Toro SA41 User Manual

ELECTRONIC AUSTRALIA
S
SA41 OWNERS MANUAL
Contents: Page
INTRODUCTION..............................................................................................................................2
WARRANTY CARD .........................................................................................................................2
INSTALLATION ...............................................................................................................................2
OPERATION......................................................................................................................................5
ENERGY MANAGEMENT..............................................................................................................5
STATUS .....................................................................................................................................5
READINGS ................................................................................................................................6
SETTINGS..................................................................................................................................8
CONTROLLER OUTPUTS .......................................................................................................8
ALARM INPUTS .....................................................................................................................12
CURRENT SHUNT SETTINGS..............................................................................................12
OVERLOAD SHUTDOWN AND ALARMS ................................................................................ 14
FAULT FINDING ............................................................................................................................15
SYSTEM MAINTENANCE............................................................................................................17
SA41 MAINTENANCE ...........................................................................................................17
BATTERY MAINTENANCE.................................................................................................. 17
SA41 ELECTRICAL SPECIFICATIONS ....................................................................................18
RADIO FREQUENCY INTERFERENCE....................................................................................19
HANDY HINT ..................................................................................................................................19
APPENDIX I: DIAGNOSTICS .....................................................................................................20
APPENDIX II: FLOW DIAGRAM FOR DISPLAYS AND SETTINGS..................................21
READINGS ..............................................................................................................................21
MINIMUM CHARGE DISPLAY ............................................................................................22
SETTINGS................................................................................................................................23
APPENDIX III: SA INVERTER OPTIONS ...............................................................................25
GENERAL .............................................................................................................................................25
SA-SB-01 INTERFACE KIT ................................................................................................................25
SA-KP-01 OPTIONAL KEYPAD INSTALLATION........................................................................... 27
SA-S200 OPTIONAL CURRENT SHUNT INSTALLATION ............................................................28
WARNING........................................................................................................................................ 29
PRODUCT WARRANTY CONDITIONS ....................................................................................29
MOUNTING TEMPLATE FOR SA-KP-01 KEYPAD................................................................30
Rev 5
1

INTRODUCTION

Thank you for purchasing the Selectronic Sine wave inverter, model SA41 with ENERGY MANAGEMENT.
Your SA41 is a state-of-the-art high performance TRUE SINE WAVE DC to AC Power Inverter incorporating ENERGY MANAGEMENT, a unique energy monitoring and controlling system developed by Selectronic to enable you to maximise your limited energy resource.
Thousands of hours of development time have been invested in the SA41 to provide you with a reliable, high quality product. The output from your SA41 is as good as, if not better than mains power and if looked after properly, the SA41 will give you many years of reliable service.

WARRANTY CARD

Before proceeding any further, it is extremely important that you complete your warranty card NOW. This will enable us to immediately register your initial 24 month warranty period, and also make you eligible for our free lifetime warranty extension. Six months after the purchase date of the SA41, Selectronic will send you a questionnaire. Simply complete and return the questionnaire to us and we will extend your warranty, free of charge, for a lifetime. By accurately completing your warranty card and questionnaire, you will provide us with valuable information that will assist us in keeping up with your alternative energy needs. Please take a few moments to fill in the warranty card. Your efforts will be greatly appreciated.

