Titus BAC-8007, BAC-8207 User Manual

Page 1
Titus Alpha
BAC-8007, BAC-8207
Dual-Duct VAV Controllers
Installation Guide
Page 2
BAC-8007 and BAC-8207 VAV Controllers
Section 1
About the controllers
Safety considerations .......................................................................................................... 7
Section 2
Installing the controller
Setting the rotation limits ................................................................................................. ..9
Mounting ............................................................................................................................ ..9
Connecting inputs .............................................................................................................11
Connecting outputs ........................................................................................................... 13
Connecting to sensors ....................................................................................................... 15
Connecting to an MS/TP network .................................................................................. 16
Connecting an airflow sensor .......................................................................................... 19
Connecting power .............................................................................................................19
Dual-duct connections ...................................................................................................... 21
Section 3
Setting up dual-duct controllers
Network communications ................................................................................................ 22
Setting temperature setpoints .......................................................................................... 23
Setting airflow setpoints ................................................................................................... 24
Setting the VAV terminal unit parameters .................................................................... 25
Setting up local lighting control ...................................................................................... 26
Balancing airflow ............................................................................................................... 26
2
Page 3
SECTION 1
About the controllers
This section provides a description of the Titus Alpha BAC-8007 and BAC-8207 VAV controllers. It also introduces safety information. Review this material before installing or operating the controllers.
BAC-8007 and BAC-8207
The designed for VAV terminal units. An integrated actuator and the supplied programs make these ideal controllers for temperature setback, overrides, reheat and other HVAC sequences. Install these versatile controllers in stand-alone environments or networked to other BACnet devices. As part of a complete facilities management system, the provide precise monitoring and control of connected points.
are native BACnet, direct digital controllers
BAC-8007 and BAC-8207
BACnet MS/TP compliant Standard VAV control sequences are incorporated to provide pressure independent control of a dual-duct VAV unit to control heating and cooling On-board airflow sensor for use with a single or multi-point differential pressure measuring station or pitot tube. Control indoor air quality and local lighting
controllers
Specifications
Analog inputs All inputs are configured as analog:
Active inputs 2 Passive inputs 4 Air flow sensor 1 Actuator position 1 Key features Standard units of measure.
Overvoltage input protection
Connector Spade connectors, 0.25 inch Conversion 12–bit analog–to–digital conversion Input range 0–12 volts DC
3
Page 4
About the controllers
Specifications
Outputs, analog 2
Key features Output short protection
Configured as BACnet analog objects. Standard units of measure
Connector Spade connectors, 0.25 inch Conversion 12–bit analog–to–digital conversion Output voltage 0–10 volts DC Output current 30 mA per output, 30 mA total for all analog
outputs
Outputs, binary 4 triacs for external equipment
2 for the internal actuator
Key features Optically isolated triac output Conversion 12–bit analog–to–digital conversion Connector Spade connectors, 0.25 inch Output range Maximum switching 24 VAC at 3 amperes
Communications
BACnet MS/TP EIA–485 operating at rates up to 76.8 kilobaud.
Removable screw terminal block. Wire size 12–24 AWG
Sensor jack RJ-45 jack compatible with model STE-8000 and
STE-6000 models with RJ-45 jacks
Supported objects See PIC statement for supported BACnet objects
Control Basic 5 program areas in BAC-8007
6 program areas in BAC-8207
PID loop objects 8 Value objects 60 analog, 32 binary, and 12 multistate
Memory Programs and program parameters are stored in
nonvolatile memory. Auto restart on power failure
Applications programs
Titus Controls supply the BAC-8x07 with programming sequences for dual-duct VAV applications:
Dual-duct VAV heating and cooling Monitor CO2 to control indoor air quality Control local lighting with motion sensing Fan control Balancing UL 864 smoke controll (BAC-8207 only)
4
Page 5
BAC-8007 and BAC-8207 VAV Controllers About the controllers
Specifications
Air flow sensor features Configured as BACnet analog input object.
