Toshiba 1700 User Manual

TOSHIBA
1
TOSHIBA
2
TOSHIBA
IMPORTANT NOTICE
The instructions contained in this manual are not intended to cover all of the details or variations in equipment, nor to provide for every possible contingency to be met in connection with installation, operation, or maintenance. Should further information be desired or should particular problems arise which are not covered sufficiently for the purchaser's purposes, the matter should be referred to the local Toshiba sales office.
The contents of this instruction manual shall not become a part of or modify any prior or existing agreement, commitment, or relationship. The sales contract contains the entire obligation of Toshiba International Corporation's UPS Division. The warranty contained in the contract between the parties is the sole warranty of Toshiba International Corporation's UPS Division and any statements contained herein do not create new warranties or modify the existing warranty.
Any electrical or mechanical modifications to this equipment, without prior written consent of Toshiba International Corporation will void all warranties and may void UL/CUL listing. Unauthorized modifications also can result in personal injury, death, or destruction of the equipment.
UNINTERRUPTIBLE POWER SUPPLY
If additional information or technical assistance is required beyond what is included in this manual contact Toshiba’s marketing department by calling toll free (800) 231-1412, by e-mail at
toshibaups@tic.toshiba.com,
or write to: Toshiba International Corporation, 13131 W. Little York Road, Houston, TX 77041-9990.
Please complete the following information for your records and to remain within this equipment manual:
Model Number:
Serial Number:
Date of Installation:
Inspected By:
December, 2004
Part no. 55349-001
3
TOSHIBA
TABLE OF CONTENTS
SECTION
Disclaimer ................................................................................................3
Table of Contents ....................................................................................4
General Safety Instructions....................................................................5
Important Safety Instructions............................................................. 6-7
Inspection/Installation.............................................................................8
Inspection of the New UPS ......................................................................................... 8
Installation Precautions............................................................................................... 8
Operating Precautions ................................................................................................ 8
External Layout........................................................................................9
Electronics Module ..................................................................................................... 9
Battery Modules........................................................................................................ 10
UPS Connections ..................................................................................10
Standard Module Connections.................................................................................. 10
Operating the UPS.................................................................................11
Display Panel Layout ................................................................................................ 11
Starting the UPS System .......................................................................................... 11
Starting when AC Power is Available........................................................................ 11
Starting on DC Power ............................................................................................... 12
Stopping the UPS ..................................................................................................... 12
UPS Display Status and Operating Condition ........................................................... 13
Battery Backup Time................................................................................................. 15
Load Shed Function.................................................................................................. 15
Battery Recharge Time............................................................................................. 15
Battery Check Function............................................................................................. 15
The Function Control Button ..................................................................................... 16
Fixed Frequency Mode ............................................................................................. 16
Adding Additional Battery Modules ........................................................................... 19
Other Option Modules............................................................................................... 19
Communication Interface .....................................................................20
Remote Contacts...................................................................................................... 20
RS-232C................................................................................................................... 20
Option Card Slot ....................................................................................................... 22
Troubleshooting ....................................................................................22
Warning/Fault Modes................................................................................................ 22
Warnings .......................................................................................................... 23
Faults................................................................................................................ 25
Storage of UPS Equipment...................................................................29
Disposal.................................................................................................................... 29
Preventative Maintenance/Parts Replacement...................................30
Preventative Maintenance......................................................................................... 30
Parts Replacement ................................................................................................... 30
Appendices ............................................................................................31
A: Specifications...................................................................................................... 31
B: Fan Speed Control.............................................................................................. 32
C: System Overload Rating ..................................................................................... 33
D: Parallel Operation............................................................................................... 34
E: Bypass Undervoltage / Overvoltage.................................................................... 35
F: Unit Configuration Options .................................................................................. 36
G: Weights and Dimensions .................................................................................... 37
Warranty Policy .....................................................................................38
PAGE
4
TOSHIBA
GENERAL SAFETY INSTRUCTIONS
Warnings in this manual appear in two different ways:
1) Danger warnings - The danger warning symbol is an exclamation mark
enclosed in a triangle that precedes the large bold letters spelling the word "DANGER". The Danger warning symbol is used to indicate situations, locations, and conditions that exist and can cause serious injury or death:
DANGER
2) Caution warnings - The caution warning symbol is an exclamation mark
enclosed in a triangle that precedes the large bold letters spelling the word "CAUTION". The Caution warning symbol is used to indicate situations and conditions that can cause operator injury and/or equipment damage:
CAUTION
Other warning symbols may appear along with the Danger and Caution symbol and are used to specify special hazards. These warnings describe particular areas where special care and/or procedures are required in order to prevent serious injury and possible death:
1) Electrical warnings - The electrical warning symbol is a lightning bolt mark enclosed in a triangle. The electrical warning symbol is used to indicate high voltage locations and conditions that may cause serious injury or death if the proper precautions are not observed.
2) Explosion warnings - The explosion warning symbol is an explosion mark enclosed in a triangle. The explosion warning symbol is used to indicate locations and conditions where molten, exploding parts may cause serious injury or death if the proper precautions are not observed.
5
TOSHIBA
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS. This manual
contains important instructions for the 1700 Series Toshiba Rackmount UPS. These instructions should be followed during the installation and maintenance of the UPS and its batteries.
The maximum ambient temperature in which this UPS unit should
be operated or stored is 104 °F (40 °C).
The batteries for the Toshiba 1700 Series Rackmount UPS are
housed in a self-contained battery module. This module should not be opened under any circumstances. To replace the batteries, a new module should be obtained from your local Toshiba representative, or contact the Toshiba UPS marketing department toll-free at (800) 231-1412.
When changing battery packs, be sure to use the proper model unit.