INSTALLATION

The installation of your inverter is extremely important. Failure to follow the recommended installation instructions may void your warranty. If in doubt, ask your supplier.
After unpacking the SA41, check for any damage which may have occurred during transit. If there are any signs of damage, contact your supplier immediately.
The inverter must be installed in a dry, cool, dust-free environment.
Please leave at least 300mm clearance at the left and right hand sides (Black heatsink fins), 300mm above the inverter and approx. 200mm at the rear as this will aid the natural cooling of the inverter. The air vents on the underside of the SA41 also need to be kept clear of obstructions.
300mm
300mm
SELECTRONIC SINE WAVE INVERTER
WITH ENERGY MANAGEMENT SA41
DC TO MAI NS POWER PROUDLY DESIGNE D & MADE IN AUSTRALIA
200mm
300mm
Front
2
y
b
SUPPLY INSTALLATION
N
N
A
To circuit breakers for other circuits
Earths
A
Power Circuits
E
System Fuse
Batter
ank
Inverter
Rear junction Box
RFI / Lightning Earth
As close as possible to inverter
MUST BE BONDED TO
ALL OTHER EARTHS
Active Earth Neutral
GND
GND Safety Earth
Ground connection to general mass of earth
E.L.C.B.
main switch
S1 S2
Neutral Link
ALL AC AND DC WIRING
MUST CONFORM TO
RELEVANT STANDARDS
Earth Le akage
Circuit Breaker
(E.L.C.B.)
We suggest that you house your inverter along with other power generating equipment in a remotely sited purpose built area. Also make sure that the exhaust from your generator or other sources of heat or fumes are kept well away from the SA41. SEIAA (Solar Energy Industries Association Of Australia) installation guidelines must be followed.
You must have a suitable 48V DC battery bank which is maintained and operated to the battery manufacturer’s recommendation. To ensure operation to SA41 specification, the battery bank should have a minimum capacity of 500 ampere hours, at the 100 hour discharge rate (ask your supplier if in doubt). Smaller capacity batteries can be used but may result in degraded performance of the SA41 under heavy surge conditions.

CONNECTION OF AC AND DC WIRING

IMPORTANT: Before making any wiring connections, check that the circuit breaker located on the front panel is in the OFF position, i.e. LEVER DOWN.
Your electrician should firstly connect the AC wiring via the three terminal rear junction box. Carefully observe the correct connections. Please refer to the rear panel view of the SA41 on the following page.
BROWN ACTIVE (red dot, top connector) GREEN/YELLOW EARTH (E, centre connector) BLUE NEUTRAL (Bottom connector)
The lid of the junction box has knockouts to allow conduit entry. Make sure the connections are tight and safe. Re-fit junction box cover.
NOTE:
ALL AC WIRING MUST BE CARRIED OUT BY A LICENSED ELECTRICIAN
AND MUST CONFORM TO AS 3000 WIRING REGULATIONS,
OR RELEVANT STANDARDS.
Verify that the circuit breaker on the front panel is in the OFF position, LEVER DOWN.
3
Now connect the battery cables:
RED = BATTERY POSITIVE (+) BLACK = BATTERY NEGATIVE (-)
These connections should be tight. If using nuts, bolts and washers, they should be stainless steel. At this point re-check the connections before proceeding any further.
NOTE:
IF THE SA41 EMITS A PULSING BUZZER SOUND, THE BATTERY LEADS HAVE BEEN CONNECTED IN REVERSE. IMMEDIATELY DISCONNECT THE LEADS AND RECONNECT WITH THE CORRECT POLARITY. DO NOT UNDER ANY CIRCUMSTANCES TURN ON THE BREAKER WHEN THE BUZZER IS PULSING AS PERMANENT DAMAGE TO THE SA41 WILL RESULT.
If all is well, turn the breaker ON, i.e. switch lever UP. If after two (2) attempts the circuit breaker does not turn on, then check that the battery voltage is between 40 and 68V DC. If the breaker still won't switch on, refer to the FAULT FINDING section of this manual.
4

OPERATION

To gain more understanding of these operational notes, it is suggested that they be read in conjunction with hands on access to an inverter with DC power applied.
When you first apply power to the SA41 with default factory settings, the SA41 should be in STANDBY mode. There may be a quiet pulsing sound and the red neons on the power point will flash if turned on. The SA41 is now ready for use with no further adjustments necessary, using the factory settings.
If the display shows TIME, the default settings have been changed, and the day and time will need to be set before the display will return to STATUS.

ENERGY MANAGEMENT

The SA41 incorporates ENERGY MANAGEMENT, which allows you to monitor and control your energy system by displaying information on the Liquid Crystal Display. Settings can be adjusted via the front panel keys.

