Timeguard PDFMCDALI, PDFMDALI Installation Instructions

Flush Mount IR DALI
Presence Detectors
Model: PDFMDALI Flush Mount
IR DALI Presence Detector
Model: PDFMCDA LI Flush Mount
IR DALI Corr idor Presence Detector
Installation & Operating Instructions
These instructions should be read carefully and retained for further reference and maintenance.
2. Safety
• Before installation or maintenance, ensure the mains supply to the PIR sensor is switched off and the circuit supply fuses are removed or the circuit breaker is turned off.
• It is recommended that a qualified electrician is consulted or employed for the installation of this PIR sensor and that
1
it is installed in accordance with the current IEE wiring and Building Regulations.
3. Technical Specifications
General
• 230V AC 50 Hz
• This PIR is of Class ll Construction and must not be earthed
• Detection angle: 360°
• Requires a 68mm diameter ceiling cut-out
• Time ON adjustment: 10 sec, 30 sec, 1 min, 5 min,
10 min, 20 min, 30 min
• LUX Light level adjustment: 10, 100, 500, 1000 Lux
2
• CONSTANT LUX level adjustment: 300, 500, 1000 Lux
• STDBY (Standby) Time adjustment: OFF, 1m, 2m, 5m, 15m, 30m, ON
• Warm up period: 60 seconds
• DALI Group: Select channel 0 to E for
grouping 0 to 14 to the connected load, Channel F = Broadcast to all the connected load
• Operating Temperature: -20°C to +40°C
• IP20 rated suitable for restricted internal applications
• CE compliant
PDFMDALI
• Motion detection range: Up to a 9m diameter approx.
at a 2.5m mounting height
• Dimensions (W x H x D): 99 x 99 x 74mm
PDFMCDALI
• Motion detection range: Cross walk approx. 40m length.
3
• Dimensions (W x H x D): 99 x 99 x 88.8mm
Straight approx. 16m width.
4. Selecting a Location
• Careful positioning of the sensor will be required to ensure optimum performance.
• The best all-around coverage is achieved with the unit mounted at the optimum height of 2.5 metres.
• The sensor is more sensitive to movement ACROSS its field of vision than to movement directly TOWARDS it. Therefore position the unit so that the sensor looks ACROSS the likely approach path.
• Reflective surfaces (i.e. white-painted walls) may cause
4
false activation under extreme conditions.
• Avoid positioning the sensor where there are any sources of heat in the detection area (extractor fans, tumble dryer exhausts etc.) including opposite any other light sources.
• Install the sensor at least 3' away from fluorescent and HVAC ducts, and at least 4' away from incandescent fixtures and HVAC diffusers.