This section provides a description of the Titus Alpha BAC-8007
and BAC-8207 VAV controllers. It also introduces safety information.
Review this material before installing or operating the controllers.
BAC-8007 and BAC-8207
The
designed for VAV terminal units. An integrated actuator and the supplied
programs make these ideal controllers for temperature setback, overrides, reheat
and other HVAC sequences. Install these versatile controllers in stand-alone
environments or networked to other BACnet devices. As part of a complete
facilities management system, the
provide precise monitoring and control of connected points.
are native BACnet, direct digital controllers
BAC-8007 and BAC-8207
BACnet MS/TP compliant
Standard VAV control sequences are incorporated to provide pressure
independent control of a dual-duct VAV unit to control heating and cooling
On-board airflow sensor for use with a single or multi-point differential
pressure measuring station or pitot tube.
Control indoor air quality and local lighting
controllers
Specifications
Analog inputsAll inputs are configured as analog:
Active inputs2
Passive inputs4
Air flow sensor1
Actuator position1
Key featuresStandard units of measure.
Overvoltage input protection
ConnectorSpade connectors, 0.25 inch
Conversion12–bit analog–to–digital conversion
Input range0–12 volts DC
3
About the controllers
Specifications
Outputs, analog2
Key featuresOutput short protection
Configured as BACnet analog objects.
Standard units of measure
ConnectorSpade connectors, 0.25 inch
Conversion12–bit analog–to–digital conversion
Output voltage0–10 volts DC
Output current30 mA per output, 30 mA total for all analog
outputs
Outputs, binary4 triacs for external equipment
2 for the internal actuator
Key featuresOptically isolated triac output
Conversion12–bit analog–to–digital conversion
ConnectorSpade connectors, 0.25 inch
Output rangeMaximum switching 24 VAC at 3 amperes
Communications
BACnet MS/TPEIA–485 operating at rates up to 76.8 kilobaud.
Sensor jackRJ-45 jack compatible with model STE-8000 and
STE-6000 models with RJ-45 jacks
Supported objectsSee PIC statement for supported BACnet objects
Control Basic5 program areas in BAC-8007
6 program areas in BAC-8207
PID loop objects8
Value objects60 analog, 32 binary, and 12 multistate
MemoryPrograms and program parameters are stored in
nonvolatile memory.
Auto restart on power failure
Applications programs
Titus Controls supply the BAC-8x07 with
programming sequences for dual-duct
VAV applications:
Dual-duct VAV heating and cooling
Monitor CO2 to control indoor air quality
Control local lighting with motion sensing
Fan control
Balancing
UL 864 smoke controll (BAC-8207 only)
4
BAC-8007 and BAC-8207 VAV ControllersAbout the controllers
Specifications
Air flow sensor featuresConfigured as BACnet analog input object.
CMOS differential pressure 0-2 inches of water
(0-500 Pa) measurement range. Internally
linearized and temperature compensated.
Span accuracy 4.5% of reading.
Barbed connections for 1/4 FR tubing.
Range dependent upon DP pickup, tubing size/
length and connections.
Actuator specifications
Torque40 in-lb. (4.5 N
m)
•
Angular rotation0 to 95°
Adjustable end stops at 45° and 60° rotation
Motor timing, BAC-800790 sec./90° at 60 Hz
108 sec./90° at 50 Hz
Motor timing, BAC-820760sec./90° at 60 Hz
72 sec./90° at 50 Hz
Shaft sizeDirectly mounts on 3/8 to 5/8 inch (9.5 to 16 mm)
round or 3/8 to 7/16 inch (9.5 to 11 mm) square
damper shafts.
RegulatoryUL 916 Energy Management Equipment
FCC Class B, Part 15, Subpart B
BACnet Testing Laboratory listed as an application
specific controller (ASC).
UL 864 smoke controls (BAC-8207 only)
Installation
Supply voltage24 volts AC, -15%, +20% 5 VA
Weight13.2 ounces (376 grams)
Case materialFlame retardant plastic
Environmental limits
Operating32 to 120°
Shipping–40 to 140°
F (0 to 49° C)
F (–40 to 60° C)
Humidity5–95% relative humidity (non-condensing)
Models
BAC-8007Dual-duct VAV controller with 90 second actuator
BAC-8207Dual-duct VAV controller with 60 second actuator
and UL 864 smoke control application
5
About the controllers
Specifications
Dimensions
A
B
C
D
E
F
G
Table 1-1 BAC-8000 dimensions
ABCD EFG
6.53 in.4.89 in.4.25 in.0.77 in.6.00 in.2.14 in.1.92 in.
166 mm124 mm108 mm 19 mm152 mm54 mm49 mm
6
About the controllers
Safety considerations
Safety
considerations
Titus assumes the responsibility for providing you a safe product and safety
guidelines during its use. Safety means protection to all individuals who
install, operate, and service the equipment as well as protection of the equipment
itself. To promote safety, we use hazard alert labeling in this manual. Follow
the associated guidelines to avoid hazards.
Danger
Danger represents the most severe hazard alert. Bodily harm or death will
occur if danger guidelines are not followed.
Warning
Warning represents hazards that could result in severe injury or death.
Caution
Caution indicates potential personal injury or equipment or property damage
if instructions are not followed.
Note
Notes provide additional information that is important.
Detail
Provides programing tips and shortcuts that may save time.
7
SECTION 2
Installing the controller
This section provides important instructions and guidelines for
installing the BAC-8007 and BAC-8207 controllers. Carefully review
this information before installing the controller.
Installing the VAV controller includes the following topics that are covered in
this section.
In addition to the topics, see the section Dual-duct connections on page 24 for
connecting the controllers to a TSP-8000 actuator for dual-duct operation.
Setting the rotation limits on page 12
Mounting on page 12
Connecting inputs on page 14
Connecting outputs on page 16
Connecting to an MS/TP network on page 19
Connecting an airflow sensor on page 22
Connecting power on page 22