STATUS

Status : STANDBY Inverter : OFF
The first screen will display the Status of the SA41. There are three status conditions: STANDBY, CONT (continuous) and RESET, which are explained in more detail below.
When this screen is displayed, the Status can be changed by pressing the UP or DOWN keys. Each time the UP key is pressed, the status will change from STANDBY to CONT then RESET and back to STANDBY whereas the DOWN key will change the Status in the reverse order.
The second line indicates whether the inverter is ON or OFF, i.e. if there is 240V available or not. During pulsing, OFF is displayed on the second line, reverting to ON when a load is connected and the inverter starts.
Status : CONT Inverter : ON
Status : RESET Inverter : OFF
The STANDBY mode means that the SA41 is producing pulses of power while waiting for an appliance to be switched on. This is frequently called the “demand start” because as soon as the appliance is operated, the SA41 will turn on and remain on until the appliance is switched off. After a 10 second delay, the SA41 will return to STANDBY mode, awaiting another load. This feature is extremely important as it conserves valuable battery power when no appliances are on.
CONT mode (continuous) means the inverter will be on at all times regardless of the load. This situation is useful if you have small loads such as VCRs or digital clocks that require 24 hour power, or if loads are too small to be sensed in the STANDBY mode. The only disadvantage is that when no appliances are operating, the SA41 will be drawing more power than it would in STANDBY mode.
RESET mode electronically shuts down the inverter. When placed in this mode, any overload or shutdown conditions are also reset.
5

READINGS

The SA41 ENERGY MANAGEMENT has six "Readings" displays to give you vital information about your inverter and your batteries. By pressing the 'NEXT DISPLAY' key on the front panel, the screen information rotates through displays of inverter Status, Time, AC Volts, AC Amps and Battery Volts. When the optional current shunt (SA-S200) is installed, four additional readings are available; these being Nett DC Current, Peak Charge Current, Nett Daily Amp Hours and Battery percentage Charge.
TIME
Mon : 15:06
- - - Readings - - -
AC VOLTS
AC Volts : 240V
- - - Readings - - -
AC AMPS
AC Amps : 2.5A
- - - Readings - - -
BATTERY VOLTS
Displays the Current Time (as a 24Hr clock) and day. This time is set as described in "Settings" (see Page 8).
This screen gives an approximate indication of the AC voltage produced by the inverter. The AC volts would normally read between 230V and 245V except under high load or low battery conditions.
The AC current reading shows the total current drawn from the AC output by the appliances connected to the inverter.
Batt Volts : 49.2V
- - - Readings - - -
Displays the DC Battery volts. This provides you with an indication of the condition of your battery bank.
WHERE THE OPTIONAL 200 AMP CURRENT SHUNT IS INSTALLED:
DC CURRENT
Amps : 23.6A OUT
- - - Battery - - -
PEAK AMPS
Pk Amps : 45.6 IN
- - - Battery - - -
This reading gives a Nett current; i.e., either charging the battery (IN) or being taken out of the battery (OUT). The range for this reading is 0-100A IN and 0-200A OUT continuous or 0-400A OUT intermittent.
This reading gives the peak Nett charging current into the batteries for the present day (today). If no load has been present for the entire day, this will indicate the peak combined charging current from your solar panels, wind generator or other charging sources, thus allowing you to monitor their operation. During the first day after the inverter is turned on at the circuit breaker, this screen will display a meaningless figure.
6
NETT AMP HOURS TODAY
Net AH : 69 IN
- - - Today - - -
BATTERY CHARGE
Charge : 87%
- - - In Battery - - -
This reading gives a nett figure of Amp Hours since midnight last night. A nett AH reading of IN indicates more Amp Hours have gone into the battery than have been used. The opposite applies for a Net AH reading of OUT. 1 Amp Hour = 1 amp for 1 hour, or 2 amps for ½ hour, etc.
This reading shows the amount of charge present in you battery bank at any given time. i.e. 100% means a fully charged battery.
MINIMUM CHARGE
With the optional current shunt (SA-S200) installed, the minimum charge in your batteries today, this week or for a number of weeks or days can be logged (Minimum daily discharge). Minimum charge readings are accessed by pressing the UP and DOWN keys together for 1 second. These vital readings give you the information you need to maximise your battery life. This is done by managing your loads to maximise this figure, e.g. using heavier loads later in the day or at other times when the battery charge is high.
MINIMUM CHARGE TODAY
MIN CHARGE : 76%
- - - In Batt Today - - -
MINIMUM CHARGE THIS WEEK
MIN CHARGE : 76%
- - - In Batt This Wk - - -
MINIMUM CHARGE WEEKLY LOG
Weeks ago : 1
Min Charge : 76%
The minimum charge in the battery since midnight last.
The minimum charge in the battery since midnight last Saturday.
This displays a log of the minimum weekly charge in the battery for up to 52 weeks. The logged weeks may be stepped through by pressing the UP or DOWN key. The weeks that have not logged AH as yet will display 255%.
MINIMUM CHARGE DAILY LOG
Days ago : 1
Min Charge : 76%
This displays a log of minimum daily charge in the battery for up to 30 days. The logged days may be stepped though by pressing the UP or DOWN key. The days that have not logged AH as yet will display 255%.
7

