WARNING
Danger of Electric Shock! Installation of this product
must be performed by trained installers in accordance
with all applicable local, state and national electrical
codes, installation standards and safety rules.
INSTALLATION INSTRUCTIONS
for "Flood-Seal"® SLK-M, SDK-M & SLT-M, SDT-M
INLINE FUSE/DISCONNECT KITS
For Copper and Aluminum Conductors Rated for 600
volts. Fuse not included. Wire range #12-#4
THIS KIT CONTAINS:
1 line-end housing
1 load-end housing
1 Connecting link (SDK-M/SDT-M only)
2 wire-end fuse clips
1 packet of silicone grease
1 assembly dowel
CAUTION
Identify Line and Load side wires and match
housing body parts before installing. All associated
wires and working area must be de-energized.
Complete Steps 1 through 7 for both the Line End and
Load End housing.
Select the correct cut-off
1
ring on the housing for the
cable being used. Cut off
the end of the housing at
the tip of the arrow, leaving
the correct cable size
showing.
14 to 8 (S/L)
8 to 4 *(.24/.38)
* DECIMAL RANGE
14 8
8 4
Housing
Install the fuse clip using a 1/8” hex wrench. Tighten the set
5
screw securely to the conductor.
CAUTION
Do not over tighten on smaller sized conductors.
COPPER OR ALUMINUM
STRANDED
# 10, 8, 6, 4 # 12, 10, 8, 6, 4
Apply a small amount of silicone grease to housing for ease
6
6
of assembly.
Slide the housing over the fuse clip until resistance is felt.
7
Using wood dowel as an assembly and depth gauge tool,
insert the fuse clip to the depth indicated for the line and
load side housings as marked on the dowel. DO NOT
exceed these depths.
SOLID
GREASE
DOWEL
Wipe the cable clean. Pencil end of
2
the cable insulation for ease of
installation. Apply silicone grease to
the end of the
cable and to the
cut opening of
the housing.
Insert the cable until it
3
extends 2” to 3” beyond
the housing.
2”-3”
4
Strip the insulation
from the cable
end baring 1/2” of
the conductor.
1/2”
Limited Warranty Applies. Refer to:
www.tnb.com/ecpwarranty for full warranty terms.
Thomas & Betts Corporation
Memphis, Tennessee
© 2011 Thomas & Betts. All Rights Reserved.
8
www.tnb.com
Insert the connecting link or a 13/32” by 1-1/2” (maximum
600 volt 30 AMP) cartridge fuse in the load-end housing. (Do
not use glass body fuses.) Mate the line-end and load-end
housings to make the electrical connection.
FUSE
LINE
END
LOAD
END
158_R4