Toshiba BMS-CM1280TLE INSTALLATION MANUAL

COMPLIANT MANAGER
Installation Manual
Model name:
BMS-CM1280TLE BMS-CM1280FTLE
Save These Instructions!
ENGLISH
Installation Manual
Contents
1 PRECAUTIONS FOR SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2 PACKAGED ITEMS OF COMPLIANT MANAGER . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
3 INSTALLATION OF THE COMPLIANT MANAGER . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
4 CONNECTION OF POWER CABLES/SIGNAL WIRES/EARTH WIRES . . . . . . . . . . . 6
5 MODE SETTING FOR THE CONTROLLER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
6 SWITCHES FOR SETTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
7 CENTRAL CONTROL ADDRESS (GROUP NUMBER) SETTING . . . . . . . . . . . . . . . 14
8 ZONE SETTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
9 CHANGING RETURN-BACK TIME/TEMPERATURE SETTINGS . . . . . . . . . . . . . . . 18
10 TEST RUN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
11 SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
1-EN
–2–
Installation Manual
1 PRECAUTIONS FOR SAFETY
After the installation work, perform a trial operation to check for any problem. Explain how to use and maintain the unit to the customer. Ask the customer to keep this Installation Manual.
WARNING
• Ask an authorized dealer or qualified installation professional to install or reinstall the Compliant Manager.
Improper installation may result in electric shock or fire.
• Turn off the main power supply switch or breaker before attempting any electrical work.
Make sure all power switches are off. Failure to do so may cause electric shock.
• Perform installation work properly according to this Installation Manual.
Improper installation may result in electric shock or fire.
• Do not modify the unit.
Any modification may cause a malfunction, resulting in overheating or fire.
CAUTION
• Do not install the unit at a place subject to leakage of flammable gas.
If flammable gas leaks and remains around the unit, it may catch fire.
• Perform wiring correctly in accordance with the specified current capacity.
Failure to do so may result in short-circuiting, overheating, or fire.
• Connect the specified cables for the terminals securely to prevent external forces from affecting them.
Failure to do so may result in disconnection, overheating, or fire.
• Make sure that the ground connection has been properly made.
Improper grounding may result in electric shock. Ask your dealer or an installation professional about how to check the ground connection.
• Do not install the unit at a humid place or a place subject to vibration.
High humidity or vibration may cause a failure of the unit.
• Do not expose the unit to direct sunlight or a heat source.
This may cause a failure of the unit.
• Do not install the unit at a place where noise is generated.
This may cause a malfunction of the unit.
REQUIREMENT
Disconnect the appliance from the main power supply. This appliance must be connected to the main power supply by a circuit breaker or switch with a contact separation of at least 3mm.
–3–
2-EN
g
Installation Manual
2
Compliant Manager 1
Manual
CD-R 1 * Packaged for BMS-CM1280FTLE only
Clamp filter
Tie-wraps
PACKAGED ITEMS OF COMPLIANT MANAGER
Part name Image Quantity Remarks
1 Owner’s Manual
1 Installation Manual
1
2 BMS-CM1280TLE
4 BMS-CM1280FTLE
2 BMS-CM1280TLE
4 BMS-CM1280FTLE
Network Setting Manual * Packaged for BMS-CM1280FTLE only
External Dimensions
8.5 155
8.5 5Ø
106.6
172
140
180
158
42
70
76
8
17.9
12.7
120
Dimensions of unit fixing holes in the wall, etc.
142
108
90
19 69
90
3-EN
46 66
–4–
* Reserve space of 10mm or more
when installin
the unit.
*
Installation Manual
3 INSTALLATION OF THE COMPLIANT
MANAGER
CAUTION
• Do not twist communication wires (used between indoor unit and outdoor unit and used for central control) and input/ output wires with power wires or bundle them together with power wires in a metal tube. Doing so may cause malfunction.
• Install the Compliant Manager away from a noise source.
• When noise is induced into the power supply of the Compliant Manager, take proper measures such as attaching of a noise filter.
