Toshiba 1600EP SERIES Instruction Manual

Page 1
TOSHIBA
1600EP SERIES
UNINTERRUPTIBLE POWER SYSTEM (UPS)
SINGLE PHASE - 3.6/6/8/10/14/18/22 kVA
January 2007 Part # 55288-001
Manufactured in the USA
© Copyright 2006 TOSHIBA International Corporation All rights reserved.
U
â
U
â
Page 2
Page 3
The Toshiba products listed in this document are intended for usage in general electronics applications (computer, personal equipment, offi ce equipment, measuring equipment, industrial robotics, domestic appliances, etc.). These Toshiba products are neither intended nor warranted for usage in equipment that requires extraordinarily high quality and/or reliability or where a malfunction or failure may cause loss of human life or bodily injury (“Unintended Usage”). Unintended Usage include atomic energy control instruments, airplane or spaceship instruments, transportation instruments, traffi c signal instruments, combustion control instruments, medical instruments, all types of safety devices, etc.. Unintended Usage of Toshiba products listed in this document shall be made at the customer’s own risk.
NOTICE
PLEASE INFORM TOSHIBA INTERNATIONAL CORPORATION OR AUTHORIZED
REPRESENTATIVE IN CASE OF INCONSISTENCIES, OMISSIONS, OR QUESTIONS.
The instructions contained in this manual are not intended to cover all of the details or variations in equipment, or to provide for every possible contingency concerning installation, operation, or maintenance. Should further information be required or if problems arise which are not covered suffi ciently , contact your Toshiba sales offi ce.
The contents of this instruction manual shall not become a part of or modify any prior or existing agreement, commitment, or relationship. The sales contract contains the entire obligation of Toshiba International Corporation’s UPS Division. The warranty contained in the contract between the parties is the sole warranty of Toshiba International Corporation’s UPS Division and any statements contained herein DO NOT create new warranties or modify the existing warranty.
Any electrical or mechanical modifi cations to this equipment without prior written consent of Toshiba International Corporation will void all warranties and may void the UL/CUL listing. Unauthorized modifi cations can also result in personal injury, death, or destruction of the equipment.
QUALIFIED PERSONNEL ONLY
Qualifi ed Personnel are those that have the skills and knowledge relating to the construction, installation, operation, and maintenance of the electrical equipment and has received safety training on the hazards involved (Refer to the latest edition of NFPA 70E for additional safety
requirements).
1600EP Series Instruction Manual
3
Page 4
UNINTERRUPTIBLE POWER SYSTEM (UPS)
Please complete the following information and retain for your records. Unless otherwise specifi ed, the warranty period for the UPS or UPS part is 36 months from the shipment
date (see Toshiba International Corporation bill of lading). Unless otherwise specifi ed, the warranty period for a UPS battery is 24 months from the shipment date
(see Toshiba International Corporation bill of lading).
JOB NUMBER
MODEL NUMBER
SERIAL NUMBER
APPLICATION
SHIPMENT DATE
INSTALLATION DATE
INSPECTED BY
4
1600EP Series Instruction Manual
Page 5
Purpose
This manual provides information on how to safely install your Toshiba International Corporation power electronics product. This manual includes a section of general safety instructions that describes the warning labels and symbols that are used throughout the manual. Read the manual completely before installing, operating, or performing maintenance on this equipment.
This manual and the accompanying drawings should be considered a permanent part of the equipment and should be readily available for reference and review. Dimensions shown in the manual are in metric and/or the English customary equivalent.
Toshiba International Corporation reserves the right, without prior notice, to update information, make product changes, or discontinue any product or service identifi ed in this publication.
Toshiba is a registered trademark of the Toshiba Corporation. All other product or trade references appearing in this manual are registered trademarks of their respective owners.
T oshiba International Corporation shall not be liable for direct, indirect, special, or consequential damages resulting from the use of the information contained within this manual.
This manual is copyrighted. No part of this manual may be photocopied or reproduced in any form without the prior written consent of Toshiba International Corporation.
© Copyright 2007 Toshiba International Corporation All rights reserved. Printed in the U.S.A.
Toshiba’s Customer Support Center
Contact the Toshiba Customer Support Center for assistance with application information or for any problems that you may experience with your Uninterruptible Power System (UPS).
Toshiba Customer Support Center
8 a.m. to 5 p.m. (CST) - Monday through Friday USA Toll Free (800) 231-1412 Tel (713) 466-0277 Fax (713) 466-8773
You may also contact Toshiba by writing to:
Toshiba International Corporation
13131 West Little York Road Houston, Texas 77041-9990 Attn: UPS Product Manager
For further information on Toshiba’s products and services, please visit our website at:
www.toshiba.com/ind
1600EP Series Instruction Manual
5
Page 6
Table of Contents
General Safety Instructions .............................................................................8
Symbols ...................................................................................................8
Signal Words ...........................................................................................9
IMPORTANT SAFETY INSTRUCTIONS ...........................................................10
QUALIFIED PERSONNEL ONLY ............................................................10
Product Description .........................................................................................12
Application and Use .................................................................................12
Output Rating...........................................................................................12
Power Backup..........................................................................................12
Power Conditioning..................................................................................12
Inspection/Storage/Disposal ...........................................................................13
Inspection ................................................................................................13
Storage ....................................................................................................13
Disposal ...................................................................................................13
Installation Precautions ...................................................................................14
Operating Precautions .....................................................................................15
UPS Connections .............................................................................................16
Communication Interfaces ..............................................................................17
UPS Stop Signal Operation ....................................................................18
RS-232C ..................................................................................................19
RemotEye Network Card .........................................................................19
UPS Specifi cations ...........................................................................................20
Operating the UPS ............................................................................................26
Battery Backup Time and Discharge Process .......................................26
Starting the UPS ......................................................................................27
Battery Recharging ..................................................................................28
Online Mode ......................................................................................................29
AC Input Mode (Run operation) .........................................................................29
Static-Bypass Mode (Stop operation) ......................................................29
Battery Backup Mode (on batteries) ........................................................30
EPO (Emergency Power Off) Function ....................................................30
Audible Alarm Functions ..........................................................................31
Display and Keys ..............................................................................................32
Front Panel Layout ..................................................................................32
Liquid Crystal Display (LCD) Functions ...................................................32
Operating Keys ........................................................................................33
Light Emitting Diodes (LED) ....................................................................33
Display Screens ................................................................................................34
Screen Arrangement ................................................................................34
System Overview Screens.......................................................................34
UPS Start-Up Screens Sequence............................................................34
Data Display Screens ..............................................................................36
Special Display Screens ..........................................................................37
6
1600EP Series Instruction Manual
Page 7
Data Setting Screens ...............................................................................38
System Warning Messages .....................................................................44
System Fault Messages ..........................................................................45
Status Change Indications .......................................................................46
UPS Protection System....................................................................................47
System Protection Features ....................................................................47
System Protection Functions ..................................................................47
Preventive Maintenance/Parts Replacement .................................................49
Preventive Maintenance ..........................................................................49
Parts Replacement ..................................................................................49
Optional Receptacle Panel Installation Instructions .....................................50
External Layouts/Dimensions/Shipping Weights ..........................................51
Dimensional Data ...................................................................................51
Shipping Weights .....................................................................................51
Index ..................................................................................................................54
1600EP Series Instruction Manual
7
Page 8
General Safety Instructions
DO NOT attempt to transport, install, operate, maintain or dispose of this equipment until you have read and understood all of the product safety information provided in this manual.
Symbols
The symbols listed below are used throughout this manual. When symbols are used in this manual they will include important safety information that must be carefully followed.
Safety Alert Symbol indicates that a potential
personal injury hazard exists.
Prohibited Symbol indicates DO NOT take action.
Mandatory Symbol indicates that the following
instruction is required.
Ground Symbol indicates the location of the
equipment grounding conductor.
Electrical - Voltage & Shock Hazard Symbol
indicates parts inside may cause electric shock.
Explosion Hazard Symbol indicates parts may
explode.
8
1600EP Series Instruction Manual
Page 9
Signal Words
The signal words listed below are used throughout this manual. When the words DANGER, WARNING, CAUTION and ATTENTION are used in this manual they will include important safety information that must be carefully followed.
The word DANGER in capital letters preceded by
DANGER
WARNING
CAUTION
the safety alert symbol indicates that an imminently hazardous situation exists, if not avoided, will result in death or serious injury to personnel.
The word WARNING in capital letters preceded by the safety alert symbol indicates that a potentially
hazardous situation exists, if not avoided, could result in death or serious injury to personnel.
The word CAUTION in capital letters preceded by the safety alert symbol indicates that a potentially
hazardous situation exists, if not avoided, may result in minor or moderate injury.
CAUTION
ATTENTION
The word CAUTION in capital letters without the safety alert symbol indicates a potentially
hazardous situation exists, if not avoided, may result in equipment and property damage.
The word ATTENTION in capital letters without the safety alert symbol indicates a potentially
hazardous situation exists, if not avoided, may result in equipment and property damage.
1600EP Series Instruction Manual
9
Page 10
IMPORTANT SAFETY INSTRUCTIONS
This manual contains important instructions for 3.6, 6, 8, 10, 14, 18, and 22 kVA Units that should be followed during the installation and maintenance of the UPS and its batteries.
Hardwire type UPS units are not equipped with an over-current protection device nor an output disconnect for the AC output. Therefore, a circuit breaker should be provided by the user between the UPS output and the load input. This device should be rated as follows:
240VAC RATING
The nominal battery voltages for these models are as follows:
BATTERY VOLTAGE
Servicing of the batteries should only be performed by a qualifi ed Toshiba Representative who is knowledgeable of batteries and the required precautions. Keep unauthorized personnel away from batteries. To arrange for battery replacement, contact your nearest Toshiba authorized service center.
1 Turn off, lockout, and tagout all not equipped before connecting the power wiring to the
equipment ow when performing maintenance.
2 Hardwire type UPS units are not equipped with an over-current protection device, nor do
they have an output disconnect for the AC output. Therefore, a user-installed circuit breaker
should be provided between the UPS output and the load input. 3 The maximum ambient operating temperature is 104 °F (40 °C). 4 Battery servicing should be performed by qualifi ed Toshiba Representative only. 5 Unauthorized personnel should not service batteries. 6 Contact your Toshiba authorized service center for battery replacement.
3.6kVA 6kVA 8kVA 10kVA 14kVA 18kVA 22kVA
20A 30A 40A 60A 80A 125A 150A
3.6kVA 6kVA 8kVA 10kVA 14kVA 18kVA 22kVA
216Vdc 216Vdc 288Vdc 288Vdc 288Vdc 288Vdc 288Vdc
QUALIFIED PERSONNEL ONLY
Qualifi ed personnel is one that has the skills and knowledge relating to the construction, installation,
operation, and maintenance of the electrical equipment and has received safety training on the hazards involved (Refer to the latest edition of NFPA 70E for additional safety requirements).