CMOS differential pressure 0-2 inches of water (0-500 Pa) measurement range. Internally linearized and temperature compensated. Span accuracy 4.5% of reading. Barbed connections for 1/4 FR tubing. Range dependent upon DP pickup, tubing size/ length and connections.
Actuator specifications
Torque 40 in-lb. (4.5 N
m)
Angular rotation 0 to 95°
Adjustable end stops at 45° and 60° rotation
Motor timing, BAC-8007 90 sec./90° at 60 Hz
108 sec./90° at 50 Hz
Motor timing, BAC-8207 60sec./90° at 60 Hz
72 sec./90° at 50 Hz
Shaft size Directly mounts on 3/8 to 5/8 inch (9.5 to 16 mm)
round or 3/8 to 7/16 inch (9.5 to 11 mm) square damper shafts.
Regulatory UL 916 Energy Management Equipment
FCC Class B, Part 15, Subpart B BACnet Testing Laboratory listed as an application specific controller (ASC). UL 864 smoke controls (BAC-8207 only)
Installation
Supply voltage 24 volts AC, -15%, +20% 5 VA Weight 13.2 ounces (376 grams) Case material Flame retardant plastic
Environmental limits
Operating 32 to 120° Shipping –40 to 140°
F (0 to 49° C)
F (–40 to 60° C)
Humidity 5–95% relative humidity (non-condensing)
Models
BAC-8007 Dual-duct VAV controller with 90 second actuator BAC-8207 Dual-duct VAV controller with 60 second actuator
and UL 864 smoke control application
5
Page 6
About the controllers
Specifications
Dimensions
A
B
C
D
E
F
G
Table 1-1 BAC-8000 dimensions
ABCD EFG
6.53 in.4.89 in.4.25 in.0.77 in.6.00 in.2.14 in.1.92 in.
166 mm 124 mm 108 mm 19 mm 152 mm 54 mm 49 mm
6
Page 7
About the controllers
Safety considerations
Safety considerations
Titus assumes the responsibility for providing you a safe product and safety guidelines during its use. Safety means protection to all individuals who install, operate, and service the equipment as well as protection of the equipment itself. To promote safety, we use hazard alert labeling in this manual. Follow the associated guidelines to avoid hazards.
Danger
Danger represents the most severe hazard alert. Bodily harm or death will occur if danger guidelines are not followed.
Warning
Warning represents hazards that could result in severe injury or death.
Caution
Caution indicates potential personal injury or equipment or property damage if instructions are not followed.
Note
Notes provide additional information that is important.
Detail
Provides programing tips and shortcuts that may save time.
7
Page 8
SECTION 2
Installing the controller
This section provides important instructions and guidelines for installing the BAC-8007 and BAC-8207 controllers. Carefully review this information before installing the controller.
Installing the VAV controller includes the following topics that are covered in this section.
In addition to the topics, see the section Dual-duct connections on page 24 for connecting the controllers to a TSP-8000 actuator for dual-duct operation.
Setting the rotation limits on page 12 Mounting on page 12 Connecting inputs on page 14 Connecting outputs on page 16 Connecting to an MS/TP network on page 19 Connecting an airflow sensor on page 22 Connecting power on page 22
8
Page 9
Setting the rotation limits
Setting the rotation limits
KMC ControlsInstalling the controller
Before mounting the controller, set the rotation limits with the supplied stop screw. Installing the stop screw limits the shaft rotation to either 45 or 60 degrees.
Caution
Before setting the rotation limits on the controller, refer to the damper position specifications in the VAV control box to which the controller will be attached. Setting rotation limits that do not match the VAV damper may result in improper operation or equipment damage.