Power supply box
Base
Panel
Shield plate
This hole is provided for penetration of the power supply box fixing screw.
This screw secures the power supply box, base, and shield plate.
The panel is secured with the claw.
The panel is secured with the screw at the bottom.
Remove the screw at the bottom of the panel, insert a flat-blade screwdriver or the like into the right and left grooves at the bottom of the panel, and then carefully detach the panel with the screwdriver.
–5–
4-EN
L
L
t/
Installation Manual
4 CONNECTION OF POWER CABLES/SIGNAL
WIRES/EARTH WIRES
Connect power cables, signal wires, and earth wires to the specified terminals on the terminal block.
Optional for BMS­CM1280FTLE only Energy Monitoring Interface Digital I/O Interface
RS-485
Power Supply 220-240VAC
*1
FG N
FG B (-)A (+)
L
U2/U4 U1/U3 U2/U4 U1/U3
Control Input
12
ON
Common (Out)
RunStatus Output
Alarm
Common (In)
Fire alarm
All Start All Stop
TCC-LINK main Bus (LINE2)
TCC-LINK main Bus (LINE1)
TIMER
COM-DO
DO2 DO1
COM-DI
DI3 DI2 DI1
Outdoor Unit
Indoor Unit
Remoto controller
Optional
Schedule Timer
Outdoor Unit
Indoor Unit
Remoto controller
*1 Secure the power cable with the clamp in the case.
NOTE
• TCC-LINK does not have polarity.
• RS-485 has a polarity. Connect A(+) to A(+) and connect B(-) to B(-).
• For TCC-LINK, connect the shield wire to the ground on the air conditioner side (single-point grounding).
• For RS-485, connect the shield wire to the ground on the Compliant Manager side (single-point grounding).
ength of stripped power cable
Length of stripped TCC-LINK and RS-485 communication wire
20
80
Attach a round pressure terminal to the end of each wire of the power cable.
L N
Be sure to attach the supplied clamp filter to the communication wire. * When attaching the clamp filter, be sure to
15 10
35
pass the communication wire twice through
Power wire Round pressure terminal
the clamp filter as shown below. Then fasten the communication wire with the supplied cable tie-wrap.
TCC-LINK wire
LAN cable
RS-485 wire
ength of stripped digital Inpu
Output communication wire
20 10
Remove and insert the wire while pressing the upper button with a screwdriver.
5-EN
–6–
<Connections to External Equipment>
Installation Manual
Designation
Digital input/output terminals
Input/
Output
item
Status output
Control input
Compliant Manager side External equipment side
Input/output
conditions
Alarm output Run output
Non-voltage “A” contacts
Static (Relay output)
Allowable contact voltage/current 30 VDC, 0.3 A
All stop input All start input Fire alarm input
Voltage-applied “A” contacts
All stop:
Pulse or static
All start:
Pulse or static Fire alarm: Static (Photocoupler
input) * Select non-
voltage contacts
that allow minute
current (12V,
1mA)
+12V
Terminal name
0.4 to 1.2 Ø Alarm
Run
Output common
0.4 to 1.2 Ø
All stop (+)
All start (+)
Fire alarm (+)
Input common (–)
Demarcation
terminal
Example of
circuit
Digital
input
(Pulse or static)
(Pulse or static)
(Static)
Input/output
conditions
Wiring length: 100 m or less
Pulse width: 300 ms or more
Wiring length: 100 m or less
COM
*Wire the cable so that the user should not touch the electricity port directly.
<Specifications for Wiring>
Use the following materials to connect signal lines and power lines (procured on site)
No Line Description
Type 2-core shield wire
1 For TCC-LINK
2 For RS-485
3For Power
4
For Digital Input/Output
connection
Wire size
Length
Type 2-core shield wire
Wire size
Length
Type
Wire size
Length
Type
Wire size
Length
1.25mm², 1000m max. (total length including
2.00mm², 2000m max. air conditioner area)
1.25mm², 500m max. (total length)
H07 RN-F or 245IEC66
0.75mm², 50m max.
227IEC75 (2-wire)
0.5mm², 100m max.