CAUTION
DANGER
CAUTION
CAUTION
CAUTION
Misuse of this equipment could result in human injury and equipment damage. In no event will Toshiba Corporation be responsible or liable for either indirect or consequential damage or injury that may result from the use of this equipment.
Do not dispose of the battery module in a fire. The batteries inside may explode.
Do not open or mutilate the battery module. Released electrolyte is harmful to the eyes and skin, and could be toxic.
This unit contains sealed lead acid batteries. Lack of preventative maintenance could result in batteries exploding and emitting gasses and/or flame.
Failure to replace the battery pack in accordance to the maintenance schedule may cause the batteries inside to crack, possibly releasing electrolytes from the battery, and resulting in secondary faults such as odor, smoke and fire.
6
TOSHIBA
INSTRUCTIONS IMPORTANTES
CONCERNANT LA SÉCURITÉ
CONSERVER CES INSTRUCTIONS. Cette notice
contient des instructions importantes concernant la sécurit.
ATTENTION
ATTENTION
ATTENTION
Une batterie peut présenter un risque de choc électrique, de brûlure par transfert d’énergie.
Pour le remplacement, utiliser le même nombre de batteries du modèle suivant.
L’élimination des batteries est réglementée. Consulter les codes locaux à cet effet.
7
TOSHIBA
Inspection/Installation
Inspection of the New UPS Equipment
Upon receipt of the UPS, a careful inspection for shipping damage should be made.
After Unpacking:
1) Check the unit for loose, broken, bent or otherwise damaged parts. If damage has occurred during shipment, keep all original packing materials for return to shipping agent. Warranty will not apply to units damaged during shipment.
2) Check to see that the rated capacity and the model number specified on the nameplate conform to the order specifications.
Installation Precautions
1) Install the unit in a well ventilated location; allow at least 10 cm (4 inches) on all sides for air ventilation and for maintenance.
2) Install the unit in a stable, level, and upright position that is free of vibration.
3) Install the unit where the ambient temperature is between 32° and 104°F (0° and 40°C).
4) Do not install the UPS in areas that are subject to high humidity.
5) Do not install the UPS in a location that will cause direct sunlight to shine on the unit.
6) Do not install the UPS in areas that are subject to contamination such as high levels of airborne dust, metal particles, or flammable gas.
7) Avoid installation near sources of electrical noise. Always make sure that the unit earth ground is intact to prevent electrical shock and to help reduce electrical noise.
8) Do not install where water or any foreign object may get inside the UPS.
9) This UPS generates and can radiate radio-frequency energy during operation. Although RFI noise filters are installed inside the unit there is no guarantee that the UPS will not influence some sensitive devices which are operating close by. If such interference is experienced, the UPS should be installed farther away from the affected equipment and/or powered from a different source than that of the affected equipment.
Operating Precautions
1) The UPS should not be powered up until this entire manual has been reviewed.
CAUTION
CAUTION
8
TOSHIBA
2) The input power source voltage and frequency must be within the allowable range as specified in appendix A. Voltages and frequencies outside of the permissible tolerance range may cause internal protection devices to activate.
3) The UPS should not be used with a load whose rated input is greater than the rated UPS output.
4) Do not use the UPS to provide power to motors that require high starting current or that require a long starting time such as vacuum cleaners and machine tools (unless appropriate sizing is done by a Toshiba applications engineer, or other qualified personnel).
5) Do not insert metal objects or combustible materials in the unit's ventilation slots.
6) Do not place, hang, or paste any objects on the top or on the exterior surfaces of the UPS.
External Layout
Electronics Module
Figure 1
Electronics Module Layout
9
TOSHIBA
Power Connections
Battery Module
Figure 2
Battery Module Layout
UPS Connections
Standard Module Connections
The following illustration shows the proper assembly of the two modules that make up the standard unit. If additional battery modules are being installed with the standard unit see page 19.
Figure 3
10
Operating the UPS
Display Panel Layout
TOSHIBA
Function Control Button
Startup on Battery Button
ON LINE (green lamp)
Lights green when the UPS’s inverter is supplying power to the load.
AC INPUT (green lamp)
Lights green when normal AC input power is being supplied to the UPS unit.
WARNING/FAULT (red lamp)
Lights red when the UPS unit is experiencing an abnormal condition.
BATTERY (red lamp)
Lights red to indicate that a condition exists that is affecting the batteries.
Starting the UPS System
Once the modules have been connected as shown in the preceding section (UPS Connections, page 10) the UPS system is ready to be started. There are two ways to start the system: from AC input power (if present) or from batteries. If not already done, switch the input breaker on (figure 1, page 9). If the “AC Input” LED is lit, proceed on to “Starting when AC power is available”. If the LED is not lit, there is no AC power available. If the unit is to be started when AC power is not available proceed to “Starting on DC power.”
Starting When AC Power is Available
If the system is being started with AC input power the system is started by switching the RUN/STOP switch to the RUN position (RUN = I, STOP = 0). When the RUN/STOP switch is in the RUN position both the “AC Input” and the “On Line” LEDs should be lit. When the unit is started with AC input power it is advisable to allow time for the batteries to fully charge before any load is connected (see “Battery Recharge Time”, page 15).
11
TOSHIBA
Starting on DC Power
If no AC power source is available, or if the AC input power is outside of the allowable range for voltage or frequency, the UPS can be started from battery power. The length of UPS operation time on battery power depends on the number of attached battery modules and the amount of load the UPS is supporting. To start the UPS from battery power follow these steps:
Step 1: Make sure the RUN/STOP switch is in the STOP position. If the UPS is being started on DC power because the AC power is out of range, the input breaker must be in the OFF position (figure 1, page 9).