Qualifi ed personnel shall:
1 Have read the entire operation manual. 2 Be trained and authorized to safely energize, de-energize, ground, lockout and tag circuits
and equipment, and clear faults in accordance with established safety practices. 3 Be trained in the proper care and use of protective equipment such as safety shoes, rubber
gloves, hard hats, safety glasses, face shields, fl ash clothing, etc., in accordance with
established safety practices. 4 Be trained in rendering fi rst aid. 5 Be knowledgeable of batteries and the required handling and maintenance precautions.
For further information on workplace safety visit www.osha.gov.
10
1600EP Series Instruction Manual
Page 11
CAUTION
Misuse of this equipment could result in human injury and equipment damage. In no event will Toshiba Corporation be responsible or liable for either indirect or consequential damage or injury that may result from the use of this equipment.
CAUTION
DO NOT open or mutilate the batteries. Released
CAUTION
To be performed by Quali ed Personnel Only:
1 Verify that the UPS is off and that the power cord is disconnected from the power source. 2 Remove watches, rings or other metal objects. 3 Use tools with insulated handles to prevent inadvertent shorts. 4 Wear rubber gloves and boots. 5 DO NOT place tools or any metal parts on top of batteries. 6 Determine if the battery is inadvertently grounded. If inadvertently grounded, remove source of
ground.
electrolyte is harmful to the eyes and skin and could also be toxic.
DO NOT dispose of the battery module in a fi re. The batteries inside may explode.
WARNING
Contact with any part of a grounded battery can result in electrical shock.
The likelihood of shock will be reduced if such grounds are removed prior to installation or maintenance.
INSTRUCTIONS IMPORTANTES
CONCERNANT LA SÉCURITÉ
CONSERVER CES INSTRUCTIONS
Cette notice contient des instructions importantes concernant la sécurité.
ATTENTION
ATTENTION
1600EP Series Instruction Manual
Une battery peut présenter un risque de choc électrique, de brûlure par transfert d’ énergie.
L’ élimination des batteries est règlementèe. Consulter les codes locaux à cet effet.
11
Page 12
Product Description
An uninterruptible power system is a system that is installed between the commercial power and the load equipment. The UPS provides steady AC output power during commercial power short-term blackouts or brownouts. This power is provided for a long enough time so that the load can be shut down in an orderly fashion. This prevents loss of data and possible damage to both hardware and software.
During normal operation, the UPS uses commercial AC power . In addition, it takes in all of the high voltage spikes and transients caused by switching and faults, and all of the common-mode and normal mode noise which is associated with commercial AC power. The UPS converts it all to fl at DC power. From this power, the UPS charges its batteries and generates its own extremely high quality AC waveform output. The result of this process is maximum power conditioning and regulation.
If the AC power supplied to the UPS drops below a specifi ed voltage level, the unit’s batteries automatically begin supplying power instead of receiving it. This insures that the loads connected to the UPS continue to receive power with no interruption. When AC input power becomes available again, operation returns to normal. The unit’s batteries begin to recharge so they will be ready for the next power interruption.
Application and Use Toshiba’s 1600EP Series of on-line uninterruptible power system (UPS) systems provide continuous
computer-grade AC power in a compact, high performance, and energy effi cient unit. The UPS unit assures safe and reliable operation of critical offi ce equipment. This can range from word processors and personal computers to mini-computers and local area networks. All units feature an audible alarm which sounds if the battery voltage drops below standard during use. This is an additional aid to help in retaining the valuable offi ce data banks. All units allow for computer interfacing.
Output Rating
Toshiba’s 1600EP Series (208/240V) offers UPS models with the following capacities:
MODEL Output Capacity @ 240V Output kW @ .85PF 240V
UE3G2L036C61T 3.6 kVA 3.1 kW UE3G2L060C61T 6 kVA 5.1 kW UE3G2L080C61T 8 kVA 6.8 kW UE3G2L100C61T 10 kVA 8.5 kW UE3G2L140C61T 14 kVA 11.9 kW UE3G2L180C61T 18 kVA 15.3 kW UE3G2L220C61T 22 kVA 18.6 kW
Power Backup
When an electrical power failure occurs, the UPS’s internal batteries automatically supply back-up power to the load without interruption. For example, when used to support a computer, the UPS back-up assures enough additional time to complete the activity and store the data. This allows an orderly shutdown after a power failure has occurred.
Power Conditioning When commercial power is present, the UPS supplies conditioned power to the load while maintaining its
batteries in a charged condition. The UPS protects against the normal, everyday problems associated with heavy use of raw commercial power, including power sags, surges, signal interference, and spikes. This protection keeps power-line problems from reaching your load, where they can cause equipment to operate erratically, or damage software and hardware.
12
1600EP Series Instruction Manual
Page 13
Inspection/ Storage/ Disposal
Inspection
Upon receipt of the UPS, an inspection for shipping damage should be performed. Use caution when removing the unit from the pallet. Refer to labels or documentation attached to packing material.
Unpacking
Check the unit for loose, broken, bent or otherwise damaged parts. If damage has occurred during shipping, keep all original crating and packing materials for return to the shipping agent. The warranty does not apply to damage incurred during shipping. Ensure that the rated capacity and the model number specifi ed on the nameplate conform to the order specifi cations.
Storage
During periods of non-use, the following guidelines are recommended for storage.
Storage Preparation
1 Power up the UPS and allow it to operate with no load for 24 hours to fully charge the
batteries. 2 Stop the unit (see “Stop Operation” on page 29). 3 Place the MCCB switch (see page 52 for location) in the “Off” position.
Storing Conditions
• For best results, store the UPS in the original shipping container and place on a wood or
metal pallet.
• Storage temperature: -20 to 40 °C (-4 to 104 °F).
• The optimum storage temperature is 21 °C (70 °F). A higher ambient temperature will
require recharging more frequently during storage. Avoid the following storage locations:
• Locations that are subject to extreme temperature changes or high humidity.
• Locations that are subject to high levels of dust or metal particles.
• Locations that are subject to excessive vibration.
• Inclined fl oor surfaces.
Storage Maintenance
• If stored at an ambient temperature less than 20 °C (68 °F), recharge the batteries every
9 months.
• If stored at an ambient temperature of 20 – 30 °C (68 – 86 °F), recharge the batteries
every 6 months.
• If stored at an ambient temperature of 30 – 40 °C (86 – 104 °F), recharge the batteries
every 3 months.
Disposal
Please contact your local or state environmental agency for details on disposal of electrical components and packaging in your particular area.
It is illegal to dump lead-acid batteries in landfi lls or dispose of improperly.
Please help our Earth by contacting the environmental protection agencies in your area, the battery manufacturer, or call Toshiba toll-free at (800) 231-1412 for more information about recycling.
1600EP Series Instruction Manual
13
Page 14
Installation Precautions
CAUTION
1 Install the unit in a well-ventilated location; allow at least 10 cm (4 inches) on all sides for air
ventilation and for maintenance. 2 Install the unit in a stable, level and upright position that is free of excessive vibration. 3 Install the unit where the ambient temperature is within the range specifi ed on pages 21 and 24. 4 DO NOT install the UPS in areas that are subject to high humidity. 5 DO NOT install the UPS in areas that allow exposure to direct sunlight. 6 DO NOT install the UPS in areas that allow exposure to high levels of airborne dust, metal particles,
or fl ammable gases. 7 DO NOT install the UPS in areas near sources of electrical noise. Ensuring a proper earth ground
will reduce the effects of electrical noise and will reduce the potential for electrical shock. 8 DO NOT install the UPS in areas that would allow fl uids or any foreign object to get inside the UPS. 9 The UPS generates and can radiate radio-frequency energy during operation. Although RFI noise
lters are installed inside of the unit, there is no guarantee that the UPS will not infl uence some
sensitive devices that are operating near by. If such interference is experienced, the UPS should be
installed farther away from the affected equipment and/or powered from a different source than that
of the affected equipment. 10 The user should provide output over-current protection for hardwired UPS systems. See the section
titled Specifi cations on page 20 and 23 for the device rating. 11 After ensuring that all power sources are turned off and isolated in accordance with established
lockout/tagout procedures, connect the power source wiring of the correct voltage to the input
terminals of the UPS. 12 Connect the output terminals of the UPS to the load (refer to NEC Article 300 – Wiring Methods and
Article 310 – Conductors For General Wiring). Size the branch circuit conductors in accordance with
NEC Table 310.16.
Conductor Routing and Grounding
1 Use separate metal conduits for routing the input power, output power, and control circuits. 2 Follow the wire size and tightening torque specifi cations listed on page 16. 3 Always ground the unit to reduce the potential for electrical shock and to help reduce electrical noise. 4 A separate ground cable should be run inside the conduit with the input power, output power, and
control circuits.
THE METAL OF CONDUIT IS NOT AN ACCEPTABLE GROUND.
14
WARNING
1600EP Series Instruction Manual
Page 15
Operating Precautions
1 The UPS should not be powered up until the entire operation manual has been read. 2 The voltage of the input power source must be within the range of +10% to -30% of the rated input
voltage. The input frequency must be within the rated input frequency range. Voltages and frequencies outside of the permissible range may activate the internal protection devices.
3 The UPS should not be used with a load that has a rated input that is greater than the rated output of
the UPS.
4 DO NOT use the UPS to provide power to motors that require high starting current or with motors that
require a long starting time, such as vacuum cleaners and machine tools (over sizing the UPS for lock
rotor current would be required). 5 DO NOT insert metal objects or combustible materials in the ventilation slots of the UPS. 6 DO NOT place, hang, or paste any objects on the exterior surfaces of the UPS. 7 The capacitors of the UPS maintain a residual charge for a while after turning the UPS off. The
required discharge time for each UPS typeform is provided via a cabinet label and a CHARGE LED.
Wait for at least the minimum time indicated on the label and ensure that the CHARGE LED has gone
out before opening the door of the UPS once the UPS power has been turned off. 8 DO NOT attempt to disassemble, modify, or repair the UPS. Call your Toshiba sales representative
for repair information. 9 Turn the power on only after attaching ALL of the covers.
10 DO NOT remove any covers of the UPS when the power is on. 11 If the UPS should emit smoke or an unusual odor or sound, turn the power off immediately. 12 The heat sink and other components may become extremely hot to the touch. Allow the unit to cool
before coming in contact with these items.
13 Warning signs should be placed on or near the load as a notifi cation that the load is being powered
by the UPS.
14 Additional warnings and notifi cations shall be posted at the equipment installation location as deemed
required by Quali ed Personnel.
WARNING
CAUTION
1600EP Series Instruction Manual
While operating in the inverter mode, placing the breaker in the OFF position will switch the UPS to the battery backup mode. The output of the UPS will continue uninterrupted to the load. The unit must be in the bypass mode at the time that the breaker is placed in the OFF position for the UPS to shutdown power to the load.
After an Emergency Power Off ( EPO), do not reset the breaker until the UPS has been fully discharged. The UPS could be damaged if the unit is not fully discharged before the breaker is reset.
