Titus Pneumatic User Manual

Installation Manual
TITUS I, II, and IIA Pneumatic Controls
Installation, Operation, and Maintenance Manual
Adjusting Minimum and Maximum Air Flow
PNEU-IOM-1.0 5-2-05
Airflow limits are printed on the label on the optional controller cover (or the side of the terminal) and the side of the controller (Figures 2 and 3).
If field adjustment becomes necessary, follow the procedure outlined below.
AIR FLOW ADJUSTING PROCEDURES FOR ALL CONTROLLERS
Figure 1. Adjusting Air Flow
(See Figure
3)
(Label, See Figure 3)
1. Remove the optional controller cover (Figure 1).
2. The action of the controller must match the settings printed on the labels (Figures 2 and 3). a. TITUS I—Direct acting, normally
open, (control color—beige).
b. TITUS I—Reverse acting, normally
closed, (control color—gray).
c. TITUS IIA—Direct or reverse acting
thermostat. No adjustment necessary.
d. TITUS IIA—Verify setting on damper
dial is correct (N.O. or N.C.).
e. TITUS II—Check thermostat and
damper compatibility selectors, verify that settings are as marked on the label.
3 Remove the caps from the tees in the HI
and LO tubes (red and green stripe). Connect a manometer gauge to both tees (gauge with a 0 to 2 inch scale is recommended).
4. Refer to the calibration curve for terminal being serviced (Page 8). From the curve read the differential pressure across the sensor for the required airflow.
5. For instructions to readjust the control refer to: a. TITUS I See page 3. b. TITUS IIA See page 4-5. c. TITUS II See page 6-7. d. For dual duct terminals, see document
PNEU-DD-IOM.
e. Quick-Check. See page 2.
6. After the flow rates are adjusted: a. Replace the thermostat connection to
the controller.
b. Remove the gauge and replace the
caps on the tees.
c. Replace the optional controller cover.
the size
Figure 2. Unit Label
MODEL NO: PESV TOTAL CFM: 600 TITUS II NO RA COOL MIN. CFM: 160 FACTORY NO:XXXXX
Figure 3. Controller Label
SIZE: 08 VP: .410
VP: .030
ITEM: 1
Quick-Check Procedure for TITUS I, II, and IIA Controllers
PNEU-IOM-2.0 5-2-05
Preparing for Calibration
1. Disconnect the actuator tube (yellow stripe) from controller Port B.
2. Connect squeeze bulb with 0 to 25 PSI gauge to the actuator.
3. Connect 0 to 25 PSI gauge to controller Port B (Figure 4).
A. Direct Acting Cooling or Reverse
Acting Heating
1. Apply zero PSI to thermostat Port T.
2. Read the differential pressure for the desired Minimum CFM from the calibration curve corresponding to the inlet size of the terminal being calibrated (Page 8).
3. Pump the squeeze bulb until the desired differential pressure is read on the manometer gauge.
4. Adjust the LO knob on the face of the controller until the gauge on Port B reads 7.5 PSI ± 1.0 PSI.
5. Read the differential pressure for the desired Maximum CFM from the calibration curve corresponding to the inlet size of the terminal being calibrated (Page 8).
6. Pump the squeeze bulb until the desired differential pressure is read on the manometer gauge.
7. Adjust the HI knob on the face of the controller until the gauge on Port B reads 7.5 PSI ± 1.0 PSI.
8. Remove gauges and reconnect actuator to controller Port B.
NOTE: If the actuator fails to respond, see Guide to Service Procedures.
RED
GR EEN
LOHI
ESV
SENSOR
YELLOW
YELLOW
GAUGE
0-25 PSI
SQUEEZE
BULB
5-10 PSI
ACTUATO R
Figure 4. Controller Setup
B. Reverse Acting Cooling or Direct
Acting Heating
For TITUS I Controllers
1. Apply zero PSI to thermostat Port T.
2. Read the differential pressure for the desired Maximum CFM from the calibration curve corresponding to the inlet size of the terminal being calibrated (Page 8).
3. Pump the squeeze bulb until the desired differential pressure is read on the manometer gauge.
4. Adjust the HI knob on the face of the controller until the gauge on Port B reads 7.5 PSI ± 1.0 PSI.
5. Read the differential pressure for the desired Minimum CFM from the calibration curve corresponding to the inlet size of the terminal being calibrated (Page 8).
6. Pump the squeeze bulb until the desired differential pressure is read on the manometer gauge.
7. Adjust the LO knob on the face of the controller until the gauge on Port B reads 7.5 PSI ± 1.0 PSI.
8. Remove gauges and reconnect actuator to controller Port B.
NOTE: If the actuator fails to respond, see Guide to Service Procedures.
