TopWorx™ engineers are happy to provide technical assistance on GOTM Switch products. However, it is the
customer's responsibility to determine the safety and suitability of the product in their application. It is also the
customer's responsibility to install the switch using the current electrical codes in their region.
TM
C7, C8, H7, H8,
M7,M8, R7, SV7
Introduction
GO™ Safety Related
Switches operate on the
principle of magnetic
attraction, reacting to
magnetic targets as they
come within the switch's
sensing range. Although
switches vary in design
according to their intended
applications, all GO
Switches use permanent
magnets which, when
actuated by the presence
of a magnetic target,
change the state of
electrical contacts.
Mounting
■ Nuclear service GO
Switches are immune
to EMC and RF
interference.
■ Use non-ferrous,
stainless steel mounting
brackets only. Consult
factory for available
mounting kits. For
the maximum rated
sensing distance, avoid
mounting near ferrous
metals or in a ferrous
metal bracket.
Caution: Do not use
excessive force on external
threads when installing.
The switch threads need
to be properly torqued
as indicated below when
mounted to any xture.
Over-torquing or undertorquing the switch threads
may cause the switch
to operate improperly.
TopWorx recommends
a torque value of 35 lbs
- ft. (47.45 Nm) with a
tolerance of + /- 2 lbs.- ft.
(2.71 Nm).
■ The switch must be
mounted on the bracket
and bolted close to
the end of its threads,
near its center of mass.
This eliminates undue
stress caused by heavy
cables, connectors, etc.
H7, M7, & SV7
Specications - SPDT
Coaxial Sensing Distance w/ C-AMS7A Target
Average Sensing 0.190” ± 0.040” (4.83 mm ± 1.02 mm)
Average Reset 0.023” ± 0.010” (0.58 mm ± 0.25 mm)
Coaxial Sensing Distance w/C-AMS12 Target
Average Sensing 0.350” ± 0.025” (8.89 mm ± 0.64 mm)
Average Reset 0.031” ± 0.015” (0.79 mm ± 0.38 mm)
Pressure Rating At Sensing Surface: 2,000 psi (137.89 bar)
Thread Options: 5/8”-18 UNF (Consult TopWorx for metric thread
options)
Operating Temperature:
Qualied Life
(Years)
5 76 °C 85 °C
10 69 °C 78 °C
20 63 °C 71.5 °C
40 57 °C 65 °C
60 52.5 °C 61.5 °C
ATEX (all except SV7): -40°C (-40°F) to 150°C (302°F)
*The switch service (qualied) life depends on its operating temperature.
Contact Material: Palladium silver with Sawtooth surface conguration
Contacts: Single Pole, Double Throw, Form C.
H7 & M7 SWITCHES SV7 SWITCHES
Max. Normal Op. Temp.*
C7 & R7
Specications - SPDT
Coaxial Sensing Distance w/ C-AMS7A Target
Average Sensing 0.100” ± 0.020” (2.54 mm ± 0.51 mm)
Average Reset 0.023” ± 0.010” (0.58 mm ± 0.25 mm)
Coaxial Sensing Distance w/C-AMS12 Target
Average Sensing 0.250” ± 0.025” (6.35 mm ± 0.64 mm)
Average Reset 0.031” ± 0.015” (0.79 mm ± 0.38 mm)
Pressure Rating At Sensing Surface: 2,000 psi (137.89 bar)
Thread Options: 5/8”-18 UNF (Consult TopWorx for metric thread
options)
Operating Temperature:
C7 & R7 SWITCHES
Qualied Life (Years) Max. Normal Op. Temp.*
5 76 °C
10 69 °C
20 63 °C
40 57 °C
60 52.5 °C
ATEX: -40°C (-40°F) to 150°C (302°F)
*The switch service (qualied) life depends on its operating temperature.
Contact Material: Palladium silver with Sawtooth surface conguration
Contacts: Single Pole, Double Throw, Form C.
C8, H8, & M8
Specications - DPDT
Coaxial Sensing Distance w/ C-AMS7A Target
Average Sensing 0.100” ± 0.020” (2.54 mm ± 0.51mm)
Average Reset 0.023” ± 0.010” (0.58 mm ± 0.25mm)
Coaxial Sensing Distance w/C-AMS12 Target
Average Sensing 0.250” ± 0.025” (6.35 mm ± 0.64 mm)
Average Reset 0.031” ± 0.015” (0.79 mm ± 0.38 mm)
Pressure Rating At Sensing Surface: 2,000 psi (137.89 bar)
Thread Options: 1”-14 UNF (Consult TopWorx for metric thread options)
Operating Temperature:
C8, H8, & M8 SWITCHES
Qualied Life (Years) Max. Normal Op. Temp.*
5 76 °C
10 69 °C
20 63 °C
40 57 °C
60 52.5 °C
ATEX: -40°C (-40°F) to 150°C (302°F)
*The switch service (qualied) life depends on its operating temperature.
