Titus Alpha Commissioning Guide

Page 1
Alpha Controller
Configuration with STE-8000 Series
The Titus A PLHA Controller can be programmed in three differen t w ay s:
- Factory Set Up
- BAS/ Computer thru BACnet netw ork with an additional router.
- STE- 8000 Series Thermostat (see below) The Titus STE-8001 ser ies thermostat has (3) buttons:
- UP / DOWN, and SETPOINT
- The flow chart on the foll owing pages is intended to simplify the calibration procedur e.
- Please note that a Level 1 passwor d is requir ed to change the set-point temperature on t he ther mostat and a Level 2 password is required for commissioning.
POWER ON - The LCD wil l displ ay the room temperature. CHANGING SETPOINT - Press SETPOINT once to select COOLING OCCUPIED SETPOINT.
- Press UP/DOWN to change numerical value.
- Press SETPOINT to return to Room temperature display.
CONTROLLER - Press and hold both UP & DOWN arrows for 5 seconds to enter into the C ON F G MENU S CONFIGURATION MENUS
** Refer to the Titus STE-8001 installation guide for additional details **
1
Page 2
Alpha Controller
MAIN MENU
Press and hold both UP & DOWN arrows for 5 seconds to enter into the CONFIGURATION MODE
Press UP and DOWN arrows to toggle between menus and SETPOINT to select the desired menu.
COMM
Communications
BLNC
Balance
CNFG
Configure
EXIT
2
Page 3
Alpha Controller
COMMUNICATION MENUS
UP / DOWN will enter value a value
in each field.
SETPOINT will toggle between menu
options.
COMM
Communication
DID
Device ID
MAC
Mac Address
NOTICE
COMM MENU
Should only be used when
connecting to BMS.
Refer to installation guide.
BAUD
Comm Speed
3
Page 4
Alpha Controller
BALANCING MENUS
BLNC
Balance
PRI
Primary
PMAX
Measured Max
CFM
PMIN
Measured Min
CFM
UP / DOWN will enter a v al ue in eac h fiel d.
SETPOINT will toggle between menu options.
SEC
Secondary
(Dual Duct)
SMAX
Measured Max
CFM
SMIN
Measured Min
CFM
4
Page 5
Alpha Controller
CONTROLLER CONFIGURATION MENUS
CNFG
Configure
STPT
Set-Point
MIN
Cool set pt
MAX
Heat set pt
OCCL
Occ. cool
OCHT
Occ. heat
UNCL
Un.Occ. Cool
UNHT
Un.Occ. Heat
CHNG
Changeover
STBY
Standby Diff
DDOF
Sup/Exh CFM
Offset
DDDP
Sup/Exh
Pressure Offset
FLOW
MNCL
Min Cool CFM
MXCL
Max Cool CFM
MNHT
Min Heat CFM
MXHT
Max Heat CFM
MIN
Min Fan Speed (%)
MAX
Max Fan Speed (%)
MNC2
Min IAQ CFM
BOX
PKFT
K-Factor
SKFT
K-Factor
REHT
No/Stg/SCR
FAN
No/Ser/Par
DDIR
CCW/CW
DUAL
Dual duct
ADVC
Advanced
PSW1
Lv.1 Password
PSW2
Lv.2 Password
OVRD
Override Timer
STBY
Standby Time
DAT
Discharge Air
Temp
0.0
Calibration Const
BACK
UP / DOW will enter a value
in each field.
SETPOINT will toggle
between MENU options.
EXIT
DIFF
Differential
C2SP
CO2 set.pt. (PPM)
MXC2
Max IAQ CFM
5