Alpha Controller
Configuration with STE-8000 Series
The Titus A PLHA Controller can be programmed in three differen t w ay s:
- Factory Set Up
- BAS/ Computer thru BACnet netw ork with an additional router.
- STE- 8000 Series Thermostat (see below)
The Titus STE-8001 ser ies thermostat has (3) buttons:
- UP / DOWN, and SETPOINT
- The flow chart on the foll owing pages is intended to simplify the
calibration procedur e.
- Please note that a Level 1 passwor d is requir ed to change the set-point
temperature on t he ther mostat and a Level 2 password is required for
commissioning.
POWER ON - The LCD wil l displ ay the room temperature.
CHANGING SETPOINT - Press SETPOINT once to select COOLING OCCUPIED SETPOINT.
- Press UP/DOWN to change numerical value.
- Press SETPOINT again to select HEATING OCCUPIED SETPOINT.
- Press SETPOINT to return to Room temperature display.
CONTROLLER - Press and hold both UP & DOWN arrows for 5 seconds to enter into the C ON F G MENU S
CONFIGURATION
MENUS
** Refer to the Titus STE-8001 installation guide for additional details **
1
![](/html/9c/9ca6/9ca60bb0ea7d2f66ce729602b179343853210b5ab9db4fee2b6d4a874059a550/bg2.png)
Alpha Controller
MAIN MENU
Press and hold both UP & DOWN arrows for 5 seconds to enter into the CONFIGURATION MODE
Press UP and DOWN arrows to toggle between menus and SETPOINT to select the desired menu.
COMM
Communications
BLNC
Balance
CNFG
Configure
EXIT
2