–7–
6-EN
Installation Manual
5 MODE SETTING FOR THE CONTROLLER
Operation mode
Use SW1-<6> for the operation mode setting. OFF side: Central control mode
This Compliant Manager is used as a central control unit. Settings with the remote controller are inhibited by the setting of the Compliant Manager.
ON side: Remote control mode
This Compliant Manager is used as a remote controller. Settings with the Compliant Manager are inhibited by the setting of another central control unit.
Control group selection
Either simultaneous mode or an arbitrary range of a line and 16 groups (1 to 16, 17 to 32, 33 to 48, and 49 to 64) can be selectively set.
DIP-SW1 DIP-SW2
<2><3><4><5><5><6>
All groups OFF OFF OFF OFF OFF OFF
Group 1 to 16 ON OFF OFF OFF OFF ON
LINE 1
LINE 2
Example: When setting LINE 1 (group 1 to 32) in
the control group selection
Group 17 to 32 OFF
Group 33 to 48 OFF OFF
Group 49 to 64 OFF OFF OFF
Group 1 to 16
Group 17 to 32 OFF
Group 33 to 48 OFF OFF
Group 49 to 64 OFF OFF OFF
ON OFF OFF OFF ON ON
ON ON OFF OFF OFF ON
ON OFF OFF OFF ON
ON OFF OFF ON
ON OFF ON
ON OFF OFF ON ON
ON OFF ON ON
ON ON ON
* When the control group selection is used, only the set group range is displayed. * The control group selection is available only for one line.
7-EN
–8–
Installation Manual
<System Configuration of the Compliant Manger>
• Each line consists of up to 64 zones and 64 groups (up to 128 zones and 128 groups in total).
• Each group number is a central control address. (Effective values 1 to 64 and 99 are unset values.)
• Default setting when shipped: One group is assigned to one zone (zone number = group number)
• Groups that can be registered in each zone must meet the following conditions.
1. Groups are connected to the same line.
2. Groups are in the same group number range when the control group selection is used.
Compliant Manager
LINE 2
Group 1 ~ 16
Group 17 ~ 32
Group 33 ~ 48
LINE 1
ALL
ZONE 1
Gr1 Gr5 Gr8 Gr16
ZONE 17
Gr17
ZONE 33
Gr33 Gr35
Gr2 Gr10
ZONE 19 ZONE 22
Gr19
ZONE 2 ZONE 10 ZONE 16
ZONE 30
Gr22 Gr25
ZONE 39
Gr39 Gr43
Gr30
Gr45
Gr32Gr32
ZONE 32
Gr32Gr48
Group 49 ~ 64
Gr = Group
ALL: The Compliant Manger operates as follows in combination with LINE selection. LINE 1 ALL (All groups on LINE 1 are selected.) LINE 2 ALL (All groups on LINE 2 are selected.)
Gr32Gr64Gr49 Gr50 Gr55 Gr58 Gr60
ZONE 64
* When the control group selection is not used ("ALL group"), all groups and zones on LINE 1 and LINE 2 can be
controlled.
* When the control group selection is used, only groups and zones in the set group range can be controlled.
• When the control group selection is used, groups and zones outside this range are not displayed and cannot be operated.
means the entire set group range.
• Zones can be registered and operated only within the set group range. (No groups outside the range can be registered or operated.)
• The group control mode is available only for one line.
* Multiple group ranges can be specified by the control group setting.
(Example) When groups 33 to 48 and groups 49 to 64 are specified at the same time, a group range (groups
33 to 64) is set by the control group setting.
–9–
8-EN
6 SWITCHES FOR SETTING
The settings switch is installed on the rear of the Compliant Manager.