15
Page 16
UPS Connections
Terminal Block
The following illustration is a detail view of the terminal block and wiring connections used for 208/240 volt units (see pages 52-53 for terminal block location).
NOTE 1 If AC input power is 240Vac rated, terminals 12 and 13 must be shorted by jumper wire DO NOT jumper
2 If AC input power is 208Vac rated, terminals 11 and 12 must be shorted by jumper wire DO NOT jumper
terminal 11 to 12 or 13.
terminal 13 to 12 or 11. Factory Setting is 208Vac.
Wire Size and Tightening Torque
Use the following table to select the recommended wire size and terminal lug tightening torque for I/O wire connections.
Note: The bold number in () is the maximum size wire that the terminal block can accommodate.
Item
AC Input Lines 1 and 2 (8) 12
AC Output Lines 4, 5, and 7 (8) 12
AC Output Neutral 6 (8) 12
Ground 3 and 8 (8) 12
EPO Switch 14 and 15 16 16 16 16 16
Remote Switch 16 and 17 16 16 16 16 16
(1 pound-inch = 0.11 Newton-meter)
16
Terminal Number
AW G
3.6kVA
AW G 6kVA
AW G 8kVA
AW G
10kVA
AWG
14-18kVA
AWG
22kVA
(8) 10 (1/0) 8 (1/0) 6 (1/0) 4 (1/0) 1 (8) 10 (1/0) 8 (1/0) 6 (1/0) 4 (1/0) 1 (8) 10 (1/0) 8 (1/0) 6 (1/0) 4 (1/0) 1 (8) 10 (1/0) 8 (1/0) 4 (1/0) 4 (1/0) 1
16 9.0 16 9.0
1600EP Series Instruction Manual
Tightening Torque
(Pounds-Inches)
14.2
14.2
14.2
14.2
Page 17
Communication Interfaces
Remote Contacts
The remote contacts interface is provided as a set of solid state relay switch contacts. The switches are available through a DB9 male connector on the rear of the UPS. The following chart shows the pin assignment for each signal.
MAXIMUM CURRENT CARRYING CAPACITY
Voltage Current
48Vdc Peak 100mAdc peak
30Vac rms
(42Vac peak)
Pin Signal Function Logic In the UPS
OF THE SWITCH
70mAac rms
(100mA peak)
DB9 MALE CONNECTOR OUTLINE
(FACING CONNECTOR)
1 2 3 4 5
6 7 8 9
1 Fault Signal Closed when fault detected 2 UPS stop common
3 UPS stop signal input
4 Normal input power supply Closed with normal supply power 5 Signal common Common signal return 6 Bypass operation Closed during bypass operation
Backup stop when the level changes from Low (-3 to – 15V) to High (+3 to +15V)
7 Battery voltage drop Closed at voltage drop 8 UPS operation Closed during inverter operation
9 Power failure signal Closed at power failure
NOTE Pin “switches” are shown in their inactive states. For example, if battery voltage is low, pin 7 will be connected to pin 5.
1600EP Series Instruction Manual
17
Page 18
UPS Stop Signal Operation
When the UPS stop signal is sent to the UPS through pin 2 and 3 of the external contact interface, it is possible to automatically reset the following operating systems (OS), which can automatically implement the shutdown function and restart the operation:
Applicable OS: Windows NT, IBM OS/2 LAN server, LANtastic
When the power fails, the OS detects the power failure signal from the UPS and starts the shutdown process.
At the end of the shutdown process, the OS sends a stop signal to the UPS, and the UPS stops. When the power recovers, the UPS automatically starts output and restarts the OS. Even when the
power recovers while in a shutdown process, the UPS temporarily cuts off the output (10 - 20 seconds) and then restarts the OS within 10 minutes after the recovery from power failure. In this case the UPS cuts off output even with normal input power. Connect the UPS stop signal of the external contact interface only for the automatic processing so that the UPS output will not be cut off by mistake. If a stop signal is sent to the UPS ten minutes or more after the recovery from a power failure, then the UPS ignores this signal and continues to output power.
If the computer is started/restarted within 10 minutes after the recovery from a power failure, the power supply may be reset while the computer is restarting.
POWER FAILURE
power failure
backup
NORMAL
normal
UPS STOP SIGNAL FROM OS
UPS stop signal from OS
UPS output voltage
UPS OUTPUT VOLTAGE
BACKUP
OS shutdown
OS SHUTDOWN
10 MINUTES
10 minutes
CHECKING TIME
Checking time
CONTINUES OUTPUT
continues output
Temporarily cuts off
TEMPORARILY CUTS OFF
THE OUTPUT FOR
the output for 10 to
10 TO 20 SECONDS
18
1600EP Series Instruction Manual
Page 19
RS-232C
The RS232C port can be used by authorized service personnel. The port is provided using a DB9 female connector located on the rear of the UPS. For reference, the pinout of the connector is illustrated below.
RS-232C CONNECTOR PIN ASSIGNMENT DB9 FEMALE CONNECTOR OUTLINE
(FACING CONNECTOR)
Pin I/O Symbol Description
1 This pin is not used 2 Input RXD Receive data 3 Output TXD Transmit data 4 Output DTR Data terminal ready
5 4 3 2 1
5 - SG Signal ground 6 Input DSR Data set ready 7 Output RTS Request to send
9 8 7 6
8 Input CTS Clear to send 9 This pin is not used
RemotEye Network Card
The RemotEye is an optional network card for Toshiba UPS. This card slides into a slot located on the back side (pages 52-53) of the UPS. The card provides a network, or LAN-based communication interface for the UPS. When installed, the UPS can be managed remotely using the common SNMP and HTTP web-based network protocols. The following diagram shows the fl ow of the Network Management Station.
NETWORK MANAGEMENT
STATION OR PC WITH
WEB BROWSER
NOTE The UPS communication mode setting must be set to “SNMP” mode when using the RemotEye network card
(see Comm Mode variable in the ‘Data Setting Screens’ on page 38).
1600EP Series Instruction Manual
TOSHIBA UPS
REMOTEYE
NETWORK CARD
NETWORK ETHERNET BACKBONE
19
Page 20
UPS Specifi cations
STANDARD MODELS: 3.6kVA; 6kVA; 8kVA
Capacity 3.6kVA (3.1kW)* 6kVA (5.1kW)* 8kVA (6.8kW)*
General Topology True On-line Certifi cations UL, CUL, ISO 9001, NEMA/PE1-1993 Input Characteristics Input Voltage Single-phase, 208/240 VAC, +10% to –30%* Input Frequency 45-65 Hz (auto-sensing) Input Capacity 3.6 kVA 6 kVA 8 kVA Input Power Factor > 0.95 for all loads Current THD (linear load) < 5% Included AC Input Breaker
Rating Battery Characteristics Battery Type Valve Regulated Lead Acid, Flame Retardant
Backup time, fully charged @ 0.7 power factor, 77°F
Backup time, fully charged @ 0.85 power factor, 77°F
Recharge Time 24hr. (full), 12hr.(90%) for internal batteries only*** Battery Voltage (Nominal) 216 VDC 216 VDC 288 VDC Output Characteristics Output Voltage Single-phase, 240/208/120 volts Output Voltage Regulation ± 3%
Output Frequency AUTO/MAN Frequency Factory or authorized service center selectable only
Voltage THD < 3% for linear load; < 6% for non-linear load Common-Mode Noise < .5 Vrms Rated Load Power Factor 0.85 (0.6 - 1.0) lagging Effi ciency (AC-DC-AC) > 83% (without battery charge) Voltage Transient < ±8% (Load of 0 to 100 %) Rated Output Current (rms) 15.0 A 25.0 A 33.3 A Max. Peak Output Current 45.0 A 75.0 A 100.0 A Inverter Overload Capacity 125%-30 sec/150%-10 sec Bypass Overload Capacity 125%-10 min./1000%-1 cycle Crest Factor 3.0
30 A / 277 V 50 A / 277 V 60 A / 277 V
3.6 kVA 6 kVA 8 kVA 14 min
minimum**
10 min
minimum**
±0.5 Hz/1 Hz/1.5 Hz (factory or authorized service center selectable
only)
7 min
minimum**
7 min
minimum**
20
1600EP Series Instruction Manual
Page 21
STANDARD MODELS: 3.6kVA; 6kVA; 8kVA (CONT’D)
Capacity 3.6kVA (3.1kW)* 6kVA (5.1kW)* 8kVA (6.8kW)*
Environment Operating Temperature
(15 – 25° C recommended)
60Hz 50Hz
0 – 40 °C 0 – 33 °C
Storage Temperature -20 – 40 °C (-4 to 104 °F) Installation Area
To be installed in a well ventilated area free of airborne dust,
metal particles or fl ammable gas, allow at least 4 inches on all sides. Operating Humidity 30 – 90% (no condensation) Altitude < 1000 m above sea level**** Acoustical Noise 50 dB (A) maximum @ 1 meter from front panel Heat Generation 1588 BTU/Hr 2610 BTU/Hr 3482 BTU/Hr Operation Diagnosis Battery Check Performed on start up, by schedule, on-demand (user confi gurable) Input OV Protection Standard
UPS calculates battery replacement time
Battery +-
based upon battery ambient temperature (LCD display, LED and
beeps) Internal Temperature UPS gives indication of internal temperature, alarm when high temp Event Data Storage 64-Supply Mode, 32-Back up, 16- Faults Applications Switches Generator compatible Bypass Switch Bypass Disable Static switch <1/4 cycle (50Hz:5ms/60Hz:4.16ms) Automatic Retransfer Factory or authorized service center selectable only User Interface Provided (can be disabled from front panel) Real Time Clock Schedule Operation Standard, Minimum 3 days memory backup during power loss RUN/STOP Disable Schedule ON/OFF operation of UPS using communication software Autostart UPS has option for UPS to start automatically when AC is applied Remote ON/OFF Standard, external terminal
LED Display
4 LED’s indicating input/output condition, warning and battery
operation LCD Screen 16 characters x 2 lines UPS Operation: 6 Keys Run/Stop, Set/Monitor, Shift/Select, Del/
Page Down, Reset/Page Up
Buzzer Volume Low, High, Mute; Selectable by keypad Power Connections Hard wire (Standard) Emergency Power Off Standard (Terminal contacts only) Remote Contacts Standard (INV, BYP, BATT, LB, AC, FLT) RS232 ASCII Interface Standard
1600EP Series Instruction Manual
21
Page 22
STANDARD MODELS: 3.6kVA; 6kVA; 8kVA (CONT’D)
Capacity 3.6kVA (3.1kW)* 6kVA (5.1kW)* 8kVA (6.8kW)*
Mechanical Design Enclosure
Enclosure of unit made from sheet metal
meeting NEMA1 and UL Type 1 Size (HxWxD) Inches (max) 27.5 x 10 x 33 28.25 x 13 x 33.5 Paint System Powder coating.
