Toro 12, 48, 36, 12-Station, 24-Station User Manual

...
Page 1
Intelli-Sense
User’s Guide
Professional Controllers
12-, 24-, 36-, and 48-Station Models
TIS-PRO
Page 2
Page 3
Page 4
Page 5
v
Using the Reports Function . . . . . . . . . . . . . . . . . . . . . . . . . 53
Weekly Stations Report. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Monthly Station Report . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Flow Report . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Using the ET Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Edit Custom Plant Kc Value . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Edit Custom Turf Kc Value . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Set Weekly ET. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Using the Help / ET Function . . . . . . . . . . . . . . . . . . . . . . . . 59
Rain Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
View Group Number . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Days Since Last ET. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Current Depletion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Run Valve Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Using the Manual Watering Function . . . . . . . . . . . . . . . . . 62
Manually Operate Specific Stations . . . . . . . . . . . . . . . . . . . . 62
Manually Operate All Stations . . . . . . . . . . . . . . . . . . . . . . . . . 63
The Run Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
The Off Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Using the Maintenance Timeout Function 55
Using the Rain Pause Function . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . .
55
Appendix A - Troubleshooting Guide . . . . . . . . . 65
Appendix B - Glossary of Terms . . . . . . . . . . . . 69
Appendix C - Installation Procedures. . . . . . . . . 71
Selecting the Installation Site . . . . . . . . . . . . . . . . . . . . . . . . . 71
Mounting the Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Connecting the Power Wires. . . . . . . . . . . . . . . . . . . . . . . . . . 73
Connecting an Earth Ground Source . . . . . . . . . . . . . . . . . . . 73
Connecting the Station Wires (includes Pump Relay). . . . . . . 74
Toro Rain Sensor Connection . . . . . . . . . . . . . . . . . . . . . . . . . 76
Flow Sensor Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Toro TMR-1 Handheld Remote Connection . . . . . . . . . . . . . . 78
Fuse Replacement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Warranty Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
FCC Compliance Information . . . . . . . . . . . . . . . . . . . . . . . . 82
Page 6
vi
Notes:
Page 7
Page 8
How the ET Everywhere Service Works
2 - Proven scientific modeling techniques are then used to
calculate and validate specific ET data down to one square kilometer.
3 - The ET data is uploaded to a communications satellite
where it received nightly by the intelli-Sense controller to automatically recalculate station-specific irrigation parameters for the next scheduled watering day.
32
1
2
1 - The WeatherTRAK ET Everywhere service collects data
from over 25,000 monitoring stations including the National Oceanic and Atmospheric Administration (NOAA) network, state and county networks, and private weather stations.
Important: The ET Everywhere subsciption service is
!
not included with the purchase of the Intelli-Sense controller. For service subscription information, contact WeatherTRAK customer service at 1-800-362-8774 during normal business hours.
Page 9
Thoroughly inspect the irrigation system for proper design, installation and operating condition, leaks, as well as broken
heads and pipes. The performance of your new controller depends on the integrity of the irrigation system design and installation. You will maximize the performance of your controller when the irrigation system is well maintained.
Activate the WeatherTrak ET Everywhere subscription service. This necessary and important step enables the Intelli-Sense to
receive daily ET updates.
Page 10
Page 11
Page 12
Page 13
Page 14
Page 15
Page 16
Page 17
Page 18
Page 19
1. Within the Setup menu, turn the Upper Line knob to view the following display:
STACK OR OVERLAP Stack
Select Stack or Overlap Option
When the Stacking option is selected, the controller will be constrained to operate one station at a time. The Water Window
start time and duration selected for Automatic Schedule A will
also be assigned to Automatic Schedule B, C and D.
When the Overlap option is selected, the constraint is removed, allowing multiple programs to run simultaneously.
When Overlap is selected, Start time and Water Window options are available in all schedules.
Page 20
1. Within the Setup menu, turn the Upper Line knob to view the following display:
2. Turn the Lower Line knob to select the preferred option.
Note: If a pump station is in use but no master valve is required, use the Normally Closed/Pump On option.
MASTER VALVE/PUMP START Normally Closed/Pump On
ASSIGN PUMP START OUTPUT NOT ASSIGNED
Set Master Valve/Pump Start Option
Page 21
Set Maximum Backup ET
1. Within the Setup menu, turn the Upper Line knob to view the following display:
Turn the Lower Line knob to adjust the decimal number value.
MAX BACKUP ET Part 1
2.00
The Maximum Backup ET value is a failsafe measure used by the controller to calculate daily watering requirments in the event that current ET Everywhere data is not recieved for an extended period.
2.