Step 2: Press the “Startup on Battery” button. The UPS will beep indicating that AC power is not available and the Startup on Battery mode has been activated.
Step 3: Switch the RUN/STOP switch to the RUN position. This must be done within 5 seconds of the Startup on Battery mode activation for the unit to startup using batteries.
Once the unit has started, the “On Line” LED will light, indicating that the inverter is running and power is available at the output receptacles. If the RUN/STOP switch is not switched to the RUN position within those 5 seconds, the unit will return to shutdown mode.
Stopping the UPS
There are two ways of turning the UPS off: switching from on line to bypass mode, or completely shutting down. Option 1: The first option is to place the UPS into bypass mode. Bypass mode means that if there is AC power available, the UPS will route power directly from the input source to the connected loads without any conditioning. The UPS inverter is off during this state, but the attached loads do not lose power during the transition. To place the UPS into bypass mode, switch the RUN/STOP switch to the STOP position. This mode is most often used manually during maintenance and programming operations or automatically upon the occurrence of an internal UPS fault. (For more information concerning bypass mode see appendix E.) Option 2: The other option is to turn the UPS off completely. This means that in addition to the UPS’s inverter shutting down, all power will be stopped to any equipment attached to the UPS. To shut the UPS down completely switch the RUN/STOP switch to the STOP position. Then switch the input breaker off (figure 1, page 9). Once the input breaker has been switched off, all the LEDs should turn off. (If the RUN/STOP switch is in the RUN position when the input breaker is switched off, the unit will switch to battery backup mode. The unit will continue to run for as long as the available battery reserves can support the connected loads.)
12
UPS Display Status and Operating Condition
Operation Mode
Display State
LED State
Alarm State
Notes
Normal
On Line .............On
AC Input............On
Alarm is off.
20% to 100%* ...On
*see note 1.
Battery
13
Backup
On Line .............On
Battery ..............On
Backup..............On
20% to 100%* ...On
*see note 2.
Alarm will sound for 1 second at 10 second
The unit will return to normal operation mode when AC power is restored.
TOSHIBA
intervals.
Bypass
AC Input............On
20% to 100%* ...On
*see note 1.
Alarm is off.
Battery backup is not available.
UPS Display Status and Operating Condition
Operation Mode
Parallel Operation
Display State
LED State
On Line .............On
AC Input............On
Battery ..............On
20% to 100%* ...On
*see note 1.
Alarm State
Alarm will sound for 1 second at 10 second intervals.
Notes
Parallel operation occurs when input power is present, but inadequate to fully power the connected load. The batteries are used to supplement the AC input power. The UPS will return to normal operation when full input power returns.
All other display conditions constitute either a warning or a fault condition. These conditions are explained in the section titled “Troubleshooting”
14
(page 22) in the charts on Warnings and Faults.
Note 1: The level meter, which consists of the LEDs labeled 20% through 150%, will light according to the current amount of load connected. As the load exceeds one level, the next level will begin to blink, increasing the blink rate as the load increases until that full percentage is reached. For example, if the unit is loaded to 40% of maximum output power the 20% and 40% LEDs will be lit. If another small load is added increasing the load to 45% the 60% LED will begin to blink. If a little bit more load is added so that the total load becomes 50% the 60% LED will blink faster. This will continue until enough load is added to equal 60% of the maximum output power at which time the 60% LED will stop blinking and light continuously.
Note 2: The level meter described in note 1 above also displays the remaining battery time when the unit is in backup mode. If the batteries are fully charged when the unit switches to backup mode the 20% through 100% LEDs will light. As the batteries begin to discharge, the LEDs starting from the top will blink rapidly then slowly and will then turn off as the battery time runs down. For example if the unit has been running on battery power and there is 90% battery capacity remaining the 20% through 80% LEDs will be lit and the 100% LED will be blinking.
TOSHIBA
TOSHIBA
Battery Backup Time
The exact amount of backup time provided will vary depending on the UPS model being used, number of batteries, condition of the batteries and other factors. However, the chart below gives the times that can be expected from the standard units with batteries in good condition. For greater backup time, an additional battery module may be added to the standard unit. Only one additional battery module may be added to the standard unit. For longer runtime options contact your Toshiba sales representative or the Toshiba marketing department at (800) 231-1412 or by e-mail at toshibaups@tic.toshiba.com.
Table 1
Backup Time*
UPS Model
With 1 Battery Module
Full Load / Half Load
With 2 Battery Modules
Full Load / Half Load
2000 VA 13 min / 32min 32 min / 77 min
2400 VA 9 min / 26 min 30 min / 64min
* Times given are approximate and will vary depending on the age of the batteries, the battery temperature, the number of previous discharges and the type of load.
Load Shed Function
The 1700 Series includes a load shed function. During battery backup operation, this function allows the load connected to two of the receptacles (figure 1, page 9) to be turned off in an effort to conserve power for more critical loads. The battery level at which these two receptacles will be turned off, or “shed”, can be set by the user (see “The Function Control Button”, page 16). By default, this feature is configured so that these two receptacles will remain on for the full battery backup time available (no “shedding”)
Battery Recharge Time
The following table gives estimates on time required to recharge the UPS’s batteries. The recharge time may vary depending on the battery temperature, the age of the batteries, and other factors.
Table 2
Battery Recharge Time*
Unit With 1 Battery Module With 2 Battery Modules
2000 VA 4 ½ hours 9 hours
2400 VA 4 ½ hours 9 hours
* Recharge times are to 90% full capacity.
