TJERNLUND XCHANGER X2D Installation Instructions Manual

Page 1
INSTALLATION INSTRUCTIONS
XCHANGER
TM
MODEL
X2D
OWNER'S INSTRUCTIONS, DO NOT DESTROY
Copyright © 2010, Tjernlund Products, Inc. All rights reserved. P/N 8504164
THIS DEVICE MUST BE INSTALLED BY A
READ INSTRUCTIONS CAREFULLY PRIOR TO
INSTALLATION AND OPERATION OF THE XCHANGER.
REV. A 05/10
TJERNLUND PRODUCTS, INC.
1601 Ninth Street • White Bear Lake, MN 55110-6794 PHONE (800) 255-4208 • (651) 426-2993 • FAX (651) 426-9547 Visit our web site • ww w.tjernlund.com
Page 2
1
TABLE OF CONTENTS
Descriptions and Specifications.......................................................................................................................................1
Installation Restrictions....................................................................................................................................................1
Cautions ..........................................................................................................................................................................2
Recommended Methods and Patterns of Operation....................................................................................................2-3
Recommended Installation and Termination Locations................................................................................................3-4
X
CHANGER
TM
Installation..............................................................................................................................................4-6
Dehumidistat Control Module Installation & Operation ...................................................................................................6
X
CHANGER
TM
Ladder Diagram ........................................................................................................................................6
Maintenance....................................................................................................................................................................7
How to Obtain Service & Warranty..................................................................................................................................7
Replacement Parts & Accessories..................................................................................................................................7
X
CHANGER
TM
is a trademark of Tjernlund Products, Inc. Tjernlund Products welcomes your comments and questions. Call us at (651) 426-2993, (800) 255-4208, Fax (651) 426-9547, email us
at fanmail@tjfans.com or write to: Customer Service, Tjernlund Products, Inc., 1601 Ninth Street, White Bear Lake, MN 55110-6794.
DESCRIPTION
The XCHANGE
R
TM
model X2D is a dual fan mechanical ventilator capable of exhausting inside air, providing fresh outside air or provid­ing a balanced air exchange. The fans can be independently switched on or off or be easily reversed to provide fresh outside air or exhaust inside air. The X2D includes a dehumidistat control which operates the fan(s) based on the relative humidity sensed by the control inside the home. The dehumidistat control includes an “On” setting that will operate the fan(s) continuously or the switch can be turned “Off” so the fan(s) do not operate during undesireable seasons. The X
CHANGER
TM
can also be operated by a standard
plug-in timer. Tjernlund’s optional SCP speed control kit is also available if desired.
SPECIFICATIONS
GENERAL INFORMATION
Each XCHANGERTMis electrically factory line tested before shipment. After opening carton, Inspect thoroughly for hidden damage.
INSTALLATION RESTRICTIONS
WARNING: Improper installation, adjustment, alterations, service or maintenance can cause injury or property damage. Refer to
this manual. For assistance or additional information consult a qualified installer, service agency or the equipment supplier.
WARNING: Sufficient air is needed for proper combustion and exhausting of gases through the flue (chimney) of fuel burning equip-
ment to prevent backdrafting. Follow the heating equipment manufacturer’s guideline and safety standards such as those published by the National Fire Protection Association (NFPA), and the American Society for Heating, Refrigeration and Air Conditioning Engineers (ASHRAE), and the local code authorities.
WARNING: Do not exhaust air from mechanical room unless makeup air is also supplied or equipment in mechanical room is sealed
combustion. Carbon monoxide poisoning may result. Use the DT2-6 6” duct take-off kit so exhaust can be removed from outside the mechanical room if necessary.
Observe proper location of hood as described on page 3. The X
CHANGER
TM
must only be installed with the hood on an exterior wall.
Only X
CHANGER
TM
fans can be plugged into dehumidistat control module or damage may result.
Do not discharge intake air onto water pipes or other equipment which may be affected by temperature extremes.