Contact Material: Palladium silver with Sawtooth surface conguration
Contacts: Double Pole Double Throw, 2 Form C.
■ C7, C8, H7, H8, M7,M8,
R7 and SV-7 nuclear
service GO Switches
must be installed with
TopWorx qualied target
magnets. Reference
sensing ranges in
corresponding sections
throughout the catalog.
■ Sensing and dierential
of switch may vary
depending on target
travel direction.
■ Congure mounting of
the switch and/or target
so that target passes
within the sensing
area without physically
contacting the switch.
Sensing range will vary
according to switch and
target mode.
■ For heavy or
inductive loads, arc
suppression devices,
or interposing relays
are recommended
for contact longevity.
Contact factory for
specics.
■ Installation must use
included Jam nuts and
Lock washers.
■ Recommended
installation distance
is equal to the half
of published sensing
distance per switch.
Electrical Ratings
Contact Ratings*
(Resistive)
Power (W) 0.5 - 480 0.2 - 72
Voltage (V) 100 - 250 24 - 137
Current (A) 0.004 - 5.0 0.004 - 3.0
ATEX (all except SV7): 4A @120VAC / 3A @ 24VDC
*Consult factory for higher Amp rating requirements
Target Material: Target magnets C-AMS7A or C-AMS12
Enclosure Material: SS type 303 or 316
Conduit Outlet: 1/2”-14 NPT. One location
AC DC
GO SWITCH HOOK-UP DIAGRAMS C7, R7, H7, M7, and SV7
SPDT (Form C) Contacts May be wired Form A (N/O) or B (N/C)
Electrical Ratings
Contact Ratings*
(Resistive)
Power (W) 0.5 - 480 0.2 - 72
Voltage (V) 100 - 250 24 - 137
Current (A) 0.004 - 5.0 0.004 - 3.0
ATEX: 4A @ 120VAC / 3A @ 24VDC
*Consult factory for higher Amp rating requirements
Target Material: Target magnets C-AMS7A or C-AMS12
Enclosure Material: SS type 303 or 316L (RCC-EK1+)
Conduit Outlet: 3/4”-14 NPT. One location
AC DC
C8, H8, and M8
DPDT (2 Form C) Contacts
Electrical Ratings:
Contact Ratings*
(Resistive)
Power (W) 0.5 - 480 0.2 - 72
Voltage (V) 100 - 250 24 - 137
Current (A) 0.004 - 5.0 0.004 - 3.0
ATEX: 3A @ 120VAC / 1A @ 24VDC
*Consult factory for higher Amp rating requirements
Target Material: Target magnets C-AMS7A or C-AMS12
Enclosure Materials: SS type 303
Conduit Outlet: 3/4”-14 NPT. One location
AC DC
Setting Up A Nuclear Service GO Switch For Optimum
Performance
Nuclear service GO Switches use permanent magnets and a push-pull
plunger to control a set of dry contacts. When a target magnet enters the
sensing area of the switch, it attracts the primary magnet, which pulls the
connecting rod and common contact. The normally closed and normally
open contacts change state.
(Continued on page 2.)
Page 1

IOM
*
*
C7 & R7 SPDT
4 COND. Peek Cable
N/C Red
N/O Blue
COM Black
GND Green
C8, H8, & M8 DPDT 7 COND.
Peek Cable & EGS Connector
N/C1 Red
N/O1 Blue
COM1 Black
N/C2 Yel low
N/O2 Brown
COM2 Natural
GND Green
EGS 4 Pin Connector
N/C A Red
N/O B White
COM C Black
GND D Green
C7 & R7 SPDT
4 COND. Peek Cable
N/C Red
N/O Blue
COM Black
GND Green
C8, H8, & M8 DPDT 7 COND.
Peek Cable & EGS Connector
N/C1 Red
N/O1 Blue
COM1 Black
N/C2 Yel low
N/O2 Brown
COM2 Natural
GND Green
EGS 4 Pin Connector
N/C A Red
N/O B White
COM C Black
GND D Green
TM
C7, C8, H7, H8,
M7,M8, R7, SV7
Attachment of Conduit or Cable Continued:
The sensing distance recommended by TopWorx is the maximum distance between
the switch and target magnet trip point. The average reset, also known as deadband
or hysteresis, is the distance that the target magnet must move from the sensing
area in order to allow the switch to reset.
To apply the Nuclear service GO Switch and obtain the least dierential, the direction
the target approaches the switch must be considered (axial, radial).
The measurements shown are nominal depending on the size of target magnet used
in the application. Consult the coaxial sensing distance for each switch model listed
in this IOM.
With proper mounting, once the switch is set, the GO Switch will maintain calibration
for life. See illustration below for correct switch alignment.
C-AMS7A Target Magnet C-AMS12 Target Magnet
*
*
*Refer to switch specications for average sensing distance.
The target magnet threads need to be properly torqued when mounted to any xture.