Fan Speed
The 1700 Series Rackmount UPS has variable speed fans. The fan speed will vary depending on a number of factors. As the load
15
TOSHIBA
placed on the UPS increases the fan speed will increase. The temperature of the environment the UPS is operating in can also cause the fan speed to increase. (For a more detailed explanation of the variable speed fan function refer to appendix B)
Battery Check Function
During startup the UPS will perform an automatic 'Battery Check' to detect whether a problem exists in the battery circuit. If the batteries pass the test, the unit will start normal operation. If a problem is detected during the test the “Warning/Fault” LED will activate. Other LED’s may also activate. If this occurs please refer to the “Troubleshooting” section on page 20 for a description of the problem and possible solutions. It is important to note that when
the UPS has detected bad batteries, the battery backup mode is disabled. The unit will continue to operate and provide clean power;
however, since there is no battery power available, the unit cannot provide backup power if input power is lost.
The Function Control Button
The function control button is located on the display panel (see “Display Panel Layout”, page 11). This button is used to perform several different UPS operations, including initiating self test, providing programming options, and silencing the alarm. A brief description of each function follows along with a step by step guide to accessing each function.
1) Self-Test. In order to perform a self-test the UPS must be operating in the normal mode (see “UPS Display Status and Operating Condition”, page 13). To initiate the self-test simply press and hold the Function Control button until the audible alarm sounds. The self-test performs the same battery check described above.
2) Alarm Silence. The alarm silence feature is used to stop the audible alarm from sounding. Any time the audible alarm is sounding pressing the Function Control button will silence the alarm.
3) Programming Mode. There are three programming options: load shed, output enable/disable after input overvoltage backup, and reset battery installed date. In order to enter the programming mode the UPS must first be operating in Bypass mode without faults (see “Stopping the UPS: Option 1”, page
12). Then press and hold the Function Control button. (“Press and hold” always means to hold until the unit gives audible feedback). The unit will give an audible feedback indicating the unit is in programming mode. (If at anytime while the UPS is in the programming mode there is one minute of inactivity the UPS
16
TOSHIBA
will automatically exit the programming mode and return to bypass operation.) What follows is a step by step guide to navigating in the programming mode, followed by a detailed description of each option.
A. Load Shed. The backup LED will light indicating the UPS is now
ready to make changes to the load-shed settings (see “The Load Shed Function”, page 15 for an explanation of load shedding). To accept this option press and hold the Function control button. A.1 The UPS comes from the factory set so the load shed
receptacles function for the full battery backup time. The LEDs on the right side of the display will light to indicate the current setting for the load-shed level. For example, since the default factory setting is for no load shed, the first time the option is accessed no LEDs will be lit. Pressing the button once will cause the 20% LED to light. This would indicate that the load shed receptacles should be turned off when there is 20% battery power remaining. Pressing the Function Control button successive times will increase the load shed level in 20% increments.
17
TOSHIBA
A.2 Once the option is set to the desired level, press and hold
the Function Control button. This will save the new load shed level setting. The UPS will indicate that the value has been stored by blinking the LEDs. After blinking the LED for a short time the UPS will exit the programming mode and return to bypass operation. To return the system to normal operation switch the RUN/STOP switch back to the RUN position.
B. Output Enable/Disable After Input Overvoltage Backup. Press
the function control button. The unit is now ready to change the output enable/disable after input overvoltage backup option. This is indicated by the 150% LED turning on. This setting determines whether the UPS will go to bypass in the case of an input overvoltage fault. To change this setting press and hold the function control button. B.1 This setting is set to disable output at the factory. Pressing
the function control button causes the 100% LED to light, indicating output has been enabled. Pressing it again will change it back to disabled and the 100% LED will go off.
B.2 Once the option is set as desired, press and hold the
function control button to save the setting. The UPS will indicate the setting has been saved by blinking the LED(s). The LED(s) will continue to blink for a short time after which the UPS will exit programming mode and return to bypass operation. To return the system to normal operation switch the RUN/STOP switch back to the RUN position.
C. Reset Battery Installed Date. This should be done whenever a
new battery pack is installed. Press the function control button. The unit is now ready to reset the battery installed date. This is indicated by the Battery LED turning on. Once this mode has been entered press and hold the function control button to reset the battery install date to the current date. The UPS will indicate that the date has been reset by blinking the Battery LED for a short time after which the UPS will return to bypass operation. To return the system to normal operation switch the RUN/STOP switch back to the RUN position.
18
TOSHIBA
Fixed Frequency Mode
The 1700 Series Rackmount UPS has the option of operating in a fixed frequency mode. Normally the UPS operates in the frequency auto-detect mode. If a specific output frequency is required (i.e. 50Hz or 60Hz) the UPS can be set at the factory to supply the desired frequency regardless of the input frequency (input frequency must be within allowable limits, see Specifications on page 29). For a unit already in use the output frequency can be set through software. For instructions on setting the output frequency through software please contact Toshiba at (800) 231-1412 or by e-mail at toshibaups@tic.toshiba.com. It is important to note that when the
UPS is operating with a fixed output frequency, output is disabled in bypass.
Adding an Additional Battery Module
Note: Only one additional battery module may be added to the standard unit. Figure 4 shows the standard unit with one additional battery module added. To install an additional battery module follow these steps:
1) Make room in the rack for the additional battery module to be placed below the other modules. Secure the new battery module in the rack.
2) Plug the new battery module output power cord into the battery input plug on the battery module.
.
Figure 4
Expansion Battery Module
19
TOSHIBA
2 3 4 5 6 7 8 9
Communication Interface
Dry Contacts
The remote contacts interface is a standard feature. It is provided through solid state relays with contacts through a DB9 male connector located on the back of the UPS (refer to the Communication Option User Manual for a more detailed description of this option). The following chart shows the signals and the connector pinout.