SETTINGS

There are a number of settings within the SA41 that can be changed via the front panel push keys (push buttons). These allow you to tailor the SA41 inverter and ENERGY MANAGEMENT sections to suit your system requirements.
Settings are accessed by holding down the NEXT DISPLAY key for at least 1 second whilst in any "Readings" display. The value of the parameter displayed can be modified by pressing the UP or DOWN keys.
Pressing the NEXT DISPLAY key will take you to the next parameter to be set. Pressing the NEXT DISPLAY key after the last parameter is displayed will take you back to the "Readings" displays.
Please note: If DC power is disconnected from the inverter, the "Settings" which have been entered will be saved and held in permanent memory. However these settings are not saved until the display is returned to "Readings".

CONTROLLER OUTPUTS

The SA41 ENERGY MANAGEMENT has 2 control outputs, as mentioned on page 25, each of which can be activated with time, inverter cutout and/or low ampere-hours. The six settings are displayed as OFF, ON, TIME, INV CO, LO A/H and CO+LAH respectively
For simplicity, the displays shown are for control output 1 only. Control output 2 settings are identical to control output 1. Pressing the UP or DOWN keys will change the setting.
On with : OFF
[Set Control 1]
On with : ON
[Set Control 1]
On with : TIME [Set Control 1]
The control 1 output will remain off at all times.
The control 1 output will remain on at all times.
The control 1 output will come on at the Start Day, Start Hour and Start Minute that is set in the three screens below. The Start Day can be set to ALL which will turn the output on every day at the set time. Pressing the UP or DOWN keys will change the setting. The output will remain on for the time set in "Duration". (see next page)
Start Day : SUN
[Set Control 1]
Start Hour : 16 [Set Control 1]
8
Start Min : 30
[Set Control 1]
On with : INV CO
[Set Control 1]
(Inverter Cut out) The control 1 output will turn on when the inverter shuts down due to overload, over temperature or low or high voltage. The output will remain on for the time set in "Duration", below. The output will not come on if the front panel circuit beaker is tripped.
On with : LO A/H
[Set Control 1]
On with : CO+LAH
[Set Control 1]
Note that the controller can only be set to LO A/H and CO+LAH if the optional external current shunt kit (SA-S200) is used. Each controller output is capable of switching an external relay or contactor which can be used to switch AC or DC loads.
If the controller is set to INV CO, LO A/H or CO+LAH and the condition still exists after the "Duration" time, the output will stay on until the condition ends. Also with these settings a "Lockout" option can be set ON or OFF. (See lockout below and on page 11)
(Low Amp-Hours) If the charge in the batteries falls below the level set in the "Minimum Charge" setting (see page 13), then the control output will come on, for the time set in "Duration", below.
(Cutout or Low Amp-Hours) This setting combines the previous two, bring the output on with low amp hours, or with the inverter cutting out. The output will stay on for the time set in "Duration", below.
LOCKOUT
Lockout: ON
[Set Control 1]
DURATION
Duration : 4 Hrs
[Set Control 1]
Duration : 30 Min
[Set Control 1]
If set to ON, lockout prevents the controller output coming on during the lockout period. (See notes on lockout on page 11.) Pressing the UP or DOWN keys will change the setting.
This screen sets the duration hours the control 1 output will stay on. Pressing the UP or DOWN keys will change the setting.
This screen sets the duration minutes the control 1 output will stay on. Pressing the UP or DOWN keys will change the setting.
9
Loading...
+ 21 hidden pages