Position notch
Rotate CW
as shown
Stop position holes
Stop screw in storage
Illustration 2-1 Controller stop selections
To set the rotational limits:
1. Turn the controller over so you have access to the back.
2. Manually rotate the actuator fully clockwise as viewed from the back.
3. Remove the stop screw from its storage location and clean any debris from the threads.
4. Insert the screw into the correct stop position hole.
5. Tighten the screw only until the head touches the plastic in the bottom of the recess.
Mounting Mount the controller inside of a metal enclosure. To maintain RF emissions
specifications, use either shielded connecting cables or enclose all cables in conduit.
Mount the controller directly over the damper shaft. A minimum shaft length of
2.0 inch (51 mm) is required.
Note
The controller is designed to directly mount to 3/8 to 5/8 inch (9.5 to 16mm) round or 3/8 to 7/16 (9.5 to 11mm) square damper shafts.
9
Page 10
BAC-8007 and BAC-8207 VAV Controllers Installing the controller
Mounting
Mount the controller close enough to the pitot tubes to keep the tubing length to a minimum. In typical installations the controller’s inputs and sensors are within 24 inches of each other.
Status LEDs
Mounting tab
Mounting bushing
Airflow sensor inputs
Gear disengagement button
Drive hub and V-bolt
Illustration 2-2 Controls and indicators
Mount the controller as follows:
1. Loosen the nuts on the U-bolt until the shaft can fit through the collar.
2. Place the controller on the damper shaft in the approximate final position. Position the controller loosely against the mounting surface so that the mounting bushing can float freely in the mounting tab.
3. Center the mounting bushing in the slot of the mounting tab and secure it using a #8 self-tapping screw.
4. Manually position the damper in the full open position.
5. Adjust the drive hub as follows: a. If the damper rotates counter clockwise to close, depress the gear
disengagement button and rotate the drive hub to the full clockwise position then release the button.
b. If the damper rotates clockwise to close, depress the gear disengagement
button and rotate the drive hub to the full counter clockwise position then release the button.
6. Lock the hub to the shaft by evenly tightening the V-bolt nuts to 30 to 35 in-lbs.
10
Page 11
Installing the controller
Connecting inputs
Connecting inputs
The BAC-8007 and BAC-8207 controllers have preconfigured analog inputs to support the supplied programs. The inputs cannot be changed to binary or accumulator inputs. Only six inputs have externally available physical terminals. All of the inputs are preconfigured for the application programs supplied in the dual-duct controllers and are listed in Ta ble 2-1.
Table 2-1 BAC-8007 and BAC-8207 input objects
Object Function Name Unit LocationPull up
AI1 Discharge Air Temperature DISCHARGE AIR°FTerminal block10k
AI2Space TemperatureSPACE SENSOR °F RJ-4510k
AI3 Space Setpoint SPACE SETPOINT°F RJ-45 10k
AI4Primary Duct Pressure PRIMARY DUCT wc Internal airflow sensor N/A
AI5Secondary Duct Pressure SECONDARY DUCT wc Terminal blockNone
AI6Secondary Damper Position SECONDARY POS VoltsTerminal block10k
AI7CO2 CO2 PPMTerminal blockNone
AI8 Primary Damper PositionPRIMARY POSVolts Internal damper positionN/A
Discharge air temperature Connect a 10k
, Type 3 thermistor temperature probe to the discharge air temperature input. The input includes the internal pull-up resistor. An STE-1405 sensor is suitable for this application. Follow the instructions supplied with the sensor for installation. See Te mperature setpoints
page 26 for setting up discharge air temperature limiting that requires this input
sensor.
on
Illustration 2-3 Discharge air temperature
Space Temperature Input The space temperature input is connected only through the RJ-45 thermostat and sensor input jack. It is a configured as an analog input for STE-6010, STE-6014, and STE-6017 sensors. If an STE-8000 sensor is connected to the controller, this input is ignored. See Connecting to
sensors on page 18.
