A B C D E F G H I J
UPS Cabinet
1
Static Bypass
THY. SW.
2
1
2
Input
3
208,240V
50/60Hz,
80Amp
Input Breaker
CONV
INV
4
Transformer
5
6
Customer
supplied
wiring
7
8
9
-
Internal Battery Modules
+
Hardwire Configuration
16543287
L1 NX2X1GL2 GX3
240V
208V
120V120V
208/240 Vac
Input Cables from
Distribution Panel
#6 AWG wire
#6 AWG wire
CHOPPER
COM208
208V 240V
Jumper Selection
See Note 1,2
131211 17161514
240
REMOTEEPO2EPO1
Remote Run/Stop
Command
Customer
supplied
wiring
Output
208/240/120V
50/60Hz
3
4
5
6
7
8
9
10
NOTES
1. If AC input power is 240Vac rated, terminals 12 and 13 must be shorted by
jumper wire
2. If AC input power is 208Vac rated, terminals 11 and 12 must be shorted by
jumper wire (factory set)
DRAWN BY
JE 10/11/05
APPROVED
GM 10/11/05
DATE
DATE
TOSHIBA
INTERNATIONAL CORPORATION
Houston Texas, USA
THIS MATERIAL IS THE EXCLUSIVE PROPERTY OF
TOSHIBA INTERNATIONAL CORPORTION AND SHALL NOT
BE REPRODUCED, USED, OR DISCLOSED TO OTHERS
UNLESS PRIOR WRITTEN AUTHORIZATION IS OBTAINED.
TITLE
1600 EP Series
10 kVA Model 208/240V Input
208/240/120V Output
DRAWING NO. REV.
UE3G2L100C61T
10
1.0