MODEL X2D XCHANGER
Dehumidistat: 20% - 80% RH Range Rough-in Wall Opening Dimensions: 12 1/4” x 5 1/4””
1 FAN 2 FANS Voltage 120 120 Watts 20
40
Amps 0.3
0.6
CFM 90
180
Page 3
2
CAUTIONS
WARNING: Failure to install, maintain and/or operate the XCHANGERTMin accordance with manufacturer’s instructions may result in
conditions that can produce bodily injury and property damage.
Disconnect power supply to fans and/or control when reversing fan direction or servicing the X
CHANGER
TM
. Failure to do so may
result in personal injury and/or equipment damage. Make certain the power source is adequate for the X
CHANGER
TM
requirements. Do not add the XCHANGERTMto a circuit where the
total electrical load is unknown.
XCHANGER DEHUMIDISTAT CONTROL MODULE OPERATION
The XCHANGERTMcontrol module includes an adjustable dehumidistat control which activates the fan(s) if the relative humidity rises above the selected set-point. It is generally recommended to maintain a Relative Humidity (RH) below 60% to inhibit mold growth. The dehumidistat can be turned fully clockwise to the ‘on’ position for constant fan(s) operation or it can be turned fully counter-clockwise to ‘off’ during seasons or times when it is not desired for the X
CHANGER
TM
fan(s) to run. Each fan can be independently turned on/off by its fan
switch on control module.
STANDARD PLUG-IN TIMER OPERATION
A standard adjustable timer can also be utilized for timed operation of the XCHANGERTMfan(s). Plug timer into standard outlet and plug X
CHANGER
TM
control module into wall timer. Turn dehumidistat control fully clockwise
to the ‘on’ position. Both outlets in X
CHANGE
R
TM
control module will be controlled by the wall timer. Each fan can be independently turned on/off by its fan switch on dehumidistat control module. You can also allow the dehumidistat control to turn the XCHANGERTMon during certain times of the day if you use a timer and keep the dehumidistat control at the desired set-point.
TJERNLUND OPTIONAL SCP SPEED CONTROL OPERATION
Tjernlund’s optional SCP speed control can be used to vary the speed of both X
CHANGER
TM
fans. Plug SCP
speed control into standard outlet and plug X
CHANGER
TM
control module into SCP speed control. Both outlets in
X
CHANGER
TM
control module will be controlled by the SCP speed control. Each fan can be independently
turned on/off by its fan switch on dehumidistat control module.
RECOMMENDED PATTERNS OF OPERATION
The XCHANGERTMX2D model includes a dehumidistat control which can cycle the XCHANGERTMfan(s) automatically based on the rel­ative humidity level of the house or it can be operated based on recommendations below. It is generally recommended to maintain a Relative Humidity (RH) below 60% to inhibit mold growth.
A standard plug-in wall timer can be programmed based on the lifestyle or needs of the occupants. For example, a family with smok­ers may want to cycle the X
CHANGER
TM
more frequently than a family of non-smokers.
Another timed method may be to cycle the X
CHANGER
TM
during peak usage of exhaust fans, such as bathroom, kitchen, laundry or
utility. Outdoor air should be brought in at these peak times to help balance out pressure inside the house. The X
CHANGER
TM
can be cycled on and off at regular intervals to periodically provide fresh air to the home, exhaust stale air or have one fan bring air in and the other fan exhaust air for a balanced air exchange. It can also be ran like an economizer to bring outside air in during evening time when it is cooler outside.
HYPOTHETICAL XCHANGER OPERATION BASED ON LIFESTYLE
The example below shows a possible way in which cycling times of the XCHANGERTMmay be determined based on household occupant lifestyles.
6:00 A.M. to 9:00 A.M. = Outside fresh air should be brought into the house to compensate for morning routines. Bathing, cooking, laundry and other activities such as smoking necessitate that outside fresh air to be brought in. Depressurization of the house at these times is common with many exhaust fans running at one time.
9:00 A.M. to 4:00 P.M. = House is normally vacant with occupants at work or school. Cycle X
CHANGER
TM
on and off for 15 minute
intervals per hour to assure fresh air is supplied to the house. 4:00 P.M. to 8:00 P.M. = Outside fresh air should be brought into the house to compensate for evening routines. Bathing, cooking,
laundry and other activities such as smoking necessitate that outside fresh air to be brought in. Depressurization of the house at these times is common with many exhaust fans running at one time.
