Airflow limits are printed on the label on the
optional controller cover (or the side of the
terminal) and the side of the controller (Figures
2 and 3).
If field adjustment becomes necessary, follow
the procedure outlined below.
AIR FLOW ADJUSTING PROCEDURES FOR
ALL CONTROLLERS
Figure 1. Adjusting Air Flow
(See Figure
3)
(Label, See Figure 3)
1.Remove the optional controller cover
(Figure 1).
2.The action of the controller must match the
settings printed on the labels (Figures 2
and 3).
a.TITUS I—Direct acting, normally
open, (control color—beige).
b.TITUS I—Reverse acting, normally
closed, (control color—gray).
c.TITUS IIA—Direct or reverse acting
thermostat. No adjustment necessary.
d.TITUS IIA—Verify setting on damper
dial is correct (N.O. or N.C.).
e.TITUS II—Check thermostat and
damper compatibility selectors, verify
that settings are as marked on the
label.
3Remove the caps from the tees in the HI
and LO tubes (red and green stripe).
Connect a manometer gauge to both tees
(gauge with a 0 to 2 inch scale is
recommended).
4.Refer to the calibration curve for
terminal being serviced (Page 8). From the
curve read the differential pressure across
the sensor for the required airflow.
5.For instructions to readjust the control refer
to:
a.TITUS I See page 3.
b.TITUS IIA See page 4-5.
c.TITUS II See page 6-7.
d.For dual duct terminals, see document
PNEU-DD-IOM.
e.Quick-Check. See page 2.
6.After the flow rates are adjusted:
a.Replace the thermostat connection to
the controller.
b.Remove the gauge and replace the
caps on the tees.
c.Replace the optional controller cover.
the size
Figure 2. Unit Label
MODEL NO: PESV
TOTAL CFM: 600
TITUS II NO RA COOL
MIN. CFM: 160
FACTORY NO:XXXXX
Figure 3. Controller Label
SIZE: 08
VP: .410
VP: .030
ITEM: 1
Quick-Check Procedure for TITUS I, II, and IIA Controllers
PNEU-IOM-2.05-2-05
Preparing for Calibration
1. Disconnect the actuator tube
(yellow stripe) from controller
Port B.
2.Connect squeeze bulb with 0 to 25
PSI gauge to the actuator.
3.Connect 0 to 25 PSI gauge to
controller Port B (Figure 4).
A. Direct Acting Cooling or Reverse
Acting Heating
1.Apply zero PSI to thermostat
Port T.
2.Read the differential pressure for
the desired Minimum CFM from the
calibration curve corresponding to
the inlet size of the terminal being
calibrated (Page 8).
3.Pump the squeeze bulb until the
desired differential pressure is read
on the manometer gauge.
4.Adjust the LO knob on the face of
the controller until the gauge on
Port B reads 7.5 PSI ± 1.0 PSI.
5.Read the differential pressure for
the desired Maximum CFM from the
calibration curve corresponding to
the inlet size of the terminal being
calibrated (Page 8).
6.Pump the squeeze bulb until the
desired differential pressure is read
on the manometer gauge.
7.Adjust the HI knob on the face of
the controller until the gauge on
Port B reads 7.5 PSI ± 1.0 PSI.
8.Remove gauges and reconnect
actuator to controller Port B.
NOTE: If the actuator fails to respond,
see Guide to Service Procedures.
RED
GR EEN
LOHI
ESV
SENSOR
YELLOW
YELLOW
GAUGE
0-25 PSI
SQUEEZE
BULB
5-10 PSI
ACTUATO R
Figure 4. Controller Setup
B. Reverse Acting Cooling or Direct
Acting Heating
For TITUS I Controllers
1.Apply zero PSI to thermostat
Port T.
2.Read the differential pressure for
the desired Maximum CFM from the
calibration curve corresponding to
the inlet size of the terminal being
calibrated (Page 8).
3.Pump the squeeze bulb until the
desired differential pressure is read
on the manometer gauge.
4.Adjust the HI knob on the face of
the controller until the gauge on
Port B reads 7.5 PSI ± 1.0 PSI.
5.Read the differential pressure for
the desired Minimum CFM from the
calibration curve corresponding to
the inlet size of the terminal being
calibrated (Page 8).
6.Pump the squeeze bulb until the
desired differential pressure is read
on the manometer gauge.
7.Adjust the LO knob on the face of
the controller until the gauge on
Port B reads 7.5 PSI ± 1.0 PSI.
8.Remove gauges and reconnect
actuator to controller Port B.
NOTE: If the actuator fails to respond,
see Guide to Service Procedures.
For TITUS II Controllers
1.Apply 15 to 25 PSI to thermostat
Port T.
