Thomas & Betts RAB-1/0-3-C Installation Manual

Page 1
WARNING
Danger of Electric Shock! Installation of this product
must be performed by trained installers in accordance
with all applicable local, state and national electrical
codes, installation standards and safety rules.
INSTALLATION INSTRUCTIONS
for Multi-Seal® RAB 1/0 SERIES
Step: 1 Step: 2 Step: 3 Step: 4
Remove the cap (the cap is not required for #2 to 1/0 awg)
Cut cap at the correct cut off ring for #14 to #4 awg.
Reinsert the cap (if required)
Measure the strip length. Place the cable alongside the markings on the bottom of the connector and strip the cable.
Step: 5 Step: 6 Step: 7 Step: 8
Insert the cable into the
tower (#2 to 1/0 awg) or the cap (#14 to #4 awg) until fully inserted.
Remove the screw plug.
IMPORTANT
• When reinstalling a cable, it must be of the same size
or larger than the one removed.
80 in/lbs.
SAFETY PRECUTIONS
Follow standard safety practices when working on energized circuits.
• Insulating gloves rated to the appropriate voltage must
be worn when installing on live conductors.
• Tap conductors may be installed on an energized main
but IT MUST NOT BE UNDER LOAD.
Replace the screw plug.Torque the connector to
Limited Warranty Applies. Refer to:
www.tnb.com/ecpwarranty for full warranty terms.
Thomas & Betts Corporation
© 2014 Thomas & Betts. All Rights Reserved.
Memphis, Tennessee
www.tnb.com
0051920 B