TopWorx GO Switch for Nuclear Applications IOM Manuals & Guides

IOM
Page 1
TopWorx™ engineers are happy to provide technical assistance on GOTM Switch products. However, it is the
customer's responsibility to determine the safety and suitability of the product in their application. It is also the
customer's responsibility to install the switch using the current electrical codes in their region.
TM
C7, C8, H7, H8,
M7,M8, R7, SV7
GO™ Safety Related Switches operate on the principle of magnetic attraction, reacting to magnetic targets as they come within the switch's sensing range. Although switches vary in design according to their intended applications, all GO Switches use permanent magnets which, when actuated by the presence of a magnetic target, change the state of electrical contacts.
Mounting
■ Nuclear service GO Switches are immune to EMC and RF interference.
■ Use non-ferrous, stainless steel mounting brackets only. Consult factory for available mounting kits. For the maximum rated sensing distance, avoid mounting near ferrous metals or in a ferrous metal bracket.
Caution: Do not use excessive force on external threads when installing. The switch threads need to be properly torqued as indicated below when
mounted to any xture.
Over-torquing or under­torquing the switch threads may cause the switch to operate improperly. TopWorx recommends a torque value of 35 lbs
- ft. (47.45 Nm) with a tolerance of + /- 2 lbs.- ft. (2.71 Nm).
■ The switch must be mounted on the bracket and bolted close to the end of its threads, near its center of mass. This eliminates undue stress caused by heavy cables, connectors, etc.
H7, M7, & SV7
Specications - SPDT
Coaxial Sensing Distance w/ C-AMS7A Target
Average Sensing 0.190” ± 0.040” (4.83 mm ± 1.02 mm) Average Reset 0.023” ± 0.010” (0.58 mm ± 0.25 mm)
Coaxial Sensing Distance w/C-AMS12 Target
Average Sensing 0.350” ± 0.025” (8.89 mm ± 0.64 mm) Average Reset 0.031” ± 0.015” (0.79 mm ± 0.38 mm)
Pressure Rating At Sensing Surface: 2,000 psi (137.89 bar)
Thread Options: 5/8”-18 UNF (Consult TopWorx for metric thread
options)
Operating Temperature:
Qualied Life
(Years)
5 76 °C 85 °C
10 69 °C 78 °C
20 63 °C 71.5 °C
40 57 °C 65 °C
60 52.5 °C 61.5 °C
ATEX (all except SV7): -40°C (-40°F) to 150°C (302°F)
*The switch service (qualied) life depends on its operating temperature.
Contact Material: Palladium silver with Sawtooth surface conguration
Contacts: Single Pole, Double Throw, Form C.
H7 & M7 SWITCHES SV7 SWITCHES
Max. Normal Op. Temp.*
C7 & R7 Specications - SPDT
Coaxial Sensing Distance w/ C-AMS7A Target
Average Sensing 0.100” ± 0.020” (2.54 mm ± 0.51 mm) Average Reset 0.023” ± 0.010” (0.58 mm ± 0.25 mm)
Coaxial Sensing Distance w/C-AMS12 Target
Average Sensing 0.250” ± 0.025” (6.35 mm ± 0.64 mm) Average Reset 0.031” ± 0.015” (0.79 mm ± 0.38 mm)
Pressure Rating At Sensing Surface: 2,000 psi (137.89 bar)
Thread Options: 5/8”-18 UNF (Consult TopWorx for metric thread
options)
Operating Temperature:
C7 & R7 SWITCHES
Qualied Life (Years) Max. Normal Op. Temp.*
5 76 °C 10 69 °C 20 63 °C 40 57 °C 60 52.5 °C
ATEX: -40°C (-40°F) to 150°C (302°F)
*The switch service (qualied) life depends on its operating temperature.
Contact Material: Palladium silver with Sawtooth surface conguration
Contacts: Single Pole, Double Throw, Form C.
C8, H8, & M8
Specications - DPDT
Coaxial Sensing Distance w/ C-AMS7A Target
Average Sensing 0.100” ± 0.020” (2.54 mm ± 0.51mm) Average Reset 0.023” ± 0.010” (0.58 mm ± 0.25mm)
Coaxial Sensing Distance w/C-AMS12 Target
Average Sensing 0.250” ± 0.025” (6.35 mm ± 0.64 mm) Average Reset 0.031” ± 0.015” (0.79 mm ± 0.38 mm)
Pressure Rating At Sensing Surface: 2,000 psi (137.89 bar)
Thread Options: 1”-14 UNF (Consult TopWorx for metric thread options)
Operating Temperature:
C8, H8, & M8 SWITCHES
Qualied Life (Years) Max. Normal Op. Temp.*
5 76 °C 10 69 °C 20 63 °C 40 57 °C 60 52.5 °C
ATEX: -40°C (-40°F) to 150°C (302°F)
*The switch service (qualied) life depends on its operating temperature.