2.Read the differential pressure for
the desired Minimum CFM from the
calibration curve corresponding to
the inlet size of the terminal being
WHI TE
LO
BLUE
MAIN AIR
(15-25 PSI)
ROOM THERMOSTAT
(0-15 PSI)
HI
PNEUMATIC
CONTROLLER
B
TM
GAUGE
0-25 PSI
0-2" W.G.
MANOMETER
calibrated (Page 8).
3.Pump the squeeze bulb until the
desired differential pressure is read
on the manometer gauge.
4.Adjust the LO knob on the face of
the controller until the gauge on
Port B reads 7.5 PSI ± 1.0 PSI.
5.Read the differential pressure of the
desired Maximum CFM from the
calibration curve corresponding to
the inlet size of the terminal being
calibrated (Page 8).
6.Pump the squeeze bulb until the
desired differential pressure is read
on the manometer gauge.
7.Adjust the HI knob on the face of
the controller until the gauge on
Port B reads 7.5 PSI ± 1.0 PSI.
8.Remove gauges and reconnect
actuator to controller Port B.
NOTE: If the actuator fails to respond,
see Guide to Service Procedures.
For TITUS IIA Controllers
1. Apply zero PSI to thermostat Port T.
2.Read the differential pressure for
the desired Maximum CFM from the
calibration curve corresponding to
the inlet size of the terminal being
calibrated (Page 8).
3.Pump the squeeze bulb until the
desired differential pressure is read
on the manometer gauge.
4.Adjust the LO knob on the face of
the controller until the gauge on
Port B 7.5 PSI ± 1.0 PSI.
5.Read the differential pressure for
the desired Minimum CFM from the
calibration curve corresponding to
the inlet size of the terminal being
calibrated (Page 8).
6.Pump the squeeze bulb until the
desired differential pressure is read
on the manometer gauge.
7.Adjust the HI knob on the face of
the controller until the gauge on
Port B reads 7.5 PSI ± 1.0 PSI.
8.Remove gauges and reconnect
actuator to controller Port B.
NOTE: If the actuator fails to respond
see Guide to Service Procedures.
Calibration Procedure for TITUS I Controller
PNEU-IOM-3.05-2-05
A. Direct Acting (Beige). (N.O.)
b.Refer again to the calibration
curve (Page 8) to determine
1.Adjusting minimum air flow:
a.Apply zero PSI signal to Port T
on the controller.
b.If the minimum CFM equals
zero, the damper should
assume a closed
position (observe the indicator
on the end of the damper
the differential pressure
necessary for the required
maximum CFM.
c.Adjust the HI knob on the
controller until the manometer
gauge reads the required
differential pressure from the
curve.
shaft). If not, adjust LO knob on
the controller until the
compressed air drives the
NOTE: If actuator fails to respond,
see Guide to Service Procedure.
damper closed.
c.If a non-zero minimum CFM is
B. Reverse Acting (Gray). (N.C.)
required, read the differential
pressure for the desired CFM
from the calibration curve
corresponding to the inlet size
of the terminal being calibrated
(Page 8).
d.Adjust the LO knob until the
desired differential pressure is
read on the manometer gauge.
Allow several seconds for the
controls to react to system
pressure and stabilize.
1.Adjusting maximum air flow:
a.Apply zero PSI signal to Port T
on the controller.
b.Refer to calibration chart (Page
8). Read the differential
pressure for the desired
maximum CFM from the curve
corresponding to the inlet size
of the terminal being
calibrated.
c.Adjust the HI knob on the
controller until the desired
2.Adjusting maximum air flow:
differential pressure is read on
a.Apply 15-25 PSI signal to
Port T on the controller.
the manometer gauge. Allow
several seconds for the
controls to react to the system
and stabilize.
2. Adjusting minimum air flow:
a.Apply 15-25 PSI signal to
Port T on the controller.
b.If minimum CFM equals zero,
the damper should assume a
closed position (observe
indicator on the end of the
damper shaft). If not, adjust the
LO knob until the damper
closes.
c.If a non-zero minimum CFM is
required, read the differential
pressure for the required CFM
from the curve (Page 8).
d.Adjust the LO knob on the
controller until the manometer
gauge reads the desired
differential pressure from the
curve.
NOTE: If actuator fails to respond,
see Guide to Service Procedures.
Table 1.
Thermostat
Action
ColorLow Port Signal
DirectBeigeYX
ReverseGreyXY
HI
SENSOR
LO
ACTUATOR
YELLOW
BLUE
WHITE
ROOM THERMOSTAT
(0-15 PSI)
MAIN AIR (20-25 PSI)
HL
MAGNAHELIC
GAUGE
(0-20" WG)
Figure 5. Titus I Controller
High Port
Signal
RED
GREEN
LO
INCREASE
LOLO
HI
INCREASE
HI
M
LO
DIRECT ACTING CONTROLLER
X
Y
B
T
REVERSE ACTING CONTROLLER
HI
BEIGE
HI
INCREASE
LO
LO
INCREASE
HI
GRAY
Loading...
+ 7 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.