Space Setpoint The space setpoint input is connected only through the RJ-45 thermostat and sensor input jack. It is a configured for the setpoint dials on STE-6014 or STE-6017 sensors. If an STE-6010 or STE-8000 sensor is connected to the controller, this input is ignored. See Connecting to sensors
on page 18.
11
Page 12
BAC-8007 and BAC-8207 VAV Controllers Installing the controller
Connecting inputs
Primary Duct Pressure The primary duct pressure input is an internal
measurement from the airflow sensor.
Secondary Duct Pressure The secondary duct pressure input is an analog input preconfigured to connect to the dual-duct operation. The TSP-8000 the TSP-8000 airflow sensor. See the section Dual-duct connections
P Out terminal of a TSP-8000 series actuator for
P Out represents actual airflow detected by
on page 24 for
connection details.
Secondary Damper Position The secondary damper position input is preconfigured to connect to the position potentiometer of an TSP-8000 series actuator for dual-duct operation. See the section
Dual-duct connections
on page 24
for connection details.
CO2 input Connect a CO2 sensor with an active output to the CO2 input. Set the sensor for a voltage output. An STE-1001 sensor is suitable for this application. Follow the instructions supplied with the sensor for sensor power, installation and calibration.
Illustration 2-4 Connections for CO2 sensor
Primary Damper Position The primary damper position input is preconfigured as an analog input that represents the position of the internal damper.
12
Page 13
Installing the controller
Connecting outputs
Connecting outputs
The BAC-8007 and BAC-8207 controllers have eight preconfigured outputs to support the supplied programs. Only six have externally available physical terminals. All of the outputs are preconfigured for the application programs supplied in the in the dual-duct controllers and are listed in Table 2-2.
Table 2-2 BAC-8007 and BAC-8207output objects
Object Function Name
BO1 Damper Clockwise DAMPER CW NeutralClockwise NeutralInternal
BO2 Damper Counter
Clockwise
AO3Analog Heat ANALOG HEAT00-10 VDC
AO4Fan Speed FAN SPEED00-10 VDC
BO5 Fan Start/Stop FANOnOff OffTriac
BO6 Secondary Damper
Clockwise
BO7 Secondary Damper
Counterclockwise
BO8LightingHEAT/LITEOnOff OffTriac
DAMPER CCW Neutral Counterclockwise NeutralInternal
SEC DAMPER CW Neutral ClockwiseNeutral Triac
SEC DAMPER CCW Neutral CounterclockwiseNeutral Triac
False value
True value
Default value
Ty pe
Damper Clockwise and Clockwise The damper outputs are binary output
objects that control the motion of the internal damper.
Analog Heat The analog heat output controls modulating analog reheat. This output is active only if the controller is set up for reheat. For staged reheat applications, use an REE-5001 relay.
Illustration 2-5 Modulating heat output
13
Page 14
BAC-8007 and BAC-8207 VAV Controllers Installing the controller
Connecting outputs
Fan Speed Controls the speed of a variable speed fan if the controller is set up
for fan operation.
Illustration 2-6 Fan speed output
Fan Start/Stop The fan start output is preconfigured to either start or stop a single speed fan or enable a multispeed fan. The output is a triac that can switch up to 1 ampere at 24 volts AC.
Illustration 2-7 Fan start output
Secondary Damper Clockwise and Counterclockwise The secondary damper output terminals are preconfigured to control the position of the damper of a TSP-8000 series actuator for dual-duct operation. The outputs are triacs that can switch up to 1 ampere at 24 volts AC. See the section Dual-duct connections
on
page 24.
Local lighting The lighting output is preconfigured to work with the motion sensor in an STE-8201 sensor to automatically control lights located in the same space as the VAV. The output is a triac that can switch up to 1 ampere at 24 volts AC.
14
Illustration 2-8 Lighting output
Page 15
Installing the controller
Connecting to sensors
Connecting to sensors
Connect any of the following sensors to the RJ-45 thermostat and sensor jack.