8:00 P.M. to 6:00 A.M. = All members of the household are usually present. Outside fresh air is needed to dilute occupant generated carbon dioxide during sleeping. Cycle X
CHANGER
TM
on and off for 15 minute intervals, with occasional 30 minute intervals to assure
fresh air is supplied to house.
Page 4
XCHANGER OPERATION BASED ON AIR CHANGES PER HOUR
This method of operation can be used to supplement or provide for guaranteed air change rates. Table 1 shows the constant Cubic Feet Per Minute (CFM) of air necessary to produce the desired Air Change Per Hour rate (ACH), assuming natural infiltration of out­side air at a rate of .10 ACH. Square footage is determined by calculating the finished living space of the house. Garages and crawl space should not be included. The constant CFM figures shown assume that the living space has standard 8 foot ceilings.
1. Determine square footage of house living space on left hand column.
2. Pick desired air change rate from top row.
3. Locate intersection of these points to determine constant CFM that should be obtained to meet desired ACH. The X
CHANGER
TM
will provide 180 CFM with both fans and 90 CFM with one fan operating. Where the CFM delivery of the XCHANGERTMexceeds that listed in Table 1, a standard plug-in timer can be set so the XCHANGERTMis cycled to obtain the desired ACH or Tjernlund’s optional SCP speed control may be used.
EXAMPLE
3000 square feet of living space
.2 ACH desired ventilation rate equals 40 CFM
X
CHANGER
TM
capacity of 90 CFM (with one fan running)
In this example the plug-in timer may be set so that the X
CHANGER
TM
operates for one half hour straight each hour or two fifteen
minute periods each hour.
RECOMMENDED INSTALLATION LOCATION
The XCHANGERTMmay be mounted anywhere in the house. The best place to mount it is the basement through the rim joist on top of the foundation wall.
WARNING: Do not exhaust air from mechanical room unless makeup air is also supplied or equipment in mechanical room is sealed
combustion. Carbon monoxide poisoning may result. Use the DT2-6 6” duct take-off kit so exhaust can be removed from outside the mechanical room if necessary.
It is required that the X
CHANGER
TM
be installed in a location where it will not be directed at the occupants. Do not discharge intake air
onto water pipes or other equipment which may be affected by temperature extremes. Do not terminate adjacent to thermostat. Outside temperatures can disrupt normal thermostat operation. Do not terminate within three feet from a barometric draft control or intake grille of a heating appliance.
XCHANGER HOOD TERMINATION CLEARANCES
Install XCHANGERTMin accordance with BOCA national Mechanical Codes M-306.1 and M-306.1.1 as follows, (See Diagram A). M-306.1 LOCATION: Outside air exhaust and intake openings shall be located a minimum of 10 feet (3048mm) from lot lines or build-
ings on the same lot. When openings front on a street or public way, the distance shall be measured to the centerline of the street or public way.
M-306.1.1 INTAKE OPENINGS: Outside air intake openings shall be located a minimum of 10 feet (3048mm) from any hazard or noxious contaminant such as vents, chimneys, plumbing vents, streets, alleys, parking lots and loading docks. When a source conta­minant is located within 10 feet (3048mm) of an intake opening, such opening shall be located a minimum of 2 feet (610mm) below the contaminant source.
IN ADDITION TO THESE CODES THE MANUFACTURER RECOMMENDS THAT:
• The X
CHANGER
TM
hood should be a minimum of 1 foot above grade or anticipated snow line.
• The X
CHANGER
TM
hood should be a minimum of 3 feet from an inside corner of the building.
3
TABLE 1
Page 5
4
INSTALLATION (TOOLS REQUIRED)
• Reciprocating saw • 5/16” nut runner or socket • Siding tools (dependent on exterior finish)
• Drill and 1/2” bit • Phillips screwdriver • Level
INSTALLATION
NOTE: Before cutting opening through wall, confirm XCHANGERTMhood termination clearances are met as noted on bottom of page 3.
1. A) Center template and tape to the rim joist between the floor joists/trusses X
CHANGE
R
TM
will be mounted through, (See
Diagram B).