For TITUS II Controllers
1. Apply 15 to 25 PSI to thermostat Port T.
2. Read the differential pressure for the desired Minimum CFM from the calibration curve corresponding to the inlet size of the terminal being
WHI TE
LO
BLUE
MAIN AIR (15-25 PSI)
ROOM THERMOSTAT (0-15 PSI)
HI
PNEUMATIC
CONTROLLER
B
TM
GAUGE
0-25 PSI
0-2" W.G. MANOMETER
calibrated (Page 8).
3. Pump the squeeze bulb until the desired differential pressure is read on the manometer gauge.
4. Adjust the LO knob on the face of the controller until the gauge on Port B reads 7.5 PSI ± 1.0 PSI.
5. Read the differential pressure of the desired Maximum CFM from the calibration curve corresponding to the inlet size of the terminal being calibrated (Page 8).
6. Pump the squeeze bulb until the desired differential pressure is read on the manometer gauge.
7. Adjust the HI knob on the face of the controller until the gauge on Port B reads 7.5 PSI ± 1.0 PSI.
8. Remove gauges and reconnect actuator to controller Port B.
NOTE: If the actuator fails to respond, see Guide to Service Procedures.
For TITUS IIA Controllers
1. Apply zero PSI to thermostat Port T.
2. Read the differential pressure for the desired Maximum CFM from the calibration curve corresponding to the inlet size of the terminal being calibrated (Page 8).
3. Pump the squeeze bulb until the desired differential pressure is read on the manometer gauge.
4. Adjust the LO knob on the face of the controller until the gauge on Port B 7.5 PSI ± 1.0 PSI.
5. Read the differential pressure for the desired Minimum CFM from the calibration curve corresponding to the inlet size of the terminal being calibrated (Page 8).
6. Pump the squeeze bulb until the desired differential pressure is read on the manometer gauge.
7. Adjust the HI knob on the face of the controller until the gauge on Port B reads 7.5 PSI ± 1.0 PSI.
8. Remove gauges and reconnect actuator to controller Port B.
NOTE: If the actuator fails to respond see Guide to Service Procedures.
Calibration Procedure for TITUS I Controller
PNEU-IOM-3.0 5-2-05
A. Direct Acting (Beige). (N.O.)
b. Refer again to the calibration
curve (Page 8) to determine
1. Adjusting minimum air flow: a. Apply zero PSI signal to Port T
on the controller.
b. If the minimum CFM equals
zero, the damper should assume a closed position (observe the indicator on the end of the damper
the differential pressure necessary for the required maximum CFM.
c. Adjust the HI knob on the
controller until the manometer gauge reads the required differential pressure from the curve.
shaft). If not, adjust LO knob on the controller until the compressed air drives the
NOTE: If actuator fails to respond, see Guide to Service Procedure.
damper closed.
c. If a non-zero minimum CFM is
B. Reverse Acting (Gray). (N.C.)
required, read the differential pressure for the desired CFM from the calibration curve corresponding to the inlet size of the terminal being calibrated (Page 8).
d. Adjust the LO knob until the
desired differential pressure is read on the manometer gauge. Allow several seconds for the controls to react to system pressure and stabilize.
1. Adjusting maximum air flow: a. Apply zero PSI signal to Port T
on the controller.
b. Refer to calibration chart (Page
8). Read the differential pressure for the desired maximum CFM from the curve corresponding to the inlet size of the terminal being calibrated.
c. Adjust the HI knob on the
controller until the desired
2. Adjusting maximum air flow:
differential pressure is read on
a. Apply 15-25 PSI signal to
Port T on the controller.
the manometer gauge. Allow several seconds for the controls to react to the system and stabilize.
2. Adjusting minimum air flow: a. Apply 15-25 PSI signal to
Port T on the controller.
b. If minimum CFM equals zero,
the damper should assume a closed position (observe indicator on the end of the damper shaft). If not, adjust the LO knob until the damper closes.
c. If a non-zero minimum CFM is
required, read the differential pressure for the required CFM from the curve (Page 8).
d. Adjust the LO knob on the
controller until the manometer gauge reads the desired differential pressure from the curve.
NOTE: If actuator fails to respond, see Guide to Service Procedures.
Table 1.
Thermostat
Action
Color Low Port Signal
Direct Beige Y X
Reverse Grey X Y
HI
SENSOR
LO
ACTUATOR
YELLOW
BLUE WHITE
ROOM THERMOSTAT (0-15 PSI)
MAIN AIR (20-25 PSI)
H L
MAGNAHELIC
GAUGE
(0-20" WG)
Figure 5. Titus I Controller
High Port
Signal
RED
GREEN
LO
INCREASE
LOLO
HI
INCREASE
HI
M
LO
DIRECT ACTING CONTROLLER X Y
B
T
REVERSE ACTING CONTROLLER
HI
BEIGE
HI
INCREASE
LO
LO
INCREASE
HI
GRAY
Loading...
+ 7 hidden pages