TJERNLUND PAI-3,PAI-4,PAI-5, PAI-6,PAI-7 User Manual

Page 1
Insufficient combustion air causes:
Flue gas spillage, flame roll-outs, decreased efficiencies, and reduced heating equipment life.
Conventional metal louvers often are a major cause of these problems:
Unregulated outdoor air supply
Architecturally unsightly large
outside wall openings that often require structural reinforcement.
Mechanical room freeze ups in
northern climates.
Often not compatible with below grade or
interior mechanical rooms.
Tjernlund In-Forcer combustion air intakes are packaged systems engineered to provide controlled, interlocked combustion air.
Wall or roof opening size can be reduced by up
to 80% compared to conventional metal louvers.
In-Forcers include
matching, low profile intake hoods that can be mounted on either a roof or sidewall.
Use small diameter
duct to deliver out­door air up to 100 feet away from intake hood.
Complies with Mechanical
Code requirements for combustion air supply.
Page 2
Use in virtually all mechanical room locations
The IN-FORCER can be ducted up to 100 equivalent feet from the intake hood. Even isolated mechanical rooms can easily be supplied with outdoor combustion air. Cold outdoor air can be distributed through standard ducts and diffusers at ceiling level, allowing the air to be tempered as it drops to the floor, eliminating cold spots in the mechanical room. Mechanical room noise transfer to the outside is further reduced since there is no direct wall opening, typical of standard air intake louvers.
Variety of applications
Restaurant kitchens with negative pressure caused by exhaust fans
Interior mechanical rooms with no direct access to an outside wall
Conversions from electricto gas or oil heating appliances
Duct air from roof
top for interior
mechanical rooms
Intake direct thru outside wall
Run horizontal duct up to 100 feet
Compared to standard louvers, wall openings can be reduced by up to 80%. This eliminates the need for extra support around the opening that can cost far more in extra construction labor and materials than the total installed cost of an IN-FORCER.
What’s more, IN-FORCER’S low profile hood blends into a sidewall or roofline and is designed to keep wind and rain out. Heavy duty 5052 aluminum construction will not corrode.
Small wall opening lowers installation cost
Improves building’s
exterior appearance
The original and most
practical alternative
to metal louvers
BY TJERNLUND
Support beams are typically required on larger louvered intakes
IN-FORCER requires maximum 12'' opening and no extra support
sidewall mounted hood roof mounted hood
Confined space installations
Below grade mechanical rooms
Factories where processes cause backdrafting
of heating equipment
Laundries, dry cleaners, indoor pools, etc. with chemically contaminated atmosphere
Page 3
UC1 with
MAC1E
or
MAC4E
Easy installation and servicing
Millivolt Safety Interlock Kit
Model WHKE
For use with UC1 Universal Control, MAC1E or MAC4E auxiliary controls. The WHKE gas pressure switch actuates the IN-FORCER through the A – B dry contacts. The Linear Limit switch disables the heater in the event of a venting malfunction. Includes JA1 thermocouple junction adapter. To interlock millivolt water heater(s) only with a UC1 controlled IN-FORCER add a WHKE for each millivolt heater. To interlock a millivolt water heater and one 24/115 VAC furnace or boiler with a UC1 controlled IN-FORCER, add a WHKE and a MAC1E.
Standard Safety Features
IN-FORCER can be easily inter-
locked with multiple appliances.
Managed air distribution assures comfort
Intake air from the IN-FORCER can be easily diffused to eliminate concentrated cold air. Air can also be heated with a hot water, steam or conventional unit heater.
The IN-FORCER includes a high limit switch to deactivate the system in the event of a mechanical room fire and a pressure switch to detect blockage or system malfunction.
Universal Control
Model UC1
The UC1 Universal Control is the standardized interlock control for Tjernlund Draft/Ventilation products. The UC1 includes adjustable pre/post purge and LED status/diagnostic indicators. Provides easy interlock with any 24/115 VAC burner control circuit and also includes"dry" contactactuation option.
Multiple Appliance Controls
Models MAC1E, MAC4E
Used in conjunction with the UC1 Universal Control to inter­lock additional 24/115 VAC burners. Powered by and communicates with the UC1 through a factory wired whip. For one additional 24/115 VAC heater add the MAC1E. To interlock up to four or more additional 24/115 VAC heaters, add the MAC4E. MAC4Es can be daisy chained together for more than 5 heaters. Important: Total combined BTU/hr. input of all heaters must be within IN-FORCERs capacity.