The Maximum Backup ET default value of 2.00 is automatically entered to help compensate for seasonal weather changes.
The whole number of the Maximum Backup ET value is selected by default. To adjust the value from 1 – 3, turn the Lower Line knob.
Note: The Maximum Backup ET is adjustable from 0.50 – 3.99. The whole number is only adjustable to 0 when the decimal number value is .50 or higher.
4.
Turn the Upper Line knob right one stop to select the decimal number.
3.
Page 22
Notes
16
Page 23
Page 24
SET STARTS/WINDOWS PRG A Edit (Button to View)
(Button to View)
3. Turn the Upper Line knob to select the following display:
4. The start time hour is underlined and flashing, indicating that it
can be edited. Turn the Lower Line knob to set the start time hour, or turn the Upper Line knob right to select next element
of the screen to be edited.
1st Start/Window PRG A Start 12:00am Win 16:00
Page 25
Page 26
20
WATER DAY MODE PRG A
Optimized by WeatherTRAK
WATER DAY MODE PRG A
Odd/Even
1. With the Function dial in the SCHEDULE position, turn the Upper Line dial to view the following display:
Set Program Water Day Mode
Each program can be assigned to unique water day schedule using one of the following options:
• Optimized by WeatherTRAK - Water day schedule selected
automatically by the Intelli-Sense scheduling engine.
• Odd/Even - Odd or Even numbered calendar days.
• Interval - Water days set by frequency ranging from 1 to 30 days.
• Days of Week - Specific days of the week (same all months)
• Days of Week by Month - Specific days of the week for each month.
• Off - Turn program off.
3. Turn the
that enables a weekday to be excluded from operation.
Upper Line knob to select the Day Exclusion feature
4. Turn the Lower Line
knob to display the day name or None.
1. Turn the Lower Line knob to select Odd/Even.
2. Turn the Upper Line knob to display Odd.
3. Turn the Lower Line
knob to select Even.
2. Optimized by WeatherTRAK is selected by default.
To use this mode, continue at step 3. To use an alternate mode, continue at the appropriate following section.
Odd/Even
Page 27
21
Page 28
22
WATER DAY MODE PGM A
Days of Week by Month
Jan OK TO WATER ON PGM A
S M T W T F S
1. Turn the Lower Line knob to select Days of Week by Month.
Water Day Mode Off
1. Turn the Lower Line knob to select Off. .
2.3.Turn the Upper Line knob to view the following display:
By default, every day of every month is an active watering day. To omit specific days from specific months, turn the Upper Line knob to select the month.
4.
Jan OK TO WATER ON PGM A
S M - W T - S
To omit specific days, turn the
Selecting the Off water day mode effectively prevents the program from
running automatically. To reinstate a program to automatic operation, simply choose an alternate watering day mode.
Upper Line knob to select the day indicator, then turn the Lower Line knob to replace the indicator with a dash (as shown in the following example).
Page 29
23
The Station Data function menu consists of several station setup parameters required for automatic operation.
Four station operating mode options provide the control flexability to program each station for optimum irrigation control.
The station operating mode selections are:
• Automated by WeatherTRAK
• User - With ET (user-defined setup parameters with ET control)
• User - No ET (user-defined setup parameters without ET control)
• Off (station disabled)
Within each operating mode are the following required setup parameters:
Automated By WeatherTRAK:
• Select Program
• Select Program
• Select Station
• Water Window option
• Select Station
• Select Station Mode • Select Station Mode
• Usable Rainfall
• Sprinkler Type
• Precipitation Rate*
• Sprinkler Efficiency*
• Soil Type
• Plant Type
• Root Depth*
• Microclimate
• Slope Factor
• Sprinkler Location (on slope)
User Defined:
• Water Window option
• Usable Rainfall
• Run Time
• Number of Cycles
• Soak Time
• Reference ET
(applies to
• Reference Month (applies to User - With ET mode and watering days by month only)
As you can see by the extent of these lists, many factors are required to formulate an accurate baseline watering schedule. To simplify
this procedure, Intelli-Sense will select default values based on your entries. You can adjust these values if needed. The items listed with an asterisk (*) will have default values based on the selection made in preceding setup parameter.
User - With ET mode only)
Note: To begin the setup process, select Automated by WeatherTRAK
mode on page 24, or User-defined modes starting on page 33.
Page 30
Page 31
Use Water Window STA 01 Yes (end time 04:00pm)
SPKLR TYPE Spray Head
2. 100% is selected by default. To decrease the value, turn the Lower Line knob right.
1. Turn the Upper Line knob to display Usable Rainfall.
1. Turn the Upper Line knob to display Use Water Window.
The current water window end time is automatically calculated and displayed for the selected program.
