360° Flush Mount Ceiling
PIR Light Controller
Model: PDFMMINIL
Mini Recessed PIR Master Linkable
and Power Box
Model: PDFMMINILS
Mini Recessed PIR Slave Linkable
Installation & Operating Instructions

1. General Information
These instructions should be read carefully and retained for further reference
and maintenance.
2. Safety
• Before installation or maintenance, ensure the mains supply to the PIR sensor
is switched off and the circuit supply fuses are removed or the circuit breaker
turned off.
• It is recommended that a qualified electrician is consulted or used for the
installation of this PIR sensor and install in accordance with the current
IEE wiring and Building Regulations.
• Check that the total load on the circuit including when this PIR sensor is fitted
does not exceed the rating of the circuit cable, fuse or circuit breaker.
3. Technical Specifications
Power Box
• 230V AC 50 Hz
1 2
• This Power Box is of Class ll Construction and must not be earthed
• Maximum Switching Load; 2300W Halogen
500W Low loss balance fluorescent
250W Electronic balance fluorescent,
CFL and LED Lighting
• Mounting Centres: 165mm
• Manual Override Mode: Double pulse within 2 seconds to enter
6 hours ON time
• IP20 Rated suitable for restricted internal applications
• CE Compliant
• Dimensions: H= 35mm, W= 175mm, D= 35mm
• The power box will fit through a 40mm diameter hole

Master PIR Sensor
• These PIRs are of Class lll Construction and must not be earthed
• Motion Detection Range: 8m diameter at a 2.5m mounting height
• Presence Detection Range: 3m diameter
• Detection Angle: 360°
• Time ON Adjustment: 30 seconds to 30 minutes
• Warm Up Time: 60 seconds
• LUX level adjustment: 10 to 2000 Lux
• Operating Temperature: -20°C to +40°C
• Ceiling Cut Out: 40mm diameter hole
• Connection Cable: Pre-fitted 250mm long cable with
an RJ11 connector
• IP40 Rated suitable for restricted internal applications
• CE Compliant
• Dimensions: 47mm diameter body, 64mm height
2 3
Slave PIR Sensor
• These PIRs are of Class lll Construction and must not be earthed
• Motion Detection Range: 8m diameter at a 2.5m mounting height
• Presence Detection Range: 3m diameter
• Detection Angle: 360°
• Warm Up Time: 60 seconds
• Operating Temperature: -20°C to +40°C
• Ceiling Cut Out: 40mm diameter hole
• Connection Cable: Pre-fitted 5m long cable with an RJ11 connector
• IP40 Rated suitable for restricted internal applications
• CE Compliant
• Dimensions: 47mm diameter body, 64mm height
Multiple PIR Sensor Switching – A maximum of 5 PDFMMINILS Slave PIR
sensors can be linked to the PDFMMINIL Master PIR, to enable any detector
to turn ON all the lights connected (The total load must not exceed the lamp
rating of a single PDFMMINIL unit).

4. Installation Advice
As the PIR sensor responds to changes in temperature,
avoid the following situations:
3 4
• Mounting the sensor near objects with highly reflective surfaces,
such as mirrors etc.
• Mounting the sensor near heat sources, such as heating vents,
air conditioning units, lights etc.
• Mounting the sensor near objects that may move in the wind,
such as curtains, tall plants etc.
5. Installation
5.1 Ensure the mains supply is switched OFF
and the circuit supply fuses are removed
or the circuit breaker turned off.