Danger of Electric Shock! Installation of this product must be performed
by trained installers in accordance with all applicable local, state and
national electrical codes, installation standards and safety rules.
INSTALLATION INSTRUCTIONS
for Sweetheart SHC 500 Connectors
WARNING
1 2 4
#8 to #4 cut here *(.24-.38)
#2 to 2/0 cut here *(.380-.600)
3/0 to 250 cut here *(.560-.780)
300 to 350 cut here *(.730-.980)
350 to 500 cut here *(.830-1.090)
* Decimal range
8 4
2 2/0
3/0 250
300 350
350 500
SHC 4596
Remove insulating sleeve from the outlet. Select
correct cut-off ring for cable being used. Cut off
rocket sleeve at the tip of arrow, leaving correct
cable size showing on opened rocket.
Strip the insulation from
the cable end baring
approximately 2-1/4” of
conductor.
Beveling the
cut edge of the
insulation is
preferred
although not
necessary.
Wipe cable clean. Apply
3
silicone grease. Slide cut
rocket over prepared
cable.
Limited Warranty Applies. Refer to:
www.tnb.com/ecpwarranty for full warranty terms.
© 2012 Thomas & Betts. All Rights Reserved.
Wire brush bare
conductor thoroughly to
break up oxides on
conductor surface.
5
Insert
conductor into
the outlet,
leaving a
maximum of
1/8” of bare
conductor
showing.
1/8” max
Thomas & Betts Corporation
Memphis, Tennessee
www.tnb.com
Tighten the set screws
6
down on the conductors to
recommended torque.
WIRE SIZE
#6 to #4
#2 to 350 MCM
400 to 500 MCM
Slide rocket sleeve over
7
the outlet and onto the
PVC shoulder until the
rocket butts against the
connector bar.
TORQUE
120 in. -lbs. or 10 ft. -lbs.
240 in. -lbs. or 20 ft. -lbs.
360 in. -lbs. or 30 ft. -lbs.
0014845 A
123_R2
Page 1 of 1
INSTALLATION INSTRUCTIONS
for Sweetheart SHC 500 Connectors
1 2 4
#8 to #4 cut here *(.24-.38)
#2 to 2/0 cut here *(.380-.600)
3/0 to 250 cut here *(.560-.780)
300 to 350 cut here *(.730-.980)
350 to 500 cut here *(.830-1.090)
* Decimal range
8 4
2 2/0
3/0 250
300 350
350 500
SHC 4596
Remove insulating sleeve from the outlet. Select
correct cut-off ring for cable being used. Cut off
rocket sleeve at the tip of arrow, leaving correct
cable size showing on opened rocket.
Strip the insulation from
the cable end baring
approximately 2-1/4” of
conductor.
Beveling the
cut edge of the
insulation is
preferred
although not
necessary.
Wipe cable clean. Apply
3
silicone grease. Slide cut
rocket over prepared
cable.
5
Wire brush bare
conductor thoroughly to
break up oxides on
conductor surface.
Insert
conductor into
the outlet,
leaving a
maximum of
1/8” of bare
conductor
showing.
1/8” max
Danger of Electric Shock! Installation of this product must be performed
WARNING
by trained installers in accordance with all applicable local, state and
national electrical codes, installation standards and safety rules.
Tighten the set screws
6
down on the conductors to
recommended torque.
WIRE SIZE
#6 to #4
#2 to 350 MCM
400 to 500 MCM
Slide rocket sleeve over
7
the outlet and onto the
PVC shoulder until the
rocket butts against the
connector bar.
TORQUE
120 in. -lbs. or 10 ft. -lbs.
240 in. -lbs. or 20 ft. -lbs.
360 in. -lbs. or 30 ft. -lbs.