2. Yes is selected by default. To disable the water window for the selected station, turn the Lower Line knob to select No.
Note: By selecting No, the station will run until irrigation is complete, regardless of the water window established for the program.
Page 32
Page 33
The default efficiency value is displayed for the sprinkler type selected. To change the value, turn the Lower Line knob to adjust the value from 10 – 95%.
2.
SPKLR EFFICIENCY
STA 01
70 Percent (default)
27
Page 34
PLANT TYPE STA 01 Cool Season Turf (default)
Page 35
Page 36
SET ROOT DEPTH STA 01 06 Inches (default)
30
Page 37
Select Slope Factor
2.
6 – 8% Grade
• Mild 9 – 12% Grade
Gentle
0 – 5% Grade
None/Slight
• Moderate 13 – 20% Grade
• Steep >20% Grade.
SET SLOPE FACTOR STA 01 None/Slight 0-5% Grade
None/ Slight (0 –5%) grade is selected by default. To select an alternate Slope Factor, turn the Lower Line knob.
Select Sprinkler Location
• All Parts of Slope (default if Slope Factor is other than None)
• Top of Slope
• Middle of Slope
• Bottom of Slope.
SPRINKLR LOCATION STA 01 None, No Slope Set
None, No Slope Set is selected by default. To choose an alternate Sprinkler Location, turn the Lower Line knob to select one of the following options:
31 9
The SlopeFactor is an important component used in the automatic watering program calculation to determine the amount of run time and number of repeat cycles required per watering day. The Slope Factor options are as follows:
1. Turn the Upper Line knob to select Set Slope Factor.
1.2.Turn the Upper Line knob to select Sprinklr Location.
Note: To prevent runnoff, selecting any slop factor other than None/Slight will result in a decrease in station run time per cycle and an increase in the watering cycle frequency.
Note: If a Slope Factor of None/Slight is selected, Sprinkler Location
setting is not enabled.
Page 38
Page 39
33
Select Station
SELECT STATION 01
Note: The Maximum Active Station number defined in Setup, determines station number access.
1. Withthe Function dial in the Station Data position, turn the Upper Line knob to display Select Station.
2. Station 01 is selected by default. To change the station number,
turn the Lower Line knob.
Select Station Mode
STATION MODE STA 01 User - With ET
Select Program
SELECT PROGRAM STA 01 A (Optm S12:00am W16:00)
2. Turn the Lower Line knob to select Use - With ET or User - No ET.
2. Program A is selected by default. To change the program selection, turn the Lower Line knob.
1. Turn the Upper Line knob to display Station Mode.
1. Turn the Upper Line knob to display Select Program.
Select Water Window Option
Use Water Window STA 01 Yes (end time 04:00pm)
1. Turn the Upper Line knob to display Use Water Window.
2. Yes is selected by default. To enable the station to ignore a water window constraint, turn the Lower Line knob to select No.
Page 40
34
Page 41
35
Page 42
1.
Set Reference [weekly] ET Value (applies to User With ET mode only)
Turn the Upper Line knob to view the following display:
The Reference ET is the weekly ET set in the User – With ET mode that your runtimes correspond to. Runtimes will be adjusted up or down automatically depending on whether the actual weekly ET is higher or lower than the Reference ET. The default Reference ET is 1.00 (0.14 inches per day). It is recommended that you set runtimes and the Reference ET value based on the highest weekly ET demand period of the year.
Page 43
Page 44
Using the Review Function
(1) Station number 1 is assigned to watering Schedule A.
(2) The station will water for 11.9 minutes, one cycle per day.
(3 Automated by WeathTRAK is the assigned station mode.
If the station mode is User-No ET, User will be displayed. UwET indicates station is assigned to User with ET mode.
(4) The active watering day schedule for Week 1 is Thursday.
(5) The % Adjust factor is +00%.
(6) Soak time is set for 30 minutes.
ST01 A 11.9 MIN 01X AUTO
Wk1:-––T-– +00% Soak 30
3.
Station 1 will be selected by default. To select a differ ent station to review, turn the Upper Line knob.
1 2 3
4 5 6
REVIEW MODE Station Data
38
1. Turn the Function dial to the REVIEW position. Review Mode will be displayed.
2. Station Data is selected by default. To select Flow Data, turn the Lower Line knob. (Refer to Flow Data Review on page 37.)
The Review function provides a convenient, at-a-glance overview of all relavent station and flow monitro setup information.
Note: Additional review information can be acquired for each station by pressing the Copy button when the Fucntion dial is in the STATION DATA position.
