Quick Installation Guide
1600XP Series UPS
Purpose
This Quick Installation Guide (QIG) provides the minimum information needed to connect and startup your 1600 XP UPS. The
complete 1600XP Users Manual and supporting documentation are provided in the accompanying CD (P/N 62908). The self-
starting CD requires a PC with a web browser (e.g Microsoft Explorer) and a PDF le viewer (e.g. Adobe Acrobat Reader).
If requested, a printed manual may be provided at no cost from Toshiba International Corporation. Contact UPS Marketing at
800-231-1412.
NOTE: This QIG is not intended to replace the 1600XP Users Manual.
Toshiba International Corporation reserves the right, without prior notice, to update information, make product changes, or
discontinue any product or service identied in this publication.
Toshiba International Corporation shall not be liable for direct, indirect, special, or consequential damages resulting from the use
of the information contained within this QIG.
QUALIFIED PERSONNEL ONLY
Qualied person is one that has the skills and knowledge relating to the construction, installation, operation, and maintenance
of the electrical equipment and has received safety training on the hazards involved (Refer to the latest edition of NFPA 70E for
additional safety requirements).
Qualied personnel shall:
Have read the entire operation manual.1.
Be trained and authorized to safely energize, de-energize, ground, lockout and tag circuits and equipment, and clear faults 2.
in accordance with established safety practices.
Be trained in the proper care and use of protective equipment such as safety shoes, rubber gloves, hard hats, safety 3.
glasses, face shields, ash clothing, etc., in accordance with established safety practices.
Be trained in rendering rst aid.4.
Be knowledgeable of batteries and the required handling and maintenance precautions.5.
For further information on workplace safety visit www.osha.gov.
Misuse of this equipment may result in human injury and equipment damage. In no event will Toshiba Corporation be responsible
or liable for either indirect or consequential damage or injury that may result from the misuse of this equipment.
DO NOT open or mutilate the batteries. Released electrolyte is harmful to the eyes and skin and could also be toxic.
DO NOT dispose of the battery module in a re. The batteries inside may explode.
To be performed by Qualied Personnel Only:
Verify that the UPS is off and that the power is disconnected from the power source.1.
Remove watches, rings or other metal objects.2.
Use tools with insulated handles to prevent inadvertent shorts.3.
Wear rubber safety gloves and boots.4.
DO NOT place tools or any metal parts on top of batteries.5.
Contact with any part of a grounded battery can result in electrical shock.
The likelihood of shock will be reduced if such grounds are removed prior to installation or maintenance.
62909-000
March 2010
1
Inspection/Unpacking
Inspection
Upon receipt of the UPS, an inspection for shipping damage should be performed. Use caution when removing the unit from the
pallet. Refer to labels or documentation attached to packing material.
Unpacking
Check the unit for loose, broken, bent or otherwise damaged parts. If damage has occurred during shipping, keep all original
crating and packing materials for return to the shipping agent. The warranty does not apply to damage incurred during shipping.
Ensure that the rated capacity and the model number specied on the nameplate conform to the order specications.
Installation Precautions
Install the unit in a well-ventilated location; allow at least 4 inches (10 cm) on all sides for air 1. ventilation and for
maintenance.
Install the unit in a stable, level and upright position that is free of excessive vibration.2.
Install the unit where the ambient temperature is within 32 – 104 °F (0 – 40 °C).3.
DO NOT install the UPS in areas that are subject to high 4. humidity.
DO NOT install the UPS in areas that allow exposure to direct sunlight.5.
DO NOT install the UPS in areas that allow exposure to high levels of airborne dust, metal particles, or ammable 6.
gases.
DO NOT install the UPS in areas near sources of electrical noise. Ensuring a proper earth 7. ground will reduce the effects
of electrical noise and will reduce the potential for electrical shock.
DO NOT install the UPS in areas that would allow uids or any foreign object to get inside the UPS.8.
The UPS generates and can radiate radio-frequency energy during operation. Although RFI noise lters are installed 9.
inside of the unit, there is no guarantee that the UPS will not inuence some sensitive devices that are operating near
by. If such interference is experienced, the UPS should be installed farther away from the affected equipment and/or
powered from a different source than that of the affected equipment.
After ensuring that all power sources are turned off and isolated in accordance with established lockout/tagout procedures, 10.
connect the power source wiring of the correct voltage to the input terminals of the UPS.
Connect the output terminals of the UPS to the load (refer to NEC Article 300 – Wiring Methods and Article 310 – 11.
Conductors For General Wiring). Size the branch circuit conductors in accordance with NEC Table 310.16.
Conductor Routing and Grounding
Use separate metal conduits for routing the input power, output power, and control circuits.1.
Follow the wire size and tightening torque specications listed on page 4.2.
Always ground the unit to reduce the potential for electrical shock and to help reduce electrical noise.3.
A separate ground cable should be run inside the conduit with the input power, output power, and control circuits.4.
THE METAL OF CONDUIT IS NOT AN ACCEPTABLE GROUND.
Operating Precautions
The UPS should not be used with a load that has a rated input that is greater than the rated output of the UPS.1.
2. DO NOT use the UPS to provide power to motors that require high starting current or with motors that require a long
starting time, such as vacuum cleaners/machine tools (oversizing the UPS for lock rotor current would be required).
DO NOT attempt to disassemble, modify, or repair the UPS. Repairs and servicing should only be performed by Toshiba 3.
Field Service personnel.
Access panels should be removed only by Toshiba Field Service personnel.4.
Turn the power on only after installing ALL of the covers.5.
If the UPS should emit smoke, produce an unusual odor, or make sound, turn the power off immediately.6.
2