1700 Series UPS
No more than three modules shoul
Transformer Module Connection Guide
SAVE THESE INSTRUCTIONS. This sheet contains important instructions for Toshiba 1700 Series Transformer Modules.
These instructions should be followed during the installation of the transformer module.
The ambient temperature range in which this unit should be operated or stored is 32°F to 104 °F (0°C to 40 °C).
This module should not be opened under any circumstances. There are no user servicable parts inside. For service
contact your local Toshiba representative, or contact the Toshiba UPS marketing department toll-free at (800) 231-1412.
When adding transformer modules, be sure to use the proper model unit.
CAUTION
Misuse of this equipment could result in human injury and equipment damage. In no event will
Toshiba Corporation be responsible or liable for either indirect or consequential damage or
injury that may result from the use of this equipment.
Inspection/Installation
After Unpacking:
1) Check the unit for loose, broken, bent or otherwise damaged parts. If damage has occurred during shipment, keep all
original packing materials for return to shipping agent. Warranty will not apply to units damaged during shipment.
2) Check to see that the rated capacity and the model number specified on the nameplate conform to the order
specifications.
Installation Precautions
This transformer module is intended for use with a Toshiba 1700 Series UPS. Any electrical or mechanical
modifications to this equipment, without prior written consent of Toshiba International Corporation will void all
warranties and may void UL/CUL listing. Unauthorized modifications also can result in personal injury, death, or
destruction of the equipment. When installing this transformer module follow all installation instructions and precautions
as listed in the 1700 Series user manual
IMPORTANT SAFETY INSTRUCTIONS
Model Number UF1-IO-024-6BG
Capacity 2400VA (1.68kW)
Input voltage1
Single phase 208/240VAC,
selectable
Output voltage Single phase 120/240VAC
Output voltage
regulation
Rated load power
factor
Rated output current
(rms)
Within +/- 3%, steady state
0.7
9.5A @ 240V
19A @120V
Transformers
Input Isolation
Output Auto
Mechanical Design
Weight 60 lbs (27.3 kg)
Dimensions (in[mm]) 6[152]H x 8[203]W x 19.7[502]D
Module Layout
Figure 1
any configuration. If the transformer module is being
used with a system that has a second battery module at
least one module must be placed beside the others.
Stacking four modules could result in a tipping hazard.
56940-000
UPS Connections
Standard Unit with 208/240V Input, 120/240V Output Transformer Module
The figures below show the standard unit, consisting of one electronics module and one battery module, with the addition of
the 208/240V input, 120/240V output transformer module. The modules do not have to be stacked for the unit to operate;
however, if the modules are to be stacked please refer to the 1700 Series user manual for instructions on interlocking
modules.
To connect the modules electrically follow these steps:
Step 1 Step 2
Plug the gray power cord coming from the transformer
module (labeled “Input from UPS”) into the gray 20A
outlet on the back of the electronics module
Plug the black power cord coming from the electronics
module into the matching outlet on the back of the
transformer module (labeled “Output to UPS”).
Step 3 Step 4
Plug the black power cord coming from the
transformer module (labeled “Input Power”) into the
power source intended to supply power to the unit.
Plug the blue battery connector coming from the
battery module into the matching blue connector on
the electronics module.