The review information is displayed in an abbrevieated format that allows the information to viewed in one screen as shown in the example below.
Note: The remainder of the 8-week watering day schedule can be viewed by turning the Lower Line knob.
Page 45
39
Page 46
Using the Copy Function
Copying Station Information
1. Turn the Function dial to COPY to view the following
display:
2. Turn the Upper Line knob to select the source station number.
3. Turn the Lower Line knob to select the destination station number.
To select All Stations, turn the Lower Line knob one stop past the highest station number, as shown in the following display:
COPY FROM STA 01 TO STA 02 (Press Button)
The Copy function provides a convenient method of transferring all watering program information from one station to another or to all active stations simultaniously. Minor changes can then be made to each station as needed, greatly simplifying the process of programming several stations with similar watering progam attributes.
The Copy function also serves as a means of quickly resetting all user­defined Setup, Schedule and Program settings back to the factory-default values. The default values can be reapplied to selected stations or all stations simultaniously as needed.
4. Press and hold the Copy button. Release the button when Copying... Done! is displayed.
COPY FROM STA 01 TO ALL STA’s (Press COPY)
COPYING...DONE!
Note: The number of active stations defined in the Setup function, determines the number of stations that can be selected.
40
Page 47
Restoring STATION Default Settings
2. Turn the Upper Line knob to select Copy Station Defaults as shown in the following example:
3. Turn the Lower Line knob to select the station number to be restored. Or, to restore defaults to all stations , turn the Lower Line knob to select All Stations.
COPY FROM STA 01 To STA 02 (Press COPY)
4.
Press and hold the Copy button. Release the button when Copying Done is displayed.
COPY STATION DEFAULTS TO To STA 02 (Press Button)
COPY STATION DEFAULTS TO ALL STA’s (Press BUTTON)
COPYING...DONE!
41
1. Turn the Function dial to the COPY position.
Soil Type -
Sandy
Plant Type - Cool Season Turf Root Depth - 6 Inches
Microclimate - Sunny All Day Slope Factor - None/Slight
Sprinkler Location - None
Station Mode -
Automated By WT
Program Mode - A Use Water Window - Yes
Usable Rainfall - 100% Sprinkler Type - Spray Head
Precipitation Rate - 1.70 In/Hr
Sprinkler Efficiency - 70%
Important: Restoring the STATION defaults erases and resets all user settings for all stations as follows:
!
Page 48
Restoring PROGRAM Default Settings
42
Important: Restoring the default Program settings erases and resets all user-defined settings for all programs as follows:
1st Start Time - 12:00am
Water Window - 16:00
2nd Start Type - High ET
2nd Start Time - 07:00 pm
Water Window - 05:00
Water Day Mode - Optimized by WT
Day Excusion - None
2. Turn the Upper Line knob to select Copy Program Defaults as shown in the following example:
3.
COPY FROM STA 01 TO STA 02 (Press BUTTON)
4.
Press and hold the Copy button. Release the button when Copying Done is displayed.
COPY PROGRAM DEFAULTS TO PGM A (Press Button)
COPY PROGRAM DEFAULTS TO ALL PGM (Press Button)
COPYING...DONE!
1. Turn the Function dial to the COPY position.
Turn the Lower Line knob to select the program A, B, C or D) to
be restored. Or, to restore defaults to all programs simultaneously,
turn the Lower Line knob to select All Pgm.
!
Page 49
Page 50
44
Using the % Adjust Function
ADJ WATER AMOUNT STA 01 0% = No Change
ADJ WATER AMOUNT STA 01 +05% = More Water
ADJUST Water Amount
1. Turn the Function dial to % ADJUST. The Water Amount adjustment option is selected by default.
1. Turn the Upper Line knob to select the station number.
% Adjust by Water Amount
2. The unadjusted water amount value is 0%. Turn the Lower Line knob right to increase, or left to decrease the value in 5% increments. Maximum adjustment range is +25 to –50%.
The % Adjust function allows you to make minor changes in overall station irrigation rate by increasing or decreasing the watering program values proportionally by percentage. Adjustments can be made in 5% increments by Water Amount (station run time and cycles per day), and by Day Frequency/Maximum Allowable Depletion (MAD).
Note: Both adjustment methods can be applied to each active station, however, DF/MAD is only available to stations operating in the Automated by WeatherTRAK mode.
Important: A small percentage adjustment can result in a significant change in irrigation rate. Always adjust in 5 or 10% increments, then monitor the condition of the landscape for 7 to 10 days prior to making additional adjustments.
!