Fan Panel
Panel mounted on back of UPS to allow for
easy replacement of fans without turning UPS off.
Battery System Battery Replacement
Battery Packs
Designed for battery acid leakage containment with (6) batteries per
Slide out battery packs accessible from front of UPS,
factory or authorized service center serviceable only
pack. Battery Pack Size HxWxD)Inches(max) 5 x 7.3 x 18.2 Battery Pack Quantity 3 3 4 Battery Manufacturer Enersys Battery Type NPX-35 Toshiba’s Part Number for
Battery Pack
51896
(*) Input/output fi gures rated for 240 volts. Output ratings given for 0.85PF are only valid when the input voltage is
greater than 204 volts; otherwise, ratings given for 0.70PF are applicable. (**) Battery backup time may vary depending on the operating conditions and ambient temperature at the installation site. (***) An initial charge time of 24 hrs. is necessary to obtain proper battery performance level before unit is placed in operation (****) At 6600 ft (2000 m) above sea level, output capacity should be derated by 3%.
22
1600EP Series Instruction Manual
Page 23
STANDARD MODELS: 10kVA; 14kVA; 18KVA; 22kVA (CONT’D)
Capacity 10kVA (8.5kW)* 14kVA (11.9kW)* 18kVA (15.3kW)* 22kVA (18.7kW)*
General Topology True On-line Certifi cations UL, CUL, ISO 9001, NEMA/PE1-1993 Input Characteristics Input Voltage Single-phase, 208/240 VAC, +10% to –30%* Input Frequency 45-65 Hz (auto-sensing) Input Capacity
10 kVA 14 kVA 18 kVA Input Power Factor > 0.95 for all loads Current THD (linear load) < 5% Included AC Input Breaker
63 A / 277 V 100 A / 277 V 125 A / 277 V
rating Battery Characteristics Battery Type Valve Regulated Lead Acid, Flame Retardant
Backup time, fully charged @ 0.7 power factor, 77 F
Backup time, fully charged @ 0.85 power factor, 77 F
10 kVA 14 kVA 18 kVA 22 kVA
7 min minimum** 5 min
5 min
minimum**
7 min
minimum**
5 min
minimum**
3 min
minimum** Recharge Time 24hr. (full), 12hr.(90%) for internal batteries only*** Battery Voltage (Nominal) 288 VDC Output Characteristics Output Voltage Single-phase, 240/208/120 volts Output Voltage Regulation ±3% Output Frequency ±0.5Hz/1Hz/1.5Hz (factory or authorized service center selectable only) AUTO/MAN Frequency Factory or authorized service center selectable only Voltage THD < 3% for linear load; < 6% for non-linear load Common-Mode Noise < .5 Vrms Rated Load Power Factor 0.85 (0.6 - 1.0) lagging Effi ciency (AC-DC-AC) > 83% (without battery charge) Voltage Transient < ±8% (Load of 0 to 100 %) Rated Output Current (rms) 41.6 A 58.0 A 75.0 A 91.6 A Max. Peak Output Current 125 A 174 A 225 A 275 A Inverter Overload Capacity 125%-30 sec/150%-10 sec Bypass Overload Capacity 125%-10 min./1000%-1 cycle Crest Factor 3.0
1600EP Series Instruction Manual
23
Page 24
STANDARD MODELS: 10kVA; 14kVA; 18KVA; 22kVA (CONT’D)
Capacity 10kVA (8.5kW)* 14kVA (11.9kW)* 18kVA (15.3kW)* 22kVA (18.7kW)*
Environment Operating temperature
(15 – 25° C recommended)
60 Hz (0 – 40 °C) ; 50Hz (0 – 33 °C) Storage Temperature -20 – 40 °C (-4 to 104 °F) Installation Area
To be installed in a well ventilated area free of airborne dust,
metal particles or fl ammable gas, allow at least 4 inches on all sides Operating Humidity 30 – 90% (no condensation) Altitude < 1000m above sea level**** Acoustical Noise 50 dB (A) maximum @ 1 meter from front panel Heat Generation 4352 BTU/Hr 6092 BTU/Hr 7832 BTU/Hr 6900 BTU/Hr Operation Diagnosis Battery Check Performed on start up, by schedule, on-demand (user confi gurable) Input OV Protection Standard
Battery Lifetime
UPS calculates battery replacement time based upon
battery ambient temperature (LCD display, LED and beeps) Internal Temperature UPS gives indication of internal temperature, alarm when high temp Event Data Storage 64-Supply Mode, 32-Back up, 16- Faults Applications Switches Generator compatible Bypass Switch Bypass Disable Static switch <1/4 cycle (50Hz:5ms/60Hz:4.16ms) Automatic Retransfer Factory or authorized service center selectable only User Interface Provided (can be disabled from front panel) Real Time Clock Schedule Operation Standard, Minimum 3 days memory backup during power loss RUN/STOP Disable Schedule ON/OFF operation of UPS using communication software Autostart UPS has option for UPS to start automatically when AC is applied Remote ON/OFF Standard, external terminal LED Display 4 LED’s indicating input/output condition, warning and battery operation LCD Screen 16 characters x 2 lines UPS Operation: 6 Keys Run/Stop, Set/Monitor, Shift/Select, Del/(
page down), Reset/(page up)
Buzzer Volume Low, High, Mute; Selectable by keypad Power Connections Hard wire (Standard) Emergency Power Off Standard (Terminal contacts only) Remote Contacts Standard (INV, BYP, BATT, LB, AC, FLT) RS232 ASCII Interface Standard
24
1600EP Series Instruction Manual
Page 25
STANDARD MODELS: 10kVA; 14kVA; 18KVA; 22kVA (CONT’D)
Capacity 10kVA (8.5kW)* 14kVA (11.9kW)* 18kVA (15.3kW)* 22kVA (18.7kW)*
Mechanical Design Enclosure Enclosure of unit made from sheet metal meeting NEMA1 and UL Type 1 Size (HxWxD)
Inches (max)
28.25 x 13 x 33.5 39.1 x 17.5 x 34.8 Paint System Powder coating. Fan Panel
Panel mounted on back of UPS to allow for
easy replacement of fans without turning UPS off.
Battery System Battery Replacement
Slide out battery packs accessible from front of UPS,
factory or authorized service center serviceable only Battery Packs Designed for battery acid leakage containment with (6) batteries per pack. Battery Pack Size 5 x 7.3 x 18.2 (HxWxD) Inches (max) Battery Pack Quantity 4 8 Battery Manufacturer Enersys Battery Type NPX-35 Toshiba’s Part Number
for Battery Pack
51896
(*) Input/output fi gures rated for 240 volts. Output ratings given for 0.85PF are only valid when the input voltage is
greater than 204 volts; otherwise, ratings given for 0.70PF are applicable. (**) Battery backup time may vary depending on the operating conditions and ambient temperature at the installation site. (***) An initial charge time of 24 hrs. is necessary to obtain proper battery performance level before unit is placed in operation (****) At 6600 ft (2000 m) above sea level, output capacity should be derated by 3%.
1600EP Series Instruction Manual
25
Page 26
Operating the UPS
Battery Backup Time and Discharge Process
The UPS batteries provide about 5-7 minutes of back-up time depending on the 1600EP unit kVA rating. These times are valid when the unit is operating under full load and at the rated power factor. The exact length of these times will depend on the UPS model used, condition of the batteries, amount and type of load, temperature and other variables. See battery backup time in ‘Standard Specifi cations’ beginning on
pages 20-25.
The following illustration graphically shows the battery discharge process at full load conditions.
CURRENT VOLTAGE
Current
V NOM
Vnom
V LOW
Vlow
V MIN
Vmin
Voltage
SHUTDOWN
Shutdow n
IMAX
Imax
IMIN
Imin
100%
100% 20% 0%
Battery Capacity
BATTERY CAPACITY
Battery Low Voltage Tolerances Excessive discharge will cause the UPS battery voltage to drop. The chart shown below lists the voltage
level at which each UPS low-voltage alarm will sound and also at what level the low-voltage condition will cause the unit to automatically shut down.
UPS Capacity
Nominal voltage (Vnom) 216Vdc 216Vdc 288Vdc 288Vdc 288Vdc 288Vdc 288Vdc Alarm voltage (Vlow) 192Vdc 192Vdc 246Vdc 246Vdc 246Vdc 246Vdc 246Vdc Shutdown voltage (Vmin) 170Vdc 170Vdc 227Vdc 227Vdc 227Vdc 227Vdc 227Vdc
3.6kVA 6kVA 8kVA 10kVA 14kVA 18kVA 22kVA
20%
0%
26
1600EP Series Instruction Manual
Page 27
Starting the UPS
Turn the main circuit breaker (MCCB) on the back of the UPS (see pages 52-53) to the “ON” position (the breaker should normally remain in the “on” position).
Check that the AC INPUT LED on the front panel (see page 32 and 33) lights ‘green’. All LED’s on the front panel may light for a moment when the input breaker is turned “on”. This is normal. The UPS will now be supplying power in the bypass mode.
CAUTION
When running the UPS for the fi rst time or after the power failure backup operation, charge the batteries for at least 24 hours (input breaker “on”) before operating the connecting load.
Using the UPS without charging the battery shortens the battery backup operation time, which could result in the destruction of data in case of a power failure.
Press RUN key to begin UPS operation (see page 34 for startup screens).
CAUTION
If the input breaker is turned off while UPS is in the bypass state, the output power stops. Any load devices will lose power.
Ensure that all sensitive loads have been previously shut down.
Stopping the UPS To stop the UPS, press the STOP key approximately 1 second until the LED changes from green to
“off”. The UPS is now in the bypass mode. To completely stop the UPS, turn the input breaker at the back of the UPS to the “OFF” position.
1600EP Series Instruction Manual
27
Page 28
Battery Recharging
The illustration below shows a graphical representation of the UPS battery recharge process after a full discharge.
Current
Icharge
ICHARGE
CURRENT VOLTAGE
VMAX
Vmax
Vmin
VMIN
Voltage
DISCHARGE
Discharge
SHUT-OFF
Shut-off Point
POINT
CURRENT
Charging
CHARGING
Current
BATTERY
Battery
CHARGE
Charge
VOLTAGE
TIME
Time
Period 1
PERIOD 1 PERIOD 2 PERIOD 3
Period 2
Period 3
The recharge process usually consists of three periods. During the fi rst period, the current is maintained at approximately 1 ampere. This current limit is the maximum value that can be used to charge the batteries (for minimal recharge time) while assuring safety and long battery life. In the second period, constant-voltage control starts and current gradually decreases as the batteries charge to their normal fully charged state. In the third period, a slight “trickle” current continues to fl ow into the batteries to keep them fully charged and “fl oating” at the normal Vdc level. A full recharge usually requires 24 hours (90% recharge in 12 hours) after a complete discharge.
The following chart shows the rated maximum and minimum battery voltages and the charge current for each of the sizes.
