Surface Mount
IR DALI Presence Detectors
Model: PDSMDALI Surface Mount
IR DALI Presence Detector
Model: PDSMCDALI Sur face Mount
IR DALI Corridor Presence Detector
Installation & Operating Instructions

1
1. General Information
These instructions should be read carefully and retained for further reference
and maintenance.
2. Safety
• Before installation or maintenance, ensure the mains supply to the PIR sensor
is switched off and the circuit supply fuses are removed or the circuit breaker
turned off.
• It is recommended that a qualified electrician is consulted or employed
for the installation of this PIR sensor and that it is installed in accordance
with the current IEE wiring and Building Regulations.

2
3. Technical Specifications
General
• 230V AC 50 Hz
• This PIR is of Class ll Construction and must not be earthed
• Detection angle: 360°
• Time ON adjustment: 10 sec, 30 sec, 1 min, 5 min, 10 min,
20 min, 30 min
• LUX Light level adjustment: 10, 100, 500, 1000 Lux
• CONSTANT LUX
level adjustment: Constant light value of 300, 500, 1000 Lux
• STDBY (Standby)
Time adjustment: OFF, 1m, 2m, 5m, 15m, 30m, ON
• Warm up period: 60 seconds
• DALI Group: Select channel 0 to E for grouping 0 to 14 to the
connected load, Channel F = Broadcast
to all the connected load
• Operating Temperature: -20°C to +40°C
• IP20 rated suitable for restricted internal applications
• CE compliant
PDSMDALI
• Motion detection range: Up to a 9m diameter approx.
at a 2.5m mounting height
• Dimensions (W x H x D): 140 x 140 x 51mm
PDSMCDALI
• Motion detection range: Cross walk approx. 40m length.
Straight approx. 16m width.
• Dimensions (W x H x D): 140 x 140 x 65.7mm

3
4. Selecting a Location
• Careful positioning of the sensor will be required to ensure optimum
performance.
• The best all-around coverage is achieved with the unit mounted
at the optimum height of 2.5 metres.
• The sensor is more sensitive to movement ACROSS its field of vision than to
movement directly TOWARDS it. Therefore position the unit so that the sensor
looks ACROSS the likely approach path.
• Reflective surfaces (i.e. white-painted walls) may cause false activation
under extreme conditions.
• Avoid positioning the sensor where there are any sources of heat in the
detection area (extractor fans, tumble dryer exhausts etc.) including opposite
any other light sources.
• Install the sensor at least 3' away from fluorescent and HVAC ducts,
and at least 4' away from incandescent fixtures and HVAC diffusers.
PDSMCDALIPDSMDALI