UNINTERRUPTIBLE POWER SYSTEMS
Black Gold Series
2 kVA Single-Phase Rackmount UPS
ß Complete Front Access
ß Hot-Swappable Battery
ß Industrial Grade Steel Construction
ß Built-in Isolation Transformer
ß True On-line
ß Power Factor Correction
ß Vibration and Shock Tested
BUILT FOR EXTREME ENVIRONMENTS
Toshiba’s Black Gold UPS is built for harsh industrial environments subjected to shock and vibration.
The Black Gold Series features a robust steel enclosure (3U), an intelligent LED status display, an input
isolation transformer, hot-swappable slide-out battery modules, front output receptacle breakers, RS-232C
and remote contacts. This system combines true on-line technology, state-of-the-art electronics and the
Toshiba name to offer one of the most reliable UPS on the market.
Black Gold Series Specifications
Model Number UC1A1A020C6RKBIG UC1E1E020C5RKBIG
General
Information
Input
Battery
Output
Environment
Bypass
Interface
Options
Rated Output Capacity 2000 VA (1400 W)
External Dimensions (W x D x H) 16.75 in x 24.0 in x 5.25 in (425 mm x 610 mm x 133 mm)
Rated Voltage 120 VAC, Single Phase 230 VAC, Single Phase
Voltage Variation +10% to -30%
Rated Frequency 50/60 Hz
Power Factor Greater than .98 when in inverter mode
Harmonic Currents Less than 5% THD
DC Nominal (Voltage Range) 72 VDC (57.6 – 82.8 VDC)
Float Charge (Regulation) 82.8 VDC (±2%)
Ripple Voltage 0.5 % R.M.S.
Rated Back-up Time when fully charged at
o
77
F (25oC)
Recharge Time Maximum 24 hrs to 100% (90% recharge after 8 hrs)
Rated Charge Time 0.40 Amps
Type of Batteries Sealed lead-acid
Rated Voltage (Single Phase) 120 VAC 230 VAC
Output Voltage Regulation ±3%, steady state
Output Frequency
Output Voltage Waveform Computer-grade sinewave with less than 3.0% THD
Rated Current (RMS) 16.6 Amps 8.6 Amps
Rated Power Factor .7 lagging
Maximum Overload Capacity 150% for 60 sec
Voltage Transient Characteristic ± 5% under 100% load step change
Crest Factor 3.0
Operating Temperature
Storage Temperature
Operating Humidity 30% to 90% (no condensation)
Altitude Less than 3000 ft (1000 m) above sea level
Net Weight 119 lbs (54 kg) 111 lbs (50 kg)
Acoustical Noise <45 dB at maximum output, measured 3.3 ft (1 m) from front panel
Efficiency (AC-DC-AC) 82%
An automatic transfer of load to bypass switch (< 4mS-transfer time) may be caused by an overload of the inverter output, or by an
internal fault condition. Also, the load can be manually transferred to bypass by putting the rocker switch in the STOP position.
Dry Contact Bypass, battery low, and on-line signals DB9 male connector
RS232 ASCII Pins 1 through 8 DB9 female connector
Receptacle 3 5-15R (Duplex) 3 IEC320 (Duplex)
RemotEye II
®
50/60 Hz ±0.5% in free running mode
32 to 104
6 min at full load
18 min at half load
(Line sync range ±1 Hz)
o
F (0 to 40oC), optimal at 77oF (25oC)
SNMP and web-based monitoring
-4 to 104
o
F (-20 to 40oC)
UPS ADJUSTABLE SPEED DRIVES MOTORS CONTROLS INSTRUMENTATION PLC
Available Through:
INDUSTRIAL DIVISION
13131 West Little York Road, Houston, Texas 77041
Tel (713)466-0277 Fax (713)892-5212
US (800)231-1412 Canada (800)872-2192 Mexico 01(800)527-1204
www.toshiba.com/ind
Copyright 8/2006
*UPSblkgldfly051205*