RATED BATTERY VOLTAGES
Model Vmax Vmin Icharge
3.6kVA 245.7 170 1.0 amp 6kVA 245.7 170 1.0 amp 8kVA 327 227 1.0 amp
10kVA 327 227 1.0 amp 14kVA 327 227 1.0 amp 18kVA 327 227 1.0 amp 22kVA 327 227 1.0 amp
28
1600EP Series Instruction Manual
Page 29
Online Mode
AC Input Mode (Run operation)
The following illustration shows circuit power fl ow when the UPS is operating normally in the AC input mode. The UPS rectifi er, including a boost chopper circuit, converts AC input power to DC power. The boost chopper circuit maintains a constant voltage, with current limiting, for charging the batteries. It also supplies a DC voltage of the proper level to the inverter section. The inverter section generates a high quality sine wave output voltage. The unit’s batteries are always maintained in a constantly charged state when the UPS is in the run operation mode.
Input power
MCCB
Surge absorber
Bypass
Input
Line Filter
POWER FLOW IN AC INPUT MODE FOR ALL MODELS
fuse
Batteries
Power Flow in AC input mode for all models
Rectifier/
Chopper
+
_
*Static
switch
Inverter
*Switches are solid state devices
Output fuse
Line Filter
Isolation Transformer
Power flow
Output power
Static- Bypass Mode (Stop operation)
If the UPS unit is severely overloaded or develops an internal fault, power fl ow is automatically switched from the unit’s main circuit to the bypass circuit. Power fl ow through the bypass is shown in the following illustration. This change-over occurs automatically in less than 4 milliseconds in phase. The switching period is not long enough to cause interruptions to occur in most loads. If the power fl ow is transferred to the bypass circuit because of an overload and that overload condition ends within a specifi ed period of time then the power fl ow will be transferred back to the AC input mode (run operation) automatically. If the power fl ow is transferred to the bypass circuit due to an external fault the UPS will shut down power through the bypass to the load and indicate a system fault message. If the power fl ow is transferred to the bypass circuit due to an internal fault the UPS will continue to supply power to the load through the bypass and indicate a system fault message (see system fault message DC-OC on page 48). If the power ow is transferred to the bypass circuit due to an overload condition (see system warning message OL: REDUCE LOAD on page 44 and AUT O RETRANSFER on page 46), then the power fl ow will automatically transfer from the UPS’s bypass circuit back to the inverter circuit after removing the overload if set to do so (see auto-transfer setting on page 40).
Input power
MCCB
Surge
absorber
Line Filter
Input fuse
Bypass
Batteries
Rectifier/ Chopper
+
_
*Static switch
Inverter
*Switches are solid state devices
Output fuse
Line Filter
Isolation Transformer
Power flow
Output power
1600EP Series Instruction Manual
POWER FLOW IN BYPASS MODE FOR ALL MODELS
29
Page 30
Battery Backup Mode (on batteries)
The following illustration shows power fl ow during the battery backup mode. When commercial AC power failures occur, the UPS’ s batteries instantly begin supplying DC voltage to the UPS’s main inverter circuit. This circuit changes (inverts) the DC power into AC power. The AC power is available at the unit’ s output. This back-up process will continue until the UPS’s battery voltage drops below a specifi c minimum level. When this occurs, the batteries will stop supplying power to the load. This minimum level is the rated minimum voltage (Vmin). The rated battery voltage chart on page 28 shows (Vmin). The battery backup time and discharge process is explained on page 28.
Input power
MCCB
Surge absorber
Bypass
Input
Line Filter
Power flow in battery backup mode for all models
POWER FLOW IN BATTERY BACKUP FOR ALL MODELS
fuse
Batteries
Rectifier/ Chopper
+
_
*Static switch
Inverter
*Switches are solid state devices
Output fuse
Line Filter
Isolation Transformer
Power flow
Output power
EPO (Emergency Power Off) Function These units are equipped with terminals for receiving an emergency power-off (EPO) “closed contact”
switch command from a remote location (see ‘terminal block details’ on page 16 and terminal block location on page 53-54). This safety feature enables quick shut-down of the UPS’s AC output and battery circuits. Usually the emergency power off switch is installed in a central location that is easily accessible to personnel concerned with the operation of the UPS unit and the load equipment connected to it. The EPO function is initiated by pressing the switch to the closed “shutdown” position. The effect of using the EPO switch is the same whether the UPS unit is in the
MCCB
Input power
30
Surge absorber
Line Filter
Input fuse
Bypass
Batteries
Rectifier/ Chopper
+
_
*Static switch
Inverter
*Switches are solid state devices
Output fuse
Isolation Transformer
Line Filter
Power flow
Output power (off)
1600EP Series Instruction Manual
Page 31
Audible Alarm Functions
Audible alarms will sound when the UPS is in the battery backup mode, has a fault, has low battery voltage, or is in an overload condition. The following chart shows the audible alarm pattern durations for each condition. Time units are shown in seconds.
The audible alarm can be silenced by pressing + key on the front panel (see page 32).
Shift
Select
AUDIBLE ALARMS
Condition Audible Pattern
Run
UPS in battery Backup mode
UPS low Battery voltage
Overload
Fault
9S
1S
1S 1S
0.5S 0.5S
1S
1S
1600EP Series Instruction Manual
31
Page 32
Display and Keys
Front Panel Layout
The front panel consists of several elements for monitor and operation of the UPS. Panel components are shown in the illustration below:
LIQUID CRYSTAL DISPLAY SCREEN
Reset
OPERATING KEYS
LIGHT EMITTING DIODES
Shift
Select
Cancel
Set
Monitor
Run
Stop
Liquid Crystal Display (LCD) Functions
The LCD screen is a 2-line by 16-character wide liquid crystal display. The LCD displays information about the operation of the UPS. It should be used in conjunction with the LED display (see page 33, 44-45) and the audible alarms (see page 31) for total system monitoring. The LCD screen displays information which may be shown only on specifi c lines of the display. This information is determined by the UPS operating mode and conditions. These messages are shown in the LED displays and LCD screens on pages 33 through 46.
32
1600EP Series Instruction Manual
Page 33
Operating Keys
Refer to this illustration for all UPS front panel operating procedures.
Key Functional Description
Shift
Select
Press and hold this key while pressing one of the other keys to execute the function marked above the upper line of the key. Pressing this key alone enters the mode set on the internal data setting LCD screen (see page 38).
Reset
Scrolls the display upward or with shift key resets the display.
Cancel
Scrolls the display downward or with shift key cancels the preceding operation.
Set
Monitor
Run
Stop
Press and hold this key to view the Data Display Screens (see page 36). Continue to press this key to access the Data Setting Screens (see page 38).
Runs the UPS or with shift key silences the trouble indicator audio alarm.
Stops the UPS and switches to bypass mode.
Light Emitting Diodes (LED)
The following table describes the various LED behaviors and the system indications they provide.
LED Behavior Signifi cance/Meaning
Lights in green (Run) Normal UPS (inverter) in operation Flashes in green UPS output off Lights in red UPS failure (no output) LED “OFF” (Stop) Bypass operation on (inverter off)
Lights in green (Run) Normal UPS input AC voltage Flashes in green UPS input AC overvoltage LED “OFF” (Stop) UPS input AC undervoltage (power failure)
Lights in amber Warning Flashes in amber Warning LED “OFF” (Stop) Normal UPS (Inverter) in operation
Lights in green Schedule/timer setting Flashes in green LED “OFF” No schedule/timer setting
1600EP Series Instruction Manual
Execution notice of reserved operation (5 mins. in advance)
33
Page 34
Display Screens
Screen Arrangement
The display screens are organized into three groups that can be cyclically selectable by pressing the
“SELECT” key. The groups are:
SCREEN ARRANGEMENT GROUPS
1 System Overview Screens Provides operational status summary 2 Data Display Screens Provides detailed UPS data monitoring 3 Data Settings Screens Provides system con guration
System Overview Screens
The System Overview Screens provide a summary of the current operational state of the UPS. Only one of the several possible overview screens is available at any moment. The current screen is automatically determined based upon the UPS state.
UPS Start-Up Screens Sequence
The Start-Up Screens consist of a series of automatically sequencing ‘System Overview Screens’. These screens notify operator of steps taken by UPS during its initialization. The sequence of Start-Up screens begins when AC input power is detected at UPS input.
If the correct AC input power is available and no abnormal operating conditions are present then the following system message will be displayed on the LCD screen.
TOSHIBA 1600 UPS
INITIALIZING...
Next, the LCD will report the current date and time. If necessary , the proper date and time can be set from the ‘Data Settings Screens’ (see pages 38 and 41 for details). The date and time appear using the format depicted in the following example:
11/04/2001(WED)
15.:22:47
Next, the LCD will report the current UPS Operational Mode and the current percentage of the maximum UPS capacity being supplied. Initially, the UPS is in bypass mode, and the following screen will appear:
BYPASS OPERATION
LOAD###%
NOTE: If input voltage is removed while UPS is in the
Bypass Mode then the output stops.
34
1600EP Series Instruction Manual
Page 35
Only if the UPS is instructed to enter its online (normal) mode, will the UPS attempt transfer into such operation mode. To enter the normal mode, the “RUN” key is pressed or the “AUTO RUN” has been confi gured to “YES” (AUTO RUN setup is described in the ‘Data Screen Settings’
actions on pages 38
- 43. If either condition exists, the following screen will appear:
UPS OPERATION
LOAD###%
Shortly after transfer into the UPS online (normal) mode, the UPS will automatically begin a battery test if the setting is enabled (see page 40). This test ensures a healthy battery system is available should it be necessary to support the load. During the test, the LCD reports the current battery voltage as a percent of its expected value at full charge. This fi gure will drop throughout the test, as the battery voltage is intentionally lowered to test performance. The test lasts for about 10 seconds, during which the following screen appears:
BATTERY TEST
BAT VOLTAGE ##%
Once the battery test has concluded, the LCD will return to display of the current UPS operation mode and percent load. It should appear as follows:
UPS OPERATION
LOAD ###%
1600EP Series Instruction Manual
35
Page 36
Data Display Screens
The ‘Data Display Screens’ sequentially display the data parameters that can be monitored by operator. To enter the series of Data Display Screens, press “UP” or “DOWN” arrows while the current System Overview Screen is appearing.
NOTES
INPUT VOLTAGE
INPUT FREQUENCY
###V
##.#Hz
1 If the “SET/MONITOR” key is pressed from any of the Data Display
Screens then the display will advance to the Data Setting Screens. (see
page 36 the Data Settings Screens.
2 Displays L-N output voltages. 3 Displays the current as a % of maximum load capacity. 4 Displays the battery charge voltage as a % of the rated nominal DC
voltage of the batteries. 5 If the “SHIFT/SELECT” key is pressed from any one of the Timer Start
Data, Timer Stop Data, W eekly Schedule, Special Operate, and Special
Off time screens then special ‘Data Display Screens’ are viewed. These
functions can only to be changed by serial communication interface (see
page 37).