STE-8001 STE-8201 STE-6010 STE-6014 STE-6017
Link the controller to sensors with standard straight-through Ethernet cables up to 75 feet long. See the installation guide supplied with the sensors for complete sensor installation instructions.
Maximum 75 feet v
Sensor jack
Illustration 2-9 Connecting to a sensor
No programming or configuration is required for the supported sensors. The controller is configured to automatically detect which type of sensor is connected to it.
15
Page 16
BAC-8007 and BAC-8207 VAV Controllers Installing the controller
Connecting to an MS/TP network
Connecting to an MS/TP network
The BAC-8000 series controllers are BACnet MS/TP compliant controllers. Connect them only to a BACnet MS/TP network.
See Application Note AN0404A, Planning BACnet Networks for additional information about installing controllers.
S +B -A
Illustration 2-10 MS/TP network connection
Connections and wiring
Use the following principles when connecting a controller to an MS/TP network:
Connect no more than 128 addressable BACnet devices to one MS/TP network. The devices can be any mix of controllers or routers. To prevent network traffic bottlenecks, limit the MS/TP network size to 60 controllers. Use 18 gauge, twisted pair, shielded cable with capacitance of no more than 51 picofarads per foot for all network wiring. Belden cable model #82760 meets the cable requirements. Connect the -A terminal in parallel with all other - terminals. Connect the +B terminal in parallel with all other + terminals. Connect the shields of the cable together at each controller. For KMC BACnet controllers use the S terminal. Connect the shield to an earth ground at one end only. Use a KMD–5575 repeater between every 32 MS/TP devices or if the cable length will exceed 4000 feet (1220 meters). Use no more than four repeaters per MS/TP network. Place a KMD–5567 surge surpressor in the cable where it exits a building.
16
Page 17
Installing the controller
Connecting to an MS/TP network
Ground shield only at one end of the segment.
Redundant network wiring for increased reliability
Illustration 2-11 MS/TP network wiring
Note
The MS/TP terminals are labeled -A, +B and S. The S terminal is provided as a connecting point for the shield. The terminal is not connected to the ground of the controller. When connecting to controllers from other manufacturers, verify the shield connection is not connected to ground.
17
Page 18
BAC-8007 and BAC-8207 VAV Controllers Installing the controller
Connecting to an MS/TP network
End of line termination switches
The controllers on the physical ends of the EIA-485 wiring segment must have end-of-line termination installed for proper network operation. Set the end-of-line termination to On using the EOL switches.
Set end-of-line termination to On in these controllers only.
Illustration 2-12 End of line termination
Illustration 2-13 shows thez position of the BAC-8000 End-of-Line switches associated with the MS/TP inputs.
On
Off
Illustration 2-13 Location of EOL switch
18
Page 19
Installing the controller
Connecting an airflow sensor
Connecting an airflow sensor
Connecting power
An airflow sensor is incorporated as one of the inputs to the controller. Remove the plugs and connect the tubing from the pitot assembly to the airflow sensor inputs next to the drive hub. (See Illustration 2-14). The airflow sensor is programmed as Input 1.
Total airflow (high) Static airflow (low)
Illustration 2-14 Airflow sensor inputs
The controllers require an external, 24 volt, AC power source. Use the following guidelines when choosing and wiring transformers.
Use a Class-2 transformer of the appropriate size to supply power to the controllers. Titus recommends powering only one controller from each transformer.
Do not run 24 volt, AC power from within an enclosure to external controllers.
Power
terminals
Illustration 2-15 Power terminals and jumper
19
Page 20
BAC-8007 and BAC-8207 VAV Controllers Installing the controller
Connecting power
Connect the 24 volt AC power supply to the power terminal block on the lower right side of the controller near the power jumper. Connect the ground side of the transformer to the ground terminal and the AC phase to the phase ~ terminal. Power is applied to the controller when the transformer is powered.
