Titus ZECV User Manual

Installation Manual
Installation, Operation & Maintenance of the ZECV
Analog Pressure Controller
General Description
When applying Zcom diusers in an changeover/ bypass application with a constant volume rooftop unit, provisions must be made to control duct static pressure. The duct static pressure is typically controlled by a system bypass damper installed o of the supply duct, and controlled from a static pressure tap installed 2/3 down the main duct.
Figure 2 illustrates a re commended installation of the bypass damper to maximize mixing of the bypass air with the return air. This location of the bypass minimizes the opportunity for developing hot or cold spots in the rooftop. Installation Instructions
ZECV-IOM-1.0 3-1-03
Figure 1. ZECV
These instructions are intended only as a basic guide for the installer. They do not assure compliance with local codes. Consult the authorities having jurisdic tion be terminal.
fore installing this
Receiving Inspection
After unpacking the pressure controller, check it for shipping damage. If any shipping damage is found, report it immediately to the delivering carrier.
Supporting the Terminal
The basic control is light enough so that it can be supported by the duct work in which it is installed. Where the accessory modules such as coils, attenuators or multiple outlets are included, the assembly should be supported directly. Use the support method prescribed for rectangular duct in the job specications.
Duct Connections
Slip the inlet duct over the inlet collar. The diameter of the inlet duct in inches must be equal to the listed size if the terminal: e.g., a duct that actually measures 8 in ches must be tted to a size 8 terminal. Attach the by using standard SMACNA slip and drive connection method. Fasten and seal all connections by the method prescribed by the job specications.
rectangular outlet duct
Figure 2.
Static
Tap
Bypass
Air
Constant Volume Rooftop Unit
Supply
Air
ZECV
Return
Air
Zcom
ZECV-IOM-2.0 3-1-03
Field Wiring Instructions
Inspection
Factory mounted controls and accessories are mounted inside the sheet metal enclosure located on the side of the terminal. Remove the cover and inspect all components for visual damage.
Power and Supply
Analog electronic controls require 24 VAC -15/+20 percent power supply. Allow 14 VA for the controller. Factory supplied transformers are available with supply voltages of 277V, 240V, 208V, or 120V. Field supplied transformers can be mounted inside the control box. Attach the 24 volt leads to terminals 9 and 10 on the controller (See Figure 3).
Single Transformer Wiring
The same 24 VAC transformer may be used to power the controller plus control relays, contractors and/or valves on a terminal. For single transformer wiring see figure 3.
Multiple Loop Wiring
If multiple controllers are looped together in a single circuit using a common transformer, wire all #9 connections together, and all #10 connections together. If the transformer secondary is connected to earth ground, this lead must also be connected to terminal #9. ALWAYS OBSERVE PHASING!
CAUTION: NEVER connect power to the controls until all wiring has been installed. ALWAYS disconnect power to the controls before servicing the unit controls or accessories. DO NOT connect line voltage to the controller or other unit components.
Balancing
The following guidelines are recommended when balancing a constant volume rooftop unit and Zcom diffuser system.
1. Adjust rooftop to supply cooling or heating during the balance. The Zcom diffuser has three modes of operation; cooling, heating and ventilation. If the supply air temperature is between the heating and cooling setpoints, the Zcom will operate in the ventilation mode and go to the ventilation damper position of 50% closed. Therefore, to properly balance the system, the rooftop unit must be in either cooling or heating.
2. Drive the Zcom diffusers fully open with the Zapper, shown on the Zapper as “CL Open” or “HT Open” (CL for cooling mode and HT for heating mode), or power down all Zcom diffusers which will return the Zcom’s to the fully open position.
3. Balance each diffuser for the required design air flow.
The next steps apply to balancing the bypass damper to maintain duct static pressure.
1. Command all Zcom diffusers to the minimum position except one Zcom master, which is to remain fully open. The Zapper is used to command the Zcom to the minimum position by pushing the down arrow selector button until “CL Close” or “HT Close” (CL for cooling mode and HT for heating mode) is displayed on the Zapper.
2. Set the bypass damper by adjusting the ZECV constant volume module to the desired static pressure as measured at the static pressure tap installed 2/3 down the main duct. The TITUS ZECV has a time delay of approximately five minutes before reacting to any adjustment.
NOTES:
Consult local codes for specific types of wires and enclosures required for low voltage wiring. Troubleshooting information is found on page.
All wiring diagrams shown in this manual show single transformer wiring.
Loading...
+ 2 hidden pages