Pin Signal Function Logic In the UPS
1 Fault Signal
UPS stop
2
common UPS stop signal
3
input Normal input
4
power supply
Closed when fault detected
Backup stop when the level changes from Low (­3 to – 15V) to High (+3 – +15V)
Closed with normal supply power
5 Signal common Common signal return
6 Bypass operation
Battery voltage
7
low
8 UPS operation
Power failure
9
signal
Closed during bypass operation
Closed at voltage drop
Closed during inverter operation
Closed at power failure
Voltage Current
48Vdc peak 100mAdc peak
DB9 Male Connector Outline
(facing connector)
30Vac rms
(42Vac peak)
70mAac rms
(100mAac peak)
RS-232C
RS-232C serial communication interface is a standard feature provided through a DB9 female connector located on the backside of the UPS (see “Electronics Module Layout “, page 9). This interface allows communication between the UPS and a personal computer. The chart on the following page shows the signals and the connector pinout.
20
1
TOSHIBA
Pin Signal Name Description In the UPS
1 -
2 RXD Receive data
3 TXD Transmit data
4 DTR Data terminal ready
5 GND Signal ground
6 DSR Data set ready
7 RTS Request to send
8 CTS Clear to send
9 -
(*) (**) These pins are tied together internal to the UPS. Signals DTR, DSR, RTS, and CTS are not used.
DB9 Female Connector Outline
(facing connector)
Special notes concerning RS-232C communication
• For Toshiba UPS protocol and command structure refer to the
Communication Option User Manual
• The optional RemotEye™ SNMP interface is the recommended
method for communication with the UPS system.
• If an optional RemotEye™ SNMP interface card is installed in the
UPS only one method (SNMP or RS-232C) will function at a time.
• For a description of the cable required to connect to a Toshiba
UPS system refer to the Communication Option User Manual or contact Toshiba’s UPS Marketing Department at (800) 231-1412 or by e-mail at toshibaups@tic.toshiba.com.
21
TOSHIBA
Option Card Slot
The option card slot is a standard feature. An optional network adapter card slides into the slot which is located on the back of the electronics module (figure 1, page 9). This optional interface allows the UPS to be monitored across the network or from any point on the Internet (refer to the Communication Option User Manual for a more detailed explanation of this option).
Troubleshooting
Warnings and Faults are those abnormal conditions that can occur and could cause the unit to stop normal operation. These conditions are detected by the protective circuitry in the unit. The UPS “Warning/Fault” lamp will light red when a warning or fault occurs. "Troubleshooting" involves monitoring the LED’s on the front panel and then interpreting the readout by using the warning and fault mode display charts that follow. Only the state of the LED’s listed in the chart should be considered. Other LED’s might be active; nevertheless, only those listed under the column “LED state” should be considered when diagnosing a warning, or fault.
Warning/Fault Modes All warnings will cause the red “Warning/Fault” LED to flash. All faults will cause the red “Warning/Fault” LED to light continuously. Some warnings and most faults will cause the UPS to transfer to bypass mode. In many cases, after the condition that caused the fault is corrected the unit will automatically transfer back to normal mode. For those cases where the unit does not transfer back automatically contact your Toshiba UPS service representative at 1­877-867-8773 (outside the U.S. call 713-466-0277).
22
temperature is reduced.
Warnings
23
Warning
Low Battery
Current Limit (Over Current)
Ambient Over Heat
Display State
LED State
Warning/Fault ...Flash
Backup..............Flash
Warning/Fault ...Flash
80%...................Flash
Warning/Fault ...Flash
100%.................Flash
Alarm State
Alarm will sound for 1-second at 5­second intervals.
Alarm will sound for 1/2- second at 1-second intervals.
Alarm will sound for 1-second at 15­second intervals.
Description and Resolution
The batteries have less than 30% power remaining. The warning will continue until either the batteries become completely exhausted or AC input power is restored.
An output current limit warning is typically a sign of misapplication. The load may not be appropriate for UPS support. For further explanation contact your Toshiba UPS service representative at 1-877­867-8773 (outside the U.S.
call 713-466-0277).
The temperature of the UPS operating environment is too high. Causes of this condition include allowing the room temperature to exceed 104°F (40°C), a blocked vent or direct sunlight on the unit. The unit will transfer to bypass until the
TOSHIBA
Warning (cont’d)
24
Warning
Battery Over Heat
Input Under Voltage (see note 1)
Input Over Voltage
(see note 1)
Display State
LED State
Warning/Fault ...Flash
Battery ..............Flash
Warning/Fault ...Flash
20%...................Flash
Warning/Fault ...Flash
40%...................Flash
Alarm State
Alarm will sound for 1-second at 15­second intervals.
Alarm will sound for 1/2­second at 10­second intervals.
Alarm will sound for 2, 1/2­second beeps at 10­second intervals.
Description and Resolution
This warning can be caused by the same conditions listed for ambient overheat. Another possible cause would be a problem with the battery module, which could prevent the unit from providing backup power.
This warning will occur if the input voltage drops below the minimum allowable voltage. If the unit was online when the warning occurred it will transfer to battery backup. After the backup the output will shutdown. If the unit was in bypass the output will be turned off. The unit will reinitialize the startup sequence if input power returns to within specified limits.
This warning will occur if the input voltage exceeds the maximum allowable voltage. If the unit was online when the warning occurred it will transfer to battery backup (see note 2). If the unit was in bypass the output will be turned off. The unit will return to normal operation if input power returns to within specified limits.
TOSHIBA
Warnings (cont’d)
Warning
Input Frequency Regulation
(see note 1)
Display State
LED State
Warning/Fault ...Flash
60%...................Flash
Alarm State
Alarm will sound for 3, 1/2­second beeps at 10-second intervals.
