Timeguard TRT035N, TRT037N Operating Instructions Manual

Installation & Operating Instructions
7 Day Programmable
Room Thermostat
Model: TRT035N
1
1. General Information
2. Safety
Before installation or maintenance, ensure the mains supply to the programmable room thermostat is switched off and the circuit supply fuses are removed or the circuit breaker turned off.
It is recommended that a qualified electrician is consulted or used for the installation of this programmable room thermostat and install in accordance with the current IEE wiring and Building Regulations.
Check that the total load on the circuit including when this programmable room thermostat is fitted does not exceed the rating of the circuit cable, fuse or circuit breaker.
To clean use a clean dry cloth only. Do not use any liquid cleaners.
3. Technical Specifications
230V AC 50 Hz
This thermostat is of Class ll Construction and must not be earthed
Switch Rating: 3(1)A
Switch Type: Single pole, voltage free
changeover contacts
Connection Type: 2 wire
Installation Type: Surface mount with wall plate
Micro Disconnection: Type 1.B control action
Operating Temperature Range: 0°C to +40°C
Set Temperature Range: 10°C to 35°C
Temperature Swing Adjuster: +/- 0.5°C or 1.0°C set by DIP switch
Optimum Start Time (OST) Adjustment: ON or OFF set by DIP switch
Frost Protection Mode: 5°C, Fixed
Sleep Mode: Suspends all output, turns off display
2
Illumination: Blue LED illuminated on setting
for button surrounds and display
Batteries: 2x 1.5V AA
CE Compliant
Dimensions (H x W x D): 90 x 135 x 30mm
TRT035N Front View
Digital room temperature/time display (illuminated on setting)
10°C to 35°C set temperature range
The heating symbol will show when heat is demanded
Battery compartment located on the side, accessible from rear of transmitter
+/- setting buttons
(illuminated on setting)
Light/Frost
protection button
Flip down cover conceals
setting buttons
3
4. Siting
The TRT035N must be sited where it will not be influenced by heat sources, for example above a radiator or a television or a refrigerator/freezer or in direct sunlight or subjected to draughts.
The product requires air circulation, so do not position above or below shelving or other wall mounted obstacles.
It should be mounted approximately 1.5 metres above floor level.
5. Installation
5.1 Ensure the mains supply is switched off and the circuit supply fuses are
removed or the circuit breaker turned off.
5.2 Remove the wall plate from the receiver unit, by undoing the retaining
screws, and pivoting the bottom of the unit outwards. The TRT035N body can then be lifted off.
5.3 Mark the position of the mounting holes on the wall using the wall
plate as a template. Drill out the mounting holes taking care to avoid any joists, electrical cables or water/gas pipes that may be hidden beneath the surface. Insert the rawl plugs into the holes.
5.4 Pass the 230V 50Hz mains supply and load cables through the opening
of the wall plate. Allow sufficient excess cable to wire up the unit, but not too much to make it difficult to close the unit to the wall plate.
5.5 Fix the wall plate to the wall using the correct mounting screws for
the rawl plugs installed. The retaining screws which secure the unit to the wall plate should be at the bottom.
5.6 Terminate the cables into the terminal block ensuring correct polarity
is observed and that all bare conductors are sleeved (See section 6. Connection Diagram). Make sure that the curved washer grips the conductor.
5.7 To insert batteries into the unit, access the battery compartment located
on the left side/rear of the unit. Use a small flat head screwdriver and release the lug and lever out the battery compartment. Insert the 2x AA batteries (supplied) maintaining the correct polarity, as shown in the base of the battery compartment. Push the battery compartment back into place until clicks shut.
4
TRT035N Wall Plate
Alternate mounting holes
Wall plate retaining screws
Retaining tabs
Mounting
holes
Loop terminal
Battery compartment lug
Release the lug and
lever out the battery
compartment to the right
5.8 To reinstall the unit onto the wall plate, first ensure the wall plate
retaining screws are loosened enough to clear the TRT035N body, then engage the top of the TRT035N onto the wall plate retaining tabs, and push firmly downwards and then upwards. There will be some resistance from the terminals.
5.9 Once in place, secure with the retaining screws making sure
not to over tighten.
NCNO
BOILER
COM
Switch Live from NO
(normally open contact
for heating) to bolier
230V AC 50Hz MAINS SUPPLY
Supply
Neutral
Supply
Live
5
6. Connection Diagram
Connect the 230V 50Hz mains supply and load cables to the terminal block which are marked as follows;
Note: Check boiler instructions before connecting.
230V 50Hz Mains Supply
Live Supply (Brown or Red) to L A ‘Loop Terminal’ is provided should a 3 core cable
be used
Load (Boiler) Switch Live (Brown or Red) to NO