Installation Manual
DIP-SW2
1 2 3 OFF ON ON OFF
ALL ON ALL OFF
NOT CHANGE
PERMITTED ALL INDOOR UNIT OPERATION BY USING RCU
ALL OFF
CENTRAL 1
ALL OFF AND CENTRAL 1
CENTRAL 2
ALL OFF AND CENTRAL 2
State for Weekly timer
ON
SW2
OFF
4 Must be set to OFF
5
LINE 1
LINE 2
Control group Selection Line
SW1
2 3 4 5
7
ON
OFF
Buzzer
SW2
6
ALL groups
group 1 ~ 16
group 17 ~ 32
group 33 ~ 48
group 49 ~ 64
Control groups Selection
3 Must be set to OFF
ON
SW3
OFF
8
ON
OFF
Indicate
1 Must be set to OFF
2
ON
OFF
Synchronization of
Setting Zone data
4
Normal
Fire alram
Normal
Fire alram
Fire alram input
switching
screwdriver edge nor a bare hand when power is supplied.
To avoid an electric shock hazard. DO NOT touch any
terminal on the Printed Circuit Board with a metal rod a
DIP-SW1
ON
SW1
OFF
1
MAIN
SUB
Central Control
8
PERMIT
INHIBIT
Central/Individual
7
MAIN
SUB
Sys.con
6
CENTRAL
RCU
Central/RCU change
DIP-SW3
9-EN
–10–
<DIP-SW1>
Installation Manual
Factory setting: All OFF
<1> Compliant Manager main/sub selection
OFF: Main ON: Sub
Normally, this bit is set to OFF.
When two Compliant Manager units are used as a main unit and a sub unit with the same mode setting, set this bit to OFF (Main) for one unit and to ON (Sub) for the other unit.
<2> to <5> Control group selection
Control group selection SW2-<6> SW1
All groups OFF -
Group 1 ~ 16 ON <2> ON
Group 17 ~ 32 ON <3> ON
Group 33 ~ 48 ON <4> ON
Group 49 ~ 64 ON <5> ON
These bits specify a group range used in the control group selection. The Compliant Manager for which control group selection is set controls only groups within the set group range.
ON
OFF
DIP-SW1
1
2 3 4 5 6 7 8
* To use the control group selection, set SW1-<2> to <5> and SW2-<5>
to <6>.
<6> Central control/remote controller mode selection
OFF: Central control mode ON: Remote controller mode
Central control mode: Individual setting by remote controller can be
inhibited by Compliant Manager.
Remote controller mode: Setting by Compliant Manager is inhibited by
other centra control equipments.
<7> Central control Main/Sub selection
OFF: Main ON: Sub
This setting is required when multiple Compliant Manager units are used or another central control unit is used.
(1) Set this bit to OFF when one Compliant Manager unit is used. (2) When multiple central control units are used as a main unit and sub
units, set to OFF (Main) for one unit and set to ON (Sub) for other units.
* It is recommended that the “All groups” (control group selection
setting) be set for the central control main unit.
<8> Central button enable/ disable
OFF: button operation is
permitted
ON: button operation is
inhibited
* The button is disabled in
the remote controller mode regardless of this setting.
–11–
10-EN
Installation Manual
<DIP-SW2>
<1> to <3> Timer input switching
These bits switch operation when the schedule timer has changed.
• Use (1) and (2) only in the remote control mode.
• When the control group selection is used, “All ON,” “All OFF” and “all indoor units” mean those within the set group range.
Switch No.
<1> <2> <3>Central controller operation
Timer OFF ON Timer ON OFF
(1) All ON All OFF OFF OFF OFF
(2) No change All OFF ON OFF OFF
Individual control of all indoor
(3)
units to be permitted
(4) Ditto
(5) Ditto All indoor units CENTRAL 2 OFF OFF ON
(6) Ditto
All indoor units CENTRAL 1 OFF ON OFF
All OFF and all indoor units to be CENTRAL 1
All OFF and all indoor units to be CENTRAL 2
ON ON OFF
ON OFF ON
ON
OFF
Factory setting: All OFF
DIP-SW2
1
2 3 4 5 6 7 8
<4> Always OFF
Always set this bit to OFF.
<5> Control group Selection line
OFF: LINE 1 ON: LINE 2
* Set a line number for which the control group selection is used.