The target magnets were mounted at a torque value of 35 lbs-ft (47.45 Nm) with a
tolerance of + /- 2 lbs.-ft. (2.71 Nm) during seismic testing.
0518
II 2 GD
Ex d IIC T3 Gb; Ex tb IIIC T200 °C Db (Tamb - 40 °C to + 150 °C)
Baseefa08ATEX0360X
IECEx BAS 08.0122X
120VAC/4A AND 24VDC/3A FOR SPDT SWITCHES
120VAC/3A AND 24VDC/1A FOR DPDT SWITCHES
PLEASE NOTE: THE SV7 SWITCH IS NOT CERTIFIED BY ATEX OR IECEx.
Attachment of Conduit or Cable
Attach conduit or cable correctly.
The switch conduit or cable needs to be properly supported when mounted to any
xture. During seismic testing, the stainless steel conduit (with PEEK cable) was
supported at 3.28 ft (1 m) from the back of the switch while the Rockbestos or PEEK
cables were supported at 1 ft (0.305 m) away from the back of the switch. EGS Flex
conduit and support kit are available from TopWorx as an option. During seismic
testing of the C7 switch with EGS QDC and ex conduit, the ex conduit was
supported 15”- 48” from the QDC interface. Please consult factory for more detailed
information.
– If the switch is mounted on a moving part, be sure exible conduit is long enough
to allow for movement, and positioned to eliminate binding or pulling.
– For installation in hazardous locations, check local electrical codes.
– All conduit connected switches should be installed using proper installation
methods.
– The GO Switch must have a qualied QDC, a qualied sealed stainless steel
conduit, or other types of qualied accepted seal when used in submerged
applications or exposed to 100% humidity. For LOCA DBA type submergence,
however, only the C7 switch has been qualied for this application.
– Per Qualtech Report No. TR-23009-14 Rev A, the EGS O-ring qualied life at
continuous operation, without disconnection, is 25.1 years at 144.14 of (62.3
°C). If for any reason these assemblies need to be detached prior to installation
or while in operation, the O-rings must then be replaced. The maximum shelf
life that can be assigned for the O-Ring is 10 years from the cure date. As long
as the O-Rings have been stored per the guidelines of ANSI N45.2.2, Level B
(now ASME NQA-1, Part II, Subpart 2.2, Level B), the O-Ring may be placed into
installed service any time prior to the shelf life expiration date without impinging
on the qualied life outlined above
All GO Switches are “pure” contact switches, meaning they have negligible
voltage drop when closed, nor do they have any leakage current when open.
For multi-unit installation, switches may be wired in series or parallel, as
shown to the right.
Series Wiring
Any number of GO Switches may be
wired in series, without voltage drop.
Parallel Wiring
Any number of GOTM Switches may be
wired in parallel, with no current leakage
and without drawing operating current.
Special Conditions for Safe Use
The eld side wires should be protected against damage and terminated to a
terminal or junction box suitable for the conditions of use.
Due to the GO Switch’s sealed construction, eld service is not available. Refer to
our trouble shooting guide for a possible solution. If problem persists, please contact
the factory directly.
EU Declaration of Conformity
The products described herein, conform to the provisions of the following European
Community Directives, including the latest amendments:
Low Voltage Directive (2006/95/EC)
EMC Directive (2004/108/EC)
ATEX Directive (2014/34/EU)
C7 & R7 SPDT
4 COND. Peek Cable
N/C Red
N/O Blue
COM Black
GND Green
Visit www.topworx.com for
comprehensive information
on our company, capabilities,
and products– including
model numbers, data sheets
specications, dimensions, and
certications.
info@topworx.com
www.topworx.com
The Emerson logo is a trademark and service mark of Emerson Electric Co. ©2016 Emerson Electric Co. ©2016
TopWorx, All rights reserved. TopWorx™ and GO™ Switch are all trademarks of TopWorx. All other marks are the
property of their respective owners. Information herein – including product specications – is subject to change without
notice.
C8, H8, & M8 DPDT 7 COND.
Peek Cable & EGS Connector
N/C1 Red
N/O1 Blue
COM1 Black
N/C2 Yel low
N/O2 Brown
COM2 Natural
GND Green
GLOBAL SUPPORT OFFICES
Americas
3300 Fern Valley Road
Louisville, Kentucky 40213
USA
+1 502 969 8000
Asia-Pacic
1 Pandan Crescent
Singapore 128461
+65 6891 7550
Europe
Horseld Way
Bredbury Industrial Estate
Stockport SK6 2SU
United Kingdom
+44 0 161 406 5155
EGS 4 Pin Connector
N/C A Red
N/O B White
COM C Black
GND D Green
Middle East
P.O. Box 17033
Jebel Ali Free Zone
Dubai 17033
United Arab Emirates
971 4 811 8283
Africa
24 Angus Crescent
Longmeadow Business Estate East
Gauteng, South Africa
+27 011 451 3700
Page 2 ES-02006-1 R14