General Installation
Attach neck of diffuser to duct by screwing through the duct into the neck of the diffuser.
Item Description
1. Inner cone assembly
2. Outer cone assembly
3. Tang
4. Receptor slot
5. “L” slide retainer
6. Spring clip
7. Safety cable
Note: Safety cables are provided for maintenance purposes to allow the inner cone assembly to hang during mantenance of the diffuser.
Warning: Cables are not to be removed from installation.
TMR/TMRA IOM
Adjusting Inner Cone Position (TMRA only)
General installation instrucctions of TMRA, TMRA-AA
Securing the Inner Cones
STEP 1. STEP 3.
Insert the inner cone assembly upwards into the outer cone assembly aligning the inner cone assembly tangs with the receptor slots on the outer cone assembly.
“L” shaped retainer brackets are shipped retracted and must be adjusted upwards against the outer cone. After installation of the inner cones, as described above, each “L” slide retainer should be released and extended upward against the outer cone.
STEP 2.
Rotate the inner cone assembly 10 degrees so that the retainer point has passed the receptor slot and the weight of the inner cone assembly is supported by the receptor slots of the outer cone assembly. A set of spring clips apply pressure to the tangs locking the tangs into the recep­tor slots.
STEP 4.
Lock each “L” slide retainer in place with the screw provided to prevent release of the tangs on the inner cones from the receptor slots.
Installation Manual - TMR/TMRA
Note: Steps 3 and 4 above apply only to diffusers with neck sizes of 14” through 36”.
Redefine your comfort zone. ™ | www.titus-hvac.com
Adjusting Inner Cone Position (TMRA) only)
Type 1 Inner Cone:
The type 1 inner cone assembly has three fixed cone positions. The cone position is adjusted by remov­ing the cone assembly and repositioning it.
To reposition the inner cone assembly, remove the positioning screws and align the screw hole with the new position desired. Insert and tighten the screws in the new position.
Type 2 Inner Cone: (Steel only, sizes 6”-12”)
The type 2 inner cone assembly is adjusted by sliding the inner cones up or down as desired.
TMR/TMRA IOM
Type 1: 3 Fixed Positions
To reposition the cones loosen the positioning screws and slide the cones to the new position. Tighten the screws to secure cones in place.
Type 3 Inner Cone: (Steel only)
The type 3 inner cone assembly is adjusted by rotating the center cone.
To reposition the cones, rotate the center cone clockwise or counter clockwise to raise or lower the cones.
Type 2: Sliding
Type 3: Rotating
Redefine your comfort zone. ™ | www.titus-hvac.com
Installation Manual - TMR/TMRA
Models TMRA and TMRA-AA adjustable round ceiling diffusers are designed for both heating and cooling applications. All sizes have four cones, giving uniformity of appearance where different sizes are used in the same area. They deliver a uni­form 360° discharge pattern and exhibit excellent performance in variable air volume systems.
TMRA, TMRA-AA
The circular shaped TMRA diffuser has a unique 4-cone design that minimizes pressure loss and provides excellent air distri­bution and occupant comfort. The adjustability of the TMRA allows for use in both cooling and heating applications.
605 Shiloh Rd Plano TX 75074 ofc: 972.212.4800 fax: 972.212.4884
Loading...