OUTPUT VOLTAGE
OUTPUT FREQUENCY
OUTPUT CURRENT
BATTERY VOLTAGE
BATT INSTALL D ATE
BATTERY LIFE REMAIN 3.5YR
INTERNAL TEMP
###V
##.#Hz
##%
##%
11/04/1998
## C
11/4/1998
10:45
36
TIMER START DATA
TO VIEW:SELECT
TIMER STOP DATA
TO VIEW: SELEC T
CAL OPER MODE
DISABLE
WEEKLY S CHDULE
TO VIEW: SELEC T
SPECIAL OPERATE
TO VIEW: SELEC T
SPECIAL OPERATE
TO VIEW: SELEC T
1600EP Series Instruction Manual
Page 37
Special Display Screens
The special ‘Data Display Screens’ show below depict settings that can be viewed (but not changed locally) on the LCD panel. These settings can only be changed through the RS232C or optional RemotEye network card.
Continued from Timer Start Data Screen page 36
Continued from Timer Stop Data Screen page 36
Continued from Weekly Schedule Data Screen page 36
Continued from Special Operate Data Screen page 36
Continued from Special Off Time Data Screen page 36
START TIME 1 DAY
##HR ##MIN ##SEC
STOP TIME 1 DAY
##HR ##MIN ##SEC
WEEKLY (MON)
(1) ###.## - ###.##
START 1:
###.## - ###.##
STOP 1:
###.## - ###.##
NOTES
1 To access the data setting screens pess the “SET/MONITOR” key from any of the (see page 38) Data
Settings Screens.
2 Pressing the “SHIFT/SELECT” and “CANCEL” key returns to the Data Display Screens.
1600EP Series Instruction Manual
37
Page 38
Data Setting Screens
The ‘Data Setting Screens’ sequentially display the data variables that can be set. Each variable is displayed as the “DOWN” arrow key is pressed. The “UP” arrow can also be pressed at any time to back up to the previous screen:
KEYS LOC K : D IS
TO CHANGE:SELECT
## / ## / ###(##)
TO CHANGE: SELECT
NOTES
1 When the automatic battery test mode has been set to YES then the this
screen is displayed when scrolling through the ‘Data Setting Screens’.
TIME ##:##:##
TO CHANGE:SELECT
BUZZER VOLUME:
TO CHANGE:SELECT
LCD SLEEP: 3MIN
TO CHANGE:SELECT
AUTO RUN: NO
TO CHANGE:SELECT
AUTO RETRAN: YES
TO CHANGE:SELECT
REMOTE:BYPASS
TO CHANGE:SELECT
COMM MODE: RS23 2 TO CHANGE:SELECT
BAUD RATE: 1200
TO CHANGE:SELECT
38
INI BAT TST: YES
TO CHANGE:SELECT
AUTO BATT TST: NO TO CHANGE:SELECT
BATTERY TEST
DATA SET: SELECT
PERFORM BAT TEST
PUSH SELECT
VOLTAGE ADJ: +0
TO CHANGE:SELECT
CLEAR TIMER SET
DEFAULT SETTINGS
PUSH: SELECT
1600EP Series Instruction Manual
Page 39
Data Setting Screens (Cont’d)
The following screens show the procedure for setting the data variables. They are accessed from the main ‘Data Setting Screens’ (see page 38) when the “SHIFT/SELECT” key is pressed:
The Keylock function allows the operator to disable the RUN + STOP button functions. When this function is set to EN the unit will remain in the operating mode it was in when enabled and will not be able to be changed with the RUN + STOP buttons until this function is disabled. With this function set to DIS, the RUN + STOP buttons function normally . The default setting is DIS.
2 = High 1 = Low 0 = Off Default setting is 2 = High (loudest)
Displays the number of minutes (3 or 30) of idle time before the LCD will go blank (this is to prolong LCD life). The LCD will be active again once a display button is pressed. Default setting is 3 min.
If set to YES, the unit will automatically start up in the UPS mode (on line) when input voltage is applied, regardless of what mode it was in when shut down. Default setting is NO.
DEFAULT SETTINGS
PUSH: SELECT
DEFAULT SETTINGS
Settings Screen page
Cont’d from Key Lock Data
Settings Screen page
Cont’d from Buzzer Data
page
Cont’d from LCD Display
Time Data Settings Screen
PUSH: SELECT
Loops through both
possibilities
BUZZER VOLUME: 2
TO ACCEPT: SET
BUZZER VOLUME: 0
TO ACCEPT: SET
BUZZER VOLUME: 1
TO ACCEPT: SET
Loops through three
possibilities
LCD SLEEP: 3MIN
TO ACCEPT: SET
LCD SLEEP:30MIN
TO ACCEPT:SET
Loops through both
possibilities
AUTO RUN: YES TO ACCEPT:SET
Shift
Select
Shift
Select
Select
Shift
Select
Shift
Select
Select
Select
Shift
Select
Shift
Shift
Shift
Set
+
Monitor
Set
Monitor
Monitor
Monitor
Monitor
+
Monitor
+
Monitor
Set
Monitor
Set
Set
Set
Set
Set
+
+
+
+
+
KEY LOC K: D IS
TO CHANGE: SELECT
KEY LCOK:EN
TO CHANGE:SELECT
Returns to Data Setting
Screens (with new value
applied)
BUZZER VOLUME:2
TO CHANGE: SELECT
BUZZER VOLUME: 0
TO CHAGNE:SELECT
BUZZER VOLUME: 1
TO CHANGE: SELECT
Returns to Data Set tin gs Screens (with new value applied)
LCD SLEEP: 3MIN
TO CHANGE: SELECT
LCD SLEEP:30MIN
TO CHANGE:SELECT
Returns to Data Set tin g
Screens (with new value
applied)
AUTO RUN: YES
TO CHANGE: SELECT
1600EP Series Instruction Manual
AUTO RUN: NO
Settings Screen page
Cont’d from Auto Run Data
TO ACCEPT:SET
Loops through both
possibilities
Shift
Select
Set
+
Monitor
AUTO RUN: NO
TO CHANGE:SELECT
Returns to Data Set tin g
Screens (with new value
applied)
39
Page 40
Data Setting Screens (Cont’d)
The following screens show the setting procedure for setting the data variables. They are accessed from the main ‘Data Setting Screens’ (see page 38) when the “SHIFT/SELECT” key is pressed:
AUTO RETRAN: YES
AUTO RETRAN: NO
Screen page
Cont’d from Auto Re-
transfer Data Settings
Cont’d Remote Operation
Data Settings Screen page
TO ACCEPT:S ET
TO ACCEPT:S ET
Loop s through both
possibilities
REMOTE:BYPASS
TO ACCEPT:S ET
REMOTE:SYSDWN
TO ACCEPT:S ET
Loops through both
possibilities
Shift
Select
Shift
Select
Shift
Select
Shift
Select
Set
+
Monitor
Set
+
Monitor
Set
+
Monitor
Set
+
Monitor
AUTO RETRAN: YES
TO CHANGE: SELECT
AUTO RETRAN: NO
TO CHANGE:SELECT
Returns to Data Setting
Screens (with new
value ap pli ed )
REMOTE:BYPASS
TO CHANGE: SELECT
REMOTE:SYSDWN
TO CHANGE:SELECT
Returns to Data Setting
Screens (with new
value ap pli ed )
Set to “Yes”, t h e un it w ill automatic ally retransfer back to UPS mode after transferring momentarily to bypass mode to prevent a sag in the outp ut du e to an instantaneous load change. If set to “No”, the unit will attempt to ride out the load chan g e and the output vol t ag e could be d ecr eased mom en tarily.
Default s etti ng is YES.
This setting uses the remote switch to pla ce the unit to bypass mode.
This setting uses the remote switch to shut the out pu t of th e unit off . While off , the onlin e LED wi ll b e fl ash ing and the LCD will dis play the message:
OUTPUT SHUTDOWN
The remote switch connection is on the rear term in al block at pos it i ons 11 and
12. The unit will transfer 2 secs. after closing the remote switch and will return to UPS mode 2 secs. after the switch opens. Default setting is BYPASS
REMOTE OFF
COMM MODE: RS232
TO ACCEPT:S ET
COMM MOD E: SNMP
TO ACCEPT:S ET
Data Settings Screen page
Cont’d from Comm Mode
Data Settings Screen
Cont’d from Int Batt Tst
40
Loops through both
possibilities
INI BATT TST: YES
TO ACCEPT:S ET
page
INI BATT TST: NO
TO ACCEPT:S ET
Loops through both
possibilities
Shift
Select
Shift
Select
Shift
Select
Shift
Select
Set
+
Monitor
Set
+
Monitor
Set
+
Monitor
Set
+
Monitor
COMM MODE: RS232
TO CHANGE: SELECT
COMM MOD E: SN MP TO CHANGE:SELECT
Returns to Data Setting
Screens ( wit h n ew val u e
applied)
INI BATT TST: YES
TO CHANGE: SELECT
INI BATT TST: N O
TO CHANGE:SELECT
Returns to Data Setting
Screens ( wit h n ew val u e
applied)
This setting selects the RS232 as the communication p or t, S NM P is disabled.
This setting selects the SNMP as the communication port, RS232 is disabled.
Default setting is SNMP.
Set to “YES”, the unit will perform a battery tes t the first time the unit transfers to On Line. If Auto Run (see page 33) is set to YES then the battery test will be done at power up.
Default setting is NO.
1600EP Series Instruction Manual
Page 41
Data Setting Screens (Cont’d)
The following screens show the setting procedure for setting the data variables. They are accessed from the main ‘Data Setting Screens’ (see page 38) when the “SHIFT/SELECT” key is pressed:
10/12/2006 (MON)
FOR NEXT:SELECT
11/12/2006 (MON)
FOR NEXT:SELECT
Cont’d from Day and
Data Settings Screen page
Settings Screen page
Cont’d from Time Data
12/12/2006 (MON)
FOR NEXT:SELECT
Loops through all
months of the year
TIME 10:13:58
FOR NEXT:SELECT
TIME 11:13:58
FOR NEXT:SELECT
TIME 12:13:58
FOR NEXT:SELECT
Loops through all h ours
of the day
Shift
Select
Shift
Select
Shift
Select
Shift
Select
Shift
Select
Shift
Select
Set
+
Monitor
Set
+
Monitor
Set
+
Monitor
+
Monitor
+
Monitor
+
Monitor
Press the SHIFT/ SELECT key until the field you want to edit is flashing.
Press the UP and DOWN arrow keys until the desired value appears in the flashing field.
Save the new value by pressing the key combination SHIFT/SELECT + SET/MONITOR.
At any time all of the preceding operations can be canceled by pressing SHIFT + CANCEL. Canceling returns to the 'Data Setting Screens' menu.
Set
Set
Set
Press the SHIFT/ SELECT key until the field you want to edit is flashing.
Press the UP and DOWN arrow keys until the desired value appears in the flashing field.
Save the new value by pressing the key combination SHIFT/SELECT + SET/MONITOR.
