Timeguard RCD01WAVN, RCD03MAVN, RCD02WPVN, RCD04MPVN Installation & Operating Instructions Manual

RCD Single Sockets
RCD01WAVN
RCD Single White Socket – Active
RCD02WPVN
RCD Single White Socket – Passive
RCD03MAVN
RCD Single Metal Socket – Active
RCD Single Metal Socket – Passive
Installation & Operating Instructions
1. General Information
These instructions should be read carefully and retained for further reference and maintenance. The Timeguard range of RCDs, provide protection against fire hazard and rapid double pole disconnection from electric shock for the appliance connected to it. They fully comply with BS7288 and BS1363-2 (including updates and amendments). They are designed to mount on either a BS4662 recessed box or a BS5733 surface mount box (plastic versions only). Note: RCD – Residual Current Device.
2. Safety
• Before installation or maintenance, ensure the mains
1 2
supply to the RCD fused connection unit is switched off and the circuit supply fuses are removed or the circuit breaker turned off.
• It is recommended that a qualified electrician is consulted or used for the installation of RCD fused connection unit and install in accordance with the current IEE wiring and Building Regulations.
• Check that the total load on the circuit including when this RCD fused connection unit is fitted does not exceed the rating of the circuit cable, fuse or circuit breaker.
• Electricity can be dangerous, use of an RCD should not be regarded as a substitute for basic electrical safety precautions.
• Always test the RCD before use. If the test procedure is not completed satisfactorily or an appliance continues to trip the RCD seek professional advice and switch off the appliance.
• To clean use a dry cloth only. Do NOT use any liquid cleaners.
• The RCD should NOT be used when it could come into contact with liquids or excessive atmospheric pollution.
• A warming of the casing during use is normal.
• Do NOT use outside the service conditions.
• For devices having a solid neutral, ensure the correct polarity of the incoming supply connections should the device trip automatically upon connection to the supply.
2 3
3. Wiring Tests – IMPORTANT
• Remove this product from the circuit if carrying out tests (as described in the IEE Wiring Regulations) for earth loop impedance, prospective short circuit current and insulation resistance.
• Use the enclosed wiring label to ensure this is carried out.
4. Technical Specifications
General RCD Specifications
• Operating Voltage: 230V AC 50 Hz
• Max Current: Fully complies with the
• Rated Trip Current: 30mA
• RCD Type: Double Pole, suitable for
• Breaking Capacity: 250A (Earth leakage)
• Through Fault Withstand: 1500A
• Operating Temp Range: -5°C to 40°C
3
• Trip Speed: Less than 40msec at 150mA
• Fully complies with: BS7288 & BS1363-2
• Fixed Cable Capacity: 1x 8mm² or 2x 4mm²
• Flexible Cable Capacity: 10.5mm diameter maximum
• Altitude: <2000m
• CE Compliant
current rating requited by BS1363-2 (including updates and amendments)
2 and 3 wire applications
residual current
or 3x 2.5mm²
Loading...
+ 8 hidden pages