⚫ Most Common Voltage & Timing Ranges
⚫ 5-Year Unconditional Warranty
DESCRIPTION
The Model 334 and 364 Delayed One-Shot Timers are
functionally interchangeable. The Model 334 is a DPDT
potentiometer (knob-adjust) timer while the Model 364 is a
DPDT, high-accuracy digital input timer. Solid-state timing
circuits in each model drive an internal electromechanical
relay.
Upon application of power, the unit will start the OFF
delay. After the OFF delay times out, the relay will
energize for the ON time. When the ON time expires, the
relay will de-energize and all timing will stop. Power must
be removed and reapplied to begin timing again.
An “SG” version of this model is available using silver with
gold flash contacts.
Models 334 and 364 are UL Recognized and CSA
Certified.
SPECIFICATIONS
MODEL334 (knob adj.) 364 (digital)
Voltage L = 10-28V AC/DC
Timing range 10SEC: 1 - 10 Sec.
60SEC: 1 - 60 Sec.
180SEC: 1 - 180 Sec.
300SEC: 1 - 300 Sec.
0.1SEC: 0.1 - 102.3 Sec.
1SEC: 1 - 1023 Sec.
1MIN: 1 - 1023 Min.
1HR: 1 - 1023 Hr.
/SG = Silver with Gold Flash Contacts
** order 8-pin socket number 51X120
UL SPECIFICATIONS*
Input
Voltage (VAC)
Power 3 Watts Max
Output
* Pilot Duty: 120V: Make 15A, Break 1.5A240V: Make 7.5A, Break 0.75A
Models 334 and 364
10-28V AC/DC OR 40-260V AC/DC
240V AC, 10A, Resistive
120V AC, 4A, General Use
240V AC, 2A, General Use
C300, Pilot Duty
Ordering Examples (Model-Voltage-Timing Range [/Options]):
364-H-0.1SEC = Model 364 with a 40-260V AC/DC voltage range
and a timing range of 0.1-102.3 seconds.
334-L-180SEC /SG = Model 334 with a 10-28V AC/DC voltage
range, a timing range of 1-180 seconds, and optional silver with gold
flash contacts.
Contact Time Mark to order a custom programmed unit
READ ALL INSTRUCTIONS BEFORE INSTALLING, OPERATING OR SERVICING THIS DEVICE.
KEEP THIS DATA SHEET FOR FUTURE REFERENCE.
GENERAL SAFETY
POTENTIALLY HAZARDOUS VOLTAGES ARE PRESENT AT THE TERMINALS OF THE MODEL 334 OR 364.
ALL ELECTRICAL POWER SHOULD BE REMOVED WHEN CONNECTING OR DISCONNECTING WIRING.
THIS DEVICE SHOULD BE INSTALLED AND SERVICED BY QUALIFIED PERSONNEL.
Installation Instructions
OPERATION
When the supply voltage is applied, the OFF cycle begins
timing. Upon completion of the delay, the internal relay
energizes and the ON cycle begins timing (ON and OFF
cycles can be of equal or unequal durations). When the
ON time expires, the relay will de-energize and all timing
will stop. Power must be removed and reapplied to begin
timing again.
DIMENSIONS - Model 334
DIMENSIONS - Model 364
PIN DIAGRAM
The Models 334 and 364 Delayed One-Shot Timers
require a standard 8-pin socket for mounting, and use a
standard pin configuration. Refer to the pin diagram
below, or on the timer, for terminal connections.
An LED on top of the unit provides a quick visual indicator of
the relay’s status.
Shows No Power Applied
LED Indicator Unit Status
Green Energized
Red De-energized
Flashing (Green or Red) Relay is Timing
2. 2. To set a desired delay period on the timer, just
add the values of the selected dip switches (beginning
with the largest value first) to total the desired time.
e.g. #1: 100 seconds OFF; 900 seconds ON
e.g. #2: 5 minutes OFF; 55 minutes ON
32+16+4+2+1 = 55 minute ON delay4+1 = 5 minute OFF delay
WARRANTY
This product is warranted to be free from defects in
materials and workmanship, and is covered by our
exclusive 5-year Unconditional Warranty. Should this
device fail to operate for any reason, we will repair it for
five years from the date of manufacture. For complete
warranty details, see the Terms and Conditions of Sales
page in the front section of the Time Mark catalog or
contact Time Mark at 1-800-862 -2875.
512+256+128+4 = 900 second ON delay64+32+4 = 100 second OFF delay