Contact Material: Palladium silver with Sawtooth surface conguration
Contacts: Double Pole Double Throw, 2 Form C.
■ C7, C8, H7, H8, M7,M8, R7 and SV-7 nuclear service GO Switches must be installed with
TopWorx qualied target
magnets. Reference sensing ranges in corresponding sections throughout the catalog.
■ Sensing and di󰀨erential of switch may vary depending on target travel direction.
■ Congure mounting of the switch and/or target so that target passes within the sensing area without physically contacting the switch. Sensing range will vary according to switch and target mode.
■ For heavy or inductive loads, arc suppression devices, or interposing relays are recommended for contact longevity. Contact factory for
specics.
■ Installation must use included Jam nuts and Lock washers.
■ Recommended installation distance is equal to the half of published sensing distance per switch.
Electrical Ratings
Contact Ratings*
(Resistive)
Power (W) 0.5 - 480 0.2 - 72 Voltage (V) 100 - 250 24 - 137 Current (A) 0.004 - 5.0 0.004 - 3.0
ATEX (all except SV7): 4A @120VAC / 3A @ 24VDC
*Consult factory for higher Amp rating requirements
Target Material: Target magnets C-AMS7A or C-AMS12 Enclosure Material: SS type 303 or 316 Conduit Outlet: 1/2”-14 NPT. One location
AC DC
GO SWITCH HOOK-UP DIAGRAMS C7, R7, H7, M7, and SV7
SPDT (Form C) Contacts May be wired Form A (N/O) or B (N/C)
Electrical Ratings
Contact Ratings*
(Resistive)
Power (W) 0.5 - 480 0.2 - 72 Voltage (V) 100 - 250 24 - 137 Current (A) 0.004 - 5.0 0.004 - 3.0
ATEX: 4A @ 120VAC / 3A @ 24VDC
*Consult factory for higher Amp rating requirements
Target Material: Target magnets C-AMS7A or C-AMS12 Enclosure Material: SS type 303 or 316L (RCC-EK1+) Conduit Outlet: 3/4”-14 NPT. One location
AC DC
C8, H8, and M8
DPDT (2 Form C) Contacts
Electrical Ratings:
Contact Ratings*
(Resistive)
Power (W) 0.5 - 480 0.2 - 72 Voltage (V) 100 - 250 24 - 137 Current (A) 0.004 - 5.0 0.004 - 3.0
ATEX: 3A @ 120VAC / 1A @ 24VDC
*Consult factory for higher Amp rating requirements
Target Material: Target magnets C-AMS7A or C-AMS12 Enclosure Materials: SS type 303 Conduit Outlet: 3/4”-14 NPT. One location
AC DC
Setting Up A Nuclear Service GO Switch For Optimum Performance
Nuclear service GO Switches use permanent magnets and a push-pull plunger to control a set of dry contacts. When a target magnet enters the sensing area of the switch, it attracts the primary magnet, which pulls the connecting rod and common contact. The normally closed and normally open contacts change state. (Continued on page 2.)
Page 1
IOM
*
*
C7 & R7 SPDT
4 COND. Peek Cable
N/C Red
N/O Blue
COM Black
GND Green
C8, H8, & M8 DPDT 7 COND.
Peek Cable & EGS Connector
N/C1 Red
N/O1 Blue
COM1 Black
N/C2 Yel low
N/O2 Brown
COM2 Natural
GND Green
EGS 4 Pin Connector
N/C A Red
N/O B White
COM C Black
GND D Green
C7 & R7 SPDT
4 COND. Peek Cable
N/C Red
N/O Blue
COM Black
GND Green
C8, H8, & M8 DPDT 7 COND.
Peek Cable & EGS Connector
N/C1 Red
N/O1 Blue
COM1 Black
N/C2 Yel low
N/O2 Brown
COM2 Natural
GND Green
EGS 4 Pin Connector
N/C A Red
N/O B White
COM C Black
GND D Green
TM
C7, C8, H7, H8,
M7,M8, R7, SV7
Attachment of Conduit or Cable Continued:
The sensing distance recommended by TopWorx is the maximum distance between the switch and target magnet trip point. The average reset, also known as deadband or hysteresis, is the distance that the target magnet must move from the sensing area in order to allow the switch to reset.
To apply the Nuclear service GO Switch and obtain the least di󰀨erential, the direction
the target approaches the switch must be considered (axial, radial).
The measurements shown are nominal depending on the size of target magnet used in the application. Consult the coaxial sensing distance for each switch model listed in this IOM.
With proper mounting, once the switch is set, the GO Switch will maintain calibration for life. See illustration below for correct switch alignment.
C-AMS7A Target Magnet C-AMS12 Target Magnet
*
*
*Refer to switch specications for average sensing distance.
The target magnet threads need to be properly torqued when mounted to any xture.