At any time all of the preceding operations can be canceled by pressing SHIFT + CANCEL. Canceling returns to the 'Data Setting Screens' menu.
12/12/2006 (FRI)
TO CHANGE:SELECT
Returns to Time Data Setting Screen (with new values applied)
TIME 12:13:58
TO CHANGE:SELECT
Returns to Time Data Setting Screen (with new values applied)
1600EP Series Instruction Manual
41
Page 42
Data Setting Screens (Cont’d)
The following screens show the setting procedure for setting the data variables. They are accessed from the main ‘Data Setting Screens’ (see page 38) when the “SHIFT/SELECT” key is pressed:
BAUD RATE:1200
TO ACCEPT: SET
BAUD RATE:2400
TO ACCEPT: SET
Settings Screen page
Cont’d from Baud Rate Data
Cont’d from Auto Batt Test Data
BAUD RATE:4800
TO ACCEPT: SET
BAUD RATE:9600
TO ACCEPT: SET
Loops through four
possibilities
AUTO BAT TEST:NO
TO ACCEPT:SET
AUTO BAT TEST:YES
TO ACCEPT:SET
Settings Screen page
Loops through both
possibilities
Shift
Select
Shift
Select
Shift
Select
Shift
Select
Select
Shift
Select
Shift
Set
+
Monitor
Set
+
Monitor
Set
+
Monitor
Set
+
Monitor
Set
+
Monitor
Set
+
Monitor
BAUD RATE:1200
TO CHANGE: SELECT
BAUD RATE:2400
TO CHAGNE:SELECT
BAUD RATE:4800
TO CHANGE: SELECT
BAUD RATE:9600
TO CHANGE: SELECT
Returns to Data Settings Screens (with new value applied)
AUTO BAT TEST:NO
TO CHANGE: SELECT
AUTO BAT TEST:YES
TO CHANGE: SELECT
This parameter allows the correct communication baud rate to be set.
Default is 9600
If set to YES, the unit will perform a periodic battery test at the interval set in the interval parameter on page 36.
Default is NO
INTERVAL: 1DAY
TO ACCEPT: SET
INTERVAL: 2DAY
TO ACCEPT: SET
INTERVAL: 99DAY
Data Settings Screen page
Cont’d from Bat. Test Interval
42
TO ACCEPT: SET
Loops through 99
possibilities
Shift
Select
Shift
Select
Shift
Select
Set
+
Monitor
Set
+
Monitor
Set
+
Monitor
INTERVAL: 1DAY
TO CHANGE: SELECT
INTERVAL: 2DAY
TO CHAGNE:SELECT
INTERVAL: 99DAY
TO CHANGE: SELECT
Returns to Data Settings Screens (with new value applied)
Selects the interval (in days), at whic h the battery test will run (1 day through 99 days).
1600EP Series Instruction Manual
Page 43
Data Setting Screens (Cont’d)
The following screens show the setting procedure for setting the data variables. They are accessed from the main ‘Data Setting Screens’ (see page 38) when the SHIFT/SELECT key is pressed:
This parameter has no options to set. A battery test will be performed once the SHIFT + SET button is pressed.
If the BAT TEST INHIBIT message is displayed, it indicated that a battery test has been performed recently. The UPS will not allow frequent battery tests to insure that the batteries remain in a fully charged state.
Cont’d from Bat. Test Interval
Data Setting Screen page
TO BEGIN:SET
OR
BATTERY TEST
INHIBIT
Shift
Select
Set
+
Monitor
BATTERY TEST
Executes battery test and returns to Data Settings Screens
###%
VOLTAGE ADJ: +5
TO ACCEPT: SET
VOLTAGE ADJ: +0
TO ACCEPT: SET
Cont’d from Voltage Adj
Data Settings Screen page
Cont’d from Clear Timer
Data Setting Screen page
VOLTAGE ADJ: -5
TO ACCEPT: SET
Loops through three
possibilities
CLEAR TIMER SET
TO ACCEPT: SET
Shift
Select
Shift
Select
Shift
Select
Shift
Select
Set
+
Monitor
Set
+
Monitor
Set
+
Monitor
Set
+
Monitor
VOLTAGE ADJ: +5
TO CHANGE: SELECT
VOLTAGE ADJ: +0
TO CHAGNE:SELECT
VOLTAGE ADJ: -5
TO CHANGE: SELECT
Returns to Data Settings Screens (with new value applied)
CLEAR TIMER SET
TO CHANGE:SELECT
Executes battery test and returns to Data Settings Screens
This parameter allows the user to offset the output voltage (while the unit is running on-line), by 1% increments between -5% to +5%.
Default value is +0
This parameter has no options to set. Pressing the SHIFT + SET button while this message is displayed will cancel timer setting.
DEFAULT SETTINGS
Cont’d from Default Settings
Data Setting Screen page
TO ACCEPT: SET
1600EP Series Instruction Manual
Shift
Select
Set
+
Monitor
DEFAULT SETTINGS
TO CHANGE:SELECT
Executes battery test and returns to Data Settings Screens
43
Page 44
System Warning Messages
Warning messages will be displayed when an abnormal operating condition occurs. The following chart shows possible messages and their meaning.
LCD Message LED Message Meaning/Action
Meaning: The UPS is overloaded (110% or above). Unit will switch to bypass operation or shut down if no action is taken.
Action: Shut down excess equipment to reduce load
Meaning: The UPS is overloaded (110% or above) and has switched to bypass. Unit will shut down the output if no action is taken.
Action: Shut down excess equipment to reduce load
Meaning: The battery level has dropped low (about 90% or less) during operation. Continued operation in this mode will deplete battery and cause output shut down.
Action: Immediately shut down the load equipment in an orderly fashion and then press the STOP key.
Meaning: The unit is overheated (warning is given when the internal temperature reaches and exceeds 50° C rise @ 40° C ambient).
Action: Check to see if the ambient temperature is abnormally high (40° C or more). If so, turn on air conditioning. Also, check ventilation fan at the back of the unit for operation or obstructions. Otherwise, shut down the unit and call for service.
Meaning: Advance notice that batteries are nearing the end of the expected lifetime.
Action: Contact your Toshiba authorized service center to arrange for battery replacement.
OVERLOAD: 132%
OL: REDUCE LOAD
BATTERY LOW 87%
UPS-TEMP 52°C
REPLACE BAT
SOON
Amber LED Flashes
Amber LED Flashes
Amber LED Flashes
Amber LED Flashes
Amber LED Flashes
REPLACE BATTS
REQUIRES SERVICE
PLEASE SERVICE
44
Amber LED Flashes
Amber LED Flashes
Meaning: Batteries at end of life. Action: Have batteries replaced immediately.
Meaning: Inspection of unit is advised. Action: Have inspection/service performed.
1600EP Series Instruction Manual
Page 45
System Fault Messages
When an abnormal operating condition occurs the following fault message will be displayed
FAULT (BYP OPER) OUT-OV DC-OV >
If the input voltage is normal when the fault occurs then the UPS will switch immediately to the bypass mode to continuously feed power to the load. If the input power is abnormal while in the bypass mode the UPS will shut down the output to prevent load equipment damage.
Press CANCEL or RESET keys to view the messages explaining the system fault (the “>” indicates
other faults:
LCD Message LED Message Meaning/Action
Meaning: DC overcurrent condition occurred. Action: UPS is probably faulty. Check the
UPS operating conditions at time of fault. Not advisable to try restarting. Call for service.
Meaning: Output overvoltage condition occurred.
Action: UPS is probably faulty. Check the UPS operating conditions at time of fault. Not advisable to try restarting. Call for service.
Meaning: Output undervoltage condition occurred.
Action: UPS is probably faulty. Check the UPS operating conditions at time of fault. Not advisable to try restarting. Call for service.
Meaning: DC overvoltage condition occurred. Action: UPS is possible faulty, input wiring
error, input overvoltage or connection of a motor load. Try restarting. If condition persists call for service.
DC-OC
OUT-OV
OUT-UV
DC-OV
Red LED Flashes
Red LED Flashes
Red LED Flashes
Red LED Flashes
1600EP Series Instruction Manual
OVERLOAD
DC-UNBALANCE
OVERHEAT
Red LED Flashes
Red LED Flashes
Red LED Flashes
Meaning: Output overload condition occurred. Action: Reduce equipment load to 100% or
less and try restarting.
Meaning: DC voltage unbalance occurred. Action: Possible causes are UPS fault or
connection of half-wave rectifi er load. Check load and try restarting. If condition persists, call for service.
Meaning: Overheating condition occurred. Action: Check unit for blocked or in-operable
fan.Lower ambient temperature if 40° C or greater.Bypass operation will also cease if overheat condition is not corrected within 1 hr. from inverter shutdown. Try restarting and if condition re-occurs plan for total shutdown and call for service.
45
Page 46
Status Change Indications
Warning messages will be displayed when an abnormal operating condition occurs. The following chart shows possible messages.
LCD Message Meaning/Action
Meaning: The UPS has automatically entered the bypass mode because it detected an
AUTO RETRANSFER
AUTO RETRANSFER
BATTERY LOW
TIME TO RUN 4 MIN
TIME TO STOP 10 SEC
KEY LOCK:EN
output current that is larger than the inverter can normally handle.
Action: Remove excess load equipment to reduce the output current.
Meaning: The UPS input frequency is outside of the ± 1 Hz synchronization frequency tolerance of the inverter output frequency.
Action: No action is necessary. Unit cannot switch to bypass mode while the input frequency is out of tolerance with the output frequency.
Meaning: The battery level has dropped low (about 90% or less) during operation. Continued operation in this mode will deplete battery and cause output shut down.
Action: Immediately shutdown the load equipment in an orderly fashion and then press the STOP key.
Meaning: A start notice is displayed 5 minutes before starting the UPS when the start timer is set by communication., and continues to display remaining time during countdown.
Action: None required Meaning: A stop notice is displayed 5 minutes
before stopping the UPS when the stop timer is set by communication.
Action: None required. Meaning: When the key lock is set or the
timer is set to start/stop the UPS by data communication, pressing the RUN or STOP key displays this message.
Action: None required.
46
1600EP Series Instruction Manual
Page 47
UPS Protection System
System Protection Features
The following schematic shows the electrical locations of the protection devices on the 1600EP models.
Input power
MCCB
Surge absorber
Input Abnormal
Line Filter
Input fuse
Batteries
Low Batt ery Level
Bypass
Rectifier/ Chopper
+
_
Overheating
*Static
switch
*Switches are solid state devices
Overcurrent
Inverter
Current Limit Overload
Isolation Transformer
Output fuse
Line Filter
Overvoltage/ Undervoltage
System Protection Functions
The following charts show the built-in UPS system fault protection functions on all the 1600EP models.
Output power
Power flow
BUILT-IN UPS FAULT PROTECTION FUNCTIONS
Protection Item Output Overvoltage Output Undervoltage Output Overload
LCD Message OUT-OV OUT-UV OVERLOAD
Cause Operation Mode
After Fault
Control malfunction;
chip error
Bypass operation;
Chopper and inverter are stopped.