B) If X
CHANGER
TM
is not installed between floor joists or trusses, attach the template to the wall it will be exiting, ensuring
XCHANGE
R
TM
will be level.
2. CAUTION: When cutting or drilling into wall, do not damage electrical wiring and other hidden utilities. Using a 1/2” bit, drill pilot holes noted on the template from inside through rim joist, wall board, siding, etc., keeping drill bit perpendicular to the wall. 1/2” bit must be long enough to penetrate through exterior.
3. Use a level to mark (4) holes drilled in step 2 and connect the holes on building exterior, (See Diagram C). Use a saw to remove material between marks, (See Diagram D).
DIAGRAM B
DIAGRAM C
DIAGRAM D
CENTER TEMPLATE BETWEEN JOISTOR PLACE ON WALL XCHANGER WILL EXIT.
DRILL (4) 1/2” CORNER HOLES THROUGH WALL FROM INTERIOR AND CONNECT HOLES ON EXTERIOR WITH ALEVEL.
CUT OPENING ALONG MARKED LINES.
DIAGRAM A
Page 6
4. Remove fans if necessary and insert XCHANGERTMhousing through exterior wall opening with fan openings facing down, (See Diagram H). For vinyl or other types of lap siding, level X
CHANGER
TM
and trace outer flange on X
CHANGER
TM
housing and
trim siding back enough to install J channel or appropriate flashing, (See Diagram E).
5. Insert (6) push clips through embossed holes of housing. Direction of clips must be as shown, (See Diagram F).
6. Place a bead of caulk on X
CHANGER
TM
mounting flange or building sheathing before inserting housing, (See Diagram G).
7. Remove fans if necessary and insert X
CHANGER
TM
housing through exterior wall opening with fan openings facing down, (See Diagram H).
8. Level housing and secure to wall using (4) screws, (See Diagram I). Install J channel or appropriate flashing around X
CHANGER
TM
mounting flange. Do not cover up mounting flange or hood will not snap on push clips, (See Diagram J).
9. Carefully align and then snap hood on (6) push clips. Apply a bead of caulk around hood and siding, (see Diagram K).
10. Insert plastic nut into X
CHANGER
TM
base. Assemble mounting bracket as shown, (See Diagram M). Attach assembled bracket to bottom of XCHANGERTM. Mark bracket mounting location on wall with a slight upward pitch in rear of X
CHANGER
TM
and connect
to wall using provided wall anchor, (See Diagram L).
5
DIAGRAM F
DIAGRAM E
DIAGRAM G
INSERT (6) PUSH CLIPS THROUGH EMBOSSED HOLES OF HOUSING. CLIPS MUST BE INSERTED AS SHOWN.
LEVEL XCHANGER AND TRACE FLANGE. TRIM SIDING BACK SO XCHANGER FLANGE CAN BE MOUNTED FLUSH TO EXTERIOR SHEATHING.
PLACE ABEAD OF CAULK ON XCHANGER MOUNTING FLANGE OR BUILDING SHEATHING BEFORE INSERTING HOUSING.
DIAGRAM J
INSTALLJ CHANNEL OR APPROPRIATE FLASHING AROUND XCHANGER MOUNTING FLANGE.
DIAGRAM M
ASSEMBLE XCHANGER MOUNTING BRACKET.
DIAGRAM L
ATTACH MOUNTING BRACKET TO BOTTOM OF XCHANGER. INSTALLBRACKET SO XCHANG­ER HAS ASLIGHT UPWARD PITCH IN REAR.
INSERT PLASTIC NUT INTO XCHANGER BASE
WALL ANCHOR
DIAGRAM I
LEVEL HOUSING AND SECURE TO WALLUSING (4) SCREWS.
DIAGRAM K
CAREFULLYALIGN AND THEN SNAP HOOD ON (6) PUSH CLIPS. APPLY A BEAD OF CAULK AROUND HOOD AND SIDING.
DIAGRAM H
INSERT XCHANGER HOUSING THROUGH WALL. FAN OPENINGS MUST FACE DOWN.
