INSTALLATION INSTRUCTIONS:
HORIZONTAL BASIC FAN COIL SERIES
HBC, HBP, HBE, HBR
INSTALLER MUST BE A TRAINED, EXPERIENCED SERVICE
1. PRESSURE CHECK
The complete unit including coil, valve package and associated piping is shipped
pressurized. Use the air valve to release the pressure. Should there be no pressure, inspect the unit for possible shipping damage. The unit must be pressure tested again prior to installation.
2. MOUNTING – HBC, HBP & HBE ONLY
Each unit has four (4) mounting holes. Rubber grommets are supplied
with each unit. Due to the various installation conditions, the mounting bolts/rods, steel washers and nuts are field supplied.
Level the unit to ensure proper condensate drainage.
2.1 MOUNTING – HBR ONLY
Each unit is provided with four mounting lugs into which rubber grommets are fitted.
Fit rods or bolts and use suitable metal washers and nuts to secure the unit.
To adjust the telescopic frame to the ceiling, remove eight screws which hold the
frame, pull out the telescopic bottom and adapt it to the ceiling. After exact alignment is made, re-screw the telescopic frame with hinged access panel to the unit using the same eight screws (two per side).
Level the unit to ensure proper condensate drainage.
Page 1 of 6
3. PIPING
3.1 All piping leading to the unit must be adequately supported to prevent excessive stress on the unit’s piping. However, sufficient free movement is required for thermal expansion/contraction.
3.2 Do NOT over-tighten threaded connections.
3.3 Do NOT overheat sweat connection. Use solder (95/5) with a melting temperature below 600oF.
3.4 When the valve package is supplied separately for field installation, carefully follow the schematic piping diagram and installation instructions provided with the package.
3.5 All pipes and fittings that extend beyond the drain pan MUST be insulated.
4. ELECTRICAL
4.1 All electrical connections are to be made in accordance with the National Electric Code, state and local codes, bylaws, ordinances or the authority having jurisdiction. Make all electrical connections inside the electric junction box by carefully following the wiring diagram.
4.2 Adhere strictly to the electrical wiring diagram in order to avoid damage and/or personal injury.
4.3 When the thermostat and fan switch are field supplied, the following are the minimum electrical ratings:
- Thermostat (valve load) = 0.1A @ 115V
(0.05A @ 230V)
- Fan Motor(s) @ full load = 5A @ 115V
(2.5A @ 230V)
5. FILTER – HBP, HBE, HBR
The filter is secured with a filter retainer. To install filter, slip filter into the filter rack
and fasten it with the filter retainer.
6.
GENERAL PRECAUTIONS
After completing the installation, recheck the following:
6.1 The drain pans, fans and motors are clean of all foreign material.
2