<6> Control group selection enable
OFF: Normal mode ON: Control group selection
Set this bit to ON when the control group selection is used. * To use the control group selection, set SW1-<2> to <5> and SW2-<5> to
<6>. For details, see the table on the previous page.
<7> Buzzer
OFF: With buzzer sound ON: Without buzzer sound
<8> indication
OFF: Displayed ON: Not displayed
11-EN
–12–
<DIP-SW3>
Factory setting: All OFF
<1> Always OFF
• Always set this bit to OFF.
<2> Synchronization of Setting Zone data
OFF: With transfer ON: Without transfer This bit specifies whether to perform synchronous communication of Setting Zone data between Compliant Managers. * When this bit is set to ON (without transfer), synchronous communication is not
performed, and when zone setting is made, the data is not reflected in other Compliant Managers.
Installation Manual
DIP-SW3
1
ON
OFF
2 3 4
<3> Always OFF
• Always set this bit to OFF.
<4> Fire alarm input switching
• OFF: CLOSE: Fire alarm (OPEN: Normal)
COM-DI
DI3
• ON: OPEN: Fire alarm (CLOSE: Normal)
COM-DI
DI3
COM-DI
DI3
(Fire alarm)(Normal)
COM-DI
DI3
(Fire alarm)(Normal)
–13–
12-EN
Installation Manual
7 CENTRAL CONTROL ADDRESS (GROUP
NUMBER) SETTING
• Central control addresses must be assigned to all air conditioners to be controlled.
• Under the control of the Compliant Manager, central control address equals group number.
For address setting when connecting a TCC-LINK adapter to the central control system, refer to this manual and the TCC-LINK adapter installation manual.
<Preparations for central control address (group number) setting>
• Turn on the power of all air conditioners.
• This Compliant Manager or a standard wired remote controller is necessary for setting central control addresses.
• Terminate the operation of air conditioners, and then set central control addresses. * To set central control addresses with the Compliant Manager, initial communication with all connected indoor
and outdoor units must have been completed. Therefore, wait at least 10 minutes after power-on, and then start central control address setting.
NOTE
If the address setting is made before the initial communication is completed, an address is not assigned to some units.
• Connect terminals U1 and U2 in the outdoor unit (Header unit) to the relay connector of terminals U3 and U4.
• Set SW30-2 on the interface P.C. board of the outdoor unit (Header unit) to ON only for one system, and to OFF for others.
* The location of SW30 is shown in the wiring diagram supplied with the outdoor unit.
<Setting central control addresses (group numbers)>
Use “manual setting from wired remote controller,” “manual setting,” or “automatic setting” to set central control addresses.
A Manual setting from wired remote controller
Set central control addresses (group numbers) from a standard wired remote controller. * The following setting procedure is described based on button operations of the wired remote controller RBC-
AMT32E or RBC-AMT31E.
(1) Press the button and button simultaneously for at least 4 seconds.
(Note: Do not press the button during setting.)
(2) Press the button to change the CODE No. 03. (3) Set central control addresses (group numbers) with the buttons.
• Group numbers used for the Compliant Manager are central control addresses (DN item 03).
• The effective address range is 1 to 64. However, there must be no duplicate address on the same line.
• An address value of 99 is used as an unset address.
(4) Press the button to fix the setting. (5) Press the button to exit the address setting mode.
* This setting procedure may vary depending on the wired remote controller model. * Perform these steps while air conditioners are not working.
13-EN
–14–
Installation Manual
B Manual setting
Set central control addresses (group numbers) manually from the Compliant Manager. (1) Press the button and ZONE button simultaneously for at least 4 seconds.
(CODE No. C1 flashes.)
(2) Check CODE No. C1, and then press the button. (3) Select the line on which the unit exists and the zone and group in which addresses are to be registered with the
LINE button, ZONE and buttons, and GROUP and buttons.
• When a zone is selected, group numbers registered in the zone are displayed.
• Groups whose numbers are displayed are already registered.
• Even when addresses have been registered, the registration can be cancelled with the button.
(4) Select the unit to be registered in the group selected in step (3).
• Switch refrigeration system No.1 to 31 with the button, and then switch indoor unit No.1 to 64 with the
button.