FAN OPENINGS FACING DOWN
Page 7
6
11. The damper stop prevents unwanted air infiltration through either fan. The Damper stop can be adjusted so the damper does not swing open into the house by wind or a negative pressure in the house. IMPORTANT: The damper stop prevents the damper from swinging inward and should not be used if using the XCHANGERTMfan to bring outside air in. With the damper stop pushed all the way forward, the damper will swing both ways. With the damper stop pulled all the way back, the damper will only swing to the outside. Use the damper stop only if you want to block air infiltration into the house during seasons when the X
CHANGER
TM
is not
being used or when using the XCHANGERTMonly to exhaust air, (See Diagram N). .
12. WARNING: Unplug fans from dehumidistat control when changing fan direction to prevent damage or injury. Insert fans in desired
direction for either exhaust or intake. See arrow on bottom of fan cartridge or side of fan shroud for air flow direction. Once installed confirm the air is being exhausted or supplied depending upon application, (See Diagram O).
13. Insulate around X
CHANGER
TM
housing with fiberglass insulation, (See Diagram P). IMPORTANT: Do not use expanding foam on
top of XCHANGERTMcase to prevent binding of damper slides. Make sure damper slides move freely.
XCHANGER DEHUMIDISTAT CONTROL MODULE INSTALLATION & OPERATION
Install XCHANGERTMdehumidistat control module on wall with provided screws and wall anchors and plug X
CHANGER
TM
fans into side outlets.
IMPORTANT: Do not plug other devices into dehumidistat control or damage may result. Once fans are installed in X
CHANGER
TM
, plug dehumidistat control into standard outlet.
The X
CHANGER
TM
control module includes an adjustable dehumidistat control which activates the fan(s) if the relative humidity rises above the selected set-point. It is gener­ally recommended to maintain a Relative Humidity (RH) below 60% to inhibit mold growth. The dehumidistat can be turned fully clockwise to the ‘on’ position for constant fan(s) operation or it can be turned fully counter-clockwise to ‘off’ during seasons or times when it is not desired for the X
CHANGER
TM
fan(s) to run. Each XCHANGERTMfan is independently controlled by its own on/off switch. Turn switch(s) off during seasons or applications where it is not desired to run that fan, (See Diagram Q).
XCHANGER LADDER DIAGRAM
DIAGRAM N
DIAGRAM O
THE DAMPER WILL SWING BOTH WAYS WITH THE DAMPER STOP PUSHED FORWARD. THE DAMPER WILL ONLY SWING TO THE OUTSIDE WITH THE DAMPER STOP PULLED ALL THE WAY BACK.
DIAGRAM Q
SCREW DEHUMIDISTAT CONTROL TO WALLAND PLUG FANS INTO SIDE OUTLETS.
WARNING: UNPLUG FANS WHEN CHANGING DIRECTION. SEE ARROW ON BOTTOM OF FAN CARTRIDGE OR SIDE OF FAN SHROUD FOR AIR FLOW DIRECTION.
DIAGRAM P
INSULATE AROUND XCHANGER HOUSING. IMPORTANT: DO NOT USE EXPANDING FOAM ON TOP OF XCHANGER TO PREVENT BINDING OF DAMPER SLIDES. MAKE SURE DAMPER SLIDES MOVE FREELY.
120 VAC 50/60 Hz
DE-HUMIDISTAT
CHANGE CONTROL BOX
HOT BLACK
WHITE
8050022
BLACK
NEUTRAL BLACK
BLUE
RED
RED
RED
RED
RX
SWITCHED OUTLETS
FAN SWITCH 2
FAN SWITCH 1
XCHANGER FANS
IMPORTANT:
ONLY PLUG XCHANGER FANS INTO CONTROL!
FAN ON/OFF SWITCHES
Page 8
MAINTENANCE
The XCHANGERTMhood screen must be inspected every 3 to 6 months. Remove any foreign material such as leaves, lint, cottonwood or other items. Remove screen to clean if necessary. Replace screen with bent edge facing up and in the front of hood, (See Diagram R).
HOW HOW TO OBTAIN SERVICE ASSISTANCE
1. If you have any questions about your X
CHANGER
TM
or if it requires adjustment, repair or routine maintenance, we suggest
that you contact your installer, contractor or service agency.