2. To adjust by Water Amount factors, continue below. To adjust by Day Frequency/MAD, continue on page 43.
Page 51
Turn the Lower Line knob to select Day Frequency/Depletion adjustment option.
ADJUST DAYS (MAD) STA 01 +05% = More Often (45%)
ADJUST DAYS (MAD) STA 01 0% = No Change (50%)
ADJUST DAYS (MAD) STA 06 Non-Adjustable Mode
1.
Day Frequency/Depletion
ADJUST
45
% Adjust by Day Frequency/Maximum Allowable Depletion
Note: If the selected station number is assigned to a User-defined
station mode, the following display will be shown:
3. Turn the Lower Line knob right to increase or left to decrease the percent value. Maximum adjustment range is +30% to -30%.
2. Turn the Upper Line knob to select the station number.
Stations assigned to the Automated by WeatherTRAK station mode can be % adjusted by watering Day Frequency/Maximum Allowable Depletion. For example, when establishing new turf, total water application can be increased while decreasing the possibility of runoff. Day Frequency is adjustable from -30% to +30% in 5% increments. The equivalent MAD value will be displayed ranging from 20% to 80% (with 50% being the standard depletion rate).
Note: In the following example, the watering day frequency for station 1 has been increased by 5%, which decreased the MAD value to 45%. This change translates to irrigation being permitted when soil moisture content drops to 45% instead of the standard 50% MAD value.
Page 52
Using the Alerts Function
FL - Flow Status VL - Valve Status CM - Communication Status
WD - Water Window Status
DY - Water Day Status HW - Hardware Status
SB - Subscription (ET) Status
01 02 03 04 05 06 07 08
SH=Short NC=NoConnect
FL VL CM WD DY HW SB
——=Ok ER=Error
-- ER -- -- —— —— ––
-- -- SH -- —— —— —— ––
VIEW VALVE STATUS Skip Short
Example: Valve Status Alert
46
Note: When the condition has been resolved, the Alert display
prompt will be removed.
1. Turn the Function dial to the ALERT position.
2. Turn the Upper Line knob to select the function to review.
The current status will be displayed, and if additional data is available, a Skip/View option will be provided.
3. To view the additional data, turn the Lower Line knob to select View. Turn the Upper Line knob to display the data.
If a problem, confilict or error occurs with one of the essential Intelli-Sense functions, an Alert prompt will be immediately posted. Selecting Alerts function provides a quick overview of the monitored functions, and flags the source of the alert condition.
From the initial Alert display screen, the specific function causing the alert condition will be identified as follows:
1. With the ALERTS function selected, turn the Upper Line knob right to select View Valve Status.
2. Turn the Lower Line knob to select View.
3. Turn the Upper Line knob right as needed to display the affected
station number(s).
Page 53
Page 54
48
EDIT EXCLUDED STATIONS Skip (No Flow Only)
01 02 03 04 05 06 07 08 N N N N N N N N
2. Turn the Lower Line knob to change Skip to Edit.
2. Turn the Lower Line knob to select the actual flow sensor size from
the following options: 1.00”, 1.25”, 1.50”, 2.00”, 3.00”, 4.00” and
Insert Type (sizes < 1” or > 4”).
Set Station Exclusion
The station exlusion feature enables individual stations to be omitted from the Flow Monitor operations.
3. Turn the Upper Line knob to display the first eight station numbers in sequence.
1. With the the Function dial in FLOW position, turn the Upper Line knob right to select Edit Excluded Stations.
SET FLOW METER SIZE
1.00”
Set Flow Meter Size
1. With the the Function dial in FLOW position, turn the Upper Line knob right to select Set Flow Meter Size
4. By default, no stations are excluded (indicated by N) and station 01 is selected. To exclude the selected station, turn the Lower Line
knob to change N to Y (Yes). To select another station number, turn the Upper Line knob. Repeat as needed for all station numbers.
Page 55
Page 56
50
HIGH FLOW THRESHOLD 050 GPM 3 Minutes
Set Threshold and Delay Values
Setting the High Flow Threshold
The threshold value is the defined limit for maximum, minimum and no-flow conditions. If monitored flow exceeds a threshold, an Alert is posted, and all remaining watering operations suspended or modified untl the alert is cleared or problem resolved.
The delay period provides a 1- to 6-minute buffer between an exceeded threshold and the controller response. Increasing the delay period, decreases controller sensitivity to temporary or minor fluctuations.
1. With the the Function dial in FLOW position, turn the Upper Line knob right to select High Flow Threshold.
Note: The High Flow threshold should be set approximately 10–15% higher than the expected flow in any program configuration to prevent a
false alert response.