25
Output Overload
Warning/Fault ...Flash
150%.................Flash
Alarm will sound for 1-second at 15­second intervals.
= Flashing LED = LED lit continuously
Note 1: If any of these faults occur while the UPS is in online mode it will immediately transfer to backup mode. In this case the percentage LED’s will be used to show the battery power status. To identify the fault that has occurred listen to the number of consecutive beeps. One beep indicates an input undervoltage, two beeps means input overvoltage, three beeps is a frequency problem. Note 2: Once the batteries are exhausted the unit will either shutdown the output, or switch to bypass according the selections set by the user (see the section entitled “Programming Mode” part B on page 18).
Description and Resolution
The input frequency is outside specified limits. If the unit was online when the warning occurred it will transfer to battery backup. After the backup the output will shutdown. If the unit was in bypass the output will be turned off. The unit will return to normal operation if input frequency returns to within specified limits.
The connected load exceeds the UPS power rating. Reduce the load attached to the UPS. The unit will automatically return to normal operation.
TOSHIBA
Faults
26
Fault
Replace Battery
Battery Shutdown
DC Bus Over Current
Display State
LED
Warning/Fault ...On
Battery ..............On
Warning/Fault ...On
Backup..............On
Warning/Fault ...On
20%...................On
Alarm State
Alarm will sound for 1/2­second, at 1/2­second intervals.
Continuous alarm
Alarm will sound for 1/2­second, at 1/2­second intervals.
Description and Resolution
Battery pack is not connected or needs replacement as soon as possible. After replacing the batteries the battery timer must be reset (see “The Function Control Button”, page 17). Failure to replace the battery pack could result in danger to the user and failure of the system to provide backup power.
The battery power of the unit has been exhausted. The unit output will shutdown. Batteries must charge before backup power will be available. For charging times see page 16.
This fault indicates an internal problem with the UPS. Contact your Toshiba UPS service representative at 1­877-867-8773 (outside the
U.S. call 713-466-0277).
TOSHIBA
Faults
27
Fault
DC Bus Over Voltage
DC Bus Voltage Imbalance
Output Under Voltage
Display State
LED State
Warning/Fault ...On
40%...................On
Warning/Fault ...On
60%...................On
Warning/Fault ...On
80%...................On
Alarm State
Alarm will sound for 1/2­second, at 1/2­second intervals.
Description and Resolution
TOSHIBA
These faults indicate an internal problem with the UPS. Contact your Toshiba UPS service representative at 1-
877-867-8773 (outside the
U.S. call 713-466-0277).
Faults
28
Fault
Display State
Output Over Voltage
System Over Heat
= Flashing LED = LED lit continuously
LED State
Warning/Fault ...On
100%.................On
Warning/Fault ...On
150%.................On
Alarm State
Alarm will sound for 1/2­second, at 1/2­second intervals.
Description and Resolution
These faults indicate an internal problem with the UPS. Contact your Toshiba UPS service representative at 1-
877-867-8773 (outside the
U.S. call 713-466-0277).
TOSHIBA
TOSHIBA
Storage of UPS Equipment.
General Guidelines
If the UPS equipment is to be stored; the following guidelines should be used.
Avoid:
1) Storage in sites subject to extreme changes in temperature or high
humidity.
2) Storage in sites subject to exposure of high levels of dust or metal
particles
3) Storage on inclined floor surfaces or in sites subject to excessive
vibration.
Before Storing:
1) Allow UPS to be operated for 4 hrs to ensure that the batteries are fully
charged.
2) Stop the unit (see "Stopping the UPS" on page 12).
3) Place the unit's Input Breaker switch in the "off" position (see “Electronics
Module Layout”, page 9).
Storing:
1) Store within a temperature range of -20° to 40° C (-4° to 104° F). If the
UPS is stored at a temperature outside of the allowable operating range, allow time for the unit to reach equilibrium with the ambient temperature before starting the UPS.
2) For best results, store the UPS in the original shipping container and
place on a wood or metal pallet.
3) The optimum storage temperature is 21° C (70° F). Higher ambient
temperatures cause UPS batteries to need recharging more frequently.
Recharging requirements during storage:
Recharging the batteries requires that the battery module be connected to the UPS and the UPS must have AC input power available. The UPS can be in either the on line or bypass mode. (See “Starting the UPS”, page 11, and “Battery Recharge Time”, page 15).
1) If stored in an ambient temperature less than 20°C (68°F), recharge the
batteries every 9 months.
2) If stored in an ambient temperature of 20° to 30°C (68° to 86°F),
recharge the batteries every 6 months.
3) If stored in an ambient temperature of 30° to 40° C (86° to 104°F),
recharge the batteries every 3 months.
Disposal
Please contact your local environmental agency for details on disposal of electrical components and packaging in your particular area. It is illegal to dump lead-acid batteries in landfills or dispose of improperly. Please help our Earth by contacting the environmental protection agencies in your area, the battery manufacturer, or call Toshiba toll-free at (800) 231-1412 for more information about recycling.
29
TOSHIBA
Preventive and Scheduled Maintenance/Parts Replacement
Preventive Maintenance
Toshiba's 1700 Series of rackmount UPS systems have been designed to provide years of trouble-free operation requiring a minimum of preventive maintenance.
The best preventive measure is to keep the area around the unit, particularly the air inlet vents, clean and free of moisture and dust accumulations. If the atmosphere of the installation site is very dusty, use a vacuum cleaner to periodically remove dust accumulations from the exterior of the unit, especially around ventilation openings. Schedule authorized Toshiba service centers to perform internal parts inspections annually, or call a Toshiba UPS service representative at 1-877-867-8773 (outside the U.S. call 713­466-0277).
CAUTION
Parts Replacement
The following list shows intervals for periodic maintenance and replacement of certain UPS parts.
