Titus T3SQ-4 User Manual

T3SQ-4-IOM-3.0 05-17-07
Installation, Operation & Maintenance of the T3SQ Thermal
VAV Diffuser
Step 1
The units should be shipped assembled except for the backpan.
Remove all packaging from the components. The thermal T protect the actuator assembly. Be sure to remove packaging between the diffuser plaque and the control disc. Make sure that no packaging is obstructing the thermal element at the top of the actuator or the induction cap on the plaque.
If unit is not assembled, follow the steps below before proceeding (See Figure 1):
1. Insert induction cap into plaque of diffuser.
2. Insert venturi tube into induction channel until
3. Slide control disc over venturi tube.
4. Insert actuator through center hole in the control disc and snap into induction channel.
Backpan
Thermal Actuator
tabs engage.
SQ is shipped with additional packaging to
Control Disc
Venturi Tube
Induction Channel
Face Plaque
IOM Label
Induction Cap
Figure 1. T3SQ-4 Parts & Assembly
T3SQ-4-IOM-3.0 05-17-07
Step 2
Step 3
Step 4
Step 5
For system balancing, the springs (A) must be disconnected from the control disc (B) to allow the control disc to go to full open. (See Figure 2)
After balancing, reconnect the springs to the control disc. If the actuator arms are not connected to the control disc the diffuser will not operate.
Ensure that each control disc spring (A) is attached to both the control disc (B) and the lever arm (C) before installing.
Place the back pan into ceiling grid. Connect duct work to back pan.
Adjust room temperature: Turn the blue ring assembly (D) to the desired temperature indicated ( 66°F to 74°F)
To adjust the offset differential between heating and cooling, turn the green tab (E) clockwise to increase positive temperature offset and counterclockwise to increase temperature offset in a negative direction.
Minimum airflow can be adjusted from 30% of maximum down to fully closed or 0% of maximum by turning the grey flow adjustment ring (F) clockwise.
D
C
E
A
F
B
Figure 2. T3SQ Thermal Actuator and Control Disc Assembly
1.
2.
Step 6
Installation is completed by lining up the hooks on the face plaque assembly with the corresponding
3.
slot. The hooks are inserted and the face plate assembly is rotated clockwise, and lowered so that each hook is firmly in place. (See Figure 3)
Figure 3. Face Plaque Installation
Note:
A simplified version of these operating instructions can be found on the plaque of each diffuser. (See Figure 4)
Thermal - T
Heating / Cooling Actuator Venturi Tube Venturi Tube Guide Control Disc Sleeve Control Disc Thermal Induction Channel Induction Cap Plaque/Actuator/Control Disc Assy T3SQ-4
Note: This IOM is meant to demonstrate general dimensions of this product. The drawings on this IOM are not meant to detail every aspect of the product with exactness. Drawings are not to scale.
All rights reserved. No part of this work may be reproduced or transmitted in any form or any means, electronic or mechanical, including photocopying and recording, or by any information storage retrieval system without permission in writing from Air Distribution Technologies.
SQ-4 Replacement Parts
Description Part Number
38203201 72540201 72540301 72540401 72540501 78200201 72549501 31763101
Figure 4. T3SQ-4 Operating Instruction Label
TITUS reserves the right to make changes without written notice.
Loading...