Illustration 2-16 Power connections
20
Page 21
Installing the controller
Dual-duct connections
Dual-duct connections
The BAC-8007 and BAC-8207 controllers are configured by the manufacturer for dual-duct operation. Connect the controllers to a TSP-8000 series actuator as shown in the illustration Dual-duct wiring diagram
on page 24.
Illustration 2-17 Dual-duct wiring diagram
21
Page 22
SECTION 3
Setting up dual-duct controllers
The topics in this section cover setting up the BAC-8007 and BAC-8207 for dual-duct VAV operation. These are advanced topics for controls technicians and engineers.
The BAC-8007 and BAC-8207 dual-duct VAV controllers are set up by the manufacturer to operate as soon as power is applied and connected as described in the section Installing the controller
Setting up the dual-duct VAV controllers may include setting BACnet objects with a BACnet Operator Workstation such as TotalControl. The objects may also be set up with a STE-8001 or STE-8201. The following topics are covered in this section.
on page 11.
Setting temperature setpoints on page 26 Setting airflow setpoints on page 27 Setting the VA V terminal unit parameters on page 28 Setting up local lighting control on page 29 Network communications on page 25
Network communications
Caution
Change only the present values of the objects listed in this section. Changing any other objects or properties will result in improper operation.
Before connecting the controller to a BACnet MS/TP network, configure the following network parameters with either a BACnet operator workstation or temporarily connecting an STE-8001 or STE-8201 to the controller.
Device instance—Set from 0 to 4,194,302. A device instance number must be unique across the BACnet internetwork.
Baud—Valid baud settings are 9600, 19200, 38400, and 76800. MAC—Set from 0 to 127. Must be unique on the MS/TP network to which
the controller is connected.
22
Page 23
Setting up dual-duct controllers
Setting temperature setpoints
Setting temperature setpoints
The space temperate setpoints listed in Table 3-1, “Temperature setpoints,” on page 26 are used to control the controller VAV operation. The temperature setpoints have default values, but may be manipulated depending on which type of wall sensor is connected to the controller.
Occupied cooling and heating setpoints These setpoints are user controlled space setpoints that originate from an attached sensor. If no sensor is attached the values for these setpoints are manually entered by a controls technician.
Unoccupied cooling and heating setpoints The unoccupied setpoints are manually entered values to set the heating and cooling temperature when the space is unoccupied.
Minimum cooling setpoint A manually entered value to limit the occupied cooling setpoint regardless of the value entered by the user.
Maximum heating setpoint A manually entered value to limit the occupied heating setpoint regardless of the value entered by the user.
Minimum setpoint differential Sets the minimum temperature separation between occupied heating and cooling setpoints.
Standby differential This differential is added or subtracted from the occupied temperature setpoints to calculate the standby setpoints.
SAT changeover temperature Sets the supply air temperature at which the controller will change from heating to cooling. The changeover takes place when the supply air temperature is 2° above or below the discharge air temperature setpoint.
Table 3-1 Temperature setpoints
Object Description Name Default
AV5Occupied Cooling Setpoint OCC CL STPT 74°F
AV6Occupied Heating Setpoint OCC HT SPT70°F
AV7Unoccupied Cooling Setpoint UNOCC CL STPT 80°F
AV8Unoccupied Heating Setpt UNOCC HT STPT 64°F
AV9Minimum Cooling Setpt MIN CL STPT 70°F
AV10 Maximum Heating Setpoint MAX HT STPT 76°F
AV11 Minimum Setpoint DifferentialMIN STPT DIFF 4°F
AV12 Standby Differential STBY DIFF 3°F
AV37 SAT Changeover Temp SAT CHANGEOVER 75°F
23
Page 24
BAC-8007 and BAC-8207 VAV Controllers Setting up dual-duct controllers
Setting airflow setpoints
Setting airflow setpoints
The airflow setpoints are limits for VAV unit operation. All values are entered by a controls technician.
Minimum and maximum cooling airflow Sets the airflow limits through the VAV unit when in the cooling mode.