2. If you require technical information contact Tjernlund Products, Inc. at 1-800-255-4208 or email us at fanmail@tjfans.com. When contacting Tjernlund Products, Inc., please have the following information available:
1. Model number and date code of the X
CHANGER
TM
2. Name and address of installer and service agency
3. Date of original installation and dates any service work was performed
4. Details of the problem
LIMITED PARTS WARRANTY AND CLAIM PROCEDURE
Tjernlund Products, Inc. warrants the components of the XCHANGERTMfor one year from date of installation. This warranty covers defects in material and workmanship. This warranty does not cover normal maintenance, transportation or installation charges for replacement parts or any other service calls or repairs. This warranty DOES NOT cover the complete X
CHANGER
TM
if it is operative,
except for the defective part. Tjernlund Products, Inc. will issue credit or provide a free part to replace one that becomes defective during the one year warranty
period. All receipts should include the date code of the X
CHANGER
TM
to ensure that the defective component corresponds with the
complete unit. This will help prevent possible credit refusal.
1.) Follow troubleshooting guide to determine defective component. If unable to determine faulty component, contact your Tjernlund distributor, Tjernlund Products Technical Customer Service Department at 1-800-255-4208 for troubleshooting assistance or email us at fanmail@tjfans.com.
2.) After the faulty component is determined, return it to your Tjernlund distributor for replacement. Please include X
CHANGER
TM
date code component was taken from. Credit or replacement will only be issued to a Tjernlund distributor after the defective part has been returned prepaid to Tjernlund.
WHAT IS NOT COVERED
Product installed contrary to our installation instructions Product that has been altered, neglected or misused Any freight charges related to the return of the defective part Any labor charges related to evaluating and replacing the defective part
XCHANGER PARTS AND ACCESSORIES
REPLACEMENT PARTS
XCHANGERTMFan Assembly 950-8350 X
CHANGER
TM
Dehumidistat 950-8351
X
CHANGER
TM
X2D Hood Screen 950-8352
ACCESSORIES
6” Duct Take-Off Kit DT2-6 Plug-In Speed Control SCP
7
TJERNLUND LIMITED 1 YEAR WARRANTY
Tjernlund Products, Inc. warrants to the original purchaser of this product that the product will be free from defects due to faulty material or workmanship for a period of (1) year from the date of original purchase or delivery to the original purchaser, whichever is earlier. Remedies under this warranty are limited to repairing or replacing, at our option, any product which shall, within the above stated warranty period, be returned to Tjernlund Products, Inc. at the address listed below, postage prepaid. THERE ARE NO WARRANTIES WHICH EXTEND BEYOND THE DESCRIPTION ON THE FACE HEREOF, AND TJERNLUND PRODUCTS, INC. EXPRESSLY DISCLAIMS LIABILITY FOR INCIDENTALOR CONSEQUENTIAL DAMAGES ARISING FROM THE USE OF THIS PRODUCT. THIS WARRANTY IS IN LIEU OF ALL OTHER EXPRESS WAR­RANTIES AND NO AGENTIS AUTHORIZED TO ASSUME FOR US ANYLIABILITYADDITIONAL TO THOSE SET FORTH IN THIS LIMITED WARRANTY. IMPLIED WAR­RANTIES ARE LIMITED TO THE STATED DURATION OF THIS LIMITED WARRANTY. Some states do not allow limitation on how long an implied warranty lasts, so that limitation may not apply to you. In addition, some states do not allow the exclusion or limitation of incidental or consequential damages, so that above limitation or exclu­sion may not apply to you. This warranty gives you specific legal rights and you may also have other rights which may vary from state to state. Send all inquiries regard­ing warranty work to Tjernlund Products, Inc. 1601 9th Street, White Bear Lake, MN 55110-6794. Phone (651) 426-2993 • (800) 255-4208 • Fax (651) 426-9547 • Email fanmail@tjfans.com.
DIAGRAM R
INSERT HOOD SCREEN WITH BENT EDGE FACING UPAT FRONT OF HOOD.
Loading...