Audible Alarm Yes; continuous buzzer
Visible Alarm Red Fault LED “ON”
Relay Contact Alarm
Fault relay closed;
Bypass relay closed
Auto-retransfer No
1600EP Series Instruction Manual
Control malfunction;
wire disconnected
Overload; Short circuit at load
Inverter OL: Transfer to bypass;
Bypass OL: inverter, chopper
see ‘Audible Alarm Functions’ on
page 31
Inverter OL: no fault lamp
Bypass OL: fault lamp “on”
Fault relay open;
Inverter OL: Bypass relay closed
Bypass OL: Bypass relay open
Inverter OL: Yes if bypass is OK
Bypass OL: No
47
Page 48
BUILT-IN UPS FAULT PROTECTION FUNCTIONS (CONT’D)
Protection Item Internal Overheat DC Circuit Overvoltage DC Circuit Overcurrent
DC-OC DC-OV
LCD Message
DC UNBALANCE
Cause
Operation Mode After Fault
High ambient temperature
Fan failure;
Shutdown; no output
Chopper malfunction Inverter/chopper fault
Bypass operation;
Chopper and inverter are stopped
Inverter OL: Transfer to bypass; Audible Alarm Yes; continuous buzzer Yes; continuous buzzer Visible Alarm Red Fault LED “on” Red Fault LED “on” Relay Contact
Alarm
Fault relay closed; Bypass relay closed
Auto-retransfer No
48
1600EP Series Instruction Manual
Page 49
Preventive Maintenance/Parts Replacement
Preventive Maintenance
Toshiba’s 1600EP Series of uninterruptible power systems have been designed to provide years of trouble-free operation requiring a minimum of preventive maintenance.
The best preventive measure that the UPS user can take is to keep the area around the unit, particularly the air inlet vents, clean and free of moisture and dust accumulations. If the atmosphere of the installation site is very dusty, use a vacuum cleaner to periodically remove dust accumulations around and from the unit.
CAUTION
Only a qualifi ed Toshiba Representative should be allowed to perform any routine maintenance or service on this equipment other than those preventive maintenance details which are described directly above this caution.
Parts Replacement
The following list shows recommended intervals for periodic replacement of certain UPS parts:
1 Batteries: In order to maintain system reliability, the UPS batteries should be replaced on a
regular schedule. To ensure reliable operation, all of the batteries should be replaced at the same time. Use the following chart for replacement:
UPS BATTERY REPLACEMENT
BATT AMB TEMP AVERAGE LIFETIME (% REDUCED)
20-25° C (68-77°F) Approximately 5 yrs 0%
30° C (86°F) Approximately 3.5 yrs 30%
35° C (95°F) Approximately 2.5 yrs 50% 40° C (104°F) Approximately 1.8 yrs 66% 45° C (113°F) Approximately 1.25 yrs 75%
2 Aluminum electrolytic capacitors: Replace once every 5 years. 3 Fuses: Replace once every 7 years.
4 Cooling fan: When operated in an ambient temperature of 30° C (86°F) to 40° C (104°F),
replace every 3.5 years. When operated in an ambient temperature of less than 30° C (86°F) , replace every 5 years.
1600EP Series Instruction Manual
49
Page 50
Optional Receptacle Panel Installation Instructions
These are the instructions for installing the optional Modular Output Receptacle Panels for the 1600EP Series UPS. These instructions apply to all UE3-RP-XX panel options.
WARNING: The work outlined in these instructions is to be performed only on a completely un-energized UPS system.
Please refer to Figure 1 for location of UPS referenced material. Refer to Figure 2 for material referring to the receptacle panel module.
Step 1: Remove modular receptacle panel cover plate On the rear of the UPS, locate the cover plate for the receptacle panel module interface
(see Figure 1). Remove the 6 mounting screws. Remove the cover plate. A square-shaped “plug” will appear exposed near the upper-left corner
of the uncovered slot. Step 2: Snap-In Output Receptacle modular panel Carefully mate the square-shaped connector on the UPS to its matching counter part on the rear of the
modular panel. Step 3: Mount the receptacle panel Attach the screws removed from the cover plate through the mounting holes of the receptacle panels and
back into the UPS mounting points.
Mounting
Screws
Figure 1
50
Figure 2
1600EP Series Instruction Manual
Page 51
External Layouts/Dimensions/ Shipping Weights
Dimensional Data
DIMENSIONAL DATA
3.6kVA 6kVA 8kVA 10kVA 14kVA 18kVA 22kVA
27.5 in
A
(699 mm)
B
C
D
E
10 in
(254 mm)
33 in
(838 mm)
24.7 in
(627 mm)
2.8 in
(72 mm)
Shipping Weights
27.5 in
(699 mm)
10 in
(254 mm)
33 in
(838 mm)
24.7 in
(627 mm)
2.8 in
(72 mm)
28.4 in
(699 mm)
13 in
(254 mm)
33.5 in
(838 mm)
25.7 in
(627 mm)
2.7 in
(72 mm)
SHIPPING WEIGHTS
Model Pounds Kilograms
3.6kVA 365 166 6kVA 385 175
8kVA 490 222
10kVA 490 222 14kVA 620 281 18kVA 750 340 22kVA 750 340
28.4 in
(699 mm)
13 in
(254 mm)
33.5 in
(838 mm)
25.7 in
(627 mm)
2.7 in
(72 mm)
39.1 in
(992 mm)
17.5 in
(445 mm)
34.8 in
(885 mm)
35.6 in
(904 mm)
3.47 in
(88 mm)
39.1 in
(992 mm)
17.5 in
(445 mm)
34.8 in
(885 mm)
35.6 in
(904 mm)
3.47 in
(88 mm)
39.1 in
(992 mm)
17.5 in
(445 mm)
34.8 in
(885 mm)
35.6 in
(904 mm)
3.47 in
(88 mm)
1600EP Series Instruction Manual
51
Page 52
External Layouts *
52
1600EP Series Instruction Manual
Page 53
External Layouts * (cont’d)
Display
Panel
SNMP
Port
Remote
Contacts
Remote
Contacts
SNMP
Port
Cooling
Fans
Terminal
Block Cover
MCCB
Front View Back View
14/18 kVA
Air
Flow
Side View
Back View
10 kVA
Air
1600EP Series Instruction Manual
53
Page 54
Index
Common-mode noise 12 Communication interface 17
, 20, 23
A
AC input mode 29, 30
Acoustical noise 21
Altitude 21, 24
Application 12
Audible alarm 12, 32, 47, 48
functions 31
Automatic Retransfer 21, 24
B
Backup mode 30 Battery
backup mode 30, 31 backup time 20, 22, 23, 26, 30 lifetime 21, 24
Cooling fan 49
D
Data. See Data Display Screens, Data Setting
Screens
Data Display Screens 33, 34–37 Data Setting Screens 33, 36, 38–43
DB9 Connector
female pinouts 19
male pinouts 17 Dimensional Data 51 Disposal 13
E
Emergency Power Off (EPO) function 15, 16,
30, 34
low-voltage tolerances 26
manufacturer 22, 25 pack 22, 25 Pack (quantity) 22, 25
recharge tolerances 28 recharging 28
replacement 10, 21, 24, 44, 49 voltage drop 12, 17, 30
Buzzer volume 21 Bypass
disable 21
mode 27, 29, 33, 34 overload capacity 20, 23 switch 21, 24
, 24
, 24
C
Enclosure 22, 25 Environment 13, 21, 24 Event Data Storage 21, 24
F
fan 22, 25, 44, 48
Fault 21
protedtion functions 47
signal 17, 29, 31
Frequency
AUTO/MAN 20, 23
input 20
output 20
synchronization 46
Warning 15, 46
Front Panel layout 32
, 24
, 48
, 23
, 23
capacitors 49
54
1600EP Series Instruction Manual
Page 55
G
battery warning light 44
ground
Importance of, 14 RS-232C 19 terminals 16
Grounding 14
H
Humidity 24 humidity 13
Operating environment 21
, 14
I
Input Capacity 20, 23 Input Frequency 20, 23
warning 15, 46
Input Mode, AC 29 Input Voltage 20
requirements 15
, 22, 23, 25
capacitors, Aluminum electrolytic 49 fan, cooling 49
fuses 49 Liquid Crystal Display (LCD) Functions 32 Low Voltage Tolerance 26
M
maximum ambient operating temperature 10 Mode
AC Input 29
Battery Backup 30
display 32, 33, 34
Static Bypass 29
test 38
monitoring. See Data Display Screens
N
Normal input power system 17
Inspection 13, 44
Installation Precautions 14 Interface
communications 17, 18, 19
receptacle panel module 50
RS232 ASCII 21, 24, 36 user 21, 24
Inverter Overload Capacity 20, 23
K
Keys 21, 24, 32, 33
L
LED (Light Emitting Diode)displays 32 Lifetime
battery 21
, 24, 49
O
Operation modes. See Modes
output disconnect 10 Overload Capacity 20 Overvoltage
DC 48
input 33
output 45, 47
, 23
P
Peak Output Current 20, 23
Power Backup 12 Power Conditioning 12 Power factor
input 20
, 23
1600EP Series Instruction Manual
55
Page 56
output, rated load 20, 23, 26
Storage 13
, 21, 24
Power failure signal 17
Precautions 14, 15
Preventive Maintenance 49 Protection System 47
, 18
R
Real Time Clock 21, 24
Receptacle Panels 50
Recharge Time 20, 23, 28
relay switch 17 remote contacts interface 17 Remote Switch 16 RemotEye Network Card 19 Restrictions on UPS use 15 RS-232C 19
S
temperature 13 synchronization frequency tolerance 46 System Fault Messages 45 System Warning Messages 44
, 21, 24
T
Terminal Block 16 Theory of operaton 12 torque, tightening 16
U
Unpacking 13 UPS
Discharge Process 26, 30
UPS Connections 16 UPS functional overview 12
UPS stop signal input 17, 18
Safety instructions 8, 10 Schedule Operation 21, 24
Shipping Weight 51 Shutdown voltage 26 Signal Function
RS-232C 17 Signal Words 9 Size
battery packs 22, 25
UPS dimensions 22, 25
wire 16 Specifi cations 20 Start-Up Screens 34 Starting the UPS 27 Status Change Indications 46 Stopping the UPS 27
, 46
V
ventilation 14, 15 Voltage Transient 20, 23 Volume, Buzzer. See Buzzer Volume
W
Warranty 3, 4, 13
Stop Signal Operation 18
56
1600EP Series Instruction Manual
Page 57
Page 58
).$5342)!,$)6)3)/.
7EST,ITTLE9ORK2OAD(OUSTON4EXAS 4EL&AX 53#ANADA-EXICO
Copyright 1/2007
WWWTOSHIBACOMIND
Printed in the U.S.A.
#OPYRIGHT
Loading...