Minimum and maximum heating airflow Sets the airflow limits through the VAV unit when in the heating mode.
Minimum and maximum fan speed Sets the limits on the fan speed. See
Connecting outputs
on page 16 for details for controlling a fan that is part of the
VAV unit.
Minimum and maximum ventilation flow Sets the minimum and maximum airflow limits for indoor air quality.
Table 3-2 Airflow setpoints
Object Description Name Defaults
AV13 Min Cooling Airflow MIN COOL FLOW0 CFM
AV14 Max Cooling AirflowMAX COOL FLOW400 CFM
AV15 Min Heating AirflowMIN HEAT FLOW 0 CFM
AV16 Max Heating AirflowMIN HEAT FLOW 400 CFM
AV32 Minimum Fan Speed MIN FAN SPEED 0%
AV33 Maximum Fan SpeedMAX FAN SPEED 100%
AV55 Minimum Vent Flow MIN VENT FLOW 0 CFM
AV56 Maximum Vent Flow MAX VENT FLOW 350 CFM
24
Page 25
Setting up dual-duct controllers
Setting the VAV terminal unit parameters
Setting the VAV terminal unit parameters
Terminal unit parameters set basic operating parameters and enable options such as reheat and series or parallel fan operation.
Reheat
reheat from the following list.
Reheat equipment is connected to the controller as described in the topic
Connecting outputs
Dual-duct mixing minimum airflow Sets the minimum airflow which may be different than the minimum cooling or heating airflow.
Damper direction to close Defines which direction the damper will turn to decrease airflow.
Enables and sets the type of reheat. Choose from the available types of
None—Reheat is not enabled. Staged—Not available on dual-duct models) Modulating—The reheat output varies from 0-10 volts. Floating—Not available on dual-duct models. Time proportional—Not available on dual-duct models.
on page 16.
CCW—The actuator turns counterclockwise to close the damper. CW—The actuator turns clockwise to close the damper.
Primary duct K-factor A property of the specific VAV unit and airflow sensor to which the primary controller is attached. This constant is supplied by the VAV unit manufacturer.
Secondary duct K-factor A property of the specific VAV unit and airflow sensor to which the secondary controller is attached. This constant is supplied by the VAV unit manufacturer
Fan operation Sets the type of VAV fan in the VAV terminal unit.
None—No fan is connected to the controller. Series—The VAV unit includes a series fan. The fan runs during a fresh air
purge, when the space is occupied or in standby. Parallel—The VAV unit includes a parallel fan. The fan runs when there is a call for heat during a fresh air purge, when the space is occupied or in standby.
Table 3-3 Unit parameters
Object Description Name Default
MSV3 Reheat Type REHEATNone
AV17 Dual Minimum DUAL MINIMUM 200 CFM
AV18 Primary K factor PR K FACT 904
BV10 Clockwise Close CLOCKWISE CLOSE CCW
MSV2 Fantype Configuration FAN CONFIG None
25
Page 26
BAC-8007 and BAC-8207 VAV Controllers Setting up dual-duct controllers
Setting up local lighting control
Setting up local lighting control
Automatic local lighting can controlled by the motion sensor in an STE-8201 connected to the controller. Local lighting is set up either with software or an attached STE-8201.
Lighting control enable When enabled, local lights will be turned on or off based on motion detected by an STE-8201.
Light off delay Sets the interval local lights will remain turned on after the last motion is detected by an STE-8201.
Table 3-4 Local lighting options
Object Description Name Default
BV11Lighting Control Enable LIGHTING CONTROL Enable
AV42 Light off delayLITE OFF DELAY15 minutes
Lighting equipment is connected to the controller as described in the topic
Connecting outputs
on page 16.
Balancing airflow An airflow balancing program is included in BAC-8000 series controllers. See the
manual STE-8000 and STE-8201 Sensor Installation Guide for balancing instructions.
26
Loading...