1) Battery Module: Replacement should be done once every 3 to 5 years at a minimum.
2) Output Fuses: Replace once every 7 years (always replace fuses with same fuse type and rating).
3) Cooling fan: Replace once every 3 years. (Fan replacement must be done by Toshiba authorized service personnel.)
Proper maintenance of the battery system of this unit is essential to the safety and reliability of the UPS system.
30
TOSHIBA
Appendix A: Specifications
Model Number UF1A1A020C6RK UF1A1A024C6RK
Capacity 2000VA (1.40KW) 2400VA (1.68KW)
Input voltage1 Single phase 120VAC, +20% to -50%
Input
Bypass
Output
Battery
Environment
Note1: Below 77% input voltage unit may begin parallel operation; supplementing input
Note2: Input voltage range is limited in bypass for load protection. (For a detailed
Input frequency 30 to 70 Hz
Input capacity 2000VA 2400VA
Input power factor Approximately unity (0.95 to 1.0)
Input voltage2 Single phase 120VAC, ±10%
Output voltage Single phase 120VAC
Overload rating See appendix C
Output voltage Single phase 120VAC
Output voltage regulation Within +/- 3%, steady state
Output frequency
50/60 Hz (+/- 0.5% in free running mode, line sync
range +/-1Hz)
Rated load power factor 0.7
Rated output current (rms) 16.7A 20A
Inverter overload capacity 125% for one minute; 150% for 30 seconds
Crest factor 2.5 at full load
Type
Battery backup time (fully
charged, 0.7 power factor, 25°C (77°F)
13 minutes (at full load)
12V, flame retardant,
valve regulated lead acid
9 minutes (at full load)
Configuration 2 strings in parallel, 4 batteries per string
Operating temperature 0° to 40°C (32° to 104°F)
Altitude Up to 1000m (3000 ft) above sea level
Efficiency 86%
Operating Humidity 30 to 90%, non-condensing
power with battery power. The point at which parallel operation begins is load dependant (for a detailed explanation of Parallel Operation see appendix D).
explanation of Bypass Undervoltage / Overvoltage see appendix E.)
31
TOSHIBA
Appendix B: Fan Speed Control
The fans in the 1700 Series will operate at any of four different speeds depending on the environment and system conditions. In the first stage the fans are off. As the load and or the temperature increase the fans will subsequently go to low, medium or high speed as required.
The temperature reference given on the graph above refers to the temperature inside the UPS. There will typically be a 5°C difference between the internal and external temperature. The 10% hysteresis shown is to ensure that the unit will not oscillate between fan speeds. When the output power reaches a level that requires the fan speed to increase the load will have to be reduced 10% below that level before the fan speed will return to the lower speed.
32
TOSHIBA
Appendix C: System Overload Rating
The 1700 Series Rackmount UPS is capable of supporting short duration overloads. When operating in the On Line mode output overloading of 125% of the rated output current can be supported for 1 minute, and 150% for 30 seconds. If the overload continues the unit will switch to bypass mode. When in bypass mode the 1700 Series overload capacity is limited by the input breaker. The following graph shows the response of the breaker depending on the applied load. The two lines shown on the graph represent the upper and lower limits of the breaker response. The response of a particular breaker could fall anywhere between these two lines.
If the load capacity of the breaker is exceeded the breaker will trip, shutting down both the UPS and the attached loads. If the breaker’s capacity is not exceeded the unit will continue to operate in the bypass mode until the applied load is reduced. When the load on the UPS is reduced to within the specified limits the UPS will automatically return to On Line mode.
33
TOSHIBA
Appendix D: Parallel Operation
The 1700 Series Rackmount UPS offers a standard feature that allows the unit to operate with very low input voltage without de-rating the output power. If the input voltage drops below a certain point the unit will switch to parallel mode. Parallel mode means that the unit is using the available input voltage and supplementing with battery power. Because battery power is being used, the time the unit can operate in parallel mode is limited. However, the time will be longer than that available when the unit is operating on battery power alone. The point when the UPS will enter parallel mode will vary depending on the output load. The following graph shows the various stages based on full output load and 75% output load.
As shown by the graph the lower the output load the lower the input voltage can go before parallel mode is activated. However, the minimum input voltage will always remain at 50% (60VAC for a 120VAC system).
34
TOSHIBA
Appendix E: Bypass Undervoltage / Overvoltage
When the 1700 Series Rackmount UPS is in bypass mode the undervoltage and overvoltage limits are restricted to +/-10% of the rated input voltage. If the input voltage is outside of this voltage window the UPS output will be turned off. There is a 5% hysteresis associated with both the upper and lower limits. This means that once output has been turned off the input voltage will have to be within ±5% of the rated input voltage before the startup sequence will reinitialize. (To start the UPS when the input power is outside of the allowable range see the section entitled “Starting on DC Power”, page 12.)
When the UPS is started, if the RUN/STOP switch is in the STOP (bypass) position the unit will start in the on-line mode for 1 second before switching to bypass mode. If the input voltage is out of range the UPS will turn off the output after 1 second rather than switching to bypass.
35
TOSHIBA
Appendix G: Weights and Dimensions
Module Module Weight Shipping Weight
Model No. Pounds Kilograms Pounds Kilograms
UF1A1A020C6RK
UF1A1A024C6RK
37 17 42 19
37 17 42 19
UF1-BR-087 75 34 80 36
36
TOSHIBA
TOSHIBA INTERNATIONAL CORPORATION LIMITED WARRANTY POLICY
TOSHIBA INTERNATIONAL CORPORATION (“TIC”) warrants that the 1700 Series Uninterruptible Power Supplies (“UPS”) and Uninterruptible Power Supply Battery (“BATTERY”) (external battery cabinet) sold by TIC to the end user (“User”) shall be free of defects in material and workmanship.