• When no system exists, indoor unit number is displayed as “- -”.
• System number 31 is for a local adapter and heat exchange ventilators. An indoor unit number is always
displayed regardless of whether the unit exists or not. (5) Press the button to register the setting or press the button to cancel the setting. (6) To continue registration, repeat steps (3) to (5). (7) Press the button to terminate the address setting.
C Automatic setting
Set central control addresses automatically from the Compliant Manager. (Central control addresses are set automatically in ascending order of unit number.)
(1) Press the button and ZONE button simultaneously for at least 4 seconds.
(CODE No. C1 flashes.) (2) Press the SET TEMP. or button to change the CODE No. to C2. (3) Press the button. (Central control addresses are automatically registered. This registration requires several
minutes. lights during this address setting.) (4) goes out and the indication of C2 flashes, which shows completion of the automatic address
registration. (5) Press the button to exit the address setting mode.
<Checking duplicate central control address>
NOTE
This function is not available for light commarcial air conditioners. For details, refer to the manual of the TCC-LINK adapter.
(1) Press the button and ZONE button simultaneously for at least 4 seconds.
(CODE No. C1 flashes.) (2) Press the SET TEMP. or button to change the CODE No. C3. (3) Press the button to start checking a duplicate central control address error. ( lights during this
check.) (4) When goes out, the check has been completed.
* When nothing appears in the group number display area at the end of checking, no duplicate address error
has been detected.
* When a group number in the group number display area flashes at the end of checking, a duplicate address
error has been detected. (Correct the duplicate address.)
–15–
14-EN
Installation Manual
<Correcting duplicate address>
Correct the duplicate address detected through the check using the following procedure. (1) When the duplicate address check has been completed, select CODE No. C1 with the SET TEMP. or
button. (2) Press the button. (3) The number of group in which the error has been detected flashes.
Select the flashing group number to be corrected with the GROUP or button. (4) Press the button to clear the set incorrect central control address.
After that, set a correct central control address. (5) Press the button to terminate the duplicate address correction.
15-EN
–16–
Installation Manual
8 ZONE SETTING
Register groups in a zone or cancel them. (1) Change the mode to the zone setting mode.
• Press the button, button, and ZONE button simultaneously for at least 4 seconds. (The displayed zone number flashes and the Compliant Manager enters the zone setting mode. Indicates CODE No. “E1”.)
(2) Select the zone to be set.
• Select the zone number to be set with the ZONE or button, and then press the button to fix the selection. (When the selection has been fixed, the selected zone number flashes.)
• When selection of zone has been fixed, the marks of the group numbers registered in the zone light up.
(3) Change registration of groups in a zone.
Register groups in a zone.
1. Select the group number to be set with the GROUP or button. Pressing the SET TEMP. or
button skips the group number by +16 or by -16.
2. Press the button.
The marks of the registered group numbers light up. (
3. Pressing the button restores the state before the button is pressed.
4. To continue registration of groups, repeat this procedure from the beginning.
→ )
NOTE
No zone data has been stored at this time. If the ZONE or button is pressed before the registration change is fixed, the set content for registration change is discarded.
(4) Fix the registration change.
Press the button. The set content for registration change is stored in the memory. * After the memory write operation has been completed, the Compliant Manager exits the zone setting mode.
–17–
16-EN
Installation Manual
9 CHANGING RETURN-BACK TIME/
TEMPERATURE SETTINGS
Return-back time and return-back temperature (CODE No. settings) can be changed using the following procedure.
NOTE
Do not change the data of CODE No. 0A and the following item codes to prevent the remote controller from malfunctioning.
CODE
No.