Easy interlock options with single or multiple appliances
The IN-FORCER attaches with integral mounting brackets or eye bolts. The inlet/outlet collars are 2 1/4 inches deep for easy duct connection. The IN-FORCER features a blower that slides out for easy servicing and a washable aluminum mesh pre-filter.
Page 4
MAX DUCT LENGTH IN
EQUIV. FEET
100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
98
MAX DUCT LENGTH IN
EQUIV. FEET
100 100 100 100 100 100 100 100
98 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
RIGID DUCT
DIAMETER IN INCHES
6 6 6 6 6 6 6 6 6 8 8 8 8
8 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 12 12 12 12 12 12 12 12 12 12 12 12
GAS
ATMOSPHERIC
GAS POWER BURNER
WITHOUT BAROMETRIC
GAS POWER BURNER
WITH BAROMETRIC
OIL FLAME RETENTION
WITH BAROMETRIC
RIGID DUCT
DIAMETER IN INCHES
6 6 6 6 6 6 8 8 8
8 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 12 12 12 12 12 12 12 12 12 12 12 12
IN-FORCER MODEL APPLICATION CHART
Not Applicable
Not Applicable
MODEL
PAI-3
PAI-4
PAI-5 PAI-6
PAI-7
TJE R NLUN D P R O DU C TS, I N C.
1601 Ninth Street White Bear Lake, MN 55110-6794 Phone: 651.426.2993 800.255.4208 Fax: 651.426.9547 Visit our web site: www.tjernlund.com
Copyright © 2003 Tjernlund Products, Inc. All rights reserved P/N 8500402 Rev B 8/03
DISTRIBUTED BY:
DIMENSIONS (in inches)
A B C IN/OUT
PAI-3 12 9-1/2 20 6 PAI-4 12 9-1/2 20 8 PAI-5 13-3/4 15-1/4 24-1/4 10 PAI-6 13-3/4 15-1/4 24-1/4 10 PAI-7 16-5/8 18 32 12
UNIT SIZE
FRONT VIEW SIDE VIEW
Multiple IN-FORCERS may be installed for capacities larger than shown on chart. Tjernlund UB-Series Universal Blowers are available for larger capacity applications.
MAX DUCT LENGTH IN
EQUIV. FEET
100 100 100 100 100 100 100 100 100 100 100 100 100
95 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
RIGID DUCT
DIAMETER IN INCHES
6 6 6 6 6 6 6 6 8 8 8 8
8 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 12 12 12 12 12 12 12 12 12 12 12 12 12 12
MAX DUCT LENGTH IN
EQUIV. FEET
100 100 100 100 100 100 100
52 100 100 100 100 100 100 100 100 100 100 100 100
95 100 100 100 100 100 100 100
98
RIGID DUCT
DIAMETER IN INCHES
6 6 6 8 8 8
8 10 10 10 10 10 10 10 10 10 10 10 10 10 10 12 12 12 12 12 12 12 12
BTU/HR
INPUT
150,000 200,000 250,000 275,000 300,000 350,000 400,000 450,000 500,000 550,000 600,000 650,000 700,000 775,000 850,000 900,000
950,000 1,000,000 1,100,000 1,200,000 1,300,000 1,400,000 1,500,000 1,600,000 1,700,000 1,800,000 1,900,000 2,000,000 2,100,000 2,200,000 2,300,000 2,400,000 2,500,000 2,600,000 2,700,000 2,800,000 2,900,000 3,000,000 3,100,000 3,200,000 3,300,000 3,400,000 3,500,000 3,600,000 3,700,000
PAI-3
PAI-4
PAI-5
PAI-6
PAI-7
A B C D
PAI-3 14 14 8-1/4 6 PAI-4 17-1/2 17-1/2 10-3/4 8 PAI-5 24-1/2 24-1/2 10-1/2 10 PAI-6 24-1/2 24-1/2 10-1/2 10 PAI-7 31 31 11 12
HOODS
DIA.
For automatic, variable speed combus­tion air or for larger capacity heating systems use the UB-Series Universal Blower and CPC-Series Constant Pressure Controller.
UB-Series Blowers are rated for 575
o
F. and are suitable for combustion air or exhausting flue gas. Capacities up to 6,000 CFM.
UB-Series Fans Also Available