The target magnets were mounted at a torque value of 35 lbs-ft (47.45 Nm) with a tolerance of + /- 2 lbs.-ft. (2.71 Nm) during seismic testing.
0518
II 2 GD
Ex d IIC T3 Gb; Ex tb IIIC T200 °C Db (Tamb - 40 °C to + 150 °C) Baseefa08ATEX0360X IECEx BAS 08.0122X 120VAC/4A AND 24VDC/3A FOR SPDT SWITCHES 120VAC/3A AND 24VDC/1A FOR DPDT SWITCHES
PLEASE NOTE: THE SV7 SWITCH IS NOT CERTIFIED BY ATEX OR IECEx.
Attachment of Conduit or Cable
Attach conduit or cable correctly.
The switch conduit or cable needs to be properly supported when mounted to any
xture. During seismic testing, the stainless steel conduit (with PEEK cable) was
supported at 3.28 ft (1 m) from the back of the switch while the Rockbestos or PEEK cables were supported at 1 ft (0.305 m) away from the back of the switch. EGS Flex conduit and support kit are available from TopWorx as an option. During seismic
testing of the C7 switch with EGS QDC and ex conduit, the ex conduit was
supported 15”- 48” from the QDC interface. Please consult factory for more detailed information.
If the switch is mounted on a moving part, be sure exible conduit is long enough
to allow for movement, and positioned to eliminate binding or pulling.
– For installation in hazardous locations, check local electrical codes.
– All conduit connected switches should be installed using proper installation
methods.
The GO Switch must have a qualied QDC, a qualied sealed stainless steel
conduit, or other types of qualied accepted seal when used in submerged
applications or exposed to 100% humidity. For LOCA DBA type submergence,
however, only the C7 switch has been qualied for this application.
Per Qualtech Report No. TR-23009-14 Rev A, the EGS O-ring qualied life at
continuous operation, without disconnection, is 25.1 years at 144.14 of (62.3 °C). If for any reason these assemblies need to be detached prior to installation or while in operation, the O-rings must then be replaced. The maximum shelf life that can be assigned for the O-Ring is 10 years from the cure date. As long as the O-Rings have been stored per the guidelines of ANSI N45.2.2, Level B (now ASME NQA-1, Part II, Subpart 2.2, Level B), the O-Ring may be placed into installed service any time prior to the shelf life expiration date without impinging
on the qualied life outlined above
All GO Switches are “pure” contact switches, meaning they have negligible voltage drop when closed, nor do they have any leakage current when open. For multi-unit installation, switches may be wired in series or parallel, as shown to the right.
Series Wiring
Any number of GO Switches may be wired in series, without voltage drop.
Parallel Wiring
Any number of GOTM Switches may be wired in parallel, with no current leakage and without drawing operating current.
Special Conditions for Safe Use
The eld side wires should be protected against damage and terminated to a
terminal or junction box suitable for the conditions of use.
Due to the GO Switch’s sealed construction, eld service is not available. Refer to
our trouble shooting guide for a possible solution. If problem persists, please contact the factory directly.
EU Declaration of Conformity
The products described herein, conform to the provisions of the following European Community Directives, including the latest amendments:
Low Voltage Directive (2006/95/EC) EMC Directive (2004/108/EC) ATEX Directive (2014/34/EU)
C7 & R7 SPDT
4 COND. Peek Cable
N/C Red
N/O Blue
COM Black
GND Green
Visit www.topworx.com for comprehensive information on our company, capabilities, and products– including model numbers, data sheets
specications, dimensions, and certications.
info@topworx.com
www.topworx.com
The Emerson logo is a trademark and service mark of Emerson Electric Co. ©2016 Emerson Electric Co. ©2016 TopWorx, All rights reserved. TopWorx™ and GO™ Switch are all trademarks of TopWorx. All other marks are the
property of their respective owners. Information herein – including product specications – is subject to change without
notice.
C8, H8, & M8 DPDT 7 COND.
Peek Cable & EGS Connector
N/C1 Red
N/O1 Blue
COM1 Black
N/C2 Yel low
N/O2 Brown
COM2 Natural
GND Green
GLOBAL SUPPORT OFFICES
Americas
3300 Fern Valley Road Louisville, Kentucky 40213 USA +1 502 969 8000
Asia-Pacic
1 Pandan Crescent Singapore 128461 +65 6891 7550
Europe Horseld Way Bredbury Industrial Estate Stockport SK6 2SU United Kingdom +44 0 161 406 5155
EGS 4 Pin Connector
N/C A Red
N/O B White
COM C Black
GND D Green
Middle East
P.O. Box 17033 Jebel Ali Free Zone Dubai 17033 United Arab Emirates 971 4 811 8283
Africa 24 Angus Crescent Longmeadow Business Estate East Gauteng, South Africa +27 011 451 3700
Page 2 ES-02006-1 R14
Loading...