Titus VHC User Manual

VERTICAL HIGH OUTPUT VHC-IOM-00 01-19-09
INSTALLATION AND MAINTENANCE INSTRUCTIONS
VHC
INSTALLER MUST BE A TRAINED, EXPERIENCED SERVICE
TECHNICIAN
1. PRESSURE CHECK
associated piping/valve package pressurized. Use the air valve to release the pressure. Should there be no pressure, inspect the unit for possible shipping damage. The unit must be pressure tested again prior to installation.
2.
This unit is free standing. It MUST be leveled when installed. When leveling legs
3.
3.1 All piping leading to the unit must be adequately supported to prevent excessive stress
3.2 Threaded connections must not be over tightened.
3.3 Sweat connections must not be overheated. Use solder (95/5) with a melting
3.4 When the valve package is supplied separately for field installation, carefully follow
MOUNTING
are supplied (optional), these are located under the unit’s bottom panel. Turn the bolts
as required until the unit is perfectly leveled to ensure proper condensate drainage.
PIPING
on the unit’s piping. However, sufficient free movement is required for thermal
expansion/contraction.
o
temperature below 600
the schematic piping diagram and installation instructions provided with the package.
F.
3.5 The inlet (supply), outlet (return) and condensate (drain) points are clearly marked on the unit’s piping. Depending upon the filed piping layout, the connecting inlet, outlet and condensate piping could be at the right or left side of the unit. Follow the Engineer’s pipe layout drawing while routing the supply, return and drain lines to and from the unit.
3.6 All pipes and fittings outside the unit’s enclosure must be properly insulated as no external condensate pan is provided with the standard unit.
5 fo 1 egaP
VERTICAL HIGH OUTPUT VHC-IOM-00 01-19-09
INSTALLATION AND MAINTENANCE INSTRUCTIONS
4. ELECTRICAL
4.1 All electrical connections are to be made in accordance with the National Electric
Code, state and local codes, bylaws, ordinances or the authority having jurisdiction.
Make all electrical connections inside the internal electric junction box by carefully
following the wiring diagram.
4.2 Electrical wiring diagram is located inside the unit’s enclosure. Adhere strictly to it in
order to avoid damage and/or personal injury.
4.3 When the thermostat and fan switch are field supplied, the following are the minimum
electrical ratings:
- Thermostat (valve load) = 0.1A @ 115V (0.05A @ 230V)
- Fan Motor(s) @ full load amps, FLA (@115V):
SIZE FLA (Amps)
06 3.5 08 3.5 10 3.7
12 4.0 14* 3.5 16* 3.5 18* 3.5 20* 4.0
*Note: Units are equipped with two (2) motors; full load amperage listed is per motor.
4.4 Where electric heating is provided with the unit (optional), an external HEAT/COOL changeover switch has to be installed – normally wall mounted together with the fan speed selector switch. At minimum, this switch should be rated: 10A @ 115V (5A @ 230V).
4.5 Follow the wiring diagram for correct installation.
5.
GENERAL PRECAUTIONS
After completing the installation, recheck the following:
5.1 The drain pans, fans and motors are clean of all foreign material.
5.2 All electric wiring is properly routed, secure and capped.
5.3 The filter is clean and secured in its position.
5 fo 2 egaP
Loading...
+ 3 hidden pages