Energy Monitoring Relay Interface is used to measure and distribute the power of the air conditioner.
Functions
• The interface calculates output power pulses with connected power meters, and then sends the calculation result
to the Touch Screen Controller or other central controller.
Specifications
Power supply220V - 240VAC, 50/60Hz
Power consumption4 W
Operating temperature/humidity0 to 40 °C, 10 to 90% RH
Storage temperature-20 to +60 °C
Chassis materialGalvanized sheet metal 0.8t
Dimensions66(H) x 193(W) x 246(D) mm
Mass1.35 kg
Use the following wiring materials to connect the signal lines and power lines. (Procured on site)
No.LineDescription
Type2-core shield wires
1For RS-485
2For connection to power meter
3For power
Wire size
Length
Type
Length
Type
Wire size
2
1.25 mm
, 500m max. (total length)
2
2-core wire, 0.3mm
H07 RN-F or 245IEC66
2
0.75mm
, 50 m max.
, 100m max.Wire size
EN
4Installation
Energy Monitoring Relay Interface Installation Method and
Orientation
There are five installation methods for this relay interface as shown below: surface mount and wall mounts.
Use the attached screws.
No good
REQUIREMENT
Do not install the unit in any of the following places.
• Humid or wet place
• Dusty place
• Place exposed to direct sunlight
• Place where there is a TV set or radio within one meter
• Place exposed to rain (outdoors, under eaves, etc.)
Installation Space and Maintenance Space
A side space for connecting through cable inlets and an upper space for maintenance
must be reserved before installation.
The other sides can be adjacent to surrounding objects.
100mm
100mm
–4–
4-EN
Energy Monitoring Relay Interface
Installation Manual
5Connection of Power cables/Earth wires/
Communication cables
CAUTION
• The RS-485 communication cable has polarity. Connect A to A, and B to B. If connected with incorrect polarity, the
unit will not work.
Power cables/Earth wires/Communication cables
Connect power cables, earth wires, and communication cables to the specified terminals on the terminal block.
To connect 2 cables, change the
preset cable clamp to the
provided one and fix the cables
with the cable clamp as shown in
the figure.
B
Touch Screen Controller or other
central controller
Power meter
RS-485
+ - + - + - + - + - + - + - + -
LED2
1234
LED5
LED4
LED3
LED1
SW1SW2SW3
SW4SW6
A
SG
DI1DI6DI2
DI3DI7 DI8DI5
DI4
SW7
Secure each cable with a
cable clamp.
Connect the
earth wire to the
earth terminal on
the chassis.
Secure each
cable with a
cable clamp.
Power supply
220-240VAC
(50/60Hz)
Length of stripped
power cable
35
10
3510
Length of stripped
communication cable
Insert the wire by pushing
the lever with a
screwdriver.
Check that the wire is
inserted securely.
LN
Length of stripped
power meter wire
35
6
When inserting two RS-485
communication cables into a single
terminal for connection to another
interface, crimp them using the
attached pin terminal.
356
REQUIREMENT
Disconnect the appliance from the main power supply.
This appliance must be connected to the main power supply by a circuit breaker or switch with a contact separation
of at least 3mm.
Fasten the screws to the terminal with torque of 0.5Nm.
5-EN
–5–
Energy Monitoring Relay Interface
Installation Manual
Wiring Connection
The following describes a connection example of Energy Monitoring Relay Interface.
Shield earthing
• The RS-485 communication cable must be earthed on TCS-NET Relay Interface or central controller. It does not
have to be earthed on Energy Monitoring Relay Interface.
The shielded wire must be crimped with closed end connector. The shielded wire end must be insulated and left
open.
Connection of power meters
• Use a power meter with a pulse generator.
Connect the non-voltage contact output of the power meter to the Energy Monitoring Relay Interface.
An external input circuit is shown below.
Input signal is electrically isolated by photo-coupler.
(1) Example of contact input connection
12V
Input
terminal
+
DI-1 to DI-8
Power meter
(with pulse generator)
Contact
-
Energy Monitoring Relay Interface
(2) Example of contact input connection
12V
Input
terminal
+
DI-1 to DI-8
Power meter
(with pulse generator)
Current
sink
-
Energy Monitoring Relay Interface
CAUTION
• Output sink current has polarity.
When they are connected to inappropriate input terminal, the unit may not operate properly.
EN