2. The default threshold will be displayed. To adjust, turn the Lower Line knob. The value is adjustable from Off –30 in one-GPM increments, or 30–995 in five-GPM increments.
Controller Response: Controller response to an exceeded threshold
is based on the selected operating mode as follows:
Stack Mode – The operating station will turn of f, and the next station in sequence will turn on. If the condition persists, all irrigation will be terminated and an alert posted. If the flow normalizes, the controller will continue the watering cycle. Bypassed stations will be indicated and given first priority in the next schedueld watering cycle.
Overlap Mode – The system will shut down. After a short delay , the master valve will be opened and flow measured. If the condition persistes, all irrigation will be terminated and an alert posted. If flow normalizes, watering will resume one station at a time. Each station will be flow monitored and bypassed if the threshold is exceeded. Bypassed stations will be indicated and given first priority in the next schedueld watering cycle.
Page 57
Page 58
52
Page 59
53
Page 60
54
Page 61
Page 62
56
1. Turn the Function dial to the blank position, located between Flow and Reports.
MAINTENANCE TIMEOUT Skip
2. Turn the Lower Line dial to Edit.
3. Turn the Upper Line dial one click.
4. Turn the Lower Line dial to ON.
5. Turn the Upper Line dial to highlight Time.
6. Turn the Lower Line dial to set timeout duration (0.5–8.0 hours).
Using the Maintenance Timeout Function
The MaintenanceTimeout feature enables a time period ranging from 0.5 to 8.0 hours to be set, then selectedas required. During the timeout period, the leak detection function is disabled and the normally-closed master valve is energized. A typical use of the Maintenance Timout function would be to facilitate quick­coupler irrigation.
Page 63
CURRENT DAILY ET P
0.14 00-00-00 12:00:00
Using the ET Function
57
1. Turn the Function dial to the ET position. The Current Daily ET value recievied from the ET Everywhere service will be displayed with the download date and time stamp.
AVERAGE WEEKLY ET
1.00
CUSTOM Kc PLANT A
1.00
2. Turn the Upper Line dial right to display Average Weekly ET. The numeric value shown is the average daily ET value compiled from the previous seven days.
1. With the Function dial in the ET position, turn the Upper Line dial right to select the Custom Kc screen.
2. Plant A is selected by default. To select Plant B, turn the Upper Line knob.
3. A Kc value of 1.0 is selected by default. Turn the lower line knob to
adjust the value between 0.10 to 1.20.
Note: If the letter P is displayed, an updated daily ET value is currently pending download. A letter I indicates that incremental ET data has been downloaded prior to the scheduled download time due to an extreme change in weather and conditions resulting ET data.
The screens provided within in the ET function enable the current daily and weekly ET values to be reviewed, and the Kc value of custom plants and turf to be defined.
Edit Custom Plant Kc Value
Note: Most common crop coefficient (Kc) values can be found on
the Irrigation Association web site at: www.irrigation.org
Page 64
58
Page 65
59
Page 66
Rain Service
60
The Rain Service feature is offered by WeatherTRAK to monitor rainfall within your location and terminate automatic watering in the event of rain.
The Group number is a function of the Rain Sevice feature and is not applicable unless the service is active. See Rain Service above.
View Group Number
Days Since Last ET
RAIN SERVICE ACTIVE No
1. With the Function dial in the HELP/INFO position, turn the Upper Line knob to select the Beep On Message screen.
VIEW GROUP NUMBER 00000
Upper Line knob to select the View Group Number screen.
DAYS SINCE LAST ET 0
Upper Line knob to select the Days Since Last ET screen.
1. With the Function dial in the HELP/INFO position, turn the
1. With the Function dial in the HELP/INFO position, turn the
Note: This reference screen indicates how many days have elapsed since the controller last received ET Everywhere service data, and is not applicable unless the ET Everywhere service is active.
Note: Rain Service is inactive by default. For detailed information regarding Rain Service activation, contact a WeatherTRAK
Customer Service at 1-800-362-8774.
Page 67
CURRENT DEPLETION Sta 01:00% MAD:50%
Current Depletion
Run Valve Test
RUN VALVE TEST Skip
01 02 03 04 05 06 07 08
-- -- -- -- -- -- -- --
Pass
The valve test feature provides a quick status check of all active station outputs including the master valve. Pass/Fail prompt will be displayed at the conclusion of the test.
1. With the Function dial in the HELP/INFO position, turn the Upper Line knob to select the Curent Depletion screen.
2. Station 1 is selected by default. Turn the Lower Line knob to
change the station number.
3. The MAD value shown represents the depletion value that is applied in the % Adjust > Day Frequency/Depletion screen. To reset the actual depletion value to the current MAD value, press the Copy button.
Upper Line knob to select the Run Valve Test screen.
3. Skip is selected by default. To view the test results, turn the Lower Line knob to select View. Turn the Upper Line knob to
view the test results for stations 1–8.
4. Press the Copy button to initiate the test. Turn the Upper Line knob to advance through the station count. Upon completion, a Pass/Fail prompt will be displayed.
61
The Current Depletion reveiw screen provides the actual depletion value and the current MAD value for each station. An additional feature provided within this screen enables the actual depletion value to be easily reset to the current MAD value.
1. With the Function dial in the HELP/INFO position, turn the
Page 68
Manually Operate Specific Stations
1. T
2. Turn the Upper Line knob to change the station number.
urn the Function dial to the MANUAL position. Specific Stations
option will be displayed by default. (See page 63 for All Stations
manual operation.)
MANUAL WATER STA 01
00.0 Minutes
MANUAL WATER SET STA 01
10.5 Minutes NOW ON
MANUAL WATER Specific Stations
3. Turn the Lower Line knob to select manual operating time from 1 – 99 minutes in one-minute increments.
4. Repeat steps 2 and 3 to select additional stations for manual operation. Each station placed in queue will operate one at a time in numerical sequence as the preceding station times out and shuts off.
The station cycle time will count down in 10th’s of a minute. The station will shut off when the run time counts down (or is adjusted down) to 00.0 minutes.
62
The Manual function enable of all stations (in sequence) or individual station(s) to be manually operated at any time. Manual operation lasts for a specified number of minutes and starts immediately, whether or not the current day is a scheduled watering day. Only one station can be on at a time when operating manually.
Note: To terminate operation, either turn the Lower Line knob to select 00.0 run time, or turn the Function dial to the OFF position. Pause until the station turns off (5 seconds) before changing Function dial position.
Page 69
Manually Operate All Stations
1. T
2. Turn the Lower Line knob to view the following display:
urn the Function Selector knob to MANUAL.
MANUAL WATER All Stations
MANUAL WATER ALL STATION
00.0 Minutes
3. Turn the Upper Line knob to select the following display:
MANUAL WATER ALL STATION
05.0 Minutes STA 01 ON
4. Turn the Lower Line knob to select manual operating time from 01 – 99 minutes in one-minute increments.
Note: To terminate operation, either reduce the station runtime
to 00.0 or turn the Function Selector knob momentarily to the
OFF position.
The station runtime will count down in 10th’s of a minute. The station will shut off when the runtime counts down (or is adjusted down) to 00.0 minutes. Each station will operate in sequence for the selected runtime.
63
Page 70
64
Page 71
65
Page 72
1. Power to the controller has been disconnected, either by a blown fuse or at the AC power source circuit breaker panel. Check fuse condition, referring to the procedure on page 76. Check the circuit breaker at the power source and reset as necessary.
2. If the display does not return, contact Toro Customer Support at
The controller programs correctly but does not operate automatically.
1.
Confirm the controller clock is synchronized with the current time and date. If the controller clock is wrong, watering may not occur as expected.
2.
If Rain Switch is displayed, the Rain Sensor circuit has placed automatic operation on hold. If a Rain Sensor is not installed, confirm the Sensor switch is in the Bypass position. Check the Sensor wiring terminals to verify installation of a jumper wire connecting the terminals.
The display is blank.
1-800-664-4740.
1. Make sure the date and time settings are correct.
2. T
resulting in minor changes to the cycle time or number of cycles,
urn the Function dial to REVIEW.
Changes made within the Adjust function may be very subtle,
or it may be more significant
depending on the percent adjustment.
You
should see the effect of Adjust in the Watering
The ADJUST Function appears to be ineffective.
If it is currently Wednesday or later in the week when reviewing the
Week 1 display.
schedule, the affect of the adjustment may not be evident in the
Day schedules of Weeks 2 – 8.
66
Page 73
1. The days prior to installation will not be shown in the Week 1 schedule. The controller shows what days have irrigated or it anticipates what days will irrigate if the weather remains as it is today. If the controller is installed on a Friday, there will be no irrigation days shown prior to Friday, which may result in no irrigation days at all for Week 1.
2. Turn the Lower Line knob to see irrigation day schedules for Week 2 – 8. The irrigation days will display a pattern as you step through the subsequent displays.
The REVIEW display indicates 99+ minutes.
1. Since the displayed cycle time is limited to two digits, 99+ is shown when the total programmed cycle time is greater than 99 minutes. This display does not indicate a controller malfunction.
Week 1 of the watering day schedule appears incomplete.
67
Page 74
68
Page 75
69
Page 76
Phase Lock – The Intelli-Sense receives daily weather updates from three different paging carriers. At the time of ET Everywhere service activation, the carrier with the highest signal strength is selected to ensure the best data reception and to expedite the activation process. After initial activation, the Intelli-Sense receives all carriers each night to provide redundancy for data reception.
Rain Service – This is an optional service available in a limited number of areas that enables the controller to receive rainfall information to
Water District Number – If you are an active participant in a water agency program, you will be given a water control district identification number to enter during the ET Everywhere service activation.
This
five-digit code will enable the controller to be automatically
notified
of local agency requirements and/or restrictions.
adjust the program accordingly. Rain Service data accounts for local reported rainfall and includes it in the soil moisture depletion calculations.
70
Page 77
Page 78
72
Page 79
73
Page 80
Page 81
75
Valve Common Wire
Valve Common Terminals
Master Valve or Pump Start Relay (0.5 A max.)
Hot Post
Caution: The controller must not be connected directly to a pump or other high current-draw equipment. A 24 VAC, 0.5A (max.) relay must be used to facilitate the connection. Failure to comply can result in severe controller damage.
!
Page 82
Toro Rain Sensor Connection
76
Installation of the Toro TWRS rain sensor or TWFRS rain/freeze sensor sensor is recommend for best results.
Note: If a rain sensor is NOT connected, the Sensor switch must be in the BYPASS position. If the Sensor switch is placed in the ACTIVE position without a rain sensor connection, the controller will be placed in a rain hold mode, and all operation will be suspended. The following screen will be displayed:
Aug 08 2007 10:58:42am RainSwitch M:
White
Brown
Red
Red
24 VAC
Rain
1. Remove one of the auxiliary wiring access plugs rom the bottom of the cabinet and insert the rain sensor connection cable.
2. Connect the Brown and White wires to the Ran Sensor terminal block as follows: Lift the terminal block lever, insert the bare wire, then secure the wire by pushing the lever down.
3. Connect the Red 24 VAC wires to the 24 VAC transformer wire terminal block.
4. Refer to rain sensor user guide for complete setup and operating information.
Note: When the rain sensor is active, the screen shown above will be displayed. To bypass rain sensor operation at any time, place the Sensor switch in the Bypass position.
Page 83
Page 84
Page 85
1. Disconnect power to the controller.
2. Carefully remove the blown fuse from the PC board.
4. Restore power to the controller.
Specifications
Mechanical
Electrical
• Cabinet (overall): 10.5" H x 17" W x 6" D
• Wiring Conduit Provisions:
• Operating Temperature Range: 32°F to 140°F (0°C to 60°C)
• Storage Temperature Range: -22°F to 149°F (-30°C to 65°C)
• Input: 120 VAC, 50/60 Hz, 0.5A (24 W max.)
• Master Valve/Pump Start Relay Output: 24 VAC, 0.5A
• Rain Sensor Compatability: Normally-closed
!
79
Output (per station): 24 VAC, 50/60 Hz, 0.5A (12 VA max.)
Output (total): 24 VAC, 50/60 Hz, 1.5A (36 VA max.)
CAUTION: The fuse protects the transformer from overload and subsequent damage due to a short circuit condition. For continued protection against the risk of controller damage or fire, replace only with a fuse of the same type. Ensure power is OFF prior to removing/replacing the fuse.
Fuse Replacement
!
Power - 0.50"/.75” (12.7mm/19mm) Aux. - 0.50"/1” (12.7mm/25.4mm)
Field - 2.5”/ 3" (64mm/76mm)
• Flow Sensor Compatability: Toro TFS Series or Data Industrial IR Series
• Fuse: 250V, 2A, Slo-Blo
3. Replace with spare fuse (clipped to PCB) or 250V, 2A (Slo-Blo).
Page 86
80
Page 87
Page 88
www.toro.com
© 2009 The Toro Company, Irrigation Division Form Number 373-0547 Rev. B
Industrial Canada compliance information
This device complies with Industry Canada licence-exempt RSS standard(s). Operation is subject to the following two conditions: (1) this device may not cause interference, and (2) this device must accept any interference, including interference that may cause undesired operation of the device.
Le présent appareil est conforme aux CNR d'Industrie Canada applicables aux appareils radio exempts de licence. L'exploitation est autorisée aux deux conditions suivantes : (1) l'appareil ne doit pas produire de brouil­lage, et (2) l'utilisateur de l'appareil doit accepter tout brouillage radioélec­trique subi, même si le brouillage est susceptible d'en compromettre le fonctionnement.
Loading...