Toro 200, 100 User Manual

Specifications:
• Controls up to 200 stations for the Stand-Alone model
• Input power supply
100 VAC, 50/60Hz 120 VAC, 50/60Hz 240 VAC, 50/60Hz
• TDC output voltage: 40 VAC max.
• TDC output power: 98VA max.
• Storage temperature: -30C–60C
• Cabinet Type: Non-corrosive, lockable wall mount, indoor/outdoor installation
• Six 25.4mm conduit openings and one 38mm conduit opening
Cabinet Installation
Selecting the proper installation site for the 2-wire decoder is essential to safe and reliable operation. The 2-wire decoder features a weather resistant cabinet designed for indoor or outdoor installation.
The TDC should be installed on a vertical wall or other sturdy structure near a grounded power source. Select a location that shades the controller during the hottest hours of the day and provides as much protection from direct sunlight, rain, wind and snow as possible. DO NOT mount the controller where it is exposed to direct spray from the irrigation system.
For easy operation and better view of the display (Stand-alone model), install the TDC so that the display is at or slightly below eye level.
Step 1 – Drill two pilot holes 15.25cm apart for the top keyholes of the
controller cabinet.
Step 2 – Install the top screws leaving approximately 5–6mm of exposed
screw to accommodate the cabinet.
If mounting the cabinet on dry wall or masonry, install the appropriate type of screw anchors or fasteners to ensure secure installation.
Step 3 – Hang the cabinet using the top keyhole slots.
See Figure 1.
Step 4 – Open the cabinet door and install the bottom two
screws to secure the cabinet.
TDC 100/200 Stand-Alone Model Installation Instructions
Figure 1
15.25cm
23.175cm
Earth Ground Installation
IMPORTANT! The TDC surge protection components cannot properly function unless an efficient pathway to earth
ground is provided. The ground path must be as direct as possible, without sharp bends and must not exceed 30 Ohm resistance (when measured with an earth ground resistance device). All electrical components throughout the irrigation system should be grounded similarly to provide the same ground potential.
The following instructions depict one of several acceptable earth grounding methods. Due to variables in soil composition and terrain, the method shown may not be suitable for your installation site. Contact your local Toro distributor for assistance and availability of the required earth ground resistance test instrument.
Step 1 – Drive a 5/8" x 8' (17mm x 2.5m) copper-clad steel rod into well moistened soil not less than 8' (2.5m) or not more
than 12' (3.7m) from the controller cabinet. The top of the ground rod should be 12" (30.5cm) below grade level. See Figure 2.
Step 2 – Using a 5/8" (17mm) clamp or “Cad weld” fastener, attach an 8 AWG (8mm
2
) solid copper wire near the top of the
ground rod. Avoiding wire bends of less than 8" (20.3cm) radius and more than 90
o
, route the wire through conduit
and into the cabinet. Secure the wire to the copper ground lug.
Make sure the soil surrounding the ground rod(s) remains well moistened at all times. The addition of
some form of irrigation may be required if the cabinet is installed in a non-irrigated location.
Step 3 – Measure the ground resistance per the instructions provided with the ground test instrument. A reading of
0.0 Ohm is optimum, up to 10 Ohm is good and 11–30 Ohm is acceptable in most cases. If the resistance exceeds the acceptable limit, additional ground rod(s) can be installed at a distance equal to twice the buried depth of the first rod; i.e., 16' (4.9m). Interconnect the ground rods using 8 AWG (8mm
2
) solid copper wire and test again. If the measured ground resistance continues to read above the acceptable limit, contact your local Toro distributor for further assistance and recommendations.
Installing a round valve box over the ground rod enables the ground rod to be easily located as well as
providing access to the ground wire connection(s).
Figure 2
Ground Lug
Valve Box
8 AWG (8mm2) Solid Copper Ground Wire
Copper Clad Ground Rod
Ground Wire To Additional Rod(s) (Optional)
12" (30.5cm)
8'–12'
(2.4m – 3.7m)
8" (20.3cm) Minimum Radius
90oMinimum Angle
Power Source Installation
Step 1 – Turn off the power at the power source location and
place the controller’s power switch to OFF. Connect and route the appropriate size 3-conductor cable (10 AWG [2.5mm
2
] maximum) from the power source to the
controller cabinet.
The provided power cable access hole can accommodate a 1" (25mm) conduit fitting. If conduit is required, install a section of flexible 1" (25mm) electrical conduit from the power source conduit box to the cabinet’s access hole.
Step 2 – Open the cabinet door and remove the two retaining
screws from the power supply cover.
Step 3 – Locate the voltage cable assembly and note the voltage
on the label. The TDC is equipped with 120V cable assembly from the factory. Replace the voltage cable assembly with the proper rating as necessary. See
Figure 3.
Step 4 – Strip the power cables and secure them to the terminal
block. Reference Table 1 for the appropriate type of power connection.
Step 5 – Reinstall the power supply cover.
Step 6 – Apply power to the controller.
WARNING! AC POWER WIRING MUST BE INSTALLED AND CONNECTED BY QUALIFIED PERSONNEL ONLY.
ALL ELECTRICAL COMPONENTS AND INSTALLATION PROCEDURES MUST COMPLY WITH ALL
APPLICABLE LOCAL AND NATIONAL ELECTRICAL CODES. SOME CODES MAY REQUIRE A MEANS OF DISCONNECTION FROM THE AC POWER SOURCE, INSTALLED IN THE FIXED WIRING, HAVING A CONTACT SEPARATION OF AT LEAST 3mm IN THE LINE AND NEUTRAL POLES.
ENSURE THE AC POWER SOURCE IS OFF PRIOR TO SERVICING. FAILURE TO COMPLY MAY RESULT IN SERIOUS INJURY DUE TO ELECTRICAL SHOCK HAZARD.
Figure 3
Line
Neutral
Voltage Cable Assembly
Flexible Conduit (Optional)
Equipment
Ground
Loading...
+ 5 hidden pages