Series Capacity
1700 2.0, 2.4 kVA 36 months No, Depot 24 months No, Depot M-F, 8AM-5PM CT
Note 1: The warranty period begins from the shipment date. The shipment date is determined by the
Note 2: For the 1700 Series the warranty applies if the unit is sent and returned (paid for) by the user
date on the TIC Bill of Lading.
to/from the Toshiba plant or a Toshiba designated Authorized Service Center.
If any UPS, part of UPS, and/or BATTERY fails to conform or is defective then TIC will repair or replace it at TIC’s option.
(48 contiguous U.S. States, Canada, Mexico)
(UNINTERRUPTIBLE POWER SUPPLIES-UPS)
UPS Unit Battery
Warrant On-Site2 Warranty
1
On-Site2
Toshiba Dispatch
LIMITATIONS AND EXCLUSIONS
This limited warranty shall not cover the UPS, UPS part, or BATTERY during their respective warranty periods, if the following storage, maintenance, installation, operating conditions are not met throughout the warranty periods (5 conditions below):
VALVE REGUALATED LEAD ACID (VRLA) BATTERIES FOR TOSHIBA UPS
REQUIRED OPERATING CONDITIONS
1. Temperature
Annual Average Temperature 25°C (77°F)
Temperature per cell < 32°C (89°F) for more than 30 days
Maximum Number of Cycles
2. Maximum number of full charge/discharge cycles
Discharge time
30 minutes 69 15 minutes 86
(24 months)
10 minutes 110
5 minutes 130
VALVE REGUALATED LEAD ACID (VRLA) BATTERIES FOT TOSHIBA UPS
INSTALLATION AND MAINTENANCE CONDITIONS
3. Storage While UPS is in transit or storage it must always be in
suitable temperature (see condition 1).
4. External Batteries Parallel battery string applications must be approved by TIC
in writing.
5. Idle Batteries User must recharge the batteries if not in use (charged) for
more than 6 months.
1. This Warranty does not cover damage or defect caused by misuse, improper application, wrong or inadequate electrical current/voltage/frequency, inadequate connections, inadequate water or drain services, user negligence, repair by non­Toshiba designated personnel, accident during shipment, tampering, alterations, a change in UPS and/or BATTERY location or application, exposure to the elements, acts of God, theft, sabotage, installation contrary to TIC's recommendations or specifications (Published Operation Manuals), also if serial numbers have been altered, defaced, or removed.
2. Repair or replacement of a defective UPS, UPS part, and/or BATTERY does not extend the respective original warranty period. All defective UPS, UPS parts, and/or BATTERIES shall be the property of TIC upon replacement.
3. This warranty shall constitute the sole and exclusive remedy of all purchasers and users of the UPS, UPS part, and/or BATTERY. TIC’s responsibility for UPS, UPS Parts, and/or BATTERY shall not exceed one times the net UPS and/or BATTERY purchase price. TIC HEREBY EXPRESSLY DISCLAIMS ALL OTHER EXPRESS,
STATUTORY AND IMPLIED WARRANTIES, INCLUDING WITHOUT LIMITATION, THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE.
37
TOSHIBA
User must contact TIC via e-mail upsservice@tic.toshiba.com (outside the U.S. call 713-466-0277), no later than 90 days after User’s discovery of occurrence or defect in UPS, UPS part, and/or BATTERY but in no event after the expiration of the respective warranty period. Subject to the limitations of this policy and product type, TIC service or TIC service representative shall repair/replace the UPS/part warranted hereunder, without charge for material, labor. If TIC determines that the requested repair is not covered under this limited warranty policy, then TIC shall advise customer and quote cost of repair. Repair charges shall be based on service parts price and prevailing service charges at the time of repair.
If the case in process is a BATTERY (stand-alone and/or cabinet) TIC will use its published Battery Diagnostic Document to evaluate warranty applicability. First, TIC will make sure that the storage, maintenance, installation, and operating conditions were met; then the BATTERY capacity will be tested in accordance with the “performance test” guidelines IEEE Std 450. If the BATTERY fails to deliver 70% of its rated capacity it shall be deemed defective and be replaced. Either float or cyclic service will be used to determine the warranty credit (as per published Battery Diagnostic Document). The typical credit applied will be as in the following table:
Credit for Replacement Battery When Approved Warranty
Time from Shipment UPS Batteries Cost to Customer
(months) % Credit % List Price
0-24 100 0 25-30 55 45 31-36 45 55 37-42 35 65 43-48 25 75 49-54 15 85 55-60 5 95
MODIFICATIONS
No representative, salesperson, agent, distributor, or employee of TIC is authorized to modify any of the terms of this warranty, unless modifications are made in writing and signed by an authorized TIC officer.
THIS WARRANTY REPRESENTS THE ENTIRE AGREEMENT BETWEEN TIC AND USER WITH RESPECT TO THE SUBJECT MATTER HEREIN AND SUPERSEDES ALL PRIOR OR CONTEMPORANEOUS ORAL OR WRITTEN COMMUNICATIONS, REPRESENTATIONS, UNDERSTANDINGS OR AGREEMENTS RELATING TO THIS SUBJECT
PROCEDURE
, or phone 1-877-867-8773
38
Notes:
TOSHIBA
39
Notes:
TOSHIBA
40
TOSHIBA
TOSHIBA
TOSHIBA INTERNATIONAL CORPORATION
INDUSTRIAL DIVISION 13131 West Little York Rd., Houston Texas 77041 Tel: (800) 231-1412 Fax: (713) 466-8773
41
Loading...