01 Return-back Enable/Disable 001 (Enabled) 000 (Disabled), 001 (Enabled)
02 Return-back 1 Time, Heating 030 (30 minutes) 1 to 60 minutes (in units of 1 minute)
03 Return-back 1 Time, Cooling 030 (30 minutes) 1 to 60 minutes (in units of 1 minute)
04 Return-back 1 Temp., Heating 018 (18°C) 18 to 29°C (in units of 1°C)
05 Return-back 1 Temp., Cooling 028 (28°C) 18 to 29°C (in units of 1°C)
06 Return-back 2 Time, Heating 030 (30 minutes) 1 to 60 minutes (in units of 1 minute)
07 Return-back 2 Time, Cooling 030 (30 minutes) 1 to 60 minutes (in units of 1 minute)
08 Return-back 2 Temp., Heating 018 (18°C) 18 to 29°C (in units of 1°C)
09 Return-back 2 Temp., Cooling 028 (28°C) 18 to 29°C (in units of 1°C)
Item
Factory setting Setting range
Data
Changing settings
The following shows an example of changing the time (factory setting) in the case of return-back 1 heating from 30 minutes to 45 minutes.
(1) Change the mode to the CODE No. setting change mode.
Press the , , and ZONE buttons simultaneously for at least 4 seconds. ( and CODE No. flash.)
(2) Set the data of the CODE No..
1. Change the CODE No. to “02” with the SET TEMP. or button.
2. Change the set data to “045” with the GROUP or button.
( and CODE No. are still flashing.)
3. Press the button to determine the data. and CODE No. change to lighting.
4. To continuously change other settings, repeat steps 1 to 3 above.
17-EN
NOTE
At this time, the entered data of the selected CODE No. has not been saved yet.
(3) Determine the change.
Press the button to write the updated data in the memory of the remote controller. * When the data has completely been written in the memory, the CODE No. setting change mode is exited.
–18–
LINE 1
Installation Manual
ZONE GROUP
133
234
335
436
537
638
739
840
941
10 42
11 43
12 44
13 45
14 46
Indoor unit
No.
Installation place ZONE GROUP
Indoor unit
No.
Installation place
15 47
16 48
17 49
18 50
19 51
20 52
21 53
22 54
23 55
24 56
25 57
26 58
27 59
28 60
29 61
30 62
31 63
32 64
–19–
18-EN
LINE 2
Installation Manual
ZONE GROUP
133
234
335
436
537
638
739
840
941
10 42
11 43
12 44
13 45
14 46
Indoor unit
No.
Installation place ZONE GROUP
Indoor unit
No.
Installation place
15 47
16 48
17 49
18 50
19 51
20 52
21 53
22 54
23 55
24 56
25 57
26 58
27 59
28 60
29 61
19-EN
30 62
31 63
32 64
–20–
Installation Manual
10TEST RUN
<Conducting a Test Run for the Compliant Manager>
• A test run is necessary to confirm that the Compliant Manager has recognized air conditioner units after the central control address setting.
(1) Turn on the power of all connected air conditioners. (2) Turn on the power of the Compliant Manager. (3) Make sure that the number of air conditioners connected to each line (only main units when group control is
performed) equals the group number count displayed on the Compliant Manager.
(4) When these numbers are identical, there is no problem.
If they differ, set central control addresses again according to “Central Control Address (Group Number) Setting.” Also make sure that there is no incorrect wiring.
<Conducting a Test Run for Air Conditioners>
(1) Press the button for at least 4 seconds. (The “TEST” indication lights in the test run mode.) (2) Press the button and button. (Temperature cannot be set during a test run.) (3) When the test run is completed, press the button to exit the test run mode.
11SPECIFICATIONS
Model BMS-CM1280TLE BMS-CM1280FTLE
Power supply 220-240 VAC 50/60Hz
Power consumption 3W 5W
Number of connectable indoor units (TCC-LINK) 128 Units (LINE1 64 Units, LINE2 64 Units)
Energy Monitoring Relay Interface (RS-485) 4 Units (max.)
Digital Input/Output Relay Interface (RS-485) 4 Units (max.)
Operating temperature 0 to 40°C to 90%RH
Dimensions -20 to +60°C (no condensation)
Mass 120 (H) × 180 (W) × 88 (D)
Weight 1.1Kg 1.2Kg
–21–
20-EN
MEMO
21-EN
–22